Download York DM072 User's Manual

Transcript
036-21502-002-A-0303
®
DESCRIPTION
YORK Sunline 2000™ units are convertible single package
air conditioners with a common cabinet and a common roof
curb for the 3, 4, 5 and 6 ton sizes. The units were designed
for light commercial and commercial applications. They can
easily be installed on a roof curb, slab, roof jack or frame.
TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
AIR CONDITIONERS
DM 036, 048, 060 & 072
3, 4, 5 & 6 NOMINAL TONS
10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)
All units include:
•
Powder Paint finish that meets ASTM-B-117 750 hour
salt spray standards
•
Permanently lubricated motors
•
Bottom or side air discharge configuration capability
(field convertible)
•
Manufactured under the quality standards of ISO9001
•
SimplicityTM Control Board
•
Copper tube/aluminum fin coils
•
Easy access to all components
•
Rigging holes in base rails for lifting
•
Fork lift slots on three sides
•
Single point power connection
•
Complete factory package - tested, charged and wired
•
CSA agency listing on all units
WARRANTY
•
Factory Limited Parts Warranty
•
One-year parts warranty
•
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21502-002-A-0303
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE. . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 9
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 10
9 SUPPLY AIR BLOWER PERFORMANCE (4 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 17
10 SUPPLY AIR BLOWER PERFORMANCE (5 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 18
11 SUPPLY AIR BLOWER PERFORMANCE (6 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 19
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 38
12 SUPPLY AIR BLOWER PERFORMANCE (3 - 6
TON DIRECT DRIVE) . . . . . . . . . . . . . . . . . . . . 20
LIST OF FIGURES
13 BELT DRIVE MOTOR AND DRIVE DATA . . . . . 20
Fig. #
Pg. #
14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . 21
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . 9
15 ELECTRIC HEATER CFM LIMITATIONS. . . . . . 21
2 TYPICAL FIELD POWER & CONTROL
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
16 ELECT DATA - DM036 & 048 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 22
3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . 32
17 ELECT DATA - DM060 & 072 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 23
4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS
HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . 32
18 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 24
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . 33
19 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 25
6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD. . . . . . . . . . . . . . . . . . . . . 33
7 UNIT DIMENSIONS (REAR VIEW). . . . . . . . . . . 34
8 DISCONNECT/BLOWER ACCESS LOCATION . 34
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . 35
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . 36
20 ELECTRICAL DATA - DM036 & 048 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
21 ELECTRICAL DATA - DM060 & 072 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . 37
22 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . 28
LIST OF TABLES
23 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . 29
Tbl. #
Pg. #
24 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 30
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . 11
25 ELECTRIC HEAT CORRECTION FACTORS . . 30
2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . 11
26 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 30
3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . 11
27 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 34
4 DM036 COOLING CAPACITIES (3 TON). . . . . . 12
28 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . 34
5 DM048 COOLING CAPACITIES (4 TON). . . . . . 13
29 DM 4 POINT LOADS WEIGHT DISTRIBUTION . 36
6 DM060 COOLING CAPACITIES (5 TON). . . . . . 14
30 DM 6 POINT LOADS WEIGHT DISTRIBUTION . 36
7 DM072 COOLING CAPACITIES (6 TON). . . . . . 15
31 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . 36
8 SUPPLY AIR BLOWER PERFORMANCE (3 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 16
32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 37
2
Unitary Products Group
036-21502-002-A-0303
PRODUCT NOMENCLATURE
3-6 Ton Sunline Model Number Nomenclature
D M 048 N04 A 2 A AA 1
Product Generation
Product Catagory
1 = First Generation
D = Air Cond., Single Package
B = Heat Pump, Single Package
Voltage
Product Identifier
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
M = R-22 Standard Efficiency (DCG/DCE)
F = R-22 Medium Efficiency (DEG/DEE)
H = R-22 High Efficiency (DHG/DHE)
Q = R-22 Std. Effic Heat Pump (BCH)
Nominal Cooling
Capacity - MBH
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4, & 5
036 = 3 Ton
048 = 4 Ton
060 = 5 Ton
072 = 6 Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N04 = 40 MBH Output Aluminized Steel (036)
N06 = 60 MBH Output Aluminized Steel (048)
N08 = 79 MBH Output Aluminized Steel (036,060,072)
N10 = 99 MBH Output Aluminized Steel (048,060,072)
S04 = 40 MBH Output Stainless Steel (036)
S06 = 60 MBH Output Stainless Steel (048)
S08 = 79 MBH Output Stainless Steel (036,060,072)
S10 = 99 MBH Output Stainless Steel (048,060,072)
Electric Heat Options
E05 = 5 kW Electric Heat
E07 = 7 kW Electric Heat
E10 = 10 kW Electric Heat
E15 = 15 kW Electric Heat
E20 = 20 kW Electric Heat
E30 = 30 kW Electric Heat
Additional Options
(See Next Page)
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Airflow
A= Direct Drive
B = Direct Drive/Single Input Econo
D = Direct Drive/Motorized Damper
L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr.
N = Belt Drive
P = Belt Drive/Single Input Econo
R = Belt Drive/Motorized Damper
Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Unitary Products Group
3
036-21502-002-A-0303
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Additional Options
AA
None
AB
Phase Monitor
AC
Coil Guard
AD
Dirty Filter Switch
AE
Phase Monitor & Coil Guard
AF
Phase Monitor & Dirty Filter Switch
AG
Coil Guard & Dirty Filter Switch
AH
Phase Monitor, Coil Guard, & Dirty Filter Switch
AS
Bottom Condensate Pan
BA
Hinged Filter Door & Toolless Access Panels
BB
Phase Monitor, Hinged Filter Door & Toolless Access Panels
BC
Coil Guard, Hinged Filter Door & Toolless Access Panels
BD
Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BE
Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
BF
Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BG
Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BH
Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
CA
CPC Controller with Dirty Filter Switch & Air Proving Switch
CB
CPC Controller, DFS, APS & Phase Monitor
CC
CPC Controller, DFS, APS & Coil Guard
CD
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE
CPC Controller, DFS, APS & Technicoat Cond. Coil
CF
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ
CPC Controller, DFS, APS & Technicoat Evap. Coil
CK
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA
CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
DB
CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DC
CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
DD
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DE
CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
DF
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DG
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DH
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DJ
CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
DK
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DL
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DM
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DN
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
DP
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DQ
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DR
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
4
Unitary Products Group
036-21502-002-A-0303
Additional Options
EA
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB
Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC
Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
ER
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GA
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC
Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GJ
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GN
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
GQ
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
HA
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC
Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Unitary Products Group
5
036-21502-002-A-0303
Additional Options
JA
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB
Johnson UNT Controller, DFS, APS & Phase Monitor
JC
Johnson UNT Controller, DFS, APS & Coil Guard
JD
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB
Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC
Novar ETC-3 Controller, DFS, APS & Coil Guard
ND
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
PB
Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PC
Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
PD
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PE
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
PF
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PG
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PH
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PJ
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
PK
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PL
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PM
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PN
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
PP
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PQ
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PR
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
TA
Technicoat Condenser Coil
TB
Technicoat Condenser Coil & Phase Monitor
TC
Technicoat Condenser Coil & Coil Guard
6
Unitary Products Group
036-21502-002-A-0303
Additional Options
TD
Technicoat Condenser Coil & Dirty Filter Switch
TE
Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ
Technicoat Evaporator Coil
TK
Technicoat Evaporator Coil & Phase Monitor
TL
Technicoat Evaporator Coil & Coil Guard
TM
Technicoat Evaporator Coil & Dirty Filter Switch
TN
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS
Technicoat Evaporator & Condenser Coils
TT
Technicoat Evaporator & Condenser Coils & Phase Monitor
TU
Technicoat Evaporator & Condenser Coils & Coil Guard
TV
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA
Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB
Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC
Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD
Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE
Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ
Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK
Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL
Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM
Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US
Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT
Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU
Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
7
036-21502-002-A-0303
FEATURES
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
•
Single enthalpy economizer
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
•
Motorized outdoor air damper
All models are CSA listed.
