Sentry Controller
MODBUS Memory Map
(Enhanced)
December 15, 1998
Updated March 4, 2005
Sierra Monitor Corp. 1991 Tarob Ct. Milpitas, CA 95035 USA 408-262-6611, Toll Free 800-727-4377, FAX: 408-262-9042
Visit our Web Site: www.sierramonitor.com
E-Mail: [email protected]
Sentry MODBUS I/O Memory Map
Sentry Controller
MODBUS Memory Map
Detail
1
All Registers are MODBUS 16 bit registers
2
There are five different ways of using MODBUS registers (see italic reference number in left column for each
address)
2.1 As an Analog Value: In most cases these values are scaled by multiplying by 10.
2.2 As eight packed digital states, packed into one register. In this case the remaining 8 bits are unused.
2.3 As a digital state where the register value can only be “0” or “1”.
2.4 As a computed value, such as where “0” = no alarm, “1” = low alarm, “2” = high alarm.
2.5 Control registers, where the SCADA host can write a value, such as alarm reset to the Sentry, or to set
calibration concentration, or alarm set point. Note that these registers are read or write.
3
Where a series of registers apply only to sensor number 1, the following sequences for sensors 2, through 8 are
only referenced by the first applicable register number.
4
Some values can be found in more than one place in different formats. For example when Sensor Number 6 is in
high alarm and latched:
• Register 40001:5 is the bit which indicates present alarm condition.
• Register 40007:5 is the bit which indicate a latched condition, regardless of the present sensor reading (until
reset)
• Register 40466 is a computed value of “2”
5
Registers starting at 40224 provide the raw data read from each of the eight sensors. The following describes the
data for sensor 1, the remaining registers through 40463 are for sensors 2 through 8:
40224
40225
40226
40227
40228
40229
40230
40231
40232
Sensor 1 Input Value - Multiplex 0 – V0 (Reference value of 0 volts)
Sensor 1 Input Value - Multiplex 1 – Vsignal (Current sensor signal)
Sensor 1 Input Value - Multiplex 2 – CH2 (Auxiliary data by type)
Sensor 1 Input Value - Multiplex 3 – CH3(Auxiliary data by type)
Sensor 1 Input Value - Multiplex 4 – Type
Sensor 1 Input Value - Multiplex 5 – Vin (Channel voltage)
Sensor 1 Input Value - Multiplex 6 – Calibration Switch Position (0=On)
Sensor 1 Input Value - Multiplex 7 – Vref (Reference value of 2.5 volts)
Sensor 1 Calibration Due Days
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
To calculate the raw signal voltage (for example), since we know Vref :
V = (Vsignal – V0) / (Vref – V0) * 2.5v
March 4, 2005
Page: 1
Sentry MODBUS I/O Memory Map
Read Only Parameters
Modbus Address
Parameter
Units
Discrete
40001:0
40001:1
40001:2
40001:3
40001:4
40001:5
40001:6
40001:7
High alarm bits - sensor 1
High alarm bits - sensor 2
High alarm bits - sensor 3
High alarm bits - sensor 4
High alarm bits - sensor 5
High alarm bits - sensor 6
High alarm bits - sensor 7
High alarm bits - sensor 8
40002:0
40002:1
40002:2
40002:3
40002:4
40002:5
40002:6
40002:7
Low alarm bits - sensor 1
Low alarm bits - sensor 2
Low alarm bits - sensor 3
Low alarm bits - sensor 4
Low alarm bits - sensor 5
Low alarm bits - sensor 6
Low alarm bits - sensor 7
Low alarm bits - sensor 8
40003:0
40003:1
40003:2
40003:3
40003:4
40003:5
40003:6
40003:7
Common (High or low) alarm bits - sensor 1
Common (High or low) alarm bits - sensor 2
Common (High or low) alarm bits - sensor 3
Common (High or low) alarm bits - sensor 4
Common (High or low) alarm bits - sensor 5
Common (High or low) alarm bits - sensor 6
Common (High or low) alarm bits - sensor 7
Common (High or low) alarm bits - sensor 8
40004:0
