Download Mini-MOD and Mini-Extension Installation Manual - Heat
Transcript
L N DHW COMB. Stage G Stage H SYSTEM PUMP AIR Stage A Stage B Stage C Stage D Stage E Stage F Lo 3Hi4 Lo 5 6 7Hi8 9 10 11 12 13 14 Unit1 Unit2 Stages LoStages Hi Lo Hi Unit1 Unit2 Stages Stages 15 16 17 18 19 20 21 22 23 24 1 2 12 Heat-Timer Corp. 25 Warning The PROVE input cannot be used as a safety limit. All equipment must have its own certified limit CAUTION: Risk of Shock.safety Lo Hi Lo HiElectricand Use Copper Conductors Only. controls as required by local codes. No boiler stage will start unless the Prove terminals are shorted. DO NOT Unit1 Unit2 OUTPUT RATING: 6 AMP RESISTIVE, PROGRAM 1 AMP PILOT CAUTION: DUTY PER OUTPUT Electric Shock. Stages Stages RiskATof120VAC. PWR remove the PROVE jumper supplied unless replacing it with a Prove signal. Use Copper Conductors Only. Wiring the System Output (Terminals 19, 20) DHW COMB. Stage G Stage H SYSTEM PUMP AIR L N Stage A Stage B Stage C Stage D Stage E Stage F 1 2 AMP PILOT DUTY PER OUTPUT AT 120VAC. 3 4 5 6 7 8 9 110 11 12 13 14 15 16 17 18 19 20 21 22 23 24 PWR OUTPUT RATING: 6 AMP RESISTIVE, L N DO NOT APP SE RUN PROGRAM TEMP RUN 25 26 27 2 DHW COMB. Stage G Stage H SYSTEM PUMP AIR Stage A Stage B Stage C Stage D Stage E Stage F •The System output has a Normally Open (N.O.) relay that acts as a dry-contact. It does not source any power. CAUTION: Risk of Electric Shock. L •Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring. Use Copper Conductors Only. 1 2 15 16 17 18 19 20 21 22 23 24 3 4 5 6 7 8 9 10 11 12 13 14 DO N OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC. PWR PROGRAM L Stage G Stage HN SYSTEM RUN System Output Operation in Set Point Mode L N 1 2 drops 3 4 below 5 6 7 8the 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 •In Heating, the System output relay will energize whenever the outdoor temperature Outdoor System Cutoff or whenever a stage output is active. If no outdoor sensor is connected and the last boiler relay has dePump System energized, the System relay will remain energized for a period set by the Run-On and then de-energize. L Pump •If the PROVE input is Open, the System relay will remain energized however, all stages will be de-energized. N If a Prove is not required, the factory-installed jumper must remain connected for proper operation. •In Cooling applications, the system relay will energize when the outdoor temperature is above the Outdoor Cutoff setting. •A typical use of the System output is to activate a system pump or its starter. The pumpCAUTION: can runRisk whenever there is a call for of Electric Shock. System Use Copper Conductors Only. DO NOT APPLY Pump heat/cool. When stages are no longer required, the pump will stay active for an adjustable Run-On delay and then PROGRAM de-energize. OUTPUT RATING: 6 AMP RESISTIVE, RUN SENSO Stage A Stage B Stage C Stage D Stage E Stage F DHW COMB. PUMP AIR 1 AMP PILOT CAUTION: DUTY PER OUTPUT ATof 120VAC. Risk Electric Shock. Use Copper Conductors Only. PWR DHW COMB. DO TEMP RUN System Output Operation in Reset Mode 1 2 3 4 5 6 7 8 25 26 27 28 PWR •The System output relay will energize whenever the outdoor temperature is below Lthe Outdoor Cutoff. N •When the outdoor temperature rises 2°F above the Outdoor Cutoff, the System output for set21 22 23 24 1 2 will 3 remain 4 5 6 7 energized 8 9 10 11 12 13 14 the 15 16period 17 18 19 20 CAUTION: Risk of Electric Shock. L by the System Run-On and then de-energize. Use Copper Conductors Only. Stage G Stage H SYSTEM PUMP AIR OUTPUT RATING: 6 AMP RESISTIVE, PROGRAM 19AMP PER 15 OUTPUT 120VAC. 16 17AT18 10 PILOT 11 12DUTY 13 14 19 20 21 22 23 24 L N Stage A Stage B Stage C Stage D Stage E Stage F N Line 120VAC L N Power Source 1 2 Stage A Stage B Stage C Stage D Stage E Stage F DO NO PROGRAM L DHW Stage G Stage H SYSTEM N PUMP RUN COMB. AIR 15 