Download Tecumseh AEA2411ZXA Performance Data Sheet

Transcript
Btu/h
2390
2130
1900
1670
1450
1220
991
Watts
461
434
430
442
459
474
480
Amps
5.88
5.99
6.08
6.14
6.20
6.25
6.30
Lb/h
35.2
33.5
32.1
31.0
29.9
28.8
27.5
0
Btu/h
2690
2410
2150
1900
1650
1400
1140
Watts
480
454
452
464
483
501
508
Amps
5.97
6.11
6.22
6.31
6.38
6.44
6.49
Lb/h
39.8
38.0
36.6
35.4
34.2
33.1
31.8
Btu/h
3010
2710
2420
2140
1870
1590
1310
5
Watts
501
475
473
487
507
527
537
Amps
6.09
6.25
6.38
6.49
6.58
6.65
6.72
Lb/h
44.8
42.9
41.5
40.2
39.1
37.9
36.6
CAPACITY
POWER
CURRENT
MASS FLOW
10
COEFFICIENTS
C1
5.800766E+03 2.499580E+03 3.386010E+00 7.537587E+01
C2
9.179586E+01 6.111915E+00 -5.492659E-02 1.040863E+00
C3
-6.536206E+01 -5.577178E+01 5.657588E-02
-9.449118E-01
C4
7.627254E-01
4.601547E-05
8.181804E-03
C5
-4.096587E-01 -6.121122E-02
1.228202E-03
-3.086052E-03
C6
3.676155E-01
4.895516E-01
-3.996738E-04
7.179242E-03
C7
2.327132E-03
6.836451E-05
4.635899E-06
5.683371E-05
C8
-3.191855E-03 -3.218960E-04
2.943541E-06
6.007668E-06
C9
-3.023249E-04
4.229471E-04
-4.098795E-06
1.065204E-05
C10
-1.043861E-03 -1.387473E-03
1.029658E-06
-2.053341E-05
3.545607E-02
Value = C1 + C2 * Te + C4 * Te^2 + C7 * Te^3 + (C3 + C5 * Te + C8 * Te^2) * Tc + (C6 + C9 * Te) * Tc^2 + C10 * Tc^3
Te = Evaporator Temperature
Tc = Condensing Temperature