40004:1
40004:2
40004:3
40004:4
40004:5
Common high alarm, any sensor
Common low alarm, any sensor
Common any alarm, any sensor
Calibrate mode
Trouble alarm
Power Flash (Startup mode)
40005:0
40005:1
40005:2
40005:3
40005:4
40005:5
40005:6
40005:7
Sensor in calibration – sensor 1
Sensor in calibration – sensor 2
Sensor in calibration – sensor 3
Sensor in calibration – sensor 4
Sensor in calibration – sensor 5
Sensor in calibration – sensor 6
Sensor in calibration – sensor 7
Sensor in calibration – sensor 8
40006:0
40006:1
40006:2
40006:3
40006:4
40006:5
40006:6
40006:7
Bits indicating analog value is valid – sensor 1
Bits indicating analog value is valid – sensor 2
Bits indicating analog value is valid – sensor 3
Bits indicating analog value is valid – sensor 4
Bits indicating analog value is valid – sensor 5
Bits indicating analog value is valid – sensor 6
Bits indicating analog value is valid – sensor 7
Bits indicating analog value is valid – sensor 8
March 4, 2005
FIX EGU
Page: 2
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40007:0
40007:1
40007:2
40007:3
40007:4
40007:5
40007:6
40007:7
High alarm relay latched – sensor 1
High alarm relay latched – sensor 2
High alarm relay latched – sensor 3
High alarm relay latched – sensor 4
High alarm relay latched – sensor 5
High alarm relay latched – sensor 6
High alarm relay latched – sensor 7
High alarm relay latched – sensor 8
40008:0
40008:1
40008:2
40008:3
40008:4
40008:5
40008:6
40008:7
Low alarm relay latched – sensor 1
Low alarm relay latched – sensor 2
Low alarm relay latched – sensor 3
Low alarm relay latched – sensor 4
Low alarm relay latched – sensor 5
Low alarm relay latched – sensor 6
Low alarm relay latched – sensor 7
Low alarm relay latched – sensor 8
40009:0
40009:1
40009:2
40009:3
40009:4
40009:5
40009:6
40009:7
Common high/low alarm relay latched – sensor 1
Common high/low alarm relay latched – sensor 2
Common high/low alarm relay latched – sensor 3
Common high/low alarm relay latched – sensor 4
Common high/low alarm relay latched – sensor 5
Common high/low alarm relay latched – sensor 6
Common high/low alarm relay latched – sensor 7
Common high/low alarm relay latched – sensor 8
40011
40012
40013
40014
40015
40016
40017
40018
Sensor 1 concentration
Sensor 2 concentration
Sensor 3 concentration
Sensor 4 concentration
Sensor 5 concentration
Sensor 6 concentration
Sensor 7 concentration
Sensor 8 concentration
March 4, 2005
Units
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
FIX EGU
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Page: 3
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40020:0
40020:2
40020:3
40020:4
40020:5
40020:6
40020:7
40021:0
40021:1
40021:2
40021:3
40021:4
40021:5
40021:6
40021:7
40022:0
40022:1
40022:2
40024:0
Sensor 1: Status 2 Sensor Disconnected
(Trouble Bits)
Sensor 1: Voltage Regulator Failure
Sensor 1: Sensor Bad
Sensor 1: Duplicate Sensor
Sensor 1: Timer Failure
Sensor 1: Sensor Bridge Failure (CH4)
Sensor 1: Type Error
Sensor 1: Status 1 Enabled
Sensor 1: Auto Calibration Enabled
Sensor 1: Low Alarm Latch
Sensor 1: Calibrated
Sensor 1: Zone Option Enabled
Sensor 1: Calibration Table Initialized
Sensor 1: H2S Sensor Resistance too high
Sensor 1: Operate Mode (as opposed to Warm Up Mode)
Sensor 1: Status 4 High Alarm Latch
Sensor 1: Low Sensitivity
Sensor 1: Sensor not Valid
Sensor 1: Concentration
% / PPM
0 - 6553.5
40030:0
40030:2
40030:3
40030:4
40030:5
40030:6
40030:7
40031:0
40031:1
40031:2
40031:3
40031:4
40031:5
40031:6
40031:7
40032:0
40032:1
40032:2
40034:0
Sensor 2: Sensor Disconnected
(Trouble Bits)
Sensor 2: Voltage Regulator Failure
Sensor 2: Sensor Bad