16 17 18 19 20 21 22 23 24 L N DHW Pump DHW Pump Use Copper Conductors Only. PWR Wiring the Combustion Air Damper (Terminals 23, L N 24) 25 2 DHW Pump Neutral Line The SQ-Elite-8T can control the DHW Pump when the DHW Pump Output option is activated from the Startup 120VAC Menu. See page 18. Power Source •The SQ-Elite-8T will energize the DHW Pump whenever there is a call for DHW using a dry contact or when the DHW temperature falls below the DHW Set Point and DHW Differential when using a DHW sensor. •The DHW Pump output relay is a Normally Open (N.O.) dry contact. It does not source any power. 120VAC •Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring. Power Source •If Shutdown was selected as the External Input (page 18), The Sq-Elite-8T will ignore a DHW call when the CAUTION: Risk of Electric Shock. Shutdown is active. 3 4 5 6 7 8 9 10 11 12 13 14 DHW COMB. PUMP AIR Stage G Stage H SYSTEM OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC. PWR Neutral Line Wiring the DHW Pump (Terminals 21, 22) Neutral Stage A Stage B Stage C Stage D Stage E Stage F OUTPUT RATING: 6 AMP RESISTIVE, PROGRAM 1 AMP PILOT CAUTION: DUTY PER OUTPUT ATof 120VAC. Risk Electric Shock. RUN DO NOT APPL SEN Use Copper Conductors Only. Stage A Stage B Stage C Stage D Stage E Stage F DHW COMB. Stage G Stage H SYSTEM PUMP AIR OUTPUT RATING: 6 AMP RESISTIVE, PROGRAM 110 AMP DUTY AT 19 120VAC. 16 17 18 11PILOT 12 13 14 PER 15 OUTPUT 20 21 22 23 24 RUN TEMP 1 2 3 4 5 6 is 7 activated 8 9 25 26 27 28 PWR The SQ-Elite-8T can control the Combustion Air Damper when the Comb. Air Output option in the N Startup Menu (Page 18). In addition, the PROVE input will function as the CombustionL Air Damper status checker. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 2 •The SQ-Elite will energize the Combustion Air Damper relay whenever there is a call to energize any of the CAUTION: Risk of Electric Shock. L Use Copper Conductors Only. unit stages. DO N N OUTPUT RATING: 6 AMP RESISTIVE, PROGRAM RUN 1 AMP PILOT DUTY PER OUTPUT AT 120VAC. •The Combustion Air output relay is a Normally Open (N.O.) dry contact. It doesPWR not source any power. L Lo Hi Lo Hi L N Unit1 N •Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage Unit2 wiring. Stage A Stage B Stage C Stage D Stage E Stage F •The relays are N.O. dry contacts only. They do not source any voltage. L •Wire the N.O. relay contacts in series with the unit’s limit circuit. Unit1 •Class 1 voltages must enter the enclosure through a different knockout from any Class 2Pump voltage wiring. N Wiring the Stage Outputs •Each Stage output (A through H) has one (N.O.) relay. •When wiring several multi-stage units, start with the lower stage of the first unit and wire it to Output A, followed by the higher stage of the same unit and wire it to Stage B. Unit2 Pump DHW COMB. Stage G Stage H SYSTEM PUMP AIR 15 16 17 18 19 20 21 22 23 24 25 2 System Sensor Stage A Stage B Stage C Stage D Stage E Stage F 3 4 5 6 Stages 11 12 13 14 Stages Lo Hi7 8 9 10Lo Hi Unit1 L Unit2 StagesUnit2 Stages Unit1 L Pump Pump Wiring the Stages (Terminals 3 to 17) Unit2 N Unit1 LoPump Hican Lo Pump Hi The SQ-Elite can be configured to operate the stages of the heating or cooling units. Moreover, it PWR Unit1 Unit2L N N be configured to operate the unit pumps or valves in addition to the unit stages. Stages Stages 1 2 1 2 DHW COMB. Stage G Stage H SYSTEM PUMP AIR Comb. Air Damper CAUTION:LRisk ofComb. Electric Shock. Use Copper N Conductors Air Only. OUTPUT RATING: 6 AMP RESISTIVE, Damper 1 AMP PILOT DUTY PER OUTPUT AT 120VAC Stage A Stage B Stage C Stage D Stage E Stage F Stage G S 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 Comb. Air Damper Lo Hi Lo Hi Unit1 Unit2 Stages Stages CAUTION: Risk of Electric Shock. Use Copper Conductors Only. OUTPUT RATING: 6 AMP RESISTIVE, 1 AMP PILOT DUTY PER OUTPUT AT 120VAC