Operating Instructions
Radar sensor for continuous level
measurement of bulk solids
VEGAPULS 68
Profibus PA
Document ID: 36537
Contents
Contents
About this document
1.1 Function ........................................................................................................................... 4
1.2 Target group ..................................................................................................................... 4
1.3 Symbolism used ............................................................................................................... 4
2
For your safety
2.1 Authorised personnel ....................................................................................................... 5
2.2 Appropriate use ................................................................................................................ 5
2.3 Warning about incorrect use............................................................................................. 5
2.4 General safety instructions ............................................................................................... 5
2.5 CE conformity................................................................................................................... 6
2.6 NAMUR recommendations .............................................................................................. 6
2.7 Radio license for Europe .................................................................................................. 6
2.8 Radio license for USA/Canada ......................................................................................... 6
2.9 Environmental instructions ............................................................................................... 7
3
Product description
3.1 Configuration .................................................................................................................... 8
3.2 Principle of operation........................................................................................................ 9
3.3 Packaging, transport and storage ................................................................................... 10
3.4 Accessories and replacement parts ............................................................................... 10
4
Mounting
4.1 General instructions ....................................................................................................... 13
4.2 Mounting preparations - Horn antenna ........................................................................... 13
4.3 Mounting preparations - Parabolic antenna .................................................................... 14
4.4 Mounting instructions ..................................................................................................... 15
5
Connecting to the bus system
5.1 Preparing the connection ............................................................................................... 28
5.2 Connecting ..................................................................................................................... 29
5.3 Wiring plan, single chamber housing.............................................................................. 30
5.4 Wiring plan, double chamber housing ............................................................................ 31
5.5 Wiring plan, double chamber housing Ex d ia ................................................................ 33
5.6 Double chamber housing with DIS-ADAPT .................................................................... 34
5.7 Wiring plan - version IP 66/IP 68, 1 bar........................................................................... 35
5.8 Set instrument address .................................................................................................. 35
5.9 Switch-on phase............................................................................................................. 36
6
Set up with the display and adjustment module
6.1 Insert display and adjustment module ............................................................................ 37
6.2 Adjustment system ......................................................................................................... 38
6.3 Parameter adjustment .................................................................................................... 39
6.4 Saving the parameter adjustment data ........................................................................... 53
7
Setup with PACTware
7.1 Connect the PC .............................................................................................................. 54
7.2 Parameter adjustment .................................................................................................... 54
7.3 Saving the parameter adjustment data ........................................................................... 55
8
Set up with other systems
8.1 DD adjustment programs ............................................................................................... 56
2
VEGAPULS 68 • Profibus PA
36537-EN-140209
1
Contents
9
Diagnosis, asset management and service
9.1 Maintenance .................................................................................................................. 57
9.2 Measured value and event memory ............................................................................... 57
9.3 Asset Management function ........................................................................................... 58
9.4 Rectify faults ................................................................................................................... 62
9.5 Exchanging the electronics module ................................................................................ 64
9.6 Software update ............................................................................................................. 65
9.7 How to proceed if a repair is needed .............................................................................. 65
10 Dismounting
10.1 Dismounting steps.......................................................................................................... 66
10.2 Disposal ......................................................................................................................... 66
36537-EN-140209
11 Supplement
11.1 Technical data ................................................................................................................ 67
11.2 Communication Profibus PA ........................................................................................... 75
11.3 Dimensions .................................................................................................................... 79
Safety instructions for Ex areas
Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating
instructions manual and come with the Ex-approved instruments.
Editing status: 2014-01-28
VEGAPULS 68 • Profibus PA
3
1 About this document
1
About this document
1.1
Function
1.2
Target group
1.3
Symbolism used
This operating instructions manual provides all the information you
need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep this manual
accessible in the immediate vicinity of the device.
This operating instructions manual is directed to trained specialist
personnel. The contents of this manual should be made available to
these personnel and put into practice by them.
Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result.
Warning: If this warning is ignored, injury to persons and/or serious
damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons and/or
destruction of the instrument can result.
•
→
1
Ex applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
Action
This arrow indicates a single action.
Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of batteries and accumulators.
36537-EN-140209
4
VEGAPULS 68 • Profibus PA
2 For your safety
2
2.1
For your safety
Authorised personnel
All operations described in this operating instructions manual must
be carried out only by trained specialist personnel authorised by the
plant operator.
During work on and with the device the required personal protective
equipment must always be worn.
2.2
Appropriate use
VEGAPULS 68 is a sensor for continuous level measurement.
You can find detailed information about the area of application in
chapter "Product description".
Operational reliability is ensured only if the instrument is properly
used according to the specifications in the operating instructions
manual as well as possible supplementary instructions.
2.3
Warning about incorrect use
2.4
General safety instructions
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards, e.g. vessel overfill or damage to system
components through incorrect mounting or adjustment.
This is a state-of-the-art instrument complying with all prevailing
regulations and guidelines. The instrument must only be operated in a
technically flawless and reliable condition. The operator is responsible
for the trouble-free operation of the instrument.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regulations.
The safety instructions in this operating instructions manual, the national installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modifications are explicitly forbidden.
The safety approval markings and safety tips on the device must also
be observed.
36537-EN-140209
Depending on the instrument version, the emitting frequencies are in
the C or K band range. The low emitting frequencies are far below the
internationally approved limit values. When used correctly, there is no
danger to health.
VEGAPULS 68 • Profibus PA
5
2 For your safety
2.5
CE conformity
The device fulfills the legal requirements of the applicable EC guidelines. By affixing the CE marking, we confirm successful testing of the
product.
You can find the CE Certificate of Conformity in the download section
of our homepage.
Electromagnetic compatibility
Instruments in four-wire or Ex-d-ia version are designed for use in an
industrial environment. Nevertheless, electromagnetic interference
from electrical conductors and radiated emissions must be taken into
account, as is usual with class A instruments according to EN 613261. If the instrument is used in a different environment, the electromagnetic compatibility to other instruments must be ensured by suitable
measures.
2.6
NAMUR recommendations
NAMUR is the automation technology user association in the process
industry in Germany. The published NAMUR recommendations are
accepted as the standard in field instrumentation.
The device fulfills the requirements of the following NAMUR recommendations:
•
•
•
•
NE 21 – Electromagnetic compatibility of equipment
NE 43 – Signal level for malfunction information from measuring
transducers
NE 53 – Compatibility of field devices and display/adjustment
components
NE 107 – Self-monitoring and diagnosis of field devices
For further information see www.namur.de.
2.7
Radio license for Europe
2.8
Radio license for USA/Canada
The instrument is approved according to EN 302372-1/2 (2006-04)
for use in closed vessels.
The instrument is in conformity with part 15 of the FCC regulations.
Take note of the following two regulations:
•
•
The instrument must not cause any interfering emissions
The device must be insensitive to interfering immissions, including
those that may cause undesirable operating conditions
Modifications not expressly approved by the manufacturer will lead to
expiry of the operating licence according to FCC/IC.
The instrument may only be used in closed vessels made of metal,
concrete, or fibre-reinforced plastic.
6
VEGAPULS 68 • Profibus PA
36537-EN-140209
The instrument is in conformity with RSS-210 of the IC regulations.
2 For your safety
2.9
Environmental instructions
Protection of the environment is one of our most important duties.
That is why we have introduced an environment management system
with the goal of continuously improving company environmental protection. The environment management system is certified according
to DIN EN ISO 14001.
Please help us fulfill this obligation by observing the environmental
instructions in this manual:
Chapter "Packaging, transport and storage"
Chapter "Disposal"
36537-EN-140209
•
•
VEGAPULS 68 • Profibus PA
7
3 Product description
3
Type label
Product description
3.1 Configuration
The type label contains the most important data for identification and
use of the instrument:
1
17
16
2
3
15
4
5
6
7
8
9
13
10
11
14
12
Fig. 1: Layout of the type label (example)
1 Instrument type
2 Product code
3 Approvals
4 Power supply and signal output, electronics
5 Protection rating
6 Measuring range
7 Process and ambient temperature, process pressure
8 Material, wetted parts
9 Hardware and software version
10 Order number
11 Serial number of the instrument
12 Data-Matrix-Code for Smartphone-App
13 Symbol of the device protection class
14 ID numbers, instrument documentation
15 Reminder to observe the instrument documentation
16 NotifiedauthorityforCEmarking
17 Approval directive
Serial number - Instrument search
The type label contains the serial number of the instrument. With it
you can find the following instrument data on our homepage:
•
•
•
•
Go to www.vega.com, "VEGATools" and "Instrument search". Enter
the serial number.
Alternatively, you can access the data via your smartphone:
8
VEGAPULS 68 • Profibus PA
36537-EN-140209
•
•
Product code (HTML)
Delivery date (HTML)
Order-specific instrument features (HTML)
Operating instructions and quick setup guide at the time of shipment (PDF)
Order-specific sensor data for an electronics exchange (XML)
Test certificate (PDF) - optional
3 Product description
•
•
•
Download the smartphone app "VEGATools" from the "Apple App
Store" or the "GooglePlayStore"
Scan the Data Matrix code on the type label of the instrument or
Enter the serial number manually in the app
Scope of this operating
instructions manual
This operating instructions manual applies to the following instrument
versions:
Scope of delivery
The scope of delivery encompasses:
•
•
•
•
•
Application area
Hardware from 2.1.1
Software from 4.5.0
Radar sensor
Documentation
– Quick setup guide VEGAPULS 68
– Test certificate Measurement accuracy, depending on the
instrument VEGAPULS 68 (optional)
– Operating instructions manual "DIsplay and adjustment module
PLICSCOM" (optional)
– Supplementary instructions "GSM/GPRSradiomodule"
(optional)
– Supplementary instructions manual "Heating for display and
adjustment module" (optional)
– Supplementary instructions manual "Plug connector for continuously measuring sensors" (optional)
– Ex-specific "Safety instructions" (with Ex versions)
– if necessary, further certificates
DVD "Software & Documents", containing
– Operating instructions
– Safety instructions
– PACTware/DTM-Collection
– Driver software
3.2
Principle of operation
The VEGAPULS 68 is a radar sensor for continuous measurement of
bulk solids also under arduous process conditions and large measuring ranges. It the ideal solution for level measurement in high silos,
large bunkers, stone crushers and melting furnaces. With different
antenna versions and materials, this sensor is the optimum solution
for virtually all applications and processes.
The instrument is also suitable for applications in liquids.
Dependent on the application range, different versions are used:
•
36537-EN-140209
•
•
Small silos and vessels, measurement of virtually all bulk solids:
Horn antenna
Large silos and vessels, measurement of bulk solids with low εr
value: Parabolic antenna
Liquids: Parabolic antenna
The instrument can be used with products with an εr value ≥1.5. The
actually achievable value depends on the measuring conditions and
the antenna system.
VEGAPULS 68 • Profibus PA
9
3 Product description
Functional principle
The antenna of the radar sensor emits short radar pulses with a
duration of approx. 1 ns. These pulses are reflected by the product
and received by the antenna as echoes. The transit time of the radar
pulses from emission to reception is proportional to the distance and
hence to the level. The determined level is converted into an appropriate output signal and outputted as measured value.
Packaging
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
3.3
Packaging, transport and storage
The packaging of standard instruments consists of environmentfriendly, recyclable cardboard. For special versions, PE foam or PE
foil is also used. Dispose of the packaging material via specialised
recycling companies.
Transport
Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
Transport inspection
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Storage
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
Storage and transport
temperature
PLICSCOM
•
•
•
•
•
•
•
Not in the open
Dry and dust free
Not exposed to corrosive media
Protected against solar radiation
Avoiding mechanical shock and vibration
Storage and transport temperature see chapter "Supplement Technicaldata-Ambientconditions"
Relative humidity 20 … 85 %
3.4
Accessories and replacement parts
The display and adjustment module PLICSCOM is used for measured
value indication, adjustment and diagnosis. It can be inserted into the
sensor or the external display and adjustment unit and removed at
any time.
VEGACONNECT
10
The interface adapter VEGACONNECT enables the connection of
communication-capable instruments to the USB interface of a PC. For
VEGAPULS 68 • Profibus PA
36537-EN-140209
You can find further information in the operating instructions "Display
and adjustment module PLICSCOM" (Document-ID 27835).
3 Product description
parameter adjustment of these instruments, the adjustment software
PACTware with VEGA-DTM is required.
You can find further information in the operating instructions "Interface
adapterVEGACONNECT" (Document-ID 32628).
VEGADIS 81
The VEGADIS 81 is an external display and adjustment unit for VEGA
plics® sensors.
For sensors with double chamber housing the interface adapter "DISADAPT" is also required for VEGADIS 81.
You can find further information in the operating instructions "VEGADIS81" (Document-ID 43814).
DIS-ADAPT
The adapter "DIS-ADAPT" is an accessory part for sensors with
double chamber housings. It enables the connection of VEGADIS 81
to the sensor housing via an M12 x 1 plug.
You can find further information in the supplementary instructions
"AdapterDISADAPT" (Document-ID 45250).
PLICSMOBILE T61
The PLICSMOBILE T61 is an external GSM/GPRS radio unit for
transmission of measured values and for remote parameter adjustment of plics® sensors. The adjustment is carried out via PACTware/
DTM by using the integrated USB connection.