Sensor 2: Duplicate Sensor
Sensor 2: Timer Failure
Sensor 2: Sensor Bridge Failure (Combustibles)
Sensor 2: Type Error
Sensor 2: Enabled
Sensor 2: Auto Calibration Enabled
Sensor 2: Low Alarm Latch
Sensor 2: Calibrated
Sensor 2: Zone Option Enabled
Sensor 2: Calibration Table Initialized
Sensor 2: H2S Sensor Resistance too high
Sensor 2: Operate Mode (as opposed to Warm Up Mode)
Sensor 2: High Alarm Latch
Sensor 2: Low Sensitivity
Sensor 2: Sensor not Valid
Sensor 2: Concentration
% / PPM
0 - 6553.5
March 4, 2005
Units
FIX EGU
Page: 4
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40040:0
40040:2
40040:3
40040:4
40040:5
40040:6
40040:7
40041:0
40041:1
40041:2
40041:3
40041:4
40041:5
40041:6
40041:7
40042:0
40042:1
40042:2
40044:0
Sensor 3: Sensor Disconnected
(Trouble Bits)
Sensor 3: Voltage Regulator Failure
Sensor 3: Sensor Bad
Sensor 3: Duplicate Sensor
Sensor 3: Timer Failure
Sensor 3: Sensor Bridge Failure (Combustibles)
Sensor 3: Type Error
Sensor 3: Enabled
Sensor 3: Auto Calibration Enabled
Sensor 3: Low Alarm Latch
Sensor 3: Calibrated
Sensor 3: Zone Option Enabled
Sensor 3: Calibration Table Initialized
Sensor 3: H2S Sensor Resistance too high
Sensor 3: Operate Mode (as opposed to Warm Up Mode)
Sensor 3: High Alarm Latch
Sensor 3: Low Sensitivity
Sensor 3: Sensor not Valid
Sensor 3: Concentration
% / PPM
0 - 6553.5
40050:0
40050:2
40050:3
40050:4
40050:5
40050:6
40050:7
40051:0
40051:1
40051:2
40051:3
40051:4
40051:5
40051:6
40051:7
40052:0
40052:1
40052:2
40054:0
Sensor 4: Sensor Disconnected
(Trouble Bits)
Sensor 4: Voltage Regulator Failure
Sensor 4: Sensor Bad
Sensor 4: Duplicate Sensor
Sensor 4: Timer Failure
Sensor 4: Sensor Bridge Failure (Combustibles)
Sensor 4: Type Error
Sensor 4: Enabled
Sensor 4: Auto Calibration Enabled
Sensor 4: Low Alarm Latch
Sensor 4: Calibrated
Sensor 4: Zone Option Enabled
Sensor 4: Calibration Table Initialized
Sensor 4: H2S Sensor Resistance too high
Sensor 4: Operate Mode (as opposed to Warm Up Mode)
Sensor 4: High Alarm Latch
Sensor 4: Low Sensitivity
Sensor 4: Sensor not Valid
Sensor 4: Concentration
% / PPM
0 - 6553.5
March 4, 2005
Units
FIX EGU
Page: 5
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40060:0
40060:2
40060:3
40060:4
40060:5
40060:6
40060:7
40061:0
40061:1
40061:2
40061:3
40061:4
40061:5
40061:6
40061:7
40062:0
40062:1
40062:2
40064:0
Sensor 5: Sensor Disconnected
(Trouble Bits)
Sensor 5: Voltage Regulator Failure
Sensor 5: Sensor Bad
Sensor 5: Duplicate Sensor
Sensor 5: Timer Failure
Sensor 5: Sensor Bridge Failure (Combustibles)
Sensor 5: Type Error
Sensor 5: Enabled
Sensor 5: Auto Calibration Enabled
Sensor 5: Low Alarm Latch
Sensor 5: Calibrated
Sensor 5: Zone Option Enabled
Sensor 5: Calibration Table Initialized
Sensor 5: H2S Sensor Resistance too high
Sensor 5: Operate Mode (as opposed to Warm Up Mode)
Sensor 5: High Alarm Latch
Sensor 5: Low Sensitivity
Sensor 5: Sensor not Valid
Sensor 5:Concentration
% / PPM
0 - 6553.5
40070:0
40070:2
40070:3
40070:4
40070:5
40070:6
40070:7
40071:0
40071:1
40071:2
40071:3
40071:4
40071:5
40071:6
40071:7
40072:0
40072:1
40072:2
40074:0
Sensor 6: Sensor Disconnected
(Trouble Bits)
Sensor 6: Voltage Regulator Failure
Sensor 6: Sensor Bad
Sensor 6: Duplicate Sensor
Sensor 6: Timer Failure
Sensor 6: Sensor Bridge Failure (Combustibles)
Sensor 6: Type Error
Sensor 6: Enabled
Sensor 6: Auto Calibration Enabled
Sensor 6: Low Alarm Latch
Sensor 6: Calibrated
Sensor 6: Zone Option Enabled
Sensor 6: Calibration Table Initialized
Sensor 6: H2S Sensor Resistance too high
Sensor 6: Operate Mode (as opposed to Warm Up Mode)
Sensor 6: High Alarm Latch
Sensor 6: Low Sensitivity
Sensor 6: Sensor not Valid
