Download Tecumseh AVA2512ZXNXM Performance Data Sheet

Transcript
September 3, 2002- Rev 3.
Tecumseh Products Company
Hermetic Condensing Units
Model: AVA2512ZXNXM
R-404A
3 HP
AIRCOOLED
Note: Dimensioning = Inches [mm]
Dimensions, inches
Line Connection*
Pumpdown
Air
Model
L
W
H
CH
Suction
Liquid
90 °F 90% SCFM
AVA2512ZXNXM
25.0
33.48
19.5
14.6
7/8”S
3/8”S
11.6
1698
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen – MUST BE EVACUATED
POE
Oil Ch
Oz.
54
Gr. Wt.
Lbs.
220
60 Hz Performance
Ambient Temperatures
Evaporator
80deg F
F PSIG BTUH Watts
4099
5479
6904
8373
9886
11444
13045
14690
16380
18114
Head
90 deg F
100 deg F
110 deg F
Cond T BTUH Watts Head Cond T BTUH Watts Head Cond T BTUH Watts Head Cond T
-40
-35
-30
-25
-20
-15
-10
-5
0
5
5.5
8.0
10.7
14.0
17.1
19.3
24.5
28.8
33.5
36.5
1690
1854
2028
2210
2401
2600
2809
3026
3252
3486
197
205
213
221
229
239
248
258
269
280
87
90
92
95
97
100
102
105
108
110
4139
5313
6531
7794
9102
10454
11851
13292
14778
16309
1661
1828
2005
2192
2389
2596
2813
3040
3277
3524
231
238
244
252
260
269
278
288
299
311
98
100
102
104
106
109
111
114
116
119
3245
4296
5387
6518
7689
8900
10151
11442
12772
14142
1501
1677
1863
2057
2260
2471
2692
2921
3159
3405
268
273
278
285
292
300
309
319
329
340
108
110
111
113
115
117
119
121
124
126
2429
3499
4582
5678
6786
7907
9041
10187
11345
12517
292
300
308
317
326
335
345
355
366
378
115
117
119
121
123
125
128
130
132
134
10
43.7 19892 3730
291
113
17884 3781 323
122
15553 3661 353
129
13701 3662 389
137
Return gas temp. 40°F, 5°F sub cooling
822
1151
1470
1779
2078
2367
2646
2915
3174
3423
September 3, 2002- Rev 3
Specifications:
Model
Nominal Volts-Hz-Ph
Unit Bill of Material
Voltage Range
Min. Circuit Ampacity
Max. Fuse Size (amps)
Compressor Model
Comp. Bill of Material
Alt. Comp. Bill of Mat.
Compressor RLA/LRA
Overload
Relay
Alternate Relay
Start Capacitor
Start Capacitor Rating
Run Cap.
Run Cap. Rating
Fan Motor (2)
Fan RLA
Fan Blade (2)
Condenser
Dbl. Fan Shroud
Unit Drawing
Electrical Drawing
AVA2512ZXNXM
208/230-60-1
2B3140-9
187 to 253
22.8
35
AVA2490ZXN
AV182ET-001
-------------------------16.3/106.6
Internal
820ARR3J56
82966
85PS330D17
145-175/330
85PR440E65
45/440
810S037B01
1.10
51533-2
50852
70648-2
SU1920
91027-2
Fan Guard (2)
70831
Cap. Cab. Assy.
AE1397-15
Control Panel
AC1390-10
Pressure Control
High 84095-2,Low 84026-5
Fan Switch
84096-1
Contactor
91014(30 AMP-3PH, 230V)
Accumulator
TK00042000
Receiver Tank
51081-1
Rec.Tank RL Valve
31581-1(3/8”S)
30334
O′Ring Gasket
Outdoor Enclosure (Optional) TP-241D
S.E.