You can find further information in the supplementary instructions
"PLICSMOBILET61" (Document-ID 37700).
PLICSMOBILE
The PLICSMOBILE is an internal GSM/GPRS radio unit for transmission of measured values and for remote parameter adjustment of
plics® sensors. The adjustment is carried out via PACTware/DTM by
using the integrated USB connection.
You can find further information in the supplementary instructions
"PLICSMOBILEGSM/GPRSradiomodule" (Document-ID 36849).
Flanges
Screwed flanges are available in different versions according to the
following standards: DIN 2501, EN 1092-1, BS 10, ANSI B 16.5,
JIS B 2210-1984, GOST 12821-80.
You can find additional information in the supplementary instructions
manual "FlangesaccordingtoDIN-EN-ASME-JIS" (Document-ID
31088).
Protective cap
The protective cover protects the sensor housing against soiling and
intense heat from solar radiation.
36537-EN-140209
You will find additional information in the supplementary instructions
manual "Protective cover" (Document-ID 34296).
Electronics module
The electronics module VEGAPULS series 60 is a replacement part
for radar sensors of VEGAPULS series 60. There is a different version
available for each type of signal output.
You can find further information in the operating instructions "ElectronicsmoduleVEGAPULSseries60" (Document-ID 36801).
VEGAPULS 68 • Profibus PA
11
3 Product description
Supplementary electronicsProfibusPA
The supplementary is a replacement part for the following sensors
with signal output Profibus PA:
•
•
•
VEGAPULS series 60
VEGAFLEX 80 series
VEGABAR series 80
You can find further information in the operating instructions "SupplementaryelectronicsforProfibusPA" (Document-ID 42767).
Antenna impedance cone The antenna impedance cone is a replacement part used for optimum
transmission of microwaves and for sealing against the process.
You find further information in the operating instructions "Antenna
impedanceconeVEGAPULS62and68" (Document-ID 31381).
36537-EN-140209
12
VEGAPULS 68 • Profibus PA
4 Mounting
4
Screwing in
Mounting
4.1
General instructions
On instruments with process fitting thread, the hexagon must be tightened with a suitable screwdriver. Wrench size see chapter "Dimensions".
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Protection against moisture
Protect your instrument against moisture penetration through the following measures:
•
•
•
•
Use the recommended cable (see chapter "Connecting to power
supply")
Tighten the cable gland
Turn the housing in such a way that the cable gland points downward
Loop the connection cable downward in front of the cable gland
This applies particularly to:
•
•
•
Outdoor mounting
Installations in areas where high humidity is expected (e.g. through
cleaning processes)
Installations on cooled or heated vessels
Suitability for the process Make sure that all parts of the instrument exposed to the process are
conditions
suitable for the existing process conditions.
These are mainly:
•
•
•
Active measuring component
Process fitting
Process seal
•
•
•
•
Process pressure
Process temperature
Chemical properties of the medium
Abrasion and mechanical influences
Process conditions are particularly:
You can find the specifications of the process conditions in chapter
"Technicaldata" as well as on the type label.
4.2
Mounting preparations - Horn antenna
36537-EN-140209
The instrument is also available in versions with an antenna whose
diameter is larger than the process fitting (thread, flange). In such
cases the antenna must be disconnected from the process fitting
before mounting. Proceed as follows:
1. Loosen the hexagon socket screws (3) on the antenna socket
with an Allen wrench (size 3)
2. Remove the antenna (4)
VEGAPULS 68 • Profibus PA
13
4 Mounting
Note:
The plastic cone may not be pulled out of the antenna socket.
3. Insert the antenna from below into the vessel socket and secure it
against falling off
4. Retighten the antenna with hexagon screws to the antenna
socket; torque max. 2.5 Nm (1.8 lbf ft)
Note:
The radar sensor with rinsing air connection or antenna extension
is provided with a notch on the antenna socket. This notch must be
aligned with the marking on the process fitting (the marking specifies
the position of the polarisation of the radar signal).
1
2
3
4
Fig. 2: Dismounting of the horn antenna
1
2
3
4
Marking for the polarisation
Marking at the antenna socket
Hexagon screws on the antenna socket
Antenna
4.3
Mounting preparations - Parabolic antenna
The instrument is also available in versions where the antenna has
a diameter larger than the process fitting (thread, flange). With such
versions the antenna must be disconnected from the process fitting
before mounting. Proceed as follows:
1. Clamp VEGAPULS 68 with the flange, e.g. in a bench vice
2. Hold the connection piece (1) with a wrench on the flat surfaces
(width across flats 22 mm)
3. Loosen counter nut (3) completely with a wrench (width across
flats 36 mm) in the direction of the antenna
5. Remove the parabolic antenna (4) axially
6. Mount sensor flange on the adapter flange and fasten it tightly
7. Check if the O-ring seal is present on the connection piece and
make sure it is not damaged.
14
VEGAPULS 68 • Profibus PA
36537-EN-140209
4. Loosen compression nut (2) completely with a wrench (width
across flats 41 mm) in the direction of the antenna
4 Mounting
Note:
A damaged O-ring seal must be replaced: FKM (SHS FPM 70C3
GLT), FFKM (Kalrez 6375)
8. Remount the parabolic antenna (4)
9. Fasten compression nut (2) with a wrench (width across flats 41),
torque max. 50 Nm
10. Fasten counter nut (3) with a wrench (width across flats 36),
torque max. 40 Nm
Note:
On the version with rinsing air connection, make sure that the holes
in the antenna and in the process fitting coincide. This ensures a sufficient air flow (the air is led through the holes to the feed system. A
rinsing of the whole parabolic antenna is not intended).
1
2
3
4
Fig. 3: Dismounting, parabolic antenna
1
2
3
4
Connection piece
Compression nut
Locknut
Parabolic antenna
4.4
Mounting instructions
Horn and parabolic
antenna
The illustrations with the following mounting instructions show a radar
sensor with horn antenna. The mounting instructions apply analogously also to the version with parabolic antenna.
Polarisation
The emitted radar impulses of the radar sensor are electromagnetic
waves. The polarisation is the direction of the electrical wave component. By turning the instrument in the connection flange or mounting
boss, the polarisation can be used to reduce the effects of false
echoes.
36537-EN-140209
The position of the polarisation is marked on the process fitting of the
instrument.
VEGAPULS 68 • Profibus PA
15
4 Mounting
2
1
Fig. 4: Position of the polarisation
1 Marking with screwed version
2 Markingwithflangeversion
Installation position
Mount the sensor at least 200 mm (7.874 in) away from the vessel
wall.
200 mm
(7.87")
Fig. 5: Mounting of the radar sensor on the vessel top
If you cannot maintain this distance, you should carry out a false
signal storage during setup. This applies particularly if buildup on the
vessel wall is expected. In such a case, it is recommended to repeat
the false signal storage at a later date with existing buildup.
Inflowingmedium
Mounting should not be too close to the inflowing material as the
microwave signal will be interferred. The optimum mounting position is
on the opposite of the filling. To avoid strong pollution, the distance to
the filter or dust extraction must be as big as possible.
36537-EN-140209
16
VEGAPULS 68 • Profibus PA
4 Mounting
Fig.6:Mountingoftheradarsensorwithinflowingmedium
36537-EN-140209
With bulk solids silos with lateral pneumatic filling, mounting should
not be in the filling stream as the microwave signal will be interferred.
The optimum mounting position is next to the filling. To avoid strong
pollution, the distance to the filter or dust extraction must be as big as
possible.
VEGAPULS 68 • Profibus PA
17
4 Mounting
Fig.7:Mountingoftheradarsensorwithinflowingmedium
Socket
The socket piece should be dimensioned in such a way that the
antenna end protrudes slightly out of the socket.
36537-EN-140209
18
VEGAPULS 68 • Profibus PA
ca. 10 mm
4 Mounting
> 10 mm
(0.39")
Fig. 8: Recommended socket mounting with horn antenna
Fig. 9: Recommended socket mounting with parabolic antenna
When using a swivelling holder, keep in mind that the distance
between antenna and socket gets smaller as the inclination of the
sensor increases. Additional false reflections may be generated which
can influence the measuring result at close range.
36537-EN-140209
Fig. 10: Distance between antenna and socket with horn antenna
VEGAPULS 68 • Profibus PA
19
4 Mounting
Fig. 11: Distance between antenna and socket with parabolic antenna
h max.
If the medium has good reflective properties, VEGAPULS 68 with
horn antenna can also be mounted on a longer socket piece. Recommended values for socket heights are specified in the following
illustration. You must carry out a false echo storage afterwards.
d
Fig. 12: Deviating socket dimensions
Socket diameter d
Socket length h
Recommended antenna diameter
40 mm
≤ 100 mm
40 mm
50 mm
≤ 150 mm
48 mm
80 mm
≤ 250 mm
75 mm
100 mm
≤ 500 mm
95 mm
150 mm
≤ 800 mm
95 mm
Socket diameter d
Socket length h
Recommended antenna diameter
1½"
≤ 3.9 in
1½"
2"
≤ 5.9 in
2"
3"
≤ 9.8 in
3"
4"
≤ 19.7 in
4"
6"
≤ 31.5 in
4"
20
VEGAPULS 68 • Profibus PA
36537-EN-140209
Tip:
The instrument is also optionally available with an antenna extension.
The antenna length can be selected (either ex works or later) to allow
the antenna to protrude slightly out of the end of the mounting socket.
Due to the antenna extension however, disturbing reflections are
generated in the close-up range. This can lead to an increase in the
4 Mounting
required minimum distance, especially with poorly reflecting media
such as plastic powder. In practice, a cleanly constructed mounting
socket, if necessary with rounded edges, introduces fewer disturbing
influences than an antenna extension.
Orientation
To measure as much of the vessel volume as possible, the sensor
should be aligned so that the measuring beam reaches the lowest
level in the vessel. In a cylindrical silo with conical outlet mounting is
carried out on a socket. It should be positioned on one third up to the
half of the vessel radius.
r
1/3 r...1/2 r
Fig. 13: Orientation
36537-EN-140209
If mounting in the centre of the silo is not possible, the sensor can be
directed to the vessel center by using the optional swivelling holder.
The following description shows a simple way to determine the
required angle of inclination.
VEGAPULS 68 • Profibus PA
21
4 Mounting
d
α
a
Fig.14:ProposalforinstallationafterorientationVEGAPULS68
The angle of inclination depends on the vessel dimensions. It can be
easily checked with a suitable level or water leve on the sensor.
The following chart specifies the distance "a" between installation
position and vessel centre dependent on the measuring distance for
inclination angles of 2° … 10°.
Distance d 2°
(m)
6°
8°
10°
2
0.1
0.1
0.2
0.3
0.4
4
0.1
0.3
0.4
0.6
0.7
6
0.2
0.4
0.6
0.8
1.1
8
0.3
0.6
0.8
1.1
1.4
10
0.3
0.7
1.1
1.4
1.8
15
0.5
1.0
1.6
2.1
2.6
20
0.7
1.4
2.1
2.8
3.5
25
0.9
1.7
2.6
3.5
4.4
30
1.0
2.1
3.2
4.2
5.3
35
1.2
2.4
3.7
4.9
6.2
40
1.4
2.8
4.2
5.6
7.1
45
1.6
3.1
4.7
6.3
7.9
50
1.7
3.5
5.3
7
8.8
VEGAPULS 68 • Profibus PA
36537-EN-140209
22
4°
4 Mounting
Distance d 2°
(m)
4°
6°
8°
10°
55
1.9
3.8
5.8
7.7
9.7
60
2.1
4.2
6.3
8.4
10.6
65
2.3
4.5
6.8
9.1
11.5
70
2.4
4.9
7.4
9.8
12.3
75
2.6
5.2
7.9
1.0
13
Example:
In a vessel 20 m high, the installation position of the sensor is 1.4 m
from the vessel centre.
The necessary angle of inclination of 4° can be read out from this
chart.
Proceed as follows to adjust the angle of inclination with the swivelling
holder:
1. Loosen terminal screw of the swivelling holder with a fork spanner
SW 13
2. Direct the sensor, check angle of inclination
Information:
The max. angle of inclination of the swivelling holder is approx. 15°
3. Tighten the terminal screw, torque max. 20 Nm.
Information:
The hexagon screws must not be loosened.
Vessel installations
The mounting location of the radar sensor should be a place where no
other equipment or fixtures cross the path of the microwave signals.
Vessel installations, such as e.g. ladders, limit switches, heating spirals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring site that the radar sensor
has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be
carried out during setup.
36537-EN-140209
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.
Fig.15:Coversmoothprofileswithdeflectors
Agitators
VEGAPULS 68 • Profibus PA
If there are agitators in the vessel, a false signal suppression should
be carried out with the agitators in motion. This ensures that the
23
4 Mounting
interfering reflections from the agitators are saved with the blades in
different positions.
Fig. 16: Agitators
Material heaps
Large material heaps are detected with several sensors, which can be
mounted on e.g. traverse cranes. For this type of application, it is best
to orient the sensor toward the solid surface. A mutual infuence of the
sensors is not possible.