Sensor 6: Concentration
% / PPM
0 - 6553.5
March 4, 2005
Units
FIX EGU
Page: 6
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40080:0
40080:2
40080:3
40080:4
40080:5
40080:6
40080:7
40081:0
40081:1
40081:2
40081:3
40081:4
40081:5
40081:6
40081:7
40082:0
40082:1
40082:2
40084:0
Sensor 7: Sensor Disconnected
(Trouble Bits)
Sensor 7: Voltage Regulator Failure
Sensor 7: Sensor Bad
Sensor 7: Duplicate Sensor
Sensor 7: Timer Failure
Sensor 7: Sensor Bridge Failure (Combustibles)
Sensor 7: Type Error
Sensor 7: Enabled
Sensor 7: Auto Calibration Enabled
Sensor 7: Low Alarm Latch
Sensor 7: Calibrated
Sensor 7: Zone Option Enabled
Sensor 7: Calibration Table Initialized
Sensor 7: H2S Sensor Resistance too high
Sensor 7: Operate Mode (as opposed to Warm Up Mode)
Sensor 7: High Alarm Latch
Sensor 7: Low Sensitivity
Sensor 7: Sensor not Valid
Sensor 7: Concentration % / PPM 0 - 6553.5
40090:0
40090:2
40090:3
40090:4
40090:5
40090:6
40090:7
40091:0
40091:1
40091:2
40091:3
40091:4
40091:5
40091:6
40091:7
40092:0
40092:1
40092:2
40094:0
Sensor 8: Sensor Disconnected
(Trouble Bits)
Sensor 8: Voltage Regulator Failure
Sensor 8: Sensor Bad
Sensor 8: Duplicate Sensor
Sensor 8: Timer Failure
Sensor 8: Sensor Bridge Failure (Combustibles)
Sensor 8: Type Error
Sensor 8: Enabled
Sensor 8: Auto Calibration Enabled
Sensor 8: Low Alarm Latch
Sensor 8: Calibrated
Sensor 8: Zone Option Enabled
Sensor 8: Calibration Table Initialized
Sensor 8: H2S Sensor Resistance too high
Sensor 8: Operate Mode (as opposed to Warm Up Mode)
Sensor 8: High Alarm Latch
Sensor 8: Low Sensitivity
Sensor 8: Sensor not Valid
Sensor 8: Concentration
% / PPM
0 - 6553.5
March 4, 2005
Units
FIX EGU
Page: 7
Sentry MODBUS I/O Memory Map
Analog Process Variables
Modbus Address
Parameter
Units
FIX EGU
40111
40112
40113
40114
40115
40116
40117
40118
Sensor 1 concentration
Sensor 2 concentration
Sensor 3 concentration
Sensor 4 concentration
Sensor 5 concentration
Sensor 6 concentration
Sensor 7 concentration
Sensor 8 concentration
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
40119
40120
40121
40122
40123
40124
40125
40126
Sensor 1 Highest Concentration
Sensor 2 Highest Concentration
Sensor 3 Highest Concentration
Sensor 4 Highest Concentration
Sensor 5 Highest Concentration
Sensor 6 Highest Concentration
Sensor 7 Highest Concentration
Sensor 8 Highest Concentration
40127
40128
40129
40130
40131
40132
40133
40134
Sensor 1 Lowest Concentration
Sensor 2 Lowest Concentration
Sensor 3 Lowest Concentration
Sensor 4 Lowest Concentration
Sensor 5 Lowest Concentration
Sensor 6 Lowest Concentration
Sensor 7 Lowest Concentration
Sensor 8 Lowest Concentration
40135
40136
40137
40138
40139
40140
40141
40142
Sensor 1 Maximum Input value (Voltage)
Sensor 2 Maximum Input value (Voltage)
Sensor 3 Maximum Input value (Voltage)
Sensor 4 Maximum Input value (Voltage)
Sensor 5 Maximum Input value (Voltage)
Sensor 6 Maximum Input value (Voltage)
Sensor 7 Maximum Input value (Voltage)
Sensor 8 Maximum Input value (Voltage)
40143
40144
40145
40146
40147
40148
40149
40150
Sensor 1 Minimum Input value (Voltage)
Sensor 2 Minimum Input value (Voltage)
Sensor 3 Minimum Input value (Voltage)
Sensor 4 Minimum Input value (Voltage)
Sensor 5 Minimum Input value (Voltage)
Sensor 6 Minimum Input value (Voltage)
Sensor 7 Minimum Input value (Voltage)
Sensor 8 Minimum Input value (Voltage)
40151
40152
40153
40154
40155
Sensor 1 Power (H2S and COMB only )
Sensor 2 Power (H2S and COMB only )
Sensor 3 Power (H2S and COMB only )
Sensor 4 Power (H2S and COMB only )
Sensor 5 Power (H2S and COMB only )
March 4, 2005
Page: 8
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40156
