Download Operating Instructions - Differential pressure transmitter DPT
Transcript
4 Mounting 1 2 3 + 2 – 4 4 5 5 6 Fig. 19: Measurement setup, flow measurement in liquids 1 Orifice or impact pressure probe 2 Blocking valves 3DPT10 4Precipitator 5 Drain valves 6 3-fold valve block In open vessels with effective pressure line 4.5 Measurement setup level 1. Mount DPT10 below the lower measurement connection so that the effective pressure lines are always filled with liquid 2. Minus side is open to the atmospheric pressure 3. When measuring liquids with solid content, the mounting of separators and drain valves is useful to be able to avoid and remove buildup. patm + min. 4 5 patm 1 2 3 Fig. 20: Measurement setup, level measurement in the open vessel 1DPT10 2 Minus side is open to the atmospheric pressure 3 Blocking valve 4Precipitator 5 Drain valve WIKA Operating Instructions - Differential pressure transmitter DPT-10 21