Fig. 17: Radar sensors on traverse crane
Information:
Keep in mind that for these applications, the sensors are designed for
relatively slow level changes. When using VEGAPULS 68 on a movable bracket, the max. measuring rate must be observed (see chapter
"Technicaldata").
24
Instruments for a temperature range up to 250 °C or up to 450 °C
have a distance piece between process fitting and electronics housing. Ths distance piece is used for thermal decoupling of the electronics against high process temperatures.
VEGAPULS 68 • Profibus PA
36537-EN-140209
Mounting in the vessel
insulation
4 Mounting
Information:
The distance piece must only be incorporated up to max. 50 mm in
the vessel isolation. Only then, a reliable temperature decoupling is
guaranteed.
max. 50 mm
(1.97")
1
2
3
Fig. 18: Mounting the instrument on insulated vessels.
1 Electronicshousing
2 Distance piece
3 Vessel insulation
Installation in subsurface For level measurements in concrete silos, the sensors are often
enclosures
mounted in protective boxes. These boxes can be for example metallic, closed subsurface enclosures.
1
2
Fig. 19: Mounting of the instrument in an subsurface enclosure
1
2
Subsurface enclosure
Concrete bottom
36537-EN-140209
For this application, the minimal amounts of stray radiation from the
sensor can be reflected and strengthened by the walls of the subsurface enclosures. In the case of sensors with plastic housings, this can
lead to coupling disturbances. This can be avoided by using a sensor
with aluminium or stainless steel housing.
VEGAPULS 68 • Profibus PA
25
4 Mounting
Mounting in multiple
chamber silo
The silo walls of multiple chamber silos are often made of profile
walls, such as e.g. profile sheeting, to ensure the required stability. If
the radar sensor is mounted very close to a heavily structured vessel
wall, considerable false reflections can be generated. Hence the sensor should be mounted at a large distance from the separating wall.
The optimal mounting position is on the outer wall of the silo with the
sensor directed towards the emptying aperture in the silo center.
Fig.20:MountingofVEGAPULS68inmultiplechambersilos
26
VEGAPULS 68 • Profibus PA
36537-EN-140209
Fig.21:OrientationofVEGAPULS68foremptyinginthesilocenter
4 Mounting
Dust layers
To avoid strong buildup and dust in the antenna system, the sensor
should not be mounted directly at the dust extraction of the vessel.
In case of extreme dust deposits in the antenna system, VEGAPULS
68 is available with a rinsing air connection. The air is distributed via
channels in the antenna system and keeps it largely free of dust.
Fig. 22: Purging air connection with horn antenna
Fig. 23: Purging air connection with parabolic antenna
36537-EN-140209
The practice has shown that a pressure of approx. 0.2 … 1 bar
provides a sufficient air flow (see diagram in chapter "Technicaldata",
"Purging air connection".
VEGAPULS 68 • Profibus PA
27
5 Connecting to the bus system
5
Safety instructions
Connecting to the bus system
5.1
Preparing the connection
Always keep in mind the following safety instructions:
•
•
Connect only in the complete absence of line voltage
If overvoltage surges are expected, overvoltage arresters should
be installed
Voltage supply
The voltage supply is provided by a Profibus DP /PA segment coupler.
Connection cable
Connection is made with screened cable according to the Profibus
specification. Power supply and digital bus signal are carried over the
same two-wire connection cable.
The voltage supply range can differ depending on the instrument
version. You can find the data for voltage supply in chapter "Technical
data".
Use cable with round cross-section. A cable outer diameter of
5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.
If you are using cable with a different diameter or cross-section,
exchange the seal or use a suitable cable gland.
Please make sure that your installation is carried out according to the
Profibus specification. In particular, make sure that the termination of
the bus is done with appropriate terminating resistors.
You can find detailed information of the cable specification, installation and topology in the "ProfibusPA-UserandInstallationGuideline" on www.profibus.com.
Cable gland ½ NPT
With plastic housing, the NPT cable gland or the Conduit steel tube
must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technicaldata".
Cable screening and
grounding
Make sure that the cable screening and ground is executed according to the Fielbus specification. If electromagnetic interference is
expected which is above the test values of EN 61326-1 for industrial
areas, we recommend to connect the cable screen on both ends to
ground potential.
In systems with potential equalisation, connect the cable screen
directly to ground potential at the power supply unit, in the connection
box and at the sensor. The screen in the sensor must be connected
directly to the internal ground terminal. The ground terminal outside
on the housing must be connected to the potential equalisation (low
impedance).
28
VEGAPULS 68 • Profibus PA
36537-EN-140209
In systems without potential equalisation with cable screening on
both sides, connect the cable screen directly to ground potential at
the power supply unit and at the sensor. In the connection box or
T-distributor, the screen of the short stub to the sensor must not be
connected to ground potential or to another cable screen. The cable
screens to the power supply unit and to the next distributor must be
connected to each other and also connected to ground potential via a
5 Connecting to the bus system
ceramic capacitor (e.g. 1 nF, 1500 V). Low-frequency potential equalisation currents are thus suppressed, but the protective effect against
high frequency interference signals remains.
Connection technology
5.2
Connecting
The voltage supply and signal output are connected via the springloaded terminals in the housing.
Connection to the display and adjustment module or to the interface
adapter is carried out via contact pins in the housing.
Information:
The terminal block is pluggable and can be removed from the
electronics. To do this, lift the terminal block with a small screwdriver
and pull it out. When reinserting the terminal block, you should hear it
snap in.
Connection procedure
Proceed as follows:
1. Unscrew the housing cover
2. If a display and adjustment module is installed, remove it by turning it slightly to the left.
3. Loosen compression nut of the cable entry gland
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
5. Insert the cable into the sensor through the cable entry
36537-EN-140209
Fig. 24: Connection steps 5 and 6 - Single chamber housing
VEGAPULS 68 • Profibus PA
29
5 Connecting to the bus system
Fig. 25: Connection steps 5 and 6 - Double chamber housing
6. Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as flexible cores with wire end sleeves are inserted directly into the terminal openings. In case of flexible cores without
end sleeves, press the terminal from above with a small screwdriver,
the terminal opening is then free. When the screwdriver is released,
the terminal closes again.
You can find further information on the max. wire cross-section under
"Technicaldata/Electromechanicaldata"
7. Check the hold of the wires in the terminals by lightly pulling on
them
8. Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
9. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
10. Reinsert the display and adjustment module, if one was installed
11. Screw the housing cover back on
The electrical connection is finished.
5.3
Wiring plan, single chamber housing
The following illustration applies to the non-Ex as well as to the Ex-ia
version.
36537-EN-140209
30
VEGAPULS 68 • Profibus PA
5 Connecting to the bus system
Electronics and terminal
compartment
2
3
78
45 6
1
4
45 6
78
901
23
1
0
(+)1
901
23
0
Bus
2(-)
5
6
7
8
5
1
Fig.26:Electronicsandterminalcompartment,singlechamberhousing
1
2
3
4
5
Voltage supply, signal output
For display and adjustment module or interface adapter
Selection switch for bus address
For external display and adjustment unit
Groundterminalforconnectionofthecablescreen
5.4
The following illustrations apply to the non-Ex as well as to the Ex-ia
version.
2
3
0
1
78
1
78
45 6
2(-)
901
23
1
(+)1
901
23
0
Bus
45 6
Electronics compartment
Wiring plan, double chamber housing
5
6
7
8
1
Fig.27:Electronicscompartment,doublechamberhousing
1
2
3
Internal connection to the connection compartment
Contact pins for the display and adjustment module or interface adapter
Selection switch for bus address
36537-EN-140209
Information:
The connection of an external display and adjustment unit is not possible with this double chamber housing.
VEGAPULS 68 • Profibus PA
31
5 Connecting to the bus system
Terminal compartment
2
Bus
(+)1
3
2(-)
1
Fig.28:Terminalcompartment,doublechamberhousing
1 Voltage supply, signal output
2 For display and adjustment module or interface adapter
3 Groundterminalforconnectionofthecablescreen
Connection compartment
- Radio module PLICSMOBILE
SIM-Card
Status
Test
USB
(+)1
2(-)
1
Fig.29:ConnectioncompartmentradiomodulePLICSMOBILE
1
Voltage supply
You can find detailed information on connection in the supplementary
instructions "PLICSMOBILEGSM/GPRSradiomodule".
36537-EN-140209
32
VEGAPULS 68 • Profibus PA
5 Connecting to the bus system
5.5
Wiring plan, double chamber housing Ex d ia
2
3
78
45 6
1
78
901
23
1
0
(+)1
901
23
0
Bus
45 6
Electronics compartment
2(-)
1
5
6
7
8
4
Fig.30:Electronicscompartment,doublechamberhousingExdia
1
2
3
4
Internal connection to the connection compartment
Contact pins for the display and adjustment module or interface adapter
Selection switch for bus address
Internal connection to the plug connector for external display and adjustment unit (optional)
Terminal compartment
Bus
(+)1
2
2(-)
1
Fig.31:Connectioncompartment,doublechamberhousingExdia
1 Voltage supply, signal output
2 Groundterminalforconnectionofthecablescreen
Plug M12 x 1 for external
display and adjustment
unit
4
3
1
2
Fig.32:Topviewoftheplugconnector
36537-EN-140209
1
2
3
4
VEGAPULS 68 • Profibus PA
Pin 1
Pin 2
Pin 3
Pin 4
Contact pin
Colour connection cable in the sensor
Terminal, electronics
module
Pin 1
Brown
5
33
5 Connecting to the bus system
Electronics compartment
Contact pin
Colour connection cable in the sensor
Terminal, electronics
module
Pin 2
White
6
Pin 3
Blue
7
Pin 4
Black
8
5.6
Double chamber housing with DIS-ADAPT
1
2
3
Fig. 33: View to the electronics compartment
1 DIS-ADAPT
2 Internal plug connection
3 Plug connector M12 x 1
Assignment of the plug
connector
4
3
1
2
Fig.34:Topviewoftheplugconnector
1
2
3
4
Contact pin
Colour connection cable in the sensor
Terminal, electronics
module
Pin 1
Brown
5
Pin 2
White
6
Pin 3
Blue
7
Pin 4
Black
8
VEGAPULS 68 • Profibus PA
36537-EN-140209
34
Pin 1
Pin 2
Pin 3
Pin 4
5 Connecting to the bus system
Wire assignment, connection cable
5.7
Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 35: Wire assignment in permanently connected connection cable
1
2
Instrument address
brown (+) and blue (-) to power supply or to the processing system
Shielding
5.8
Set instrument address
An address must be assigned to each Profibus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Profibus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This address can be used for function test of the instrument and for connection to a Profibus PA network. Then address must be changed to
integrate additional instruments.
The address setting is carried out either via:
•
•
•
Hardware addressing
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
The display and adjustment module (address setting via software)
PACTware/DTM (address setting via software)
The hardware addressing is effective if an address <126 is adjusted
with the address selection switches on the instrument. Hence the
software addressing is no longer effective, the adjusted hardware
address is valid.
1
2
3
78
1
78
45 6
0
36537-EN-140209
45 6
2(-)
901
23
(+)1
1
Bus
901
23
0
5
6
7
8
Fig. 36: Address selection switch
1 Addresses <100 (selection 0), addresses >100 (selection 1)
2 Decade of the address (selection 0 to 9)
3 Unitpositionoftheaddress(selection0to9)
VEGAPULS 68 • Profibus PA
35
5 Connecting to the bus system
Software addressing
The software addressing is only effective if address 126 or higher is
adjusted on the instrument with the address selection switches.
The addressing procedure is described in the operating instructions
manual "Display and adjustment module.
5.9
Switch-on phase
After VEGAPULS 68 is connected to the bus system, the instrument
carries out a self-test for approx. 30 seconds. The following steps are
carried out:
•
•
•
•
Internal check of the electronics
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
Indication of the status message "F 105 Determine measured
value" on the display or PC
Status byte goes briefly to fault value
As soon as a plausible measured value is found, it is outputted to the
signal cable. The value corresponds to the actual level as well as the
settings already carried out, e.g. factory settings.
36537-EN-140209
36
VEGAPULS 68 • Profibus PA
6 Set up with the display and adjustment module
6
6.1
Set up with the display and adjustment
module
Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
and removed again at any time. You can choose any one of four different positions - each displaced by 90°. It is not necessary to interrupt
the power supply.
Proceed as follows:
1. Unscrew the housing cover
2. Place the display and adjustment module in the requested position onto the electronics and turn to the right until it snaps in
3. Screw housing cover with inspection window tightly back on
Removal is carried out in reverse order.
The display and adjustment module is powered by the sensor, an additional connection is not necessary.
36537-EN-140209
Fig. 37: Installing the display and adjustment module in the electronics compartment of the single chamber housing
VEGAPULS 68 • Profibus PA
37
6 Set up with the display and adjustment module
1
2
Fig. 38: Insertion of the display and adjustment module into the double chamber
housing
1 In the electronics compartment
2 Intheconnectioncompartment(withEx-d-iaversionnotpossible)
Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher cover with
an inspection glass is required.