40157
40158
Sensor 6 Power (H2S and COMB only )
Sensor 7 Power (H2S and COMB only )
Sensor 8 Power (H2S and COMB only )
40159
40160
40161
40162
40163
40164
40165
40166
Sensor 1 Type
Sensor 2 Type
Sensor 3 Type
Sensor 4 Type
Sensor 5 Type
Sensor 6 Type
Sensor 7 Type
Sensor 8 Type
40170
40171
40172
40173
System Historical Reset Time Month
System Historical Reset Time Day
System Historical Reset Time Hr
System Historical Reset Time Min
40174
40175
40176
40177
System Power Up Time Month
System Power Up Time Day
System Power Up Time Hr
System Power Up Time Min
40178
40179
40180
40181
System Power Down Time Month
System Power Down Time Day
System Power Down Time Hr
System Power Down Time Min
40200
40201
40202
40203
Sensor 1 High Alarm Time
Sensor 1 High Alarm Time
Sensor 1 High Alarm Time
Sensor 1 High Alarm Time
Month
Day
Hr
Min
40204
40205
40206
40207
Sensor 1 Low Alarm Time
Sensor 1 Low Alarm Time
Sensor 1 Low Alarm Time
Sensor 1 Low Alarm Time
Month
Day
Hr
Min
40208
40209
40210
40211
Sensor 1 Calibration Time Month
Sensor 1 Calibration Time Day
Sensor 1 Calibration Time Hr
Sensor 1 Calibration Time Min
40212
40213
40214
40215
Sensor 1 High Conc. Time
Sensor 1 High Conc. Time
Sensor 1 High Conc. Time
Sensor 1 High Conc. Time
Month
Day
Hr
Min
40216
40217
40218
40219
Sensor 1 Low Conc. Time
Sensor 1 Low Conc. Time
Sensor 1 Low Conc. Time
Sensor 1 Low Conc. Time
Month
Day
Hr
Min
40220
40221
40222
40223
Sensor 1 Trouble Time
Sensor 1 Trouble Time
Sensor 1 Trouble Time
Sensor 1 Trouble Time
March 4, 2005
Units
FIX EGU
(1,2,3 or 4)
(1,2,3 or 4)
(1,2,3 or 4)
(1,2,3 or 4)
(1,2,3 or 4)
(1,2,3 or 4)
(1,2,3 or 4)
(1,2,3 or 4)
Month
Day
Hr
Min
Page: 9
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40224
40225
40226
40227
40228
40229
40230
40231
Sensor 1 Input Value - Multiplex 0
Sensor 1 Input Value - Multiplex 1
Sensor 1 Input Value - Multiplex 2
Sensor 1 Input Value - Multiplex 3
Sensor 1 Input Value - Multiplex 4
Sensor 1 Input Value - Multiplex 5
Sensor 1 Input Value - Multiplex 6
Sensor 1 Input Value - Multiplex 7
40232
Sensor 1 Calibration Due Days
40233
40234
40235
40236
Sensor 2 High Alarm Time
Sensor 2 High Alarm Time
Sensor 2 High Alarm Time
Sensor 2 High Alarm Time
Month
Day
Hr
Min
40237
40238
40239
40240
Sensor 2 Low Alarm Time
Sensor 2 Low Alarm Time
Sensor 2 Low Alarm Time
Sensor 2 Low Alarm Time
Month
Day
Hr
Min
40241
40242
40243
40244
Sensor 2 Calibration Time Month
Sensor 2 Calibration Time Day
Sensor 2 Calibration Time Hr
Sensor 2 Calibration Time Min
40245
40246
40247
40248
Sensor 2 High Conc. Time
Sensor 2 High Conc. Time
Sensor 2 High Conc. Time
Sensor 2 High Conc. Time
Month
Day
Hr
Min
40249
40250
40251
40252
Sensor 2 Low Conc. Time
Sensor 2 Low Conc. Time
Sensor 2 Low Conc. Time
Sensor 2 Low Conc. Time
Month
Day
Hr
Min
40253
40254
40255
40256
Sensor 2 Trouble Time
Sensor 2 Trouble Time
Sensor 2 Trouble Time
Sensor 2 Trouble Time
40257
40258
40259
40260
40261
40262
40263
40264
Sensor 2 Input Value - Multiplex 0
Sensor 2 Input Value - Multiplex 1
Sensor 2 Input Value - Multiplex 2
Sensor 2 Input Value - Multiplex 3
Sensor 2 Input Value - Multiplex 4
Sensor 2 Input Value - Multiplex 5
Sensor 2 Input Value - Multiplex 6
Sensor 2 Input Value - Multiplex 7
40265
Sensor 2 Calibration Due Days
March 4, 2005
Units
FIX EGU
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Month
Day
Hr
Min
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Page: 10
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40266
40267
40268
40269
Sensor 3 High Alarm Time
Sensor 3 High Alarm Time
Sensor 3 High Alarm Time
Sensor 3 High Alarm Time
Month
Day
Hr
Min
40270
40271
40272
40273
