Download Tecumseh AE4440Z-AA1AGB Performance Data Sheet

Transcript
AE4440Z-AA1AGL_REV 1
TPC - July 17, 2013
TECUMSEH HERMETIC
CONDENSING UNIT
Model
BOM
Air Cooled
Application
Refrigerant
Volts-Hz-Ph
AE4440Z-AA1AGL, GK, GB, GC
33Y364-2, -3, -4, -5
1/3 HP
High/Commercial Temp
R404A
115-60-1
19.00
SUCTION 5/16"
18.35
LIQUID 1/4"
10.37
9.61
7.60 8.25
1.25
Ø0.31
Model
AE4440Z-AA1AGL
AE4440Z-AA1AGK
AE4440Z-AA1AGB
AE4440Z-AA1AGC
Dimensions, inches (mm)
Line connections
L
W
H
Suction
Liquid
8.7
5/16 Sweat
1/4 Sweat
19
10.3
(221)
(483)
(262)
9.7
5/16 Valve Sweat 1/4 Valve Sweat
(246)
Pumpdown
o
90% @90 F
Air flow
CFM
Oil Ch.
Oz.
242
16
BTUH
850
960
1080
1200
1330
1460
1590
1890
2030
2160
2290
110 F
Watts
320
340
370
400
420
450
470
520
540
570
600
n/a
1.79
2.12
Gross wt.
Lbs (kg)
39.6
(18)
40.2 (18.2)
40.8 (18.5)
Factory charge 20 psig dry air, MUST BE EVACUATED
Ambient Temperatures
Evaporator
o
F
-10
-5
0
5
10
15
20
25
30
35
40
Psig
23.9
28.2
32.8
37.9
42.4
48.2
54.5
61.2
68.4
76.1
84.4
o
BTUH
1270
1420
1600
1780
1970
2160
2350
2720
2930
3140
3340
80 F
Watts
310
330
350
370
400
420
440
470
500
520
540
o
o
Cond T
98
101
103
106
109
112
115
118
121
125
128
BTUH
1120
1260
1420
1580
1750
1920
2090
2440
2620
2810
2980
o
90 F
Watts
310
340
360
380
400
430
450
490
510
540
560
o
Cond T
107
109
112
114
117
120
123
126
129
132
135
o
BTUH
980
1110
1240
1390
1540
1690
1840
2160
2320
2480
2630
o
100 F
Watts
310
340
360
390
410
440
460
500
530
550
580
o
Cond T
116
118
120
123
125
128
131
134
136
139
142
o
Performance @ 60 Hz, Return gas 40 F below 20 F Evaporator and 65 F above 20 F evaporator, SubCooling 5 F
Cond T
124
126
128
131
133
136
138
141
144
146
149
AE4440Z-AA1AGL_ REV 1
TPC - July 17, 2013
Parts/Specifications
Unit BOM
Unit MODEL
33Y364-2
AE4440Z-AA1AGL
Refrigeration RANGE
Design Pressure Low
Design Pressure High
Volts - HZ - Ph
Voltage Range
Min. Circuit Ampacity
Max. Fuse Size
-10°F to 45°F
181
450
115-60-1
126.5 to 103.5
8.46
15
Compressor MODEL
Compressor BOM
Compressor LRA
Compressor RLA
AE4440Z-AA1A
AE-1168-E
36
6.3
OverLoad
Replacement Overload
Relay
Replacement Relay
Run Capacitor
Run Capacitor Rating
Start Capacitor
Start Capacitor Rating
830-10116
Electrical Diagram
Unit Drawing
DEAE-10
DGBU-062
820-10078
85PS165C99
270-324 MFD 165V
Condenser
Fan Motor
Fan Motor RLA
Fan Blade
Shroud
Fan Guard
50734-G04
NUT6B09PUN301
0.58
4VEA010
116-003P
Replacement Fan Motor
F. M., blade, guard assy
F. M., blade, guard, shroud assy
9W115
YFBG-109
Unit BOM
Unit MODEL
Power Cord
Unit Drawing
33Y364-3
AE4440Z-AA1AGK
85106-10
DGBU-062
Unit BOM
Unit MODEL
Receiver
Unit Drawing
33Y364-4
AE4440Z-AA1AGB
51085-1H
DGBU-062R
Unit BOM
Unit MODEL
Receiver w/Liquid Valve
Suction Valve
Unit Drawing
33Y364-5
AE4440Z-AA1AGC
56580-1
DGBU-062V