6.2
Adjustment system
1
2
36537-EN-140209
Fig. 39: Display and adjustment elements
Key functions
38
1
2
LC display
Adjustment keys
•
[OK] key:
– Move to the menu overview
VEGAPULS 68 • Profibus PA
6 Set up with the display and adjustment module
•
•
•
Adjustment system
– Confirm selected menu
– Edit parameter
– Save value
[-] key:
– Presentation, change measured value
– Select list entry
– Select editing position
[+] key:
– Change value of the parameter
[ESC] key:
– Interrupt input
– Jump to next higher menu
The device is adjusted via the four keys of the display and adjustment
module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration. Approx. 60 minutes after the last pressing of a key, an automatic reset to
measured value indication is triggered. Any values not confirmed with
[OK] will not be saved.
6.3
Parameter adjustment
The instrument is adapted to the application conditions via the parameter adjustment. The parameter adjustment is carried out with an
adjustment menu.
Main menu
The main menu is divided into five sections with the following functions:
Setup: Settings, for example, to measurement loop name, medium,
application, vessel, adjustment, AI FB 1 Channel - scaling - damping
Display: Language setting, settings for the measured value indication
as well as lighting
Diagnosis: Information, for example on the instrument status, pointer,
reliability, AI FB 1 simulation, echo curve
Further settings: Instrument units, false signal suppression, linearization, sensor address, PIN, date/time, reset, copy sensor data
Info: Instrument name, hardware and software version, date of manufacture, instrument features
36537-EN-140209
In the main menu point "Setup", the individual submenu points
should be selected one after the other and provided with the correct
parameters to ensure optimum adjustment of the measurement. The
procedure is described in the following.
VEGAPULS 68 • Profibus PA
39
6 Set up with the display and adjustment module
Setup
Setup - Medium
Each medium has different reflection properties. With liquids, further
interfering factors are fluctuation product surface and foam generation. With bulk solids, these are dust generation, material cone and
additional echoes from the vessel wall.
To adapt the sensor to these different measuring conditions, the
selection "Liquid" or "Bulk solid" should be made in this menu item.
Through this selection, the sensor is adapted perfectly to the product
and measurement reliability, particularly in products with poor reflective properties, is considerably increased.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup - Application
In addition to the medium, also the application, i.e. the measuring site,
can influence the measurement.
With this menu item, the sensor can be adapted to the applications.
The adjustment possibilities depend on the selection "Liquid" or "Bulk
solid" under "Medium".
The following options are available when "Liquid" is selected:
The selection "Standpipe" opens a new window in which the inner
diameter of the applied standpipe is entered.
Storage tank:
• Setup: large-volumed, upright cylindrical, spherical
• Product speed: slow filling and emptying
• Process/measurement conditions:
40
VEGAPULS 68 • Profibus PA
36537-EN-140209
The following features form the basis of the applications:
6 Set up with the display and adjustment module
•
– Condensation
– Smooth product surface
– High requirements to the measurement accuracy
Properties, sensor:
– Slight sensitivity against sporadic false echoes
– Stable and reliable measured values by averaging
– High accuracy
– Short reaction time of the sensor not required
Storage tanke with product circulation:
Setup: large-volumed, upright cylindrical, spherical
Product speed: slow filling and emptying
Installations: small laterally mounted or large top mounted stirrer
Process/measurement conditions:
– Relatively smooth product surface
– High requirements to the measurement accuracy
– Condensation
– Slight foam generation
– Overfilling possible
• Properties, sensor:
– Slight sensitivity against sporadic false echoes
– Stable and reliable measured values by averaging
– High accuracy because not adjusted for max. speed
– False signal suppression recommended
•
•
•
•
Storage tank on ships (Cargo Tank):
Product speed: slow filling and emptying
Vessel:
– Installations in the bottom section (bracers, heating spirals)
– High sockets 200 … 500 mm, also with large diameters
• Process/measurement conditions:
– Condensation, buildup by movement
– Max. requirement on measurement accuracy from 95 %
• Properties, sensor:
– Slight sensitivity against sporadic false echoes
– Stable and reliable measured values by averaging
– High accuracy
– False signal suppression required
•
•
Stirrer vessel (reactor):
Setup: all vessel sizes possible
Product speed:
– Fast to slow filling possible
– Vessel is very often filled and emptied
• Vessel:
– Socket available
– Large agitator blades of metal
– Vortex breakers, heating spirals
• Process/measurement conditions:
– Condensation, buildup by movement
– Strong spout generation
– Very agitated surface, foam generation
• Properties, sensor:
36537-EN-140209
•
•
VEGAPULS 68 • Profibus PA
41
6 Set up with the display and adjustment module
– Higher measurement speed through lower averaging
– Sporadic false echoes are suppressed
Dosing vessel:
Setup: all vessel sizes possible
Product speed:
– Fast filling and emptying
– Vessel is very often filled and emptied
• Vessel: narrow installation situation
• Process/measurement conditions:
– Condensation, buildup on the antenna
– Foam generation
• Properties, sensor:
– Measurement speed optimized by virtually no averaging
– Sporadic false echoes are suppressed
– False signal suppression recommended
•
•
Standpipe:
Product speed: very fast filling and emptying
Vessel:
– Vent hole
– Joins like flanges, weld joints
– Shifting of the running time in the tube
• Process/measurement conditions:
– Condensation
– Buildup
• Properties, sensor:
– Measurement speed optimized through little averaging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
•
•
Bypass:
Product speed:
– Fast up to slow filling with short up to long bypass tube possible
– Often the level is hold via a control facility
• Vessel:
– Lateral outlets and inlets
– Joins like flanges, weld joints
– Shifting of the running time in the tube
• Process/measurement conditions:
– Condensation
– Buildup
– Separation of oil and water possible
– Overfilling into the antenna possible
• Properties, sensor:
– Measurement speed optimized through little averaging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
– False signal suppression recommended
•
VEGAPULS 68 • Profibus PA
36537-EN-140209
42
6 Set up with the display and adjustment module
Plastic tank:
• Vessel:
– Measurement fix mounted or integrated
– Measurement depending on the application through the vessel
top
– With empty vessel, the measurement can be carried out
through the bottom
• Process/measurement conditions:
– Condensation on the plastic ceiling
– In outside facilities water and snow on the vessel top possible
• Properties, sensor:
– False signals outside the vessel are not taken into consideration
– False signal suppression recommended
Transportable plastic tank:
Vessel:
– Material and thickness different
– Measurement through the vessel top
• Process/measurement conditions:
– Measured value jump with vessel change
• Properties, sensor:
– Quick adaptation to changing reflection conditions through
vessel change
– False signal suppression required
•
Open water (gauge measurement):
Gauge rate of change: slow gauge change
Process/measurement conditions:
– Distance sensor to water surface to big
– Extreme damping of output signal due to wave generation
– Ice and condensation on the antenna possible
– Spiders and insect nestle in the antennas
– Floating material and animals sporadically on the water surface
• Properties, sensor:
– Stable and reliable measured values by high averaging
– Insensitive in the close range
•
•
Openflume(flowmeasurement):
Gauge rate of change: slow gauge change
Process/measurement conditions:
– Ice and condensation on the antenna possible
– Spiders and insect nestle in the antennas
– Smooth water surface
– Exact measurement result required
– Distance to the water surface normally relatively high
• Properties, sensor:
– Stable and reliable measured values by high averaging
– Insensitive in the close range
36537-EN-140209
•
•
Rain water overfall (weir):
Gauge rate of change: slow gauge change
Process/measurement conditions:
– Ice and condensation on the antenna possible
•
•
VEGAPULS 68 • Profibus PA
43
6 Set up with the display and adjustment module
•
– Spiders and insect nestle in the antennas
– Turbulent water surface
– Sensor flooding possible
Properties, sensor:
– Stable and reliable measured values by high averaging
– Insensitive in the close range
Demonstration:
Adjustment for all applications which are not typically level measurement
– Instrument demonstration
– Object recognition/monitoring (additional settings required)
• Properties, sensor:
– Sensor accepts all measured value changes within the measuring range immediately
– High sensitivity against interferences, because virtually no
averaging
•
Caution:
If a separation of liquids with different dielectric constant occurs in
the vessel, for example through condensation, the radar sensor can
detect under certain circumstances only the medium with the higher
dielectric constant. Keep in mind that layer interfaces can cause faulty
measurements.
If you want to measure the total height of both liquids reliably, please
contact our service department or use an instrument specially designed for interface measurement.
The following options are available when "Bulk solid" is selected:
The following features form the basis of the applications:
Silo (slim and high):
• Vessel of metal: weld joints
• Process/measurement conditions:
– Filling too close to the sensor
– System noise with completely empty silo increased
• Properties, sensor:
– Stable measured values through higher averaging
– False signal suppression recommended with setup, required for
automatic false signal suppression
– Automatic false signal suppression with partly filled vessel
Bunker (large-volumed):
Vessel of concrete or metal:
– Structured vessel walls
– Installations present
• Process/measurement conditions:
– Large distance to the medium
– Large angles of repose
44
36537-EN-140209
•
VEGAPULS 68 • Profibus PA
6 Set up with the display and adjustment module
•
Properties, sensor:
– Mean averaging
– High measured value jumps are accepted
Bunkerwithfastfilling:
Vessel of concrete or metal, also multiple chamber silo:
– Structured vessel walls
– Installations present
• Process/measurement conditions:
– Measured value jumps, e.g. by truck loading
– Large distance to the medium
– Large angles of repose
• Properties, sensor:
– Lower averaging
– Very high measured value jumps are accepted
•
Heap:
Sensor mounting on movable conveyor belts
Detection of the heap profile
Height detection during filling
Process/measurement conditions:
– Measured value jumps, e.g. by the profile of the heap or traverses
– Large angles of repose
– Measurement near the filling stream
• Properties, sensor:
– Mean averaging
– High measured value jumps are accepted
•
•
•
•
Crusher:
Vessel: installations, wear and protective facilities available
Process/measurement conditions:
– Measured value jumps, e.g. by truck loading
– Fast reaction time
– Large distance to the medium
• Properties, sensor:
– Little averaging
– Max. reaction speed, very high measured value jumps are
accepted
•
•
Demonstration:
Adjustment for all applications which are not typically level measurement
– Instrument demonstration
– Object recognition/monitoring (additional settings required)
• Properties, sensor:
– Sensor accepts all measured value changes within the measuring range immediately
– High sensitivity against interferences, because virtually no
averaging
36537-EN-140209
•
VEGAPULS 68 • Profibus PA
45
6 Set up with the display and adjustment module
Through this selection, the sensor is adapted optimally to the application or the location and measurement reliability under the various
basic conditions is increased considerably.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup - Vessel height,
measuring range
With this selection, the operating range of the sensor is adapted to
the vessel height and the reliability with different frame conditions is
increased considerably.
Independent from this, the min. adjustment must be carried out.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup - Vessel form
Also the vessel form can influence the measurement apart from the
medium and the application. To adapt the sensor to these measurement conditions, this menu item offers you different options for vessel
bottom and ceiling in case of certain applications.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup - Adjustment
Since the radar sensor is a distance measuring instrument, the
distance from the sensor to the product surface is measured. For
indication of the real level, an allocation of the measured distance to
the percentage height must be carried out.
To perform the adjustment, enter the distance with full and empty vessel, see the following example:
36537-EN-140209
46
VEGAPULS 68 • Profibus PA
3
100%
2
35 m
(1378")
1m
(39.37")
6 Set up with the display and adjustment module
0%
1
Fig.40:Parameteradjustmentexamplemin./max.adjustment
1
2
Min. level = max. meas. distance
Max. level = min. meas. distance
If these values are not known, an adjustment with the distances of for
example 10 % and 90 % is possible. Starting point for these distance
specifications is always the seal surface of the thread or flange. You
can find specifications of the reference plane in chapter "Technical
data". By means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, because the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time
without the instrument having to be installed.
Setup - Min. adjustment
Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "Min. adjustment" and confirm
with [OK].
36537-EN-140209
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
VEGAPULS 68 • Profibus PA
47
6 Set up with the display and adjustment module
4. Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5. Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Setup - Max. adjustment
Proceed as follows:
1. Select with [->] the menu item "Max. adjustment" and confirm
with [OK].
2. Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
5. Save settings with [OK]
Diagnosis - Peak value
The respective min. and max. measured value is saved in the sensor.
The values are displayed in the menu item "Peak values".
48
VEGAPULS 68 • Profibus PA
36537-EN-140209
Diagnosis - Measurement When non-contact level sensors are used, the measurement can be
reliability
influenced by the respective process conditions. In this menu item,
the measurement reliability of the level echo is displayed as dB value.
The measurement reliability equals signal strength minus noise. The
higher the value, the more reliable the measurement. With a functioning measurement, the values are > 10 dB.
6 Set up with the display and adjustment module
Diagnoses - Curve indica- The "Echocurve" shows the signal strength of the echoes over the
tion
measuring range in dB. The signal strength enables an evaluation of
the quality of the measurement.
The "False signal suppression" displays the saved false echoes (see
menu "Additional settings") of the empty vessel with signal strength in
"dB" over the measuring range.
A comparison of echo curve and false signal suppression allows a
more detailed statement of the reliability.