Sensor 3 Low Alarm Time
Sensor 3 Low Alarm Time
Sensor 3 Low Alarm Time
Sensor 3 Low Alarm Time
Month
Day
Hr
Min
40274
40275
40276
40277
Sensor 3 Calibration Time Month
Sensor 3 Calibration Time Day
Sensor 3 Calibration Time Hr
Sensor 3 Calibration Time Min
40278
40279
40280
40281
Sensor 3 High Conc. Time
Sensor 3 High Conc. Time
Sensor 3 High Conc. Time
Sensor 3 High Conc. Time
Month
Day
Hr
Min
40282
40283
40284
40285
Sensor 3 Low Conc. Time
Sensor 3 Low Conc. Time
Sensor 3 Low Conc. Time
Sensor 3 Low Conc. Time
Month
Day
Hr
Min
40286
40287
40288
40289
Sensor 3 Trouble Time
Sensor 3 Trouble Time
Sensor 3 Trouble Time
Sensor 3 Trouble Time
40290
40291
40292
40293
40294
40295
40296
40297
Sensor 3 Input Value - Multiplex 0
Sensor 3 Input Value - Multiplex 1
Sensor 3 Input Value - Multiplex 2
Sensor 3 Input Value - Multiplex 3
Sensor 3 Input Value - Multiplex 4
Sensor 3 Input Value - Multiplex 5
Sensor 3 Input Value - Multiplex 6
Sensor 3 Input Value - Multiplex 7
40298
Sensor 3 Calibration Due Days
40299
40300
40301
40302
Sensor 4 High Alarm Time
Sensor 4 High Alarm Time
Sensor 4 High Alarm Time
Sensor 4 High Alarm Time
Month
Day
Hr
Min
40303
40304
40305
40306
Sensor 4 Low Alarm Time
Sensor 4 Low Alarm Time
Sensor 4 Low Alarm Time
Sensor 4 Low Alarm Time
Month
Day
Hr
Min
40307
40308
40309
40310
Sensor 4 Calibration Time Month
Sensor 4 Calibration Time Day
Sensor 4 Calibration Time Hr
Sensor 4 Calibration Time Min
March 4, 2005
Units
FIX EGU
Month
Day
Hr
Min
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Page: 11
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40311
40312
40313
40314
Sensor 4 High Conc. Time
Sensor 4 High Conc. Time
Sensor 4 High Conc. Time
Sensor 4 High Conc. Time
Month
Day
Hr
Min
40315
40316
40317
40318
Sensor 4 Low Conc. Time
Sensor 4 Low Conc. Time
Sensor 4 Low Conc. Time
Sensor 4 Low Conc. Time
Month
Day
Hr
Min
40319
40320
40321
40322
Sensor 4 Trouble Time
Sensor 4 Trouble Time
Sensor 4 Trouble Time
Sensor 4 Trouble Time
40323
40324
40325
40326
40327
40328
40329
40330
Sensor 4 Input Value - Multiplex 0
Sensor 4 Input Value - Multiplex 1
Sensor 4 Input Value - Multiplex 2
Sensor 4 Input Value - Multiplex 3
Sensor 4 Input Value - Multiplex 4
Sensor 4 Input Value - Multiplex 5
Sensor 4 Input Value - Multiplex 6
Sensor 4 Input Value - Multiplex 7
40331
Sensor 4 Calibration Due Days
40332
40333
40334
40335
Sensor 5 High Alarm Time
Sensor 5 High Alarm Time
Sensor 5 High Alarm Time
Sensor 5 High Alarm Time
Month
Day
Hr
Min
40336
40337
40338
40339
Sensor 5 Low Alarm Time
Sensor 5 Low Alarm Time
Sensor 5 Low Alarm Time
Sensor 5 Low Alarm Time
Month
Day
Hr
Min
40340
40341
40342
40343
Sensor 5 Calibration Time Month
Sensor 5 Calibration Time Day
Sensor 5 Calibration Time Hr
Sensor 5 Calibration Time Min
40344
40345
40346
40347
Sensor 5 High Conc. Time
Sensor 5 High Conc. Time
Sensor 5 High Conc. Time
Sensor 5 High Conc. Time
Month
Day
Hr
Min
40348
40349
40350
40351
Sensor 5 Low Conc. Time
Sensor 5 Low Conc. Time
Sensor 5 Low Conc. Time
Sensor 5 Low Conc. Time
Month
Day
Hr
Min
40352
40353
40354
40355
Sensor 5 Trouble Time
Sensor 5 Trouble Time
Sensor 5 Trouble Time
Sensor 5 Trouble Time
March 4, 2005
Units
FIX EGU
Month
Day
Hr
Min
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Month
Day
Hr
Min
Page: 12
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40356
40357
40358
40359
40360
40361
40362
40363
Sensor 5 Input Value - Multiplex 0
Sensor 5 Input Value - Multiplex 1
Sensor 5 Input Value - Multiplex 2
Sensor 5 Input Value - Multiplex 3
Sensor 5 Input Value - Multiplex 4
Sensor 5 Input Value - Multiplex 5
Sensor 5 Input Value - Multiplex 6
Sensor 5 Input Value - Multiplex 7
