Download Operating Instructions

Transcript
60
Chapter 9
Configuration and adjustments
[P062] XPH2/XPH2 - Heating Proportional Band 2
Data type
Adjustment range interfaces/ multiplier
Adjustment range BA
Byte
0.0...[9.9]...25.5% / 10
0.0...[9.9]...25.5%
Without function
[P063] TDH2/TDH2 - Heating Derivative Time 2
Data type
Adjustment range interfaces & BA / multiplier
Byte
0...[2]...255 seconds / 1
Without function
[P064] TIH2/TIH2 - Heating Integral Time 2
Data type
Adjustment range interfaces/ multiplier
Adjustment range BA
Word
0...[9]...65535 seconds / 1
0...[9]...1275 seconds
Without function
[P065] TAH2/CTH2 - Heating Sampling Time 2
Data type
Adjustment range interfaces/ multiplier
Adjustment range BA
Byte
[0]...255 seconds / 1
[0]...60 seconds
Without function
[P066] XPK2/XPC2 - Cooling Proportional Band 2
Data type
Adjustment range interfaces/ multiplier
Adjustment range BA
Byte
0.0...[9.9]...25.5% / 10
0.0...[9.9]...25.5%
Without function
[P067] TDK2/TDC2 - Cooling Derivative Time 2
Data type
Adjustment range interfaces & BA / multiplier
Byte
0...[2]...255 seconds / 1
Without function
[P068] TIK2/TIC2 - Cooling Integral Time 2
Data type
Adjustment range interfaces/ multiplier
Adjustment range BA
Word
0...[9]...65535 seconds / 1
0...[9]...1275 seconds
Without function
[P069] TAK2/CTC2 - Cooling Sampling Time 2
Data type
Adjustment range interfaces/ multiplier
Adjustment range BA
Without function
Rev. 1.00.10
Subject to technical changes without notice
Byte
[0]...255 seconds / 1
[0]...60 seconds