The selected curve is permanently updated. A submenu with zoom
functions is opened with the [OK] key:
•
•
•
Diagnostics - Echo curve
memory
"X-Zoom": Zoom function for the meas. distance
"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"
"Unzoom": Reset the presentation to the nominal measuring range
with single magnification
With the function "Echocurvememory" the echo curve can be saved
at the time of setup. This is generally recommended; for using the Asset Management functions it is absolutely necessary. If possible, the
curve should be saved with a low level in the vessel.
36537-EN-140209
With the adjustment software PACTware and the PC, the high resolution echo curve can be displayed and used to recognize signal
changes over the operating time. In addition, the echo curve of the
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
Additional adjustments False signal suppression
VEGAPULS 68 • Profibus PA
The following circumstances cause interfering reflections and can
influence the measurement:
•
•
•
•
High sockets
Vessel installations such as struts
Agitators
Buildup or welded joints on vessel walls
49
6 Set up with the display and adjustment module
Note:
A false signal suppression detects, marks and saves these false signals so that they are no longer taken into account for level measurement.
This should be done with the low level so that all potential interfering
reflections can be detected.
Proceed as follows:
1. Select the menu item "Additional settins" with [->] and confirm
with [OK]. With [->] you have to select the menu item "False
signal suppression" and confirm with [OK].
2. Confirm again with [OK].
3. Confirm again with [OK].
4. Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.
5. All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,
the following menu window appears when selecting "False signal
suppression":
50
VEGAPULS 68 • Profibus PA
36537-EN-140209
The menu item "Delete" is used to completely delete an already created false signal suppression. This is useful if the saved false signal
suppression no longer matches the metrological conditions in the
vessel.
6 Set up with the display and adjustment module
The menu item "Extend" is used to extend an already created false
signal suppression. This is useful if a false signal suppression was
carried out with a too high level and not all false signals could be detected. When selecting "Extend", the distance to the product surface
of the created false signal suppression is displayed. This value can
now be changed and the false signal suppression can be extended to
this range.
Additional adjustments Linearization curve
A linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. a horizontal cylindrical or spherical tank - and the indication or output of the volume is
required. Corresponding linearization curves are preprogrammed
for these vessels. They represent the correlation between the level
percentage and vessel volume.
By activating the appropriate curve, the volume percentage of the
vessel is displayed correctly. If the volume should not be displayed in
percent but e.g. in l or kg, a scaling can be also set in the menu item
"Display".
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [ESC] and [->] key.
Caution:
Note the following if the instrument with corresponding approval is
used as part of an overfill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer
necessarily linear to the filling height. This must be considered by the
user especially when adjusting the switching point on the limit signal
transmitter.
Additional adjustments
- Reset
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.
The following reset functions are available:
36537-EN-140209
•
•
VEGAPULS 68 • Profibus PA
Delivery status: Restoring the parameter settings at the time of
shipment from the factory incl. the order-specific settings. A created false signal suppression, user-programmable linearization
curve, the measured value memory, echo curve memory as well
as event memory will be deleted.
Basic settings: Resetting of the parameter settings incl. special
parameters to the default values of the respective instrument. Any
created false signal suppression, user programmable linearization
curve, measured value memory as well as event memory will be
deleted.
51
6 Set up with the display and adjustment module
•
•
•
Setup: Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, measured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
False signal suppression: Deleting a previously created false
signal suppression. The false signal suppression created in the
factory remains active.
Peak values measured value: Resetting of the measured min.
and max. distances to the actual measured value.
Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 68:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Application
Storage tank
Vessel form
Vessel bottom, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"Technicaldata" in the supplement
Min. adjustment
Recommended measuring range, see
"Technicaldata" in the supplement
Max. adjustment
0,000 m(d)
Display
Bulk solids/Crushed stones, gravel
Silo
Vessel top, dished boiler end
AI FB1 Channnel
PV (lin. perc.)
AI FB1 scaling
unit
Height
AI FB1 scaling
0.00 lin %, 0.00 %
AI FB1 damping
0s
Block adjustment
Released
Language
Like order
Displayed value
SV 1
Backlight
Switched off
%
100.00 lin %, 100.00 %
36537-EN-140209
52
VEGAPULS 68 • Profibus PA
6 Set up with the display and adjustment module
Menu
Menu item
Default value
Additional adjustments
Distance unit
m
Temperature unit
°C
Unit SV2
m
Probe length
Length of the standpipe Ex factory
Linearisation
curve
Linear
Sensor address
126
6.4
Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,
the data in the sensor can be saved in the display and adjustment
module. The procedure is described in the operating instructions
manual "Display and adjustment module" in the menu item "Copy
sensor data". The data remain there permanently even if the sensor
power supply fails.
The following data or settings for adjustment of the display and adjustment module are saved:
•
•
•
All data of the menu "Setup" and "Display"
In the menu "Additional adjustments" the items "Sensor-specific
units, temperature unit and linearization"
The values of the user programmable linearization curve
36537-EN-140209
The function can also be used to transfer settings from one instrument to another instrument of the same type. If it is necessary to
exchange a sensor, the display and adjustment module is inserted
into the replacement instrument and the data are likewise written into
the sensor via the menu item "Copy sensor data".
VEGAPULS 68 • Profibus PA
53
7 Setup with PACTware
7
7.1
Setup with PACTware
Connect the PC
Via the interface adapter
directly on the sensor
2
1
3
Fig. 41: Connection of the PC directly to the sensor via the interface adapter
1 USBcabletothePC
2 InterfaceadapterVEGACONNECT
3 Sensor
Prerequisites
7.2
Parameter adjustment
For parameter adjustment of the sensor via a Windows PC, the configuration software PACTware and a suitable instrument driver (DTM)
according to FDT standard are required. The up-to-date PACTware
version as well as all available DTMs are compiled in a DTM Collection. The DTMs can also be integrated into other frame applications
according to FDT standard.
Note:
To ensure that all instrument functions are supported, you should
always use the latest DTM Collection. Furthermore, not all described
functions are included in older firmware versions. You can download
the latest instrument software from our homepage. A description of
the update procedure is also available in the Internet.
Further setup steps are described in the operating instructions manual "DTMCollection/PACTware" attached to each DTM Collection and
which can also be downloaded from the Internet. Detailed descriptions are available in the online help of PACTware and the DTMs.
36537-EN-140209
54
VEGAPULS 68 • Profibus PA
7 Setup with PACTware
Fig.42:ExampleofaDTMview
Standard/Full version
All device DTMs are available as a free-of-charge standard version
and as a full version that must be purchased. In the standard version,
all functions for complete setup are already included. An assistant for
simple project configuration simplifies the adjustment considerably.
Saving/printing the project as well as import/export functions are also
part of the standard version.
In the full version there is also an extended print function for complete
project documentation as well as a save function for measured value
and echo curves. In addition, there is a tank calculation program as
well as a multiviewer for display and analysis of the saved measured
value and echo curves.
The standard version is available as a download under
www.vega.com/downloads and "Software". The full version is available on CD from the agency serving you.
7.3
Saving the parameter adjustment data
36537-EN-140209
We recommend documenting or saving the parameter adjustment
data via PACTware. That way the data are available for multiple use or
service purposes.
VEGAPULS 68 • Profibus PA
55
8 Set up with other systems
8
8.1
Set up with other systems
DD adjustment programs
Device descriptions as Enhanced Device Description (EDD) are
available for DD adjustment programs such as, for example, AMS™
and PDM.
The files can be downloaded at www.vega.com/downloads under
"Software".
36537-EN-140209
56
VEGAPULS 68 • Profibus PA
9 Diagnosis, asset management and service
9
Diagnosis, asset management and service
9.1
Maintenance
If the device is used correctly, no maintenance is required in normal
operation.
In some applications, buildup on the antenna system can influence
the measuring result. Depending on the sensor and application, make
arrangements to avoid strong pollution of the antenna system. If necessary, clean the antenna system in certain intervals.
9.2
Measured value and event memory
The instrument has several memories which are available for diagnosis purposes. The data remain even with voltage interruption.
Measured value memory
Up to 60,000 measured values can be stored in the sensor in a ring
memory. Each entry contains date/time as well as the respective
measured value. Storable values are for example:
•
•
•
•
•
•
•
•
Distance
Filling height
Percentage value
Lin. percent
Scaled
Current value
Meas. reliability
Electronics temperature
When the instrument is shipped, the measured value memory is
active and stores distance, measurement certainty and electronics
temperature every 3 minutes.
The requested values and recording conditions are set via a PC with
PACTware/DTM or the control system with EDD. Data are thus read
out and also reset.
Event memory
Up to 500 events are automatically stored with a time stamp in the
sensor (non-deletable). Each entry contains date/time, event type,
event description and value. Event types are for example:
•
•
•
•
Modification of a parameter
Switch-on and switch-off times
Status messages (according to NE 107)
Error messages (according to NE 107)
36537-EN-140209
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
Echo curve memory
The echo curves are stored with date and time and the corresponding
echo data. The memory is divided into two sections:
Echo curve of the setup: This is used as reference echo curve for
the measurement conditions during setup. Changes in the measurement conditions during operation or buildup on the sensor can thus
be recognized. The echo curve of the setup is stored via:
VEGAPULS 68 • Profibus PA
57
9 Diagnosis, asset management and service
•
•
•
PC with PACTware/DTM
Control system with EDD
Display and adjustment module
•
•
PC with PACTware/DTM
Control system with EDD
Further echo curves: Up to 10 echo curves can be stored in a ring
buffer in this memory section. Further echo curves are stored via:
9.3
Asset Management function
The instrument features self-monitoring and diagnostics according
to NE 107 and VDI/VDE 2650. In addition to the status messages in
the following tables there are more detailed error messages available
under the menu item "Diagnostics" via the display and adjustment
module, PACTware/DTM and EDD.
Status messages
The status messages are divided into the following categories:
•
•
•
•
Failure
Function check
Out of specification
Maintenance requirement
and explained by pictographs:
1
2
3
4
Fig. 43: Pictographs of the status messages
1
2
3
4
Failure - red
Outofspecification-yellow
Function check - orange
Maintenance - blue
Failure: Due to a malfunction in the instrument, a failure message is
outputted.
This status message is always active. It cannot be deactivated by the
user.
Function check: The instrument is in operation, the measured value
is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
58
VEGAPULS 68 • Profibus PA
36537-EN-140209
Outofspecification: The measured value is unstable because the
instrument specification is exceeded (e.g. electronics temperature).
9 Diagnosis, asset management and service
Maintenance: Due to external influences, the instrument function
is limited. The measurement is affected, but the measured value is
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Failure (failure)
The following table shows the codes and text messages of the status
message "Failure" and provides information on causes as well as
corrective measures.
Code
Cause
F013
– Sensor does not
– Check or correct
Bit 0
detect an echo during
installation and/or
operation
parameter adjustment
– Antenna system con- – Clean or exchange
taminated or defective
process component or
antenna
F017
– Adjustment not within
specification
F025
– Index markers are not – Check linearization
continuously rising, for
table
example illogical value – Delete table/Create
pairs
new
Bit 2
F036
– Failed or interrupted
software update
– Repeat software
update
– Check electronics
version
– Exchanging the electronics
– Send instrument for
repair
Bit 3
F040
– Hardware defect
– Exchanging the electronics
– Send instrument for
repair
Bit 4
F080
– General software error – Disconnect operating
voltage briefly
Bit 5
F105
– The instrument is still – Wait for the end of the Bit 6
in the start phase, the
switch-on phase
measured value could – Duration depending
not yet be determined
on the version and
parameter adjustment
up to approximately
3 min.
Text message
no measured value
available
Adjustment
span too
small
Error in the
linearization table
No operable
software
Error in the
electronics
36537-EN-140209
Determine
measured
value
VEGAPULS 68 • Profibus PA
Rectification
PA DevSpec
Diagnosis
– Change adjustment
according to the limit
values (difference
between min. and
max. ≥ 10 mm)
Bit 1
59
9 Diagnosis, asset management and service
Code
Text message
Cause
– Error in the internal
instrument communiCommunication
cation error
Bit 7
– Temperature of the
– Check ambient temelectronics in the nonperature
specified section
– Isolate electronics
– Use instrument with
higher temperature
range
Bit 8
F260
– Error in the calibration carried out in the
factory
– Error in the EEPROM
– Exchanging the electronics
– Send instrument for
repair
Bit 9
– Repeat setup
– Repeat reset
Bit 10
Error in the
calibration
F261
– Error during setup
Error in the – False signal suppression faulty
configura– Error when carrying
tion
out a reset
F264
– Adjustment not within – Check or correct
Bit 11
the vessel height/
installation and/or
measuring range
parameter adjustment
– Max. measuring range – Use an instrument
of the instrument not
with bigger measuring
sufficient
range
F265
– Sensor no longer
– Check operating
carries out a measurevoltage
ment
– Carry out a reset
– Operating voltage
– Disconnect operating
too low
voltage briefly
Installation/Setup
error
Measurement
function
disturbed
Bit 12
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Code
Cause
Rectification
C700
– A simulation is active
– Finish simulation
– Wait for the automatic end
after 60 mins.