40364
Sensor 5 Calibration Due Days
40365
40366
40367
40368
Sensor 6 High Alarm Time
Sensor 6 High Alarm Time
Sensor 6 High Alarm Time
Sensor 6 High Alarm Time
Month
Day
Hr
Min
40369
40370
40371
40372
Sensor 6 Low Alarm Time
Sensor 6 Low Alarm Time
Sensor 6 Low Alarm Time
Sensor 6 Low Alarm Time
Month
Day
Hr
Min
40373
40374
40375
40376
Sensor 6 Calibration Time Month
Sensor 6 Calibration Time Day
Sensor 6 Calibration Time Hr
Sensor 6 Calibration Time Min
40377
40378
40379
40380
Sensor 6 High Conc. Time
Sensor 6 High Conc. Time
Sensor 6 High Conc. Time
Sensor 6 High Conc. Time
Month
Day
Hr
Min
40381
40382
40383
40384
Sensor 6 Low Conc. Time
Sensor 6 Low Conc. Time
Sensor 6 Low Conc. Time
Sensor 6 Low Conc. Time
Month
Day
Hr
Min
40385
40386
40387
40388
Sensor 6 Trouble Time
Sensor 6 Trouble Time
Sensor 6 Trouble Time
Sensor 6 Trouble Time
40389
40390
40391
40392
40393
40394
40395
40396
Sensor 6 Input Value - Multiplex 0
Sensor 6 Input Value - Multiplex 1
Sensor 6 Input Value - Multiplex 2
Sensor 6 Input Value - Multiplex 3
Sensor 6 Input Value - Multiplex 4
Sensor 6 Input Value - Multiplex 5
Sensor 6 Input Value - Multiplex 6
Sensor 6 Input Value - Multiplex 7
40397
Sensor 6 Calibration Due Days
March 4, 2005
Units
FIX EGU
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Month
Day
Hr
Min
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Page: 13
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40398
40399
40400
40401
Sensor 7 High Alarm Time
Sensor 7 High Alarm Time
Sensor 7 High Alarm Time
Sensor 7 High Alarm Time
Month
Day
Hr
Min
40402
40403
40404
40405
Sensor 7 Low Alarm Time
Sensor 7 Low Alarm Time
Sensor 7 Low Alarm Time
Sensor 7 Low Alarm Time
Month
Day
Hr
Min
40406
40407
40408
40409
Sensor 7 Calibration Time Month
Sensor 7 Calibration Time Day
Sensor 7 Calibration Time Hr
Sensor 7 Calibration Time Min
40410
40411
40412
40413
Sensor 7 High Conc. Time
Sensor 7 High Conc. Time
Sensor 7 High Conc. Time
Sensor 7 High Conc. Time
Month
Day
Hr
Min
40414
40415
40416
40417
Sensor 7 Low Conc. Time
Sensor 7 Low Conc. Time
Sensor 7 Low Conc. Time
Sensor 7 Low Conc. Time
Month
Day
Hr
Min
40418
40419
40420
40421
Sensor 7 Trouble Time
Sensor 7 Trouble Time
Sensor 7 Trouble Time
Sensor 7 Trouble Time
40422
40423
40424
40425
40426
40427
40428
40429
Sensor 7 Input Value - Multiplex 0
Sensor 7 Input Value - Multiplex 1
Sensor 7 Input Value - Multiplex 2
Sensor 7 Input Value - Multiplex 3
Sensor 7 Input Value - Multiplex 4
Sensor 7 Input Value - Multiplex 5
Sensor 7 Input Value - Multiplex 6
Sensor 7 Input Value - Multiplex 7
40430
Sensor 7 Calibration Due Days
40431
40432
40433
40434
Sensor 8 High Alarm Time
Sensor 8 High Alarm Time
Sensor 8 High Alarm Time
Sensor 8 High Alarm Time
Month
Day
Hr
Min
40435
40436
40437
40438
Sensor 8 Low Alarm Time
Sensor 8 Low Alarm Time
Sensor 8 Low Alarm Time
Sensor 8 Low Alarm Time
Month
Day
Hr
Min
40439
40440
40441
40442
Sensor 8 Calibration Time Month
Sensor 8 Calibration Time Day
Sensor 8 Calibration Time Hr
Sensor 8 Calibration Time Min
March 4, 2005
Units
FIX EGU
Month
Day
Hr
Min
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Page: 14
Sentry MODBUS I/O Memory Map
Modbus Address
Parameter
40443
40444
40445
40446
Sensor 8 High Conc. Time
Sensor 8 High Conc. Time
Sensor 8 High Conc. Time
Sensor 8 High Conc. Time
Month
Day
Hr
Min
40447
40448
40449
40450
Sensor 8Low Conc. Time
Sensor 8 Low Conc. Time
Sensor 8 Low Conc. Time
Sensor 8 Low Conc. Time
Month
Day
Hr
Min
40451
40452
40453
40454
Sensor 8 Trouble Time
Sensor 8 Trouble Time
Sensor 8 Trouble Time
Sensor 8 Trouble Time
40455
40456
40457
40458
40459
40460
40461
40462
