Sentry Controller MODBUS Memory Map (Enhanced) December 15, 1998 Updated March 4, 2005 Sierra Monitor Corp. 1991 Tarob Ct. Milpitas, CA 95035 USA 408-262-6611, Toll Free 800-727-4377, FAX: 408-262-9042 Visit our Web Site: www.sierramonitor.com E-Mail: [email protected] Sentry MODBUS I/O Memory Map Sentry Controller MODBUS Memory Map Detail 1 All Registers are MODBUS 16 bit registers 2 There are five different ways of using MODBUS registers (see italic reference number in left column for each address) 2.1 As an Analog Value: In most cases these values are scaled by multiplying by 10. 2.2 As eight packed digital states, packed into one register. In this case the remaining 8 bits are unused. 2.3 As a digital state where the register value can only be “0” or “1”. 2.4 As a computed value, such as where “0” = no alarm, “1” = low alarm, “2” = high alarm. 2.5 Control registers, where the SCADA host can write a value, such as alarm reset to the Sentry, or to set calibration concentration, or alarm set point. Note that these registers are read or write. 3 Where a series of registers apply only to sensor number 1, the following sequences for sensors 2, through 8 are only referenced by the first applicable register number. 4 Some values can be found in more than one place in different formats. For example when Sensor Number 6 is in high alarm and latched: • Register 40001:5 is the bit which indicates present alarm condition. • Register 40007:5 is the bit which indicate a latched condition, regardless of the present sensor reading (until reset) • Register 40466 is a computed value of “2” 5 Registers starting at 40224 provide the raw data read from each of the eight sensors. The following describes the data for sensor 1, the remaining registers through 40463 are for sensors 2 through 8: 40224 40225 40226 40227 40228 40229 40230 40231 40232 Sensor 1 Input Value - Multiplex 0 – V0 (Reference value of 0 volts) Sensor 1 Input Value - Multiplex 1 – Vsignal (Current sensor signal) Sensor 1 Input Value - Multiplex 2 – CH2 (Auxiliary data by type) Sensor 1 Input Value - Multiplex 3 – CH3(Auxiliary data by type) Sensor 1 Input Value - Multiplex 4 – Type Sensor 1 Input Value - Multiplex 5 – Vin (Channel voltage) Sensor 1 Input Value - Multiplex 6 – Calibration Switch Position (0=On) Sensor 1 Input Value - Multiplex 7 – Vref (Reference value of 2.5 volts) Sensor 1 Calibration Due Days 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 To calculate the raw signal voltage (for example), since we know Vref : V = (Vsignal – V0) / (Vref – V0) * 2.5v March 4, 2005 Page: 1 Sentry MODBUS I/O Memory Map Read Only Parameters Modbus Address Parameter Units Discrete 40001:0 40001:1 40001:2 40001:3 40001:4 40001:5 40001:6 40001:7 High alarm bits - sensor 1 High alarm bits - sensor 2 High alarm bits - sensor 3 High alarm bits - sensor 4 High alarm bits - sensor 5 High alarm bits - sensor 6 High alarm bits - sensor 7 High alarm bits - sensor 8 40002:0 40002:1 40002:2 40002:3 40002:4 40002:5 40002:6 40002:7 Low alarm bits - sensor 1 Low alarm bits - sensor 2 Low alarm bits - sensor 3 Low alarm bits - sensor 4 Low alarm bits - sensor 5 Low alarm bits - sensor 6 Low alarm bits - sensor 7 Low alarm bits - sensor 8 40003:0 40003:1 40003:2 40003:3 40003:4 40003:5 40003:6 40003:7 Common (High or low) alarm bits - sensor 1 Common (High or low) alarm bits - sensor 2 Common (High or low) alarm bits - sensor 3 Common (High or low) alarm bits - sensor 4 Common (High or low) alarm bits - sensor 5 Common (High or low) alarm bits - sensor 6 Common (High or low) alarm bits - sensor 7 Common (High or low) alarm bits - sensor 8 40004:0 40004:1 40004:2 40004:3 40004:4 40004:5 Common high alarm, any sensor Common low alarm, any sensor Common any alarm, any sensor Calibrate mode Trouble alarm Power Flash (Startup mode) 40005:0 40005:1 40005:2 40005:3 40005:4 40005:5 40005:6 40005:7 Sensor in calibration – sensor 1 Sensor in calibration – sensor 2 Sensor in calibration – sensor 3 Sensor in calibration – sensor 4 Sensor in calibration – sensor 5 Sensor in calibration – sensor 6 Sensor in calibration – sensor 7 Sensor in calibration – sensor 8 40006:0 40006:1 40006:2 40006:3 40006:4 40006:5 40006:6 40006:7 Bits indicating analog value is valid – sensor 1 Bits indicating analog value is valid – sensor 2 Bits indicating analog value is valid – sensor 3 Bits indicating analog value is valid – sensor 4 Bits indicating analog value is valid – sensor 5 Bits indicating analog value is valid – sensor 6 Bits indicating analog value is valid – sensor 7 Bits indicating analog value is valid – sensor 8 March 4, 2005 FIX EGU Page: 2 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40007:0 40007:1 40007:2 40007:3 40007:4 40007:5 40007:6 40007:7 High alarm relay latched – sensor 1 High alarm relay latched – sensor 2 High alarm relay latched – sensor 3 High alarm relay latched – sensor 4 High alarm relay latched – sensor 5 High alarm relay latched – sensor 6 High alarm relay latched – sensor 7 High alarm relay latched – sensor 8 40008:0 40008:1 40008:2 40008:3 40008:4 40008:5 40008:6 40008:7 Low alarm relay latched – sensor 1 Low alarm relay latched – sensor 2 Low alarm relay latched – sensor 3 Low alarm relay latched – sensor 4 Low alarm relay latched – sensor 5 Low alarm relay latched – sensor 6 Low alarm relay latched – sensor 7 Low alarm relay latched – sensor 8 40009:0 40009:1 40009:2 40009:3 40009:4 40009:5 40009:6 40009:7 Common high/low alarm relay latched – sensor 1 Common high/low alarm relay latched – sensor 2 Common high/low alarm relay latched – sensor 3 Common high/low alarm relay latched – sensor 4 Common high/low alarm relay latched – sensor 5 Common high/low alarm relay latched – sensor 6 Common high/low alarm relay latched – sensor 7 Common high/low alarm relay latched – sensor 8 40011 40012 40013 40014 40015 40016 40017 40018 Sensor 1 concentration Sensor 2 concentration Sensor 3 concentration Sensor 4 concentration Sensor 5 concentration Sensor 6 concentration Sensor 7 concentration Sensor 8 concentration March 4, 2005 Units % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM FIX EGU 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Page: 3 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40020:0 40020:2 40020:3 40020:4 40020:5 40020:6 40020:7 40021:0 40021:1 40021:2 40021:3 40021:4 40021:5 40021:6 40021:7 40022:0 40022:1 40022:2 40024:0 Sensor 1: Status 2 Sensor