Text message
Simulation active
The following table shows the error codes and text messages in the
status message "Outofspecification" and provides information on
causes as well as corrective measures.
VEGAPULS 68 • Profibus PA
36537-EN-140209
60
– Disconnect operating
voltage briefly
– Send instrument for
repair
F125
Impermissible
electronics
temperature
Outofspecification
PA DevSpec
Diagnosis
F113
Function check
Rectification
9 Diagnosis, asset management and service
Code
Cause
Rectification
S600
– Temperature of the electronics in the non-specified
section
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
S601
– Danger of vessel overfilling
– Make sure that there is no
further filling
– Check level in the vessel
S603
– Operating voltage below
specified range
– Check electrical connection
– if necessary, increase
operating voltage
Text message
Impermissible electronics
temperature
Overfilling
Impermissible operating
voltage
Maintenance
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
Code
Cause
Rectification
M500
– With the reset to delivery
status, the data could not
be restored
– Repeat reset
– Load XML file with sensor
data into the sensor
M501
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M502
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M503
Reliability too
low
– The echot/noise ratio is the
small for a reliable measurement
– Check installation and
process conditions
– Clean the antenna
– Change polarisation direction
– Use instrument with higher
sensitivity
M504
– Hardware defect
– Check connections
– Exchanging the electronics
– Send instrument for repair
Text message
Error with the
reset delivery
status
Error in the
non-active
linearization
table
Error in the
diagnosis
memory
36537-EN-140209
Error on an
device interface
VEGAPULS 68 • Profibus PA
61
9 Diagnosis, asset management and service
Code
Cause
Rectification
M505
– Level echo can no longer
be detected
– Clean the antenna
– Use a more suitable
antenna/sensor
– Remove possible false
echoes
– Optimize sensor position
and orientation
Text message
No echo available
9.4
Rectify faults
Reaction when malfunctions occur
The operator of the system is responsible for taking suitable measures to rectify faults.
Procedure for fault rectification
The first measures are:
•
•
•
Evaluation of fault messages, for example via the display and
adjustment module
Checking the output signal
Treatment of measurement errors
Further comprehensive diagnostics options are available with a PC
with PACTware and the suitable DTM. In many cases, the reasons can
be determined in this way and faults rectified.
Treatment of measurement errors with bulk
solids
The below tables show typical examples for application-relevant
measurement errors with bulk solids. There are two measurement
errors:
•
•
•
Constant level
Filling
Emptying
Level
The images in column "Errorpattern" show the real level with a broken line and the level displayed by the sensor as a continuous line.
1
2
0
1
2
time
Real level
Level displayed by the sensor
•
•
62
Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"
In case of a too low level indication, the reason could be a line
resistance that is too high
VEGAPULS 68 • Profibus PA
36537-EN-140209
Notes:
9 Diagnosis, asset management and service
Measurement error with constant level
1. Measured value
shows a too low or too
high level
Error pattern
Level
Fault description
2. Measured value
jumps towards 100 %
0
Rectification
– Adapt min./max. adjustment
– Wrong linearization curve
– Adapt linearization curve
– Due to the process, the amplitude of the product echo sinks
– A false signal suppression was
not carried out
– Carry out a false signal suppression
– Amplitude or position of a
false echo has changed (e.g.
condensation, buildup); false
signal suppression no longer
matches
– Determine the reason for the
changed false echoes, carry
out false signal suppression,
e.g. with condensation
Cause
Rectification
time
Level
0
Cause
– Min./max. adjustment not
correct
time
Measurementerrorduringfilling
3. Measured value
jumps towards 0 %
during filling
Error pattern
Level
Fault description
0
time
– Amplitude of a multiple echo
– Check parameter "Application",
(vessel top - product surface) is
especially vessel top, type
larger than the level echo
of medium, dished end, high
dielectric constant, adapt if
necessary
– The level echo cannot be distin- – Remove/reduce false echo:
guished from the false echo at
minimize interfering installaa false echo position (jumps to
tions by changing the polarizamultiple echo)
tion direction
– Chose a more suitable installation position
4. Measured value fluctuates around
10 … 20 %
Level
– Transverse reflection from an
extraction funnel, amplitude of
the transverse reflection larger
than the level echo
0
time
– Various echoes from an uneven – Check parameter "Type of
product surface, e.g. a material
medium" and adapt, if necescone
sary
– Optimize installation position
and sensor orientation
36537-EN-140209
Level
– Reflections from the product
surface via the vessel wall
(deflection)
5. Measured value
jumps sporadically to
100 % during filling
0
VEGAPULS 68 • Profibus PA
time
– Direct sensor to the opposite
funnel wall, avoid crossing with
the filling stream
– Select a more suitable installation position, optimize sensor
orientation, e.g. with a swivelling holder
– Changing condensation or con- – Carry out a false signal suptamination on the antenna
pression or increase false
signal suppression with condensation/contamination in the
close range by editing
– With bulk solids use radar sensor with purging air connection
or flexible antenna cover
63
9 Diagnosis, asset management and service
Measurement error during emptying
7. Measured value
jumps sporadically towards 100 % during
emptying
8. Measured value fluctuates around
10 … 20 %
Level
Error pattern
0
time
Level
6. Measured value remains unchanged in
the close range during
emptying
0
time
Level
Fault description
0
time
Cause
Rectification
– False echo larger than the level – Remove false echoes in the
echo
close range. Check: Antenna
must protrude out of the socket
– Level echo too small
– Remove contamination on the
antenna
– Minimize interfering installations in the close range by
changing the polarization
direction
– After removing the false echoes, the false signal suppression must be deleted. Carry out
a new false signal suppression
– Changing condensation or con- – Carry out false signal supprestamination on the antenna
sion or increase false signal
suppression in the close range
by editing
– With bulk solids use radar sensor with purging air connection
or flexible antenna cover
– Various echoes from an uneven – Check parameter "Type of
product surface, e.g. an extracmedium" and adapt, if necestion funnel
sary
– Optimize installation position
– Reflections from the product
and sensor orientation
surface via the vessel wall
(deflection)
Reaction after fault rectification
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
24 hour service hotline
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven
days a week around the clock.
Since we offer this service worldwide, the support is provided in
English. The service itself is free of charge, the only costs involved are
the normal call charges.
9.5
Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with appropriate Ex approval may be used.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
64
VEGAPULS 68 • Profibus PA
36537-EN-140209
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electronics modules are adapted to the respective sensor and differ in signal
output or voltage supply.
9 Diagnosis, asset management and service
•
•
In the factory
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside
of the housing as well as on the delivery note.
When loading on site, first of all the order data must be downloaded
from the Internet (see operating instructions manual "Electronics
module").
9.6
Software update
The following components are required to update the sensor software:
•
•
•
•
•
Sensor
Voltage supply
Interface adapter VEGACONNECT
PC with PACTware
Current sensor software as file
You can find the actual sensor software as well as detailed information of the procedure under "www.vega.com/downloads" and
"Software".
You can find information about the installation in the download file.
Caution:
Instruments with approvals can be bound to certain software versions. Therefore make sure that the approval remains effective with a
software update.
You can find detailed information on www.vega.com/downloads and
"Approvals".
9.7
How to proceed if a repair is needed
You can find a repair form as well as detailed information on how to
proceed under www.vega.com/downloads and "Formsandcertificates".
By doing this you help us carry out the repair quickly and without having to call back for needed information.
If a repair is necessary, please proceed as follows:
•
•
•
36537-EN-140209
•
VEGAPULS 68 • Profibus PA
Print and fill out one form per instrument
Clean the instrument and pack it damage-proof
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
Please contact the agency serving you to get the address for
the return shipment. You can find the agency on our home page
www.vega.com.
65
10 Dismounting
10 Dismounting
10.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process conditions such
as e.g. pressure in the vessel or pipeline, high temperatures, corrosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to power supply"
and carry out the listed steps in reverse order.
10.2 Disposal
The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have
designed the parts to be easily separable.
Correct disposal avoids negative effects on humans and the environment and ensures recycling of useful raw materials.
Materials: see chapter "Technicaldata"
If you have no way to dispose of the old instrument properly, please
contact us concerning return and disposal.
WEEE directive 2002/96/EG
This instrument is not subject to the WEEE directive 2002/96/EG and
the respective national laws. Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting
points. These may be used only for privately used products according
to the WEEE directive.
36537-EN-140209
66
VEGAPULS 68 • Profibus PA
11 Supplement
11 Supplement
11.1 Technical data
General data
316L corresponds to 1.4404 or 1.4435
Materials, wetted parts
Ʋ Process fitting
316L, Hastelloy C22, Monell Alloy
Ʋ Antenna
316L, Hastelloy C22, Tantalum, 316L electropolished,
stainless steel investment casting 1.4848, Monell Alloy,
316L Safecoat coated
Ʋ Process seal
Ʋ Antenna impedance cone
Ʋ seal, antenna system
Materials, non-wetted parts
Ʋ Plastic housing
Ʋ Aluminium die-casting housing
Ʋ Stainless steel housing
Ʋ Seal between housing and housing
cover
Ʋ Inspection window in housing cover
(optional)
Ʋ Ground terminal
Ohmic contact
Process fittings
On site (instruments with thread: Klingersil C-4400 is
attached)
PTFE TFM 1600 or PTFE INOFLON M290, PP, PEEK,
ceramic (99.7 % Al2O3)
FKM (SHS FPM 70C3 GLT), FFKM (Kalrez 6375), FFKM
(Kalrez 2035), FFKM (Kalrez 6230 - FDA), graphite
(99.9 %)
plastic PBT (Polyester)
Aluminium die-casting AlSi10Mg, powder-coated - basis:
Polyester
316L
NBR (stainless steel housing, precision casting), silicone
(aluminium/plastic housing; stainless steel housing,
electropolished)
Polycarbonate
316L
Between ground terminal, process fitting and antenna
Ʋ Pipe thread, cylindrical (ISO 228 T1)
G1½ according to DIN 3852-A
Ʋ Flanges
DIN from DN 25, ANSI from 1"
Ʋ American pipe thread, tapered
Weights
Ʋ Instrument (depending on housing,
process fitting and antenna)
Ʋ Antenna extension
Length antenna extension max.
1½ NPT, 2 NPT
approx. 2 … 17.2 kg (4.409 … 37.92 lbs)
1.6 kg/m (1.157 lbs/ft)
5.85 m (19.19 ft)
36537-EN-140209
Torque for NPT cable glands and Conduit tubes
Ʋ Plastic housing
Ʋ Aluminium/Stainless steel housing
VEGAPULS 68 • Profibus PA
max. 10 Nm (7.376 lbf ft)
max. 50 Nm (36.88 lbf ft)
67
11 Supplement
Input variable
Measured variable
The measured quantity is the distance between process
fitting of the sensor and product surface. The reference
plane is the seal surface on the hexagon or the lower
side of the flange.
1
3
4
2
Fig. 53: Data of the input variable
1
2
3
4
Reference plane
Measured variable, max. measuring range
Antenna length
Usefulmeasuringrange
Max. measuring range
75 m (246.1 ft)
Recommended meas. range depending on the antenna diameter
Ʋ ø 40 mm (1.575 in)
up to 15 m (49.21 ft)
Ʋ ø 75 mm (2.953 in)
up to 40 m (131.2 ft)
Ʋ ø 48 mm (1.89 in)
Ʋ ø 95 mm (3.74 in)
Ʋ Parabolic antenna
up to 20 m (65.62 ft)
up to 50 m (164 ft)
up to 75 m (246.1 ft)
Output variable
Output signal
digital output signal, format according to IEEE-754
Damping (63 % of the input variable)
0 … 999 s, adjustable
Number of FBs with AI (function blocks
with analogue input)
3
Profibus PA profile
68
126 (default setting)
36537-EN-140209
Sensor address
3.02
VEGAPULS 68 • Profibus PA
11 Supplement
Default values
Ʋ 1. FB
PV
Ʋ 3. FB
SV 2
Ʋ 2. FB
SV 1
Current value
Ʋ Non-Ex and Ex ia instrument
10 mA, ±0.5 mA
Ʋ Ex-d instruments
16 mA, ±0.5 mA
Resolution, digital
< 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Ʋ Min. distance to installations
> 200 mm (7.874 in)
Ʋ False reflections
Biggest false signal, 20 dB smaller than the useful signal
Ʋ Relative humidity
45 … 75 %
Installation reference conditions
Ʋ Reflector
Plane plate reflector
Deviation with liquids
See following diagrams
10 mm (0.394 in)
2 mm (0.079 in)
0
- 2 mm (- 0.079 in)
1,0 m (3.28 ft)
- 10 mm (- 0.394 in)
1 2
3
Fig. 54: Deviation under reference conditions
1
2
3
Reference plane
Antenna edge
Recommended measuring range
Repeatability
≤ ±1 mm
Deviation under EMC influence
≤ ±30 mm
36537-EN-140209
Deviation with bulk solids
The values depend to a great extent on the application.
Binding specifications are thus not possible.
Variablesinfluencingmeasurementaccuracy
Temperature drift - Digital output
±3 mm/10 K relating to the max. measuring range or
max. 10 mm
VEGAPULS 68 • Profibus PA
69
11 Supplement
Additional deviation through electromag- < ±50 mm
netic interference acc. to EN 61326
Characteristics and performance data
Measuring frequency
K-band (26 GHz technology)
Measuring cycle time approx.
