Download Operating Instructions
Transcript
0300 0300 SUBMENU REGULATION 0305 0305 JOG 0.0Hz X.XX Bar Both current output frequency and actual value are shown. • By pressing ▲ or ▼ in this menu, the internal controller of the HYDROVAR will be shut off and the inverter changes to manual mode. • With the ▲ and ▼ buttons any constant speed can be set without influence of the actual value of the control signal! • If this value becomes 0.00 Hz the HYDROVAR stops. • As soon as the window will be left by pressing ◄ or ►, the HYDROVAR restart normal mode. 0310 0310 WINDOW 10 % Possible settings: regulation Window 0 – 100% of required value • Determines the band, where the slow ramp changes to the fast ramp • for steep pump-curves and closed loop systems ~20-30% 0315 0315 HYSTERESIS 80% Possible settings: ramp Hysterics 0 – 100% • Determines the band, where the normal regulation is done (change between the slow ramps) • for an accurate control (without automatic shut-off) ~99%, e.g. constant flow control 0320 0320 REG. MODE normal Possible settings: Regulation mode normal, invers Normal: Speed is increased with falling actual value signals. (e.g.: control at constant output pressure) Inverse: Speed is reduced with falling actual value signal. (e.g.: control at constant suction pressure or at constant level on the suction side) 68