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
•
Simplicity
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•
Gas Heat Operation - All gas heat units have a minimum AFUE of 80%. Each section includes a durable
heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition,
power venting, an ignition module for 100% shut-off and
all of the safety controls required to meet the latest ANSI
standards.
Simplicity
™ Controls ™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
•
•
•
8
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
Unitary Products Group
036-21502-002-A-0303
FIGURE 1:
UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
•
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
BAS - See “Additional Options” section in the product
nomenclature.
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.
Unitary Products Group
9
036-21502-002-A-0303
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
•
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
•
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.
•
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The power exhaust option can only be used on bottom duct configurations.
•
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
•
CO 2 SENSOR - Senses CO 2 levels and automatically
overrides the economizer when levels rise above the
present limits.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
•
10
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assembly.
Unitary Products Group
036-21502-002-A-0303
TABLE 1: SOUND POWER RATING1
UNIT
SIZE
ESP
SOUND POWER (db 10-12 Watts)
BLOWER
Octave Band Centerline Frequency (Hz)
CFM
IWG
SPEED
KW
63
125
250
500
1,000
2,000
4,000
8,000
SWL
dB(A)
dB(A)
@
10Ft.2
036
1,200
0.6
LOW
0.60
84
84
74
67
69
62
57
52
74
41
048
1,600
0.55
HIGH
0.80
85
85
75
68
70
63
58
53
75
42
060
2,000
0.45
HIGH
1.00
86
86
76
69
71
64
59
54
76
43
072
2,200
0.3
HIGH
1.35
87
87
77
70
72
65
60
55
77
44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)1
MODEL
MBH
EER2
SEER3
DM036
36.0
9.1
10.0
DM048
47.4
9.0
10.0
DM060
59.0
9.1
10.0
DM072
72.0
9.0
-
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
TABLE 3: GAS HEAT RATINGS1
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DM036N04
DM036N08
50
100
40
79
80.9
80.5
15 - 45
40 - 70
DM048N06
DM048N10
75
125
59
99
80.9
80.3
25 - 55
45 - 75
DM060N08
DM060N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65
DM072N08
DM072N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65
1. All units are single-stage heating.
Unitary Products Group
11
036-21502-002-A-0303
TABLE 4: DM036 COOLING CAPACITIES (3 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
TOTAL
1
CFM
1750
1475
1200
1050
900
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
45
43
39
40
44
41
38
39
42
40
36
37
41
38
35
36
39
37
34
34
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
35
43
39
40
31
39
38
39
28
35
36
37
26
32
35
36
24
30
34
34
30
38
39
40
28
35
38
39
25
32
36
37
23
30
35
36
21
27
33
34
26
34
39
40
24
31
37
39
22
28
35
37
20
27
33
35
19
25
30
33
21
29
34
35
20
27
33
35
18
25
31
34
17
24
30
32
16
22
28
30
17
25
30
31
16
23
29
31
15
22
28
31
14
21
27
29
14
20
25
27
20
25
26
19
25
27
18
25
27
18
24
26
17
23
25
16
21
22
16
21
23
15
21
24
15
21
23
15
20
22
43
41
36
38
42
39
36
37
41
38
35
36
39
37
33
34
38
36
32
33
3.3
3.3
3.3
3.2
3.3
3.3
3.3
3.2
3.3
3.2
3.3
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.1
86
83
80
77
74
71
68
35
41
36
38
31
37
36
37
28
34
35
36
26
32
33
34
23
29
32
33
30
38
36
38
27
35
36
37
24
31
35
36
23
29
33
34
21
26
31
33
26
34
36
38
23
31
35
36
21
28
34
35
20
26
31
32
18
24
29
30
21
29
32
33
20
27
31
32
18
25
30
32
17
23
28
30
16
21
26
27
17
25
27
29
16
23
27
28
14
21
27
28
14
20
25
27
13
19
24
25
21
23
24
19
23
25
18
24
25
17
22
24
16
21
22
16
18
20
15
19
21
15
20
22
14
20
21
14
19
20
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
1750
1475
1200
1050
900
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
41
38
34
35
40
37
33
34
39
36
32
33
37
35
31
32
36
33
30
31
3.7
3.7
3.7
3.6
3.7
3.6
3.7
3.6
3.7
3.6
3.6
3.6
3.6
3.6
3.6
3.5
3.6
3.6
3.6
3.5
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
34
38
34
35
30
36
33
34
27
34
32
33
25
31
31
32
22
28
30
31
29
37
34
35
26
34
33
34
24
30
32
33
22
28
31
32
20
25
29
30
25
33
34
35
23
30
33
34
20
27
32
33
19
25
29
30
17
23
27
28
20
28
30
31
19
26
29
30
17
24
29
29
16
22
27
27
15
20
24
25
16
24
25
26
15
22
25
26
14
20
25
26
13
19
24
24
12
18
22
22
19
21
22
18
21
22
17
22
23
16
21
21
15
19
20
15
16
17
14
17
18
14
19
19
13
18
18
13
17
17
39
36
32
33
38
35
31
32
37
34
30
31
36
32
29
30
34
31
28
28
4.1
4.0
4.0
4.0
4.1
4.0
4.0
4.0
4.1
4.0
4.0
3.9
4.1
4.0
4.0
3.9
4.0
4.0
4.0
3.9
86
83
80
77
74
71
68
33
36
32
33
30
34
31
32
26
33
30
31
24
30
29
30
21
27
28
28
28
36
32
33
26
33
31
32
23
30
30
31
21
27
29
29
19
24
28
28
24
32
32
33
22
29
31
32
20
26
30
31
18
24
28
28
16
22
25
25
19
27
27
28
18
25
27
28
16
23
27
27
15
21
25
25
14
19
22
23
15
23
23
24
14
21
23
24
13
20
24
24
12
18
22
22
11
17
20
20
18
18
19
17
19
20
16
20
21
15
19
19
14
17
17
14
14
15
13
15
16
13
17
17
12
16
16
11
15
15
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
12
Unitary Products Group
036-21502-002-A-0303
TABLE 5: DM048 COOLING CAPACITIES (4 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
60
55
51
49
58
53
49
47
56
51
47