Disconnected (Trouble Bits) Sensor 1: Voltage Regulator Failure Sensor 1: Sensor Bad Sensor 1: Duplicate Sensor Sensor 1: Timer Failure Sensor 1: Sensor Bridge Failure (CH4) Sensor 1: Type Error Sensor 1: Status 1 Enabled Sensor 1: Auto Calibration Enabled Sensor 1: Low Alarm Latch Sensor 1: Calibrated Sensor 1: Zone Option Enabled Sensor 1: Calibration Table Initialized Sensor 1: H2S Sensor Resistance too high Sensor 1: Operate Mode (as opposed to Warm Up Mode) Sensor 1: Status 4 High Alarm Latch Sensor 1: Low Sensitivity Sensor 1: Sensor not Valid Sensor 1: Concentration % / PPM 0 - 6553.5 40030:0 40030:2 40030:3 40030:4 40030:5 40030:6 40030:7 40031:0 40031:1 40031:2 40031:3 40031:4 40031:5 40031:6 40031:7 40032:0 40032:1 40032:2 40034:0 Sensor 2: Sensor Disconnected (Trouble Bits) Sensor 2: Voltage Regulator Failure Sensor 2: Sensor Bad Sensor 2: Duplicate Sensor Sensor 2: Timer Failure Sensor 2: Sensor Bridge Failure (Combustibles) Sensor 2: Type Error Sensor 2: Enabled Sensor 2: Auto Calibration Enabled Sensor 2: Low Alarm Latch Sensor 2: Calibrated Sensor 2: Zone Option Enabled Sensor 2: Calibration Table Initialized Sensor 2: H2S Sensor Resistance too high Sensor 2: Operate Mode (as opposed to Warm Up Mode) Sensor 2: High Alarm Latch Sensor 2: Low Sensitivity Sensor 2: Sensor not Valid Sensor 2: Concentration % / PPM 0 - 6553.5 March 4, 2005 Units FIX EGU Page: 4 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40040:0 40040:2 40040:3 40040:4 40040:5 40040:6 40040:7 40041:0 40041:1 40041:2 40041:3 40041:4 40041:5 40041:6 40041:7 40042:0 40042:1 40042:2 40044:0 Sensor 3: Sensor Disconnected (Trouble Bits) Sensor 3: Voltage Regulator Failure Sensor 3: Sensor Bad Sensor 3: Duplicate Sensor Sensor 3: Timer Failure Sensor 3: Sensor Bridge Failure (Combustibles) Sensor 3: Type Error Sensor 3: Enabled Sensor 3: Auto Calibration Enabled Sensor 3: Low Alarm Latch Sensor 3: Calibrated Sensor 3: Zone Option Enabled Sensor 3: Calibration Table Initialized Sensor 3: H2S Sensor Resistance too high Sensor 3: Operate Mode (as opposed to Warm Up Mode) Sensor 3: High Alarm Latch Sensor 3: Low Sensitivity Sensor 3: Sensor not Valid Sensor 3: Concentration % / PPM 0 - 6553.5 40050:0 40050:2 40050:3 40050:4 40050:5 40050:6 40050:7 40051:0 40051:1 40051:2 40051:3 40051:4 40051:5 40051:6 40051:7 40052:0 40052:1 40052:2 40054:0 Sensor 4: Sensor Disconnected (Trouble Bits) Sensor 4: Voltage Regulator Failure Sensor 4: Sensor Bad Sensor 4: Duplicate Sensor Sensor 4: Timer Failure Sensor 4: Sensor Bridge Failure (Combustibles) Sensor 4: Type Error Sensor 4: Enabled Sensor 4: Auto Calibration Enabled Sensor 4: Low Alarm Latch Sensor 4: Calibrated Sensor 4: Zone Option Enabled Sensor 4: Calibration Table Initialized Sensor 4: H2S Sensor Resistance too high Sensor 4: Operate Mode (as opposed to Warm Up Mode) Sensor 4: High Alarm Latch Sensor 4: Low Sensitivity Sensor 4: Sensor not Valid Sensor 4: Concentration % / PPM 0 - 6553.5 March 4, 2005 Units FIX EGU Page: 5 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40060:0 40060:2 40060:3 40060:4 40060:5 40060:6 40060:7 40061:0 40061:1 40061:2 40061:3 40061:4 40061:5 40061:6 40061:7 40062:0 40062:1 40062:2 40064:0 Sensor 5: Sensor