Sensor 8 Input Value - Multiplex 0
Sensor 8 Input Value - Multiplex 1
Sensor 8 Input Value - Multiplex 2
Sensor 8 Input Value - Multiplex 3
Sensor 8 Input Value - Multiplex 4
Sensor 8 Input Value - Multiplex 5
Sensor 8 Input Value - Multiplex 6
Sensor 8 Input Value - Multiplex 7
40463
Sensor 8 Calibration Due Days
40466
40467
40468
40469
40470
40471
40472
40473
Contrived alarm - Sensor 1 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
Contrived alarm - Sensor 2 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
Contrived alarm - Sensor 3 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
Contrived alarm - Sensor 4 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
Contrived alarm - Sensor 5 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
Contrived alarm - Sensor 6 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
Contrived alarm - Sensor 7 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
Contrived alarm - Sensor 8 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
March 4, 2005
Units
FIX EGU
Month
Day
Hr
Min
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
0 - 6553.5
Page: 15
Sentry MODBUS I/O Memory Map
Read/Write Parameters
High Alarm Limits
Modbus Address
Parameter
Units
FIX EGU
40501
40502
40503
40504
40505
40506
40507
40508
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Sensor 5
Sensor 6
Sensor 7
Sensor 8
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Sensor 5
Sensor 6
Sensor 7
Sensor 8
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
% / PPM
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
0 - 65535
Low Alarm Limits
40511
40512
40513
40514
40515
40516
40517
40518
H2S/CH4/Oxy/CO
40520
40521
40522
40523
40524
40525
40526
40527
40528
Sensor 1 Calib.
40530
40521
40532
40533
40534
40535
40536
40537
40538
Sensor 2 Calib.
40540
40541
40542
40543
40544
40545
40546
40547
40548
Sensor 3 Calib.
March 4, 2005
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
-
-
-
ccn
vmax
-
ccn
vmin
vmax
-
ccn
vmax
-
ccn
vmin
vmax
-
ccn
vmax
-
ccn
vmin
vmax
-
Page: 16
Sentry MODBUS I/O Memory Map
40550
40551
40552
40553
40554
40555
40556
40557
40558
Sensor 4 Calib.
40560
40561
40562
40563
40564
40565
40566
40567
40568
Sensor 5 Calib.
40570
40571
40572
40573
40574
40575
40576
40577
40578
Sensor 6 Calib.
40580
40581
40582
40583
40584
40585
40586
40587
40588
Sensor 7 Calib.
40590
40591
40592
40593
40594
40595
40596
40597
40598
Sensor 8 Calib.
March 4, 2005
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
Coeff. 1
2
3
4
5
6
7
8
9
k1
k2
k3
n1
n2
n3
bp12
bp23
ccn
ccn
vmin
vmax
gasfac
-
-
-
-
-
-
ccn
vmax
-
ccn
vmin
vmax
-
ccn
vmax
-
ccn
vmin
vmax
-
ccn
vmax
-
ccn
vmin
vmax
-
ccn
vmax
-
ccn
vmin
vmax
-
ccn
vmax
-
ccn
vmin
vmax
-
Page: 17
Sentry MODBUS I/O Memory Map
Control Bits
Modbus Address
Parameter
40601
40602
40603
System Reset
Alarm Reset
History Reset
40610
40611
40612
40613
System Time Month
System Time Day
System Time Hr
System Time Min
40614
40615
40616
40617
40618
40619
40620
40621
Latch High Alarms - Sensor 1
Latch High Alarms - Sensor 2
Latch High Alarms - Sensor 3
Latch High Alarms - Sensor 4
Latch High Alarms - Sensor 5
Latch High Alarms - Sensor 6
Latch High Alarms - Sensor 7
Latch High Alarms - Sensor 8
40622
40623
40624
40625
40626
40627
40628
40629
Latch Low Alarms - Sensor 1
Latch Low Alarms - Sensor 2
Latch Low Alarms - Sensor 3
Latch Low Alarms - Sensor 4
Latch Low Alarms - Sensor 5
Latch Low Alarms - Sensor 6
Latch Low Alarms - Sensor 7
Latch Low Alarms - Sensor 8
40631
40632
40633
Calibration Concentration Comb (Type 2)
Calibration Concentration Oxy (Type 3)
Calibration Concentration Toxic (Type 4)
March 4, 2005
Units
FIX EGU
Page: 18