46
54
49
45
44
52
47
43
42
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
2000
1800
1600
1400
1200
85°F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
44
53
51
49
41
49
49
47
38
46
47
46
35
42
45
44
32
39
43
42
39
48
51
49
36
45
49
47
34
41
47
46
31
38
45
44
29
35
43
42
33
42
51
49
31
40
48
47
29
37
45
46
27
34
42
43
25
32
39
39
28
37
45
44
26
35
43
43
25
32
41
41
23
30
38
39
22
28
36
36
23
32
40
39
21
30
38
38
20
28
36
37
19
26
34
35
18
25
32
32
26
34
33
25
33
33
24
32
32
22
30
31
21
29
29
21
29
28
20
28
28
19
27
28
19
26
27
18
25
25
60
52
48
47
57
50
46
45
55
48
44
44
53
47
43
42
51
45
41
41
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
4.5
4.5
4.4
4.3
4.5
4.5
4.4
4.3
4.6
4.5
4.4
4.4
4.5
4.5
4.4
4.3
4.5
4.4
4.3
4.3
86
83
80
77
74
71
68
44
52
48
47
41
49
46
45
38
45
44
44
35
41
43
42
32
38
41
41
39
47
48
47
36
44
46
45
33
40
44
44
31
38
43
42
28
35
41
41
33
42
48
47
31
39
46
45
29
36
44
44
27
34
41
41
25
31
38
38
28
36
42
42
26
34
41
40
24
31
40
39
23
30
37
37
21
28
35
34
23
31
37
36
21
29
36
36
20
27
35
35
19
26
33
33
18
24
31
31
25
32
31
24
31
31
23
31
30
22
29
29
21
28
27
20
26
26
19
26
26
18
26
26
18
25
25
17
24
24
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
2000
1800
1600
1400
1200
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
56
49
45
44
55
48
43
43
53
46
42
41
51
44
40
40
49
42
38
38
5.1
5.0
4.9
4.9
5.0
5.0
4.9
4.9
5.0
4.9
4.9
4.8
5.0
4.9
4.8
4.8
4.9
4.9
4.8
4.8
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
42
49
45
44
39
47
43
43
36
44
42
41
33
41
40
40
30
37
38
38
37
46
45
44
34
43
43
43
32
40
42
41
29
37
40
40
27
34
38
38
31
40
45
44
29
38
43
43
28
35
42
41
26
33
39
38
23
30
36
35
26
35
39
39
24
33
38
38
23
31
37
37
22
29
35
34
20
27
32
32
21
29
34
33
20
28
33
33
19
26
33
32
18
25
31
30
16
23
29
28
24
28
28
23
28
28
22
28
28
21
27
26
20
25
25
19
23
22
18
23
23
17
24
23
17
23
22
16
22
21
53
46
41
41
52
45
40
40
51
44
39
39
48
42
37
37
46
39
35
35
5.6
5.5
5.4
5.4
5.5
5.4
5.4
5.4
5.5
5.4
5.3
5.3
5.5
5.3
5.3
5.3
5.4
5.3
5.3
5.3
86
83
80
77
74
71
68
40
46
41
41
38
45
40
40
35
44
39
39
32
40
37
37
29
36
35
35
35
44
41
41
33
42
40
40
31
39
39
39
28
36
37
37
26
33
35
35
29
39
41
41
28
37
40
40
26
35
39
39
24
32
36
36
22
29
33
33
24
33
36
35
23
32
35
35
22
30
35
34
20
28
32
32
19
26
29
29
19
28
30
30
18
27
30
30
17
26
30
30
16
24
28
28
15
22
26
26
23
25
25
22
26
25
21
26
25
20
24
24
19
22
22
17
20
19
17
21
20
17
21
21
16
20
20
15
19
19
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
13
036-21502-002-A-0303
TABLE 6: DM060 COOLING CAPACITIES (5 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
68
62
57
55
67
62
56
54
66
61
55
53
63
58
53
51
60
56
51
49
4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.6
4.8
4.7
4.6
4.6
4.8
4.7
4.6
4.6
2500
2250
2000
1750
1500
85°F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
50
62
57
55
48
59
56
54
45
55
55
53
41
51
53
51
37
46
51
49
44
56
57
55
42
53
56
54
39
50
55
53
36
46
53
51
33
42
51
49
38
50
57
55
36
47
56
54
34
44
55
53
31
41
51
49
29
38
47
45
32
43
51
48
30
41
50
48
29
39
50
48
27
36
47
44
25
34
43
41
25
37
44
42
24
35
45
42
23
34
45
42
22
32
42
40
21
30
39
37
31
38
36
30
39
36
28
39
37
27
37
35
26
35
33
24
32
29
24
33
31
23
34
32
22
32
30
21
31
29
65
60
53
51
65
59
53
50
64
58
52
50
61
56
50
47
58
53
47
45
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
5.6
5.3
5.3
5.4
5.4
5.2
5.2
5.3
5.3
5.1
5.1
5.2
5.4
5.1
5.2
5.2
5.4
5.2
5.2
5.3
86
83
80
77
74
71
68
50
60
53
51
47
57
53
50
44
54
52
50
40
49
50
47
36
44
47
45
43
54
53
51
41
51
53
50
39
48
52
50
35
44
50
47
32
40
47
45
37
48
53
51
35
45
53
50
33
43
52
50
31
39
48
46
28
36
44
42
31
42
47
44
29
40
47
44
28
38
47
44
26
35
43
41
24
32
40
38
24
35
41
38
23
34
41
39
22
32
42
39
21
30
39
36
20
28
36
34
29
34
32
28
35
33
27
36
34
25
34
32
24
32
29
23
28
25
22
29
27
22
31
28
21
29
27
20
27
25
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
2500
2250
2000
1750
1500
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
61
55
49
47
61
54
48
46
60
54
48
46
57
51
45
43
54
48
43
41
6.1
5.9
5.9
5.9
6.0
5.9
5.8
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
48
55
49
47
45
53
48
46
42
52
48
46
38
47
45
43
34
42
43
41
41
52
49
47
39
49
48
46
37
47
48
46
34
42
45
43
30
38
43
41
35
46
49
47
33
44
48
46
32
41
48
46
29
38
44
42
26
34
39
38
29
39
42
40
28
38
42
40
26
36
43
41
24
33
39
37
22
30
35
34
22
33
36
34
22
32
37
35
21
31
37
35
19
28
34
32
18
26
31
30
27
30
28
26
31
29
25
32
30
24
30
28
22
27
26
20
23
21
20
25
23
20
27
25
19
25
23
18
23
21
57
50
44
42
57
50
44
42
57
50
44
42
53
46
41
39
49
43
38
37
6.7
6.6
6.5
6.5
6.6
6.5
6.4
6.4
6.6
6.5
6.4
6.3
6.5
6.4
6.3
6.3
6.5
6.4
6.3
6.2
86
83
80
77
74
71
68
46
50
44
42
43
50
44
42
41
50
44
42
37
45
41
39
33
40
38
37
39
50
44
42
38
47
44
42
36
45
44
42
32
41
41
39
28
36
38
37
33
43
44
42
32
42
44
42
30
40
44
42
27
36
39
38
24
32
35
34
27
37
38
36
26
36
38
36
25
34
38
37
23
31
35
33
20
28
31
30
20
31
31
30
20
30
32
31
20
29
33
32
18
26
30
29
16
24
27
26
24
25
23
24
26
25
24
28
26
22
25
24
20
23
22
18
19
17
18
20
19
18
22
21
17
21
19
16
19
18
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
14
Unitary Products Group
036-21502-002-A-0303
TABLE 7: DM072 COOLING CAPACITIES (6 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
80
80
70
68
82
82
71
69
83
83
73
71
79
79
69
67
74
74
65
63