Disconnected (Trouble Bits) Sensor 5: Voltage Regulator Failure Sensor 5: Sensor Bad Sensor 5: Duplicate Sensor Sensor 5: Timer Failure Sensor 5: Sensor Bridge Failure (Combustibles) Sensor 5: Type Error Sensor 5: Enabled Sensor 5: Auto Calibration Enabled Sensor 5: Low Alarm Latch Sensor 5: Calibrated Sensor 5: Zone Option Enabled Sensor 5: Calibration Table Initialized Sensor 5: H2S Sensor Resistance too high Sensor 5: Operate Mode (as opposed to Warm Up Mode) Sensor 5: High Alarm Latch Sensor 5: Low Sensitivity Sensor 5: Sensor not Valid Sensor 5:Concentration % / PPM 0 - 6553.5 40070:0 40070:2 40070:3 40070:4 40070:5 40070:6 40070:7 40071:0 40071:1 40071:2 40071:3 40071:4 40071:5 40071:6 40071:7 40072:0 40072:1 40072:2 40074:0 Sensor 6: Sensor Disconnected (Trouble Bits) Sensor 6: Voltage Regulator Failure Sensor 6: Sensor Bad Sensor 6: Duplicate Sensor Sensor 6: Timer Failure Sensor 6: Sensor Bridge Failure (Combustibles) Sensor 6: Type Error Sensor 6: Enabled Sensor 6: Auto Calibration Enabled Sensor 6: Low Alarm Latch Sensor 6: Calibrated Sensor 6: Zone Option Enabled Sensor 6: Calibration Table Initialized Sensor 6: H2S Sensor Resistance too high Sensor 6: Operate Mode (as opposed to Warm Up Mode) Sensor 6: High Alarm Latch Sensor 6: Low Sensitivity Sensor 6: Sensor not Valid Sensor 6: Concentration % / PPM 0 - 6553.5 March 4, 2005 Units FIX EGU Page: 6 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40080:0 40080:2 40080:3 40080:4 40080:5 40080:6 40080:7 40081:0 40081:1 40081:2 40081:3 40081:4 40081:5 40081:6 40081:7 40082:0 40082:1 40082:2 40084:0 Sensor 7: Sensor Disconnected (Trouble Bits) Sensor 7: Voltage Regulator Failure Sensor 7: Sensor Bad Sensor 7: Duplicate Sensor Sensor 7: Timer Failure Sensor 7: Sensor Bridge Failure (Combustibles) Sensor 7: Type Error Sensor 7: Enabled Sensor 7: Auto Calibration Enabled Sensor 7: Low Alarm Latch Sensor 7: Calibrated Sensor 7: Zone Option Enabled Sensor 7: Calibration Table Initialized Sensor 7: H2S Sensor Resistance too high Sensor 7: Operate Mode (as opposed to Warm Up Mode) Sensor 7: High Alarm Latch Sensor 7: Low Sensitivity Sensor 7: Sensor not Valid Sensor 7: Concentration % / PPM 0 - 6553.5 40090:0 40090:2 40090:3 40090:4 40090:5 40090:6 40090:7 40091:0 40091:1 40091:2 40091:3 40091:4 40091:5 40091:6 40091:7 40092:0 40092:1 40092:2 40094:0 Sensor 8: Sensor Disconnected (Trouble Bits) Sensor 8: Voltage Regulator Failure Sensor 8: Sensor Bad Sensor 8: Duplicate Sensor Sensor 8: Timer Failure Sensor 8: Sensor Bridge Failure (Combustibles) Sensor 8: Type Error Sensor 8: Enabled Sensor 8: Auto Calibration Enabled Sensor 8: Low Alarm Latch Sensor 8: Calibrated Sensor 8: Zone Option Enabled Sensor 8: Calibration Table Initialized Sensor 8: H2S Sensor Resistance too high Sensor 8: Operate Mode (as opposed to Warm Up Mode) Sensor 8: High Alarm Latch Sensor 8: Low Sensitivity Sensor 8: Sensor not Valid Sensor 8: Concentration % / PPM 0 - 6553.5 March 4, 2005 Units FIX EGU Page: 7 Sentry MODBUS I/O Memory Map Analog Process Variables Modbus Address Parameter Units FIX EGU 40111 40112 40113 40114 40115 40116 40117 40118 Sensor 1 concentration Sensor 2 concentration Sensor 3 concentration Sensor 4 concentration