Step response time
700 ms
≤3s
1)
Beam angle2)
Ʋ Horn antenna ø 40 mm (1.575 in)
20°
Ʋ Horn antenna ø 75 mm (2.953 in)
10°
Ʋ Horn antenna ø 48 mm (1.89 in)
Ʋ Horn antenna ø 95 mm (3.74 in)
Ʋ Parabolic antenna
15°
8°
3°
Emitted HF power (depending on the parameter adjustment)3)
Ʋ Average spectral transmission power
density
Ʋ Max. spectral transmission power
density
Ʋ Max. power density in a distance of
1m
-14 dBm/MHz EIRP
+43 dBm/50 MHz EIRP
< 1 µW/cm²
Ambient conditions
Ambient, storage and transport tempera- -40 … +80 °C (-40 … +176 °F)
ture
Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value
always applies.
Seal
Antenna impedance
cone
Process temperature (measured on the process
fitting)
FKM (SHS FPM 70C3
GLT)
PTFE
-40 … +130 °C (-40 … +266 °F)
FFKM (Kalrez 6375)
FFKM (Kalrez 2035)
2)
3)
4)
5)
70
-40 … +200 °C (-40 … +392 °F)
PEEK5)
-40 … +200 °C (-40 … +392 °F)
PTFE
-20 … +130 °C (-4 … +266 °F)
PEEK
-20 … +250 °C (-4 … +482 °F)
PTFE
-15 … +130 °C (5 … +266 °F)
PEEK
-15 … +210 °C (5 … +410 °F)
PTFE
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).
Outside the specified beam angle, the energy of the radar signal has a level which is reduced by 50 % (-3 dB)
EIRP: Equivalent Isotropic Radiated Power
Not with steam
Not with steam
VEGAPULS 68 • Profibus PA
36537-EN-140209
1)
4)
11 Supplement
Seal
Antenna impedance
cone
Process temperature (measured on the process
fitting)
FFKM (Kalrez 6230)
PTFE
-15 … +130 °C (5 … +266 °F)
PEEK
-15 … +250 °C (5 … +482 °F)
Graphite
Ceramic
-196 … +450 °C (-321 … +842 °F)
Graphite (process fitting
Hastelloy C 22)
Ceramic
-196 … +400 °C (-321 … +752 °F)
Vessel pressure - horn antenna
Ʋ Antenna impedance cone PTFE
-1 … 40 bar (-100 … 4000 kPa/-14.5 … 580 psig)
Ʋ Antenna impedance cone PEEK
-1 … 100 bar (-100 … 10000 kPa/-14.5 … 1450 psig)
Ʋ Antenna impedance cone PP
-1 … 3 bar (-100 … 300 kPa/-14.5 … 43.5 psig)
Ʋ Antenna impedance cone ceramic
-1 … 160 bar (-100 … 16000 kPa/-14.5 … 2320 psig)
Vessel pressure - parabolic antenna
-1 … 6 bar (-100 … 6000 kPa/-14.5 … 870 psig)
Vessel pressure relating to the flange
nominal stage
see supplementary instructions manual "Flanges accordingtoDIN-EN-ASME-JIS"
Vessel pressure with swivelling holder
-1 … 1 bar (-100 … 100 kPa/-14.5 … 14.5 psig)
Vibration resistance
Ʋ Horn antenna
4 g at 5 … 200 Hz according to EN 60068-2-6 (vibration
with resonance)
Ʋ Parabolic antenna
1 g at 5 … 200 Hz according to EN 60068-2-6 (vibration
with resonance)
Shock resistance
Ʋ Horn antenna
100 g, 6 ms according to EN 60068-2-27 (mechanical
shock)
Ʋ Parabolic antenna
25 g, 6 ms according to EN 60068-2-27 (mechanical
shock)
Data on rinsing air connection
Max. permissible pressure
6 bar (87.02 psig)
36537-EN-140209
Air volume with horn antenna, depending on pressure (recommended area)
Pressure
Withoutrefluxvalve
Withrefluxvalve
0.5 bar (7.25 psig)
3.3 m3/h
1.2 m3/h
0.6 bar (8.70 psig)
3.5 m3/h
1.4 m3/h
0.7 bar (10.15 psig)
3.7 m3/h
1.7 m3/h
0.8 bar (11.60 psig)
3.9 m /h
1.8 m3/h
0.9 bar (13.05 psig)
4.0 m /h
2.1 m3/h
1 bar (14.5 psig)
4.2 m3/h
2.2 m3/h
1.5 bar (21.76 psig)
5.0 m3/h
3.2 m3/h
2 bar (29.0 psig)
5.5 m /h
4.5 m3/h
3
3
3
Air volume with parabolic antenna, depending on pressure (recommended area)
VEGAPULS 68 • Profibus PA
71
11 Supplement
Pressure
Withoutrefluxvalve
Withrefluxvalve
0.5 bar (7.25 psig)
3.0 m3/h
1.2 m3/h
0.6 bar (8.70 psig)
3.2 m3/h
1.4 m3/h
0.7 bar (10.15 psig)
3.4 m /h
1.7 m3/h
0.8 bar (11.60 psig)
3.5 m /h
1.9 m3/h
0.9 bar (13.05 psig)
3.6 m3/h
2.0 m3/h
1 bar (14.5 psig)
3.8 m3/h
2.2 m3/h
1.5 bar (21.76 psig)
4.3 m /h
3.5 m3/h
2 bar (29.0 psig)
4.8 m /h
4.0 m3/h
3
3
3
3
Thread
Closure with
Ʋ Non-Ex
Ʋ Ex
G⅛
Dust protection cover of PE
Threaded plug of 316Ti
Reflux valve - unmounted (as option with non-Ex version, included in the scope of delivery with Ex
version)
Ʋ Material
Ʋ Seal
Ʋ for tube diameter
Ʋ opening pressure
Ʋ Nominal pressure stage
316Ti
FKM (SHS FPM 70C3 GLT), FFKM (Kalrez 6375)
6 mm
0.5 bar (7.25 psig)
PN 250
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Options of the cable entry
Ʋ Cable gland
M20 x 1.5 (cable: ø 5 … 9 mm)
Ʋ Blind plug
M20 x 1.5; ½ NPT
Ʋ Cable entry
Ʋ Closing cap
Plug options
Ʋ Signal circuit
Ʋ Indication circuit
½ NPT
M20 x 1.5; ½ NPT
Plug M12 x 1, according to ISO 4400, Harting HAN,
7/8" FF
M12 x 1 plug
Wire cross-section (spring-loaded terminals)
Ʋ Massive wire, cord
Ʋ Stranded wire with end sleeve
0.2 … 2.5 mm² (AWG 24 … 14)
0.2 … 1.5 mm² (AWG 24 … 16)
Ʋ Cable gland with integrated connection cable
M20 x 1.5 (cable: ø 5 … 9 mm)
Ʋ Blind plug
M20 x 1.5; ½ NPT
Ʋ Cable entry
72
½ NPT
VEGAPULS 68 • Profibus PA
36537-EN-140209
Electromechanical data - version IP 66/IP 68 (1 bar)
Options of the cable entry
11 Supplement
Connection cable
Ʋ Wire cross-section
0.5 mm² (AWG 20)
Ʋ Wire resistance
< 0.036 Ω/m
Ʋ Standard length
5 m (16.4 ft)
Ʋ Tensile strength
Ʋ Max. length
Ʋ Min. bending radius
Ʋ Diameter approx.
Ʋ Colour - Non-Ex version
Ʋ Colour - Ex-version
Display and adjustment module
Display element
Measured value indication
Ʋ Number of digits
Ʋ Size of digits
Adjustment elements
Protection rating
Ʋ unassembled
< 1200 N (270 lbf)
180 m (590.6 ft)
25 mm (0.984 in) with 25 °C (77 °F)
8 mm (0.315 in)
Black
Blue
Display with backlight
5
W x H = 7 x 13 mm
4 keys
IP 20
Ʋ mounted into the housing without
cover
IP 40
Ʋ Housing
ABS
Materials
Ʋ Inspection window
Polyester foil
Interface to the external display and adjustment unit
Data transmission
digital (I²C-Bus)
Configuration, connection cable
4-wire, screened
Integrated clock
Date format
Day.Month.Year
Time zone Ex factory
CET
Cable length max.
Time format
Rate deviation max.
25 m
12 h/24 h
10.5 min/year
36537-EN-140209
Measurement electronics temerature
Resolution
1 °C (1.8 °F)
Accuracy
Voltage supply
Operating voltage
Ʋ Non-Ex instrument
VEGAPULS 68 • Profibus PA
±1 °C (1.8 °F)
9 … 32 V DC
73
11 Supplement
Ʋ Ex-ia instrument - Power supply
FISCO model
Ʋ Ex-ia instrument - Power supply
ENTITY model
9 … 17.5 V DC
9 … 24 V DC
Ʋ Ex-d-ia instrument
14 … 32 V DC
Ʋ Non-Ex
32
Number of sensors per DP/PA segment coupler, max.
Ʋ Ex
10
Electrical protective measures
Protection rating
Housing material
Version
IP-protection class
NEMA protection
Plastic
Single chamber
IP 66/IP 67
NEMA 4X
Double chamber
IP 66/IP 67
NEMA 4X
Single chamber
IP 66/IP 68 (0.2 bar)
NEMA 6P
Double chamber
IP 66/IP 67
NEMA 4X
Aluminium
IP 68 (1 bar)
IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)
Stainless steel, electropolished
NEMA 6P
NEMA 6P
NEMA 6P
Single chamber
IP 66/IP 68 (0.2 bar)
NEMA 6P
Stainless steel, investment Single chamber
casting
IP 66/IP 68 (0.2 bar)
NEMA 6P
IP 66/IP 67
NEMA 4X
IP 68 (1 bar)
NEMA 6P
IP 68 (1 bar)
Double chamber
Overvoltage category
Protection class
IP 66/IP 68 (0.2 bar)
NEMA 6P
NEMA 6P
III
III
Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded under www.vega.com, "VEGATools"
and "Instrument search" as well as via www.vega.com/downloads and "Approvals".
Overvoltage protection
Max. permissible current per circuit
0.6 A
Li per circuit
0 mH
Ci per circuit
Response voltage
Response time
74
< 3.6 Ω
36537-EN-140209
Ri per circuit
0 nF
41 V DC
< 10-11 s
VEGAPULS 68 • Profibus PA
11 Supplement
Nominal leakage current
< 10 kA (8/20 µs)
11.2 CommunicationProfibusPA
Instrumentmasterfile
The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.
These data are, e.g. the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automatically when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instrument in the configuration tool.
ID number
Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user
organisation (PNO). This ID number is also included in the name of the GSD file. Optionally to this
manufacturer-specific GSD file, PNO provides also a general so-called profile-specific GSD file. If
the general GSD file is used, the sensor must be set to the profile-specific ident number via the DTM
software. By default, the sensor operates with the manufacturer-specific ID number. When using the
instruments on a segment coupler SK-2 or SK-3, no special GSD files are required.
The following table shows the instrument ID and the GSD file names for VEGAPULS radar sensors.
Device name
Instrument ID
GSDfilename
VEGA
Instrument class in VEGA
profile3.02
Profile-specific
VEGAPULS WL 61
0x0CDB
0x9702
PS61WL0CDB.GSD PA139702.GSD
VEGAPULS 61
0x0BFC
0x9702
PS610BFC.GSD
PA139702.GSD
VEGAPULS 62
0x0BFD
0x9702
PS620BFD.GSD
PA139702.GSD
VEGAPULS 63
0x0BFE
0x9702
PS630BFE.GSD
PA139702.GSD
VEGAPULS 65
0x0BFF
0x9702
PS650BFF.GSD
PA139702.GSD
VEGAPULS 66
0x0C00
0x9702
PS660C00.GSD
PA139702.GSD
VEGAPULS 67
0x0C01
0x9702
PS670C01.GSD
PA139702.GSD
VEGAPULS SR 68
0x0CDC
0x9702
PS68R0CDC.GSD
PA139702.GSD
VEGAPULS 68
0x0C02
0x9702
PS680C02.GSD
PA139702.GSD
Cyclicaldatatraffic
36537-EN-140209
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during operation. The below block diagram below shows which data can be accessed by the PLC.
VEGAPULS 68 • Profibus PA
75
11 Supplement
Fig.55:VEGAPULS68:BlockdiagramwithAIFB1…AIFB3OUTvalues
TB TransducerBlock
FB1…FB3
FunctionBlock
Module of the PA sensors
For the cyclic data traffic, VEGAPULS 68 provides the following modules:
•
•
•
•
AI FB1 (OUT)
– Out value of the AI FB1 after scaling
AI FB2 (OUT)
– Out value of the AI FB2 after scaling
AI FB3 (OUT)
– Out value of the AI FB3 after scaling
Free Place
– This module must be used if a value in the data telegram of the cyclical data traffic should not
be used (e.g. replacement of temperature and Additional Cyclic Value)
Note:
The modules are available in two versions:
•
76
Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen
Bradley
VEGAPULS 68 • Profibus PA
36537-EN-140209
A maximum of three modules can be active. By means of the configuration software of the Profibus
master you can determine the configuration of the cyclical data telegram with these modules. The
procedure depends on the respective configuration software.