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.6
5.6
5.4
5.5
2700
2550
2400
2100
1800
85°F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
63
76
70
68
60
73
71
69
58
70
73
71
54
65
69
67
50
60
65
63
55
68
70
68
53
65
71
69
51
63
73
71
48
59
69
67
44
55
65
63
47
60
70
68
46
58
70
69
44
56
70
71
41
53
66
67
39
50
62
63
40
53
62
60
38
51
62
62
37
49
63
64
35
47
60
61
34
44
57
58
32
45
55
52
31
43
55
55
30
42
56
57
29
40
54
54
28
39
51
52
37
47
45
36
48
47
35
49
50
34
47
48
34
46
47
30
39
37
29
41
40
28
42
43
28
41
42
28
41
42
77
77
71
71
76
76
70
70
75
75
69
69
73
73
67
67
71
71
65
65
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.2
6.3
86
83
80
77
74
71
68
63
75
71
71
60
73
70
70
58
70
69
69
53
65
67
67
49
59
65
65
55
68
71
71
53
66
70
70
51
64
69
69
47
59
66
66
43
54
63
63
47
60
71
71
46
58
69
70
44
57
68
68
41
52
63
63
38
48
58
58
40
53
63
63
39
51
62
62
37
50
61
61
35
46
57
57
33
43
53
53
32
45
56
56
31
44
55
55
30
43
54
54
29
40
51
51
27
38
47
47
37
48
48
36
48
48
36
47
47
34
45
45
32
42
42
30
40
40
29
40
40
29
40
40
28
38
39
27
37
37
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
2700
2550
2400
2100
1800
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
76
71
64
64
76
71
64
64
75
70
64
64
73
68
61
61
70
65
59
59
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.0
7.0
6.9
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
61
70
64
64
59
69
64
64
56
68
64
64
52
63
61
61
47
57
59
59
53
66
64
64
51
64
64
64
49
61
64
64
45
56
61
61
41
51
58
58
45
58
64
64
44
56
64
64
43
54
63
63
39
50
58
58
36
46
54
53
38
50
56
56
37
49
56
56
36
48
56
56
33
44
52
52
31
41
48
48
30
43
49
49
29
42
49
49
29
41
49
49
27
38
46
46
25
35
43
43
35
41
41
34
42
42
34
42
42
32
40
40
30
38
37
27
34
34
27
35
34
27
35
35
26
34
34
25
32
32
75
65
57
57
76
66
58
58
76
66
59
59
73
63
56
56
69
60
53
53
7.9
7.8
7.8
7.7
7.9
7.9
7.8
7.7
8.0
7.9
7.8
7.7
7.9
7.8
7.7
7.7
7.8
7.8
7.7
7.6
86
83
80
77
74
71
68
59
65
57
57
57
66
58
58
55
66
59
59
50
61
56
56
45
55
53
53
51
64
57
57
49
61
58
58
48
59
59
59
44
54
56
56
40
49
53
53
43
56
57
57
42
54
58
58
41
52
59
58
37
48
54
53
34
44
49
49
36
48
50
50
35
47
51
50
34
45
52
51
31
42
48
47
29
39
44
44
28
41
42
42
27
40
43
43
27
38
45
44
25
36
42
41
23
33
39
38
33
34
34
32
36
36
32
38
37
30
35
35
28
33
33
25
27
27
25
29
29
25
31
30
24
29
29
23
28
27
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
15
036-21502-002-A-0303
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
0361 2
UNIT
SIZE
(MBH)
0361 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
1700
835
705
880
745
923
795
969
860
1013
970
-
-
-
-
1600
811
655
854
695
898
740
942
790
986
840
1029
900
-
-
1500
782
610
827
650
871
685
917
730
960
775
1003
825
1046
905
1400
-
-
798
595
844
640
889
680
932
720
975
765
1018
790
1300
-
-
-
-
816
590
862
635
907
675
951
715
995
750
1200
-
-
-
-
-
-
834
585
881
630
927
665
970
705
1100
-
-
-
-
-
-
809
550
855
590
900
625
942
665
1000
-
-
-
-
-
-
782
510
829
545
872
858
919
625
900
-
-
-
-
-
-
-
-
797
500
843
540
890
580
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
1.10
1.20
1.30
0.80
WATTS
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
1700
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1600
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1400
1055
875
-
-
-
-
-
-
-
-
-
-
-
-
1300
1036
780
1066
850
-
-
-
-
-
-
-
-
-
-
1200
1011
735
1047
765
1075
800
-
-
-
-
-
-
-
-
1100
987
690
1028
720
1060
750
1084
775
-
-
-
-
-
-
1000
963
655
1005
680
1040
695
1068
715
1089
735
-
-
-
-
900
936
615
980
645
1020
660
1050
670
1053
680
1090
690
-
-
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
16
Unitary Products Group
036-21502-002-A-0303
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
0481 2
UNIT
SIZE
(MBH)
0481 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802
670
840
745
881
815
920
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
820
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
922
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
820
1300
-
-
-
-
-
-
-
-
858
665
893
725
932
785
1200
-
-
-
-
-
-
-
-
847
640
880
680
916
730
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
1102
1180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group
17
036-21502-002-A-0303
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
0601 2
UNIT
SIZE
(MBH)
0601 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
1059
1560
1077
1590
1095
1630
1114
1650
1134
1660
1158
1685
1181
1720
2400
1032
1405
1054
1470
1074
1525
1094
1560
1116
1595
1140
1620
1167
1640
2300
1005
1260
1024
1275
1049
1370
1069
1440
1090
1475
1116
1505
1142
1535
2200
980
1160
1002
1170
1022
1190
1044
1250
1066
1350
1090
1410
1117
1440
2100
930
1060
957
1070
983
1080
1010
1100
1039
1160
1064
1260
1092
1340
2000
877
950
908
975
941
1000
976
1020
1009
1050
1040
1100
1070
1225
1900
-
-
-
-
894
885
940
940
980
980
1014
1020
1047
1095
1800
-
-
-
-
855
815
903
860
950
905
988
940
1022
970
1700
-
-
-
-
-
-
884
815
925
850
964
880
1001
910
1600
-
-
-
-
-
-
864
770
908
805
948
835
987
870
1500
-
-
-
-
-
-
-
-
882
740
926
780
965
830
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
1193
1665
-
-
-
-
-
-
-
-
-
-
-
-
2300
1170
1580
1202
1620
-
-
-
-
-
-
-
-
-
-
2200
1148
1480
1180
1530
-
-
-
-
-
-
-
-
-
-
2100
1121
1385
1155
1425
1190
1475
-
-
-
-
-
-
-
-
2000
1100
1285
1133
1340
1169
1385
1205
1445
-
