SMA America, LLC Parameters Parameter Name Range Default ChkGdVtgMax 288 ... 332,4 Vrms 332,4 Vrms ChkGdVtgMin ChkGnFrqLo ChkGnFrqLoT ChkGnFrqMax ChkGnFrqMin ChkGnVtgHi ChkGnVtgLo ChkGnVtgMax ChkGnVtgMin Dt Ofs_E-Total Ofs_h-On 138,5 ... 265,9 Hz 138,5 Hz Parameter Description Maximum voltage for Sunny Central operation. If the voltage exceeds the value defined in ChkGdVtgMax, the Sunny Central shuts down immediately. Minimum voltage for Sunny Central operation. If the voltage drops below the value defined at ChkGdVtgMin, the Sunny Central shuts down immediately. Sunny Central operation with a generator. More information on parameter settings and operating the Sunny Central with a generator can be obtained from SMA America. yyyymmdd Current Date. 0 ... 214748364 kWh 0 kWh 0 ... 2147483 h 0h Here you can set the current date. The Sunny Central's total energy yield Changing the Ofs_E_Total parameter may be necessary if you exchange the computer assembly (BFR) of the Sunny Central and want to transfer the data from the old device. The Sunny Central's total number of hours of operation Changing the Ofs_h_On parameter may be necessary if you exchange the computer assembly (BFR) of the Sunny Central and want to transfer the data from the old device. User Manual SCUS-BE-BUS120514 29