AKD Installation | 9 Electrical Installation
9.14.7.2 FAULT relay contacts
Operational readiness (terminals X8/1 and X8/2 ) is signaled by a floating relay contact.
The fault relay can be programmed to two modes of operation:
- Contact closed when there is no fault
- Contact closed when there is no fault and the drive is enabled.
The signal is not influenced by the enable signal, the I²t-limit, or the regen threshold.
Technical characteristics
l
l
l
FAULT: Relay output, max. 30 Vdc or 42 Vac, 1 A
Time to close: max. 10 ms
Time to open: max. 10 ms
All faults cause the FAULT contact to open and the output stage to be
switched off (if the FAULT contact is open, the output stage is inhibited -> no
power output). List of the fault messages: => p. 171.
Wiring diagram
128
Kollmorgen™ | November 2012