-
-
-
-
-
1900
1079
1180
1110
1240
1143
1280
1178
1330
1222
1375
-
-
-
-
1800
1058
1060
1090
1135
1122
1190
1158
1240
1196
1295
-
-
-
-
1700
1035
960
1071
1030
1103
1100
1134
1140
1164
1175
1197
1205
-
-
1600
1020
900
1056
965
1088
1035
1118
1065
1145
1105
1170
1130
1198
1150
1500
1004
860
1038
880
1070
925
1101
980
1130
1045
1158
1075
1184
1110
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
18
Unitary Products Group
036-21502-002-A-0303
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
12
072
UNIT
SIZE
(MBH)
12
072
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
3200
1150
2325
1182
2425
1212
2525
-
-
-
-
-
-
-
-
3000
1100
2010
1129
2090
1157
2150
1185
2225
1215
2290
1242
2360
-
-
2800
1045
1700
1074
1780
1102
1850
1131
1940
1160
2025
1190
2075
1217
2130
2600
985
1425
1015
1475
1045
1540
1075
1630
1103
1715
1135
1760
1163
1825
2400
930
1240
958
1300
990
1350
1020
1400
1051
1430
1081
1490
1111
1600
2200
-
-
905
1070
933
1160
965
1210
997
1250
1028
1285
1060
1325
2000
-
-
-
-
-
-
919
1025
950
1100
982
1130
1014
1160
1800
-
-
-
-
-
-
-
-
909
925
939
1005
968
1030
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG3
1.10
1.20
1.30
0.80
WATTS
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
3200
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2800
1245
2190
-
-
-
-
-
-
-
-
-
-
-
-
2600
1193
1920
1222
1990
1250
2060
-
-
-
-
-
-
-
-
2400
1142
1675
1173
1730
1205
1800
1234
1885
-
-
-
-
-
-
2200
1090
1380
1124
1450
1155
1550
1186
1640
1217
1710
1249
1775
-
-
2000
1045
1175
1077
1200
1109
1275
1140
1360
1170
1460
1205
1545
1235
1600
1800
998
1050
1028
1060
1058
1060
1087
1075
1118
1150
1148
1250
1176
1360
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group
19
036-21502-002-A-0303
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
UNIT SIZE
(MBH)
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2
MOTOR SPEED
0361
0481
0601
0721
UNIT SIZE
(MBH)
0.20
0481
0601
0721
0.40
0.50
0.60
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
HI
-
-
-
-
1699
825
1650
785
1570
755
MED
1684
800
1631
780
1582
750
1524
720
1410
690
LOW
1487
710
1464
690
1421
670
1367
650
1315
620
HI
1996
960
1933
936
1868
910
1795
880
1722
845
MED
1804
838
1765
810
1714
785
1650
765
1589
735
LOW
1681
760
1640
738
1604
715
1541
695
1490
670
HI
2400
1155
2338
1125
2274
1095
2167
1045
2096
1010
WATTS
950
MED
2290
1105
2214
1065
2145
1030
2071
990
1990
LOW
2150
1020
2100
990
2029
950
1965
910
1905
880
HI
2461
1480
2402
1440
2361
1395
2260
1350
2178
1305
MOTOR SPEED
0361
0.30
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2
0.80
0.90
0.70
1.00
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
HI
1430
725
1360
700
1280
680
1180
655
MED
1324
650
1260
630
1185
610
1100
590
LOW
1246
605
1185
590
1110
570
1020
545
HI
1635
820
1544
790
1419
765
1300
740
MED
1508
705
1407
675
1306
645
1195
625
LOW
1416
645
1337
620
1230
595
1120
575
HI
1990
980
1887
945
1771
905
1629
855
MED
1911
920
1828
885
1724
835
1604
798
LOW
1816
838
1724
800
1644
770
1531
710
HI
2101
1260
2000
1205
1914
1155
1830
1110
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values
TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MOTOR1
ADJUSTABLE MOTOR PULLEY
BELT
(NOTCHED)
FIXED BLOWER PULLEY
MODEL
SIZE
BLOWER
RANGE
(RPM)
HP
FRAME
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
PITCH
LENGTH
(IN.)
QTY.
3 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
4 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
5 TON
850/1220
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK56
5.4
5.2
1
A36
37.3
1
6 TON
900/1250
1 1/2
56
1VL44
3.1-4.1
2.8-3.8
7/8
AK56
5.4
5.2
1
A36
37.3
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
20
Unitary Products Group
036-21502-002-A-0303
TABLE 14: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
CFM
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.30
5-15KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.19
0.22
20-30KW
ECONOMIZER1 2
ELECTRIC
HEATERS3
3000
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
BOTTOM DUCT CONNECTIONS1
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
0.19
0.22
COOLING ONLY2
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
3. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
TABLE 15: ELECTRIC HEATER CFM LIMITATIONS
UNIT MODEL SIZE NOMINAL
TONS
3
4
5
6
Unitary Products Group
MINIMUM SUPPLY AIR CFM
VOLTAGE
HEATER SIZE NOMINAL KW
5
7
10
15
20
30
208/230-1-60
1100
1100
1200
1200
1300
-
208/230-3-60
1100
1100
1200
1200
1300
-
460-3-60
-
1100
1200
1200
1300
-
575-3-60
-
-
1200
1200
1300
-
208/230-1-60
1300
1300
1300
1300
1300
-
208/230-3-60
1300
1300
1300
1300
1300
-
460-3-60
-
1300
1300
1300
1300
-
575-3-60
-
-
1300
1300
1400
-
208/230-1-60
1600
1600
1600
1600
1600
1600
208/230-3-60
1600
1600
1600
1600
1600
1600
460-3-60
-
1600
1600
1600
1600
1600
575-3-60
-
-
1600
1600
1600
1800
208/230-1-60
1800
1800
1800
1800
1800
1800
208/230-3-60
1800
1800
1800
1800
1800
1800
460-3-60
-
1800
1800
1800
1800
1800
575-3-60
-
-
1800
1800
1800
1800
21
036-21502-002-A-0303
TABLE 16: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
19.2
87
2.3
4.4
0.0
230-1-60
19.2
87
2.3
4.4
0.0
208-3-60
14.1
110
2.3
4.4
0.0
230-3-60
14.1
110
2.3
4.4
0.0
460-3-60
7.1
54
1.3
2.2
0.0
575-3-60
5.8
44
1.3
2.2
0.0
208-1-60
25.0
135
2.3
5.0
0.0
230-1-60
25.0
135
2.3
5.0
0.0
208-3-60