11 Supplement
•
Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens
S7-300/400
Examplesoftelegramconfiguration
In the following you will see how the modules can be combined and how the appendant data telegram is structured.
Example 1
•
•
•
AI FB1 (OUT)
AI FB2 (OUT)
AI FB3 (OUT)
ByteNo.
1
2
4
5
Format
IEEE-754-Floating point
value
AI FB1 (OUT)
Value
3
6
7
8
9
10
Status
IEEE-754-Floating point
value
AI
FB1
AI FB2 (OUT)
11
12
13
14
15
Status
IEEE-754-Floating point
value
Status
AI
FB2
AI FB3 (OUT)
AI
FB3
Example 2
•
•
•
AI FB1 (OUT)
Free Place
Free Place
Byte-No.
1
2
Format
3
4
5
IEEE-754-Floating point value
Status
AI FB1 (OUT)
AI FB1
Value
Note:
Bytes 6-15 are not used in this example.
Data format of the output signal
Byte4 Byte3 Byte2 Byte1 Byte0
Status
Value (IEEE-754)
Fig. 56: Data format of the output signal
The status byte corresponds to profile 3.02 "Profibus PA Profile for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).
36537-EN-140209
The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.
Byte n+2
Byte n+3
Byte n
Byte n+1
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
VZ 27 26 25 24 23 22 21 20 2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17 2-18 2-19 2-20 2-21 2-22 2-23
Sign
Significant
Significant
Exponent
Significant
Bit
Value = (-1)VZ
2 (Exponent - 127)
(1 + Significant)
Fig. 57: Data format of the measured value
VEGAPULS 68 • Profibus PA
77
11 Supplement
Coding of the status byte associated with the PA output value
You can find further information for the coding of the status byte in the Device Description 3.02 on
www.profibus.com.
Status code
Description according to Possible cause
Profibusstandard
0 x 00
bad - non-specific
Flash-Update active
0 x 04
bad - configuration error
– Adjustment error
– Configuration error with PV-Scale (PV-Span too
small)
– Unit irregularity
– Error in the linearization table
0 x 0C
bad - sensor failure
–
–
–
–
0 x 10
bad - sensor failure
– Measured value generation error
– Temperature measurement error
0 x 1f
bad - out of service constant
"Out of Service" mode switched on
0 x 44
uncertain - last unstable
value
Failsafe replacement value (Failsafe-Mode = "Last value" and already valid measured value since switching
on)
0 x 48
uncertain substitute set
– Switch on simulation
– Failsafe replacement value (Failsafe-Mode = "Fsafe
value")
0 x 4c
uncertain - initial value
Failsafe replacement value (Failsafe-Mode = "Last valid
value" and no valid measured value since switching on)
0 x 51
uncertain - sensor; conversion not accurate - low
limited
Sensor value < lower limit
0 x 52
uncertain - sensor; conSensor value > upper limit
version not accurate - high
limited
0 x 80
good (non-cascade) - OK
OK
0 x 84
good (non-cascade) - active block alarm
Static revision (FB, TB) changed (10 sec. active, after
the parameter of the static category has been written)
0 x 89
good (non-cascade) - active advisory alarm - low
limited
Lo-Alarm
0 x 8a
good (non-cascade) - active advisory alarm - high
limited
Hi-Alarm
0 x 8d
good (non-cascade) - active critical alarm - low
limited
Lo-Lo-Alarm
0 x 8e
good (non-cascade) - active critical alarm - high
limited
Hi-Hi-Alarm
36537-EN-140209
78
Hardware error
Converter error
Leakage pulse error
Trigger error
VEGAPULS 68 • Profibus PA
11 Supplement
11.3 Dimensions
The following dimensional drawings represent only an extract of all possible versions. Detailed
dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".
Plastic housing
~ 69 mm
(2.72")
ø 79 mm
(3.11")
~ 84 mm
(3.31")
ø 79 mm
(3.11")
M20x1,5/
½ NPT
112 mm
(4.41")
112 mm
(4.41")
M16x1,5
M20x1,5/
½ NPT
1
2
Fig.58:HousingversionsinprotectionIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethe
housingis9mm/0.35inhigher
1
2
Single chamber version
Double chamber version
Aluminium housing
~ 116 mm
(4.57")
~ 87 mm
(3.43")
ø 86 mm
(3.39")
ø 86 mm
(3.39")
120 mm
(4.72")
116 mm
(4.57")
M16x1,5
M20x1,5
M20x1,5/
½ NPT
1
M20x1,5/
½ NPT
2
Fig.59:HousingversionsinprotectionIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethe
housingis9mm/0.35inhigher
Single chamber version
Double chamber version
36537-EN-140209
1
2
VEGAPULS 68 • Profibus PA
79
11 Supplement
Aluminium housing in protection rating IP 66/IP 68 (1 bar)
~ 105 mm
(4.13")
~ 150 mm
(5.91")
ø 86 mm
(3.39")
ø 86 mm
(3.39")
120 mm
(4.72")
116 mm
(4.57")
M16x1,5
M20x1,5
M20x1,5
M20x1,5/
½ NPT
1
2
Fig.60:HousingversionsinprotectionIP␣66/IP␣68(1␣bar)-withintegrateddisplayandadjustmentmodulethe
housingis9␣mm/0.35␣inhigher
1
2
Single chamber version
Double chamber version
Stainless steel housing
~ 87 mm
(3.43")
~ 69 mm
(2.72")
ø 79 mm
(3.11")
~ 59 mm
(2.32")
ø 80 mm
(3.15")
ø 86 mm
(3.39")
M20x1,5/
½ NPT
M20x1,5/
½ NPT
1
2
120 mm
(4.72")
112 mm
(4.41")
117 mm
(4.61")
M16x1,5
M20x1,5/
½ NPT
3
Fig.61:HousingversionsinprotectionIP66/IP68(0.2bar)-withintegrateddisplayandadjustmentmodulethe
housingis9mm/0.35inhigher
1
2
3
Single chamber version, electropolished
Single chamber version, precision casting
Double chamber version, precision casting
36537-EN-140209
80
VEGAPULS 68 • Profibus PA
11 Supplement
Stainless steel housing in protection rating IP 66/IP 68, 1 bar
~ 93 mm
(3.66")
~ 103 mm
(4.06")
ø 80 mm
(3.15")
~ 105 mm
(4.13")
ø 79 mm
(3.11")
ø 86 mm
(3.39")
M20x1,5/
½ NPT
120 mm
(4.72")
112 mm
(4.41")
117 mm
(4.61")
M16x1,5
M20x1,5
1
M20x1,5/
½ NPT
2
3
Fig.62:HousingversionsinprotectionIP␣66/IP␣68(1␣bar)-withintegrateddisplayandadjustmentmodulethe
housingis9␣mm/0.35␣inhigher
1
2
3
Single chamber version, electropolished
Single chamber version, precision casting
Double chamber version, precision casting
G1½A / 1½ NPT
x
100
ø40
3"
216
ø75
2"
4"
x
y
1½"
inch
1½"
2"
3"
4"
120
430
y
3.94"
4.72"
8.50"
16.93"
ø48
ø95
x
ø1.58"
ø1.89"
ø2.95"
ø3.74"
y
y
mm
22 mm (0.87")
2
144 mm (5.67")
38 mm (1.50")
1
SW 46 mm
(1.81")
22 mm (0.87")
VEGAPULS 68, horn antenna in threaded version
36537-EN-140209
x
Fig.63:VEGAPULS68,hornantennainthreadedversion
1
2
Standard
With temperature adapter up to 250 °C
VEGAPULS 68 • Profibus PA
81
11 Supplement
VEGAPULS68,hornantennainflangeversion
2
165 mm (6.5")
y
60 mm
(2.36")
1
x
mm
y
x
inch
ø48
2"
1½"
100
ø40
3"
216
ø75
2"
4"
120
430
ø95
1½"
3"
4"
y
3.94"
4.72"
8.50"
16.93"
x
ø1.58"
ø1.89"
ø2.95"
ø3.74"
Fig.64:VEGAPULS68,hornantennainflangeversion
1
2
Standard
With temperature adapter up to 250 °C
36537-EN-140209
82
VEGAPULS 68 • Profibus PA
11 Supplement
260 mm (10.24")
VEGAPULS68,hornantennainflangeversion450°C
y
120
216
287
y
inch
4.72"
2"
3" 8.50"
4" 11.30"
x
ø 48
ø 75
ø 95
y
mm
2"
3"
4"
x
ø 1.89"
ø 2.95"
ø 3.74"
x
36537-EN-140209
Fig.65:VEGAPULS68,hornantennainflangeversionwithtemperatureadapterupto450°C
VEGAPULS 68 • Profibus PA
83
11 Supplement
VEGAPULS 68, horn antenna and swivelling holder
max. 15
°
(0.59")
2
x
100
ø 40
3"
216
ø 75
2"
x
y
1½"
4"
inch
1½"
2"
3"
4"
120
430
y
3.94"
4.72"
8.50"
16.93"
ø 48
ø 95
20 m
m
(0.79
")
mm
x
ø 1.58"
ø 1.89"
ø 2.95"
ø 3.74"
y
y
20 m
m
(0.79
")
146 m
m (5.7
5")
40 m
m
(1.58
")
1
x
Fig.66:VEGAPULS68,hornantennaandswivellingholder
1
2
Standard
With temperature adapter up to 250 °C
36537-EN-140209
84
VEGAPULS 68 • Profibus PA
11 Supplement
VEGAPULS68,hornantennaandswivellingholder,threadedfitting
max. 10°
(0.39")
2
102,2 m
m
(4.02")
159,6 mm
(6.28")
53,6 mm
(2.11")
1
SW 70 mm
(2.76")
G2 / 2NPT
102,2 m
m
(4.02")
ø 40 / 4
8
(1.57" / mm
1.89")
ø 40 / 4
8
(1.57" / mm
1.89")
Fig.67:VEGAPULS68,hornantennaandswivellingholder,threadedfitting
Standard
With temperature adapter up to 250 °C
36537-EN-140209
1
2
VEGAPULS 68 • Profibus PA
85
11 Supplement
VEGAPULS 68, parabolic antenna and swivelling holder
max. 15
°
(0.59")
1
ø 243
130 m
m (5.1
2")
120 m
m (4.7
2")
40 m
m
(1.58
")
2
mm (9
.57")
Fig.68:VEGAPULS68,parabolicantennaandswivellingholder
1
2
Standard
With temperature adapter up to 200 °C
36537-EN-140209
86
VEGAPULS 68 • Profibus PA
11 Supplement
11.4 Industrial property rights
VEGA product lines are global protected by industrial property rights. Further information see
www.vega.com.
Only in U.S.A.: Further information see patent label at the sensor housing.
VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.
Nähere Informationen unter www.vega.com.
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellectuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.
VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad industrial. Para mayor información revise la pagina web www.vega.com.
Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную
собственность. Дальнейшую информацию смотрите на сайте www.vega.com.
VEGA系列产品在全球享有知识产权保护。
进一步信息请参见网站<www.vega.com>。
11.5 Trademark
36537-EN-140209
All the brands as well as trade and company names used are property of their lawful proprietor/
originator.
VEGAPULS 68 • Profibus PA
87
INDEX
INDEX
A
Adjustment 47, 48
Adjustment system 39
Agitator 23
Application
– Bulk solid 44
– Liquid 40
– Standpipe 40
C
Connecting
– Electrically 29
– Mechanically 13
– To the PC 54
Connection
– Steps 29
– Technology 29
Curve indication
– Echo curve 49
– False signal suppression 49
Cyclical data traffic 75
D
Data format, output signal 77
Deviation 62
E
Echo curve memory 57
Echo curve of the setup 49
EDD (Enhanced Device Description) 56
Error codes 60
Event memory 57
F
False signal suppression 49
Fault rectification 62
Functional principle 10
G
GSD file 75
M
Main menu 39
Meas. reliability 48
Measured value memory 57
N
NAMUR NE 107 61
– Failure 59
O
Overfill protection according to WHG 51
P
PA modules 76
Peak value indicator 48
Polarisation 15
R
Reflection properties 40
Repair 65
Replacement parts
– Supplementary electronics Profibus PA 12
S
Service hotline 64
Socket 18
Software addressing 36
Status bytes PA output value 78
Status messages - NAMUR NE 107 58
Subsurface enclosure 25
T
Telegram configuration 77
Type label 8
V
Vessel form 46
Vessel height 46
Vessel installations 23
Vessel insulation 24
H
Hardware addressing 35
36537-EN-140209
I
Instrument address 35
Instrument master file 75
L
Linearisation curve 51
88
VEGAPULS 68 • Profibus PA
36537-EN-140209
Notes
VEGAPULS 68 • Profibus PA
89
Notes
36537-EN-140209
90
VEGAPULS 68 • Profibus PA
36537-EN-140209
Notes
VEGAPULS 68 • Profibus PA
91
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information