Sensor 5 concentration Sensor 6 concentration Sensor 7 concentration Sensor 8 concentration % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 40119 40120 40121 40122 40123 40124 40125 40126 Sensor 1 Highest Concentration Sensor 2 Highest Concentration Sensor 3 Highest Concentration Sensor 4 Highest Concentration Sensor 5 Highest Concentration Sensor 6 Highest Concentration Sensor 7 Highest Concentration Sensor 8 Highest Concentration 40127 40128 40129 40130 40131 40132 40133 40134 Sensor 1 Lowest Concentration Sensor 2 Lowest Concentration Sensor 3 Lowest Concentration Sensor 4 Lowest Concentration Sensor 5 Lowest Concentration Sensor 6 Lowest Concentration Sensor 7 Lowest Concentration Sensor 8 Lowest Concentration 40135 40136 40137 40138 40139 40140 40141 40142 Sensor 1 Maximum Input value (Voltage) Sensor 2 Maximum Input value (Voltage) Sensor 3 Maximum Input value (Voltage) Sensor 4 Maximum Input value (Voltage) Sensor 5 Maximum Input value (Voltage) Sensor 6 Maximum Input value (Voltage) Sensor 7 Maximum Input value (Voltage) Sensor 8 Maximum Input value (Voltage) 40143 40144 40145 40146 40147 40148 40149 40150 Sensor 1 Minimum Input value (Voltage) Sensor 2 Minimum Input value (Voltage) Sensor 3 Minimum Input value (Voltage) Sensor 4 Minimum Input value (Voltage) Sensor 5 Minimum Input value (Voltage) Sensor 6 Minimum Input value (Voltage) Sensor 7 Minimum Input value (Voltage) Sensor 8 Minimum Input value (Voltage) 40151 40152 40153 40154 40155 Sensor 1 Power (H2S and COMB only ) Sensor 2 Power (H2S and COMB only ) Sensor 3 Power (H2S and COMB only ) Sensor 4 Power (H2S and COMB only ) Sensor 5 Power (H2S and COMB only ) March 4, 2005 Page: 8 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40156 40157 40158 Sensor 6 Power (H2S and COMB only ) Sensor 7 Power (H2S and COMB only ) Sensor 8 Power (H2S and COMB only ) 40159 40160 40161 40162 40163 40164 40165 40166 Sensor 1 Type Sensor 2 Type Sensor 3 Type Sensor 4 Type Sensor 5 Type Sensor 6 Type Sensor 7 Type Sensor 8 Type 40170 40171 40172 40173 System Historical Reset Time Month System Historical Reset Time Day System Historical Reset Time Hr System Historical Reset Time Min 40174 40175 40176 40177 System Power Up Time Month System Power Up Time Day System Power Up Time Hr System Power Up Time Min 40178 40179 40180 40181 System Power Down Time Month System Power Down Time Day System Power Down Time Hr System Power Down Time Min 40200 40201 40202 40203 Sensor 1 High Alarm Time Sensor 1 High Alarm Time Sensor 1 High Alarm Time Sensor 1 High Alarm Time Month Day Hr Min 40204 40205 40206 40207 Sensor 1 Low Alarm Time Sensor 1 Low Alarm Time Sensor 1 Low Alarm Time Sensor 1 Low Alarm Time Month Day Hr Min 40208 40209 40210 40211 Sensor 1 Calibration Time Month Sensor 1 Calibration Time Day Sensor 1 Calibration Time Hr Sensor 1 Calibration Time Min 40212 40213 40214 40215 Sensor 1 High Conc. Time Sensor 1 High Conc. Time Sensor 1 High Conc. Time Sensor 1 High Conc. Time Month Day Hr Min 40216 40217 40218 40219 Sensor 1 Low Conc. Time Sensor 1 Low Conc. Time Sensor 1 Low Conc. Time Sensor 1 Low Conc. Time Month Day Hr Min 40220 40221 40222 40223 Sensor 1 Trouble Time Sensor 1 Trouble Time Sensor 1 Trouble Time