14.7
130
2.3
5.0
0.0
230-3-60
14.7
130
2.3
5.0
0.0
460-3-60
7.7
64
1.3
2.2
0.0
575-3-60
6.4
52
1.3
2.2
0.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
1
BRKR Size
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2CE04510525 2
2
2CE04510725
2CE04511525
2CE04512025
NONE
2CE04510746 2
2CE04511046 2
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
30.7
30.7
39.2
53.6
77.0
101.1
30.7
33.1
44.6
60.7
88.3
115.9
24.3
24.3
24.9
33.3
46.8
60.7
24.3
24.3
28.1
37.4
53.3
69.2
12.4
13.0
17.9
23.2
32.1
10.1
14.9
21.3
27.7
38.5
38.5
39.9
54.3
77.8
101.8
38.5
38.5
45.3
61.5
89.1
116.7
25.7
25.7
25.7
34.0
47.5
61.4
25.7
25.7
28.8
38.1
54.1
70.0
13.1
13.1
17.9
23.2
32.1
10.8
14.9
21.3
27.7
45
45
45
60
80
110
45
45
45
70
90
125
35
35
35
35
50
70
35
35
35
40
60
70
15
15
20
25
35
15
15
25
30
60
60
60
60
80
110
60
60
60
70
90
125
40
40
40
40
50
70
40
40
40
40
60
70
20
20
20
25
35
15
15
25
30
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
22
Unitary Products Group
036-21502-002-A-0303
TABLE 17: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
28.9
165
1.3
6.6
0.0
230-1-60
28.9
165
1.3
6.6
0.0
208-3-60
16.0
125
1.3
6.6
0.0
230-3-60
16.0
125
1.3
6.6
0.0
460-3-60
8.0
66.5
0.8
3.3
0.0
575-3-60
6.4
50
0.8
3.3
0.0
208-3-60
18.9
146
1.3
6.8
0.0
230-3-60
18.9
146
1.3
6.8
0.0
460-3-60
9.5
73
0.8
3.6
0.0
575-3-60
7.6
58.4
0.8
3.6
0.0
5
6
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2
2CE04511546
2CE04512046 2
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
44.0
44.0
44.0
56.3
79.8
103.8
141.7
44.0
44.0
47.3
63.5
91.1
118.7
162.4
27.9
27.9
27.9
36.0
49.5
63.4
85.3
27.9
27.9
30.8
40.1
56.1
72.0
97.3
14.1
14.3
19.3
24.6
33.4
47.4
11.3
16.0
22.4
28.8
39.9
31.7
31.7
31.7
36.3
49.8
63.7
85.5
31.7
31.7
31.7
40.4
56.3
72.2
97.5
16.3
16.3
19.7
24.9
33.8
47.8
13.0
16.3
22.7
29.1
40.2
Max Fuse /
BRKR1 Size
Amps
70
70
70
70
80
110
150
70
70
70
70
100
125
175
40
40
40
40
50
70
90
40
40
40
45
60
80
100
20
20
20
25
35
50
15
20
25
30
40
50
50
50
50
50
70
90
50
50
50
50
60
80
100
25
25
25
25
35
50
15
20
25
30
40
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
23
036-21502-002-A-0303
TABLE 18: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
18.0
105
1.3
7.6
0.0
230-1-60
18.0
105
1.3
7.6
0.0
208-3-60
11.4
90
1.3
5.2
0.0
230-3-60
11.4
90
1.3
5.2
0.0
460-3-60
6.2
45
0.8
2.6
0.0
575-3-60
5.0
36
0.8
2
0.0
208-1-60
24.4
140
1.3
7.6
0.0
230-1-60
24.4
140
1.3
7.6
0.0
208-3-60
14.1
105
1.3
5.2
0.0
230-3-60
14.1
105
1.3
5.2
0.0
460-3-60
7.1
55
0.8
2.6
0.0
575-3-60
5.8
44
0.8
2
0.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
31.4
33.5
43.2
57.6
81.0
105.1
31.4
37.1
48.6
64.7
92.3
119.9
20.8
20.8
25.9
34.3
47.8
61.7
20.8
22.4
29.1
38.4
54.3
70.2
11.1
13.5
18.4
23.7
32.6
8.5
14.7
21.1
27.5
39.4
39.4
43.2
57.6
81.0
105.1
39.4
39.4
48.6
64.7
92.3
119.9
24.1
24.1
25.9
34.3
47.8
61.7
24.1
24.1
29.1
38.4
54.3
70.2
12.3
13.5
18.4
23.7
32.6
9.5
14.7
21.1
27.5
Max Fuse /
BRKR1 Size
Amps
45
45
45
60
90
110
45
45
50
70
100
125
30
30
30
35
50
70
30
30
30
40
60
80
15
15
20
25
35
15
15
25
30
60
60
60
60
90
110
60
60
60
70
100
125
35
35
35
35
50
70
35
35
35
40
60
80
15
15
20
25
35
15
15
25
30
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
24
Unitary Products Group
036-21502-002-A-0303
TABLE 19: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
28.9
165
1.3
7.6
0.0
230-1-60
28.9
165
1.3
7.6
0.0
208-3-60
16.0
125
1.3
5.2
0.0
230-3-60
16.0
125
1.3
5.2
0.0
460-3-60
8.0
66.5
0.8
2.6
0.0
575-3-60
6.4
50
0.8
2
0.0
208-3-60
18.9
146
1.3
5.0
0.0
230-3-60
18.9
146
1.3
5.0
0.0
460-3-60
9.5
73
0.8
2.5
0.0
575-3-60
7.6
58.4
0.8
2
0.0
5
6
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
45.0
45.0
45.0
57.6
81.0
105.1
142.9
45.0
45.0
48.6
64.7
92.3
119.9
163.7
26.5
26.5
26.5
34.3
47.8
61.7
83.5
26.5
26.5
29.1
38.4
54.3
70.2
95.5
13.4
13.5
18.4
23.7
32.6
46.6
10.2
14.7
21.1
27.5
38.6
29.9
29.9
29.9
34.0
47.5
61.4
83.3
29.9
29.9
29.9
38.1
54.1
70.0
95.3
15.2
15.2
18.3
23.6
32.4
46.4
11.7
14.7
21.1
27.5
38.6
Max Fuse /
BRKR1 Size
Amps
70
70
70
70
90
110
150
70
70
70
70
100
125
175
40
40
40
40
50
70
90
40
40
40
40
60
80
100
20
20
20
25
35
50
15
15
25
30
40
45
45
45
45
50
70
90
45
45
45
45
60
70
100
20
20
20
25
35
50
15
15
25
30
40
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
25
036-21502-002-A-0303
TABLE 20: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
18.0
105
1.3
4.4
10.0
230-1-60
18.0
105
1.3
4.4
10.0
208-3-60
11.4
90
1.3
4.4
10.0
230-3-60
11.4
90
1.3
4.4
10.0
460-3-60
6.2
45
0.8
2.2
5.0
575-3-60
5.0
36
0.8
2.2
4.0
208-1-60
24.4
140
1.3
5.0
10.0
230-1-60
24.4
140
1.3
5.0
10.0
208-3-60
14.1
105
1.3
5.0
10.0
230-3-60
14.1
105
1.3
5.0
10.0
460-3-60
7.1
55
0.8
2.2
5.0
575-3-60
5.8
44
0.8
2.2
4.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746 2
2CE04511046 2
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
38.2
42.0
51.7
66.1
89.5
113.6
38.2
45.6
57.1
73.2
100.8
128.4
29.9
31.9
37.4
45.8
59.3
73.2
29.9
33.9
40.6
49.9
65.8
81.7
15.8
19.2
24.2
29.4
38.3
12.7
19.9
26.3
32.7
46.8
46.8
52.4
66.8
90.3
114.3
46.8
46.8
57.8
74.0
101.6
129.2
33.9
33.9
38.2
46.5
60.0
73.9
33.9
34.7
41.3
50.6
66.6
82.5
16.9
19.2
24.2
29.4
38.3
13.7
19.9
26.3
32.7
Max Fuse /
BRKR1 Size
Amps
50
50
60
70
90
125
50
50
60
80
110
150
40
40
40
50
60
80
40
40
45
50
70
90
20
20
25
30
40
15
20
30
35
70
70
70
70
100
125
70
70
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
26
Unitary Products Group
036-21502-002-A-0303
TABLE 21: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
28.9
165
1.3
6.6
10.0
230-1-60
28.9
165
1.3
6.6
10.0
208-3-60
16.0
125
1.3
6.6
10.0
230-3-60
16.0
125
1.3
6.6
10.0
460-3-60
8.0
66.5
0.8
3.3
5.0
575-3-60
6.4
50
0.8
3.3
4.0
208-3-60
18.9
146
1.3
6.8
10.0
230-3-60
18.9
146
1.3
6.8
10.0
460-3-60
9.5
73
0.8
3.6
5.0
575-3-60
7.6
58.4
0.8
3.6
4.0
5
6
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2
2CE04511546
2CE04512046 2
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
54.0
54.0
54.4
68.8
92.3
116.3
154.2
54.0
54.0
59.8
76.0
103.6
131.2
174.9
37.9
37.9
40.2
48.5
62.0
75.9
97.8
37.9
37.9
43.3
52.6
68.6
84.5
109.8
19.1
20.6
25.6
30.8
39.7
53.7
15.3
21.0
27.4
33.8
44.9
41.7
41.7
41.7
48.8
62.3
76.2
98.0
41.7
41.7
43.6
52.9
68.8
84.7
110.0
21.3
21.3
25.9
31.2
40.1
54.1
17.0
21.3
27.7
34.1
45.2
Max Fuse /
BRKR1 Size
Amps
80
80
80
80
100
125
175
80
80
80
80
110
150
175
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
30
35
40
60
20
25
30
35
45
60
60
60
60
70
80
100
60
60
60
60
70
90
125
30
30
30
35
45
60
20
25
30
35
45
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
27
036-21502-002-A-0303
TABLE 22: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
18.0
105
1.3
7.6
10.0
230-1-60
18.0
105
1.3
7.6
10.0
208-3-60
11.4
90
1.3
5.2
10.0
230-3-60
11.4
90
1.3
5.2
10.0
460-3-60
6.2
45
0.8
2.6
5.0
575-3-60
5.0
36
0.8
2
4.0
208-1-60
24.4
140
1.3
7.6
10.0
230-1-60
24.4
140
1.3
7.6
10.0
208-3-60
14.1
105
1.3
5.2
10.0
230-3-60
14.1
105
1.3
5.2
10.0
460-3-60
7.1
55
0.8
2.6
5.0
575-3-60
5.8
44
0.8
2
4.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
41.4
46.0
55.7
70.1
93.5
117.6
41.4
49.6
61.1
77.2
104.8
132.4
30.8
32.9
38.4
46.8
60.3
74.2
30.8
34.9
41.6
50.9
66.8
82.7
16.1
19.7
24.7
29.9
38.8
12.5
19.7
26.1
32.5
49.4
49.4
55.7
70.1
93.5
117.6
49.4
49.6
61.1
77.2
104.8
132.4
34.1
34.1
38.4
46.8
60.3
74.2
34.1
34.9
41.6
50.9
66.8
82.7
17.3
19.7
24.7
29.9
38.8
13.5
19.7
26.1
32.5
Max Fuse /
BRKR1 Size
Amps
50
50
60
80
100
125
50
50
70
80
110
150
40
40
40
50
70
80
40
40
45
60
70
90
20
20
25
30
40
15
20
30
35
70
70
70
80
100
125
70
70
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
28
Unitary Products Group
036-21502-002-A-0303
TABLE 23: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
28.9
165
1.3
7.6
10.0
230-1-60
28.9
165
1.3
7.6
10.0
208-3-60
16.0
125
1.3
5.2
10.0
230-3-60
16.0
125
1.3
5.2
10.0
460-3-60
8.0
66.5
0.8
2.6
5.0
575-3-60
6.4
50
0.8
2
4.0
208-3-60
18.9
146
1.3
5.0
10.0
230-3-60
18.9
146
1.3
5.0
10.0
460-3-60
9.5
73
0.8
2.5
5.0
575-3-60
7.6
58.4
0.8
2
4.0
5
6
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2
2CE04511546
2CE04512046 2
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
55.0
55.0
55.7
70.1
93.5
117.6
155.4
55.0
55.0
61.1
77.2
104.8
132.4
176.2
36.5
36.5
38.4
46.8
60.3
74.2
96.0
36.5
36.5
41.6
50.9
66.8
82.7
108.0
18.4
19.7
24.7
29.9
38.8
52.8
14.2
19.7
26.1
32.5
43.6
39.9
39.9
39.9
46.5
60.0
73.9
95.8
39.9
39.9
41.3
50.6
66.6
82.5
107.8
20.2
20.2
24.6
29.8
38.7
52.7
15.7
19.7
26.1
32.5
43.6
Max Fuse /
BRKR1 Size
Amps
80
80
80
80
100
125
175
80
80
80
80
110
150
200
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
25
30
40
60
20
20
30
35
45
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
25
30
40
60
20
20
30
35
45
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
29
036-21502-002-A-0303
TABLE 24: PHYSICAL DATA
DM
MODELS
Centrifugal Blower (Dia. x Wd. in.)
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
VOLTAGE
12 X 11
3/4
1
1
1 1/2
1 1/2
1 1/2
Rows Deep
3
3
3
4
Fins Per Inch
13
13
13
13
Face Area (Sq. Ft.)
3.6
4.3
5.1
5.1
Propeller Dia. (in.)
24
24
24
24
Fan Motor Hp
1/4
1/4
1/4
1/4
3400
Nom. CFM
3400
3400
3400
Rows Deep
1
1
1
2
Fins Per Inch
16
16
22
16
Face Area (Sq. Ft.)
17.1
17.1
17.1
16.7
Scroll Type
1
1
1
1
Quantity Per Unit (15” X 20” X 1” or 2“)
2
2
2
2
Quantity Per Unit (14” X 25” X 1” or 2“)
1
1
1
1
Total Face Area (sq. ft.)
6.3
6.3
6.3
6.3
Refrigerant 22
(lbs./oz.)
5/8
6/8
6/8
10/0
kW CAP. MULTIPLIER
TABLE 26: VOLTAGE LIMITATIONS1
VOLTAGE
POWER SUPPLY
MIN.
MAX.
208/230-3-60
187
253
0.92
460-3-60
414
506
0.92
575-3-60
518
506
240
230
0.92
575
12 X 10
1/2
1.00
600
072
12 X 10
1 1/2
208
460
060
12 X 10
Fan Motor HP (Belt Drive)
208
480
048
Fan Motor HP (Direct Drive)
TABLE 25: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
036
1. Utilization Range “A” in accordance with ARI Standard
110.
30
Unitary Products Group
036-21502-002-A-0303
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
UNIT TERMINAL
STRIP TB1
THERMOSTAT1
TERMINALS
RV
R
YC
Y1
UNIT TERMINAL
STRIP TB1
RH
ADD
JUMPER
24 VOLT
TRANSFORMER
RC
R
Y
Y1
Y2
Y2
W1
W
G
GF
24 VOLT
TRANSFORMER
W2
C
G
G
1
24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
C
1
24 VOLT THEROMSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
COOLING / HEATING (ELECTRONIC THEROMSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
RC
RH
ADD
JUMPER
4
ADD
JUMPER
Y1
Y2
W1
W2
G
2
3
Y1
Y2
W1
W2
G
C
X
OCC
RH
ADD
JUMPER
UNIT TERMINAL
STRIP TB1
RC
R
Y
Y1
W1
W
G
G
C
24 VOLT
TRANSFORMER
1
ELECTRONIC PROGRAMMABLE THEROMSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
2TH040702224 IF USED
1
ELECTRONIC PROGRAMMABLE THEROMSTAT 2TH04700224 (INCLUDES SUBBASE).
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER.
FIGURE 2:
THERMOSTAT1
TERMINALS
UNIT TERMINAL
STRIP TB1
24 VOLT
R
TRANSFORMER
B
LED 1
LED 2 NOT
USED
COM
4
A1
A2
TO REMOTE SENSOR
T
T
COOLING / HEATING (ELECTRONIC THEROMSTAT)
SINGLE STAGE
TYPICAL FIELD POWER & CONTROL WIRING
Unitary Products Group
31
036-21502-002-A-0303
FIGURE 3:
UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4:
UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW
32
Unitary Products Group
036-21502-002-A-0303
DETAIL “A”
FIGURE 5:
UNIT WITH ECONOMIZER RAINHOOD
DETAIL “B”
FIGURE 6:
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Unitary Products Group
33
036-21502-002-A-0303
FIGURE 7:
UNIT DIMENSIONS (REAR VIEW)
TABLE 28: MINIMUM CLEARANCES
FILTER
ACCESS
BLOWER MOTOR
ACCESS
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Back
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
Below
A,B
WIRING ENTRY
(See Detail “B”)
Above Unit 2
CONTROL BOX
ACCESS
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
FIGURE 8:
Unit1
DISCONNECT/BLOWER ACCESS
LOCATION
0”
72” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
TABLE 27: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
USED FOR
A
7/8” KO1
Control Wiring2
B
2” KO1
Power Wiring
C
1-5/8” KO
Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
Side
Bottom
Side
Bottom
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
34
Unitary Products Group
036-21502-002-A-0303
FIGURE 9:
TYPICAL APPLICATIONS
Unitary Products Group
35
036-21502-002-A-0303
BACK OF UNIT
A
447/8
BACK OF UNIT
A
447/8
821/4
821/4
D
B
F
X
X
B
APPROXIMATE
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
C
Y
FRONT OF UNIT
C
E
APPROXIMATE
CENTER OF GRAVITY
D
Y
FRONT OF UNIT
CONDENSER COIL
END OF UNIT
FIGURE 10: FOUR AND SIX POINT LOADING
TABLE 29: DM 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
A
B
C
D
DM036 Cooling/ Electric
565
125
123
157
160
DM036N04
625
140
133
172
180
DM036N08
635
140
138
177
180
DM048 Cooling/ Electric
615
137
135
170
173
DM048N06
675
152
145
185
193
DM048N10
685
152
150
190
193
DM060 Cooling/ Electric
640
143
140
177
180
DM060N08
700
158
150
192
200
DM060N10
710
158
155
197
200
DM072 Cooling/ Electric
720
164
189
196
171
DM072N08
775
179
201
209
186
DM072N10
785
179
206
214
186
TABLE 30: DM 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
A
B
C
D
E
F
107
DM036 Cooling/ Electric
565
84
83
82
104
105
DM036N04
625
93
92
91
115
117
118
DM036N08
635
94
93
92
117
119
120
DM048 Cooling/ Electric
615
91
90
89
113
115
116
DM048N06
675
100
99
98
124
126
128
DM048N10
685
102
100
99
126
128
129
DM060 Cooling/ Electric
640
95
94
93
118
119
121
DM060N08
700
104
103
101
129
131
132
DM060N10
710
105
104
103
131
133
134
DM072 Cooling/ Electric
720
107
117
129
134
122
111
DM072N08
775
115
126
139
144
131
120
DM072N10
785
117
128
141
146
133
121
TABLE 31: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
6 TON
X
40-¾”
44”
Y
19-¾”
22”
36
Unitary Products Group
036-21502-002-A-0303
TABLE 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE
3 TON
4 TON
5 TON
6 TON
565
615
640
720
N04
625
-
-
-
N06
-
675
-
-
N08
635
-
700
775
N10
-
685
710
785
DM (Cooling Only)
BASIC
UNIT
DM
(Gas/Electric)
Economizer
50
Motorized Damper
OPTIONS
Electric Heater
ACCY.
26
5 - 7 kW
18
10 - 15 kW
23
20 - 30 kW
28
Roof Curb
92
Barometric Relief / Fixed Air Damper
10
Belt-Drive Blower
5
FIGURE 11: ROOF CURB DIMENSIONS
Unitary Products Group
37
036-21502-002-A-0303
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline 2000TM units are convertible single packageunits. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All units
have long lasting powder paint cabinets with 750 hour salt
spray test approval under ASTMB117 procedures. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 750 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected (B.H.P.) brake horsepower
shall not exceed the motors nameplate horsepower rating,
plus the service factor. Units shall be designed not to operate
above service factor. Fan wheel shall be double-inlet type
with forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
The 3 thru 5 ton units shall have minimum SEER ratings of
10.0 and the 6 ton units shall have minimum EER ratings of
9.0. They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or
field installed accessories. The units shall be factory wired,
piped, charged with R-22 refrigerant and factory tested prior
to shipment. All unit wiring shall be both numbered and color
coded. All units the cooling performance shall be rated in
accordance with DOE and ARI test procedures. Units shall be
CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236
standards.
38
Compressor:
a.
Shall be internally protected with internal high-pressure relief and over temperature protection.
b.
Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent
mounting.
Coils:
a.
Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
Unitary Products Group
036-21502-002-A-0303
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b.
Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.
Independent fixed-orifice expansion devices.
b.
Filter drier/strainer to eliminate any moisture or foreign matter.
c.
Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.
d.
dant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
UNIT CONTROLS
a.
Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil.
f.
If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h.
Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i.
Unit control board shall have on-board diagnostics
and fault code display.
j.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
k.
Control board shall monitor each refrigerant safety
switch independently.
l.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
a.
Primary and auxiliary high-temperature limit
switches.
b.
Induced draft motor speed sensor.
c.
Flame roll out switch (manual reset).
d.
Flame proving controls.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The
heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. The heating section
assembly shall slide out of the unit for easy maintenance and
service. Units with Electric Heating shall be wired for a single
point power supply with branch circuit fusing (where
required).
UNIT OPERATING CHARACTERISTICS
a.
Unit shall be capable of starting and running at
125°F outdoor temperature, exceeding maximum
load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be
provided with fan time delay to prevent cold air
delivery before heat exchanger warms up (Gas heat
only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•
Compressor 5 Years
•
Heat Exchanger 10 Years
GAS HEATING SECTION
•
Electric Heat Element 5 Years
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-
•
Other Parts 1 Year
Unitary Products Group
39
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
•
ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
•
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
•
LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
•
GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
ELECTRIC HEATERS
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.
•
MANUAL OUTDOOR AIR DAMPER
•
COIL GUARD KIT - Guard for cooling coil.
•
HAIL GUARD
•
FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
STAINLESS STEEL HEAT EXCHANGER
•
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
•
DIRTY FILTER SWITCH
•
PHASE MONITOR
•
COIL GUARD
•
POWERED GFI CONVENIENCE OUTLET
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
NON-POWERED GFI CONVENIENCE OUTLET
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•
BAS CONTROLS (CPC, JOHNSON, HONEYWELL,
NOVAR)
•
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
•
BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
•
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
2" PLEATED FILTERS
•
DISCONNECT SWITCH
•
SUPPLY AIR SMOKE DETECTOR
•
RETURN AIR SMOKE DETECTOR
•
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
Subject to change without notice. Printed in U.S.A.
Copyright © by Unitary Products 2003. All rights reserved.
Unitary
Products
Group
036-21502-002-A-0303
Supersedes: 036-21502-001-A-0103
5005
York
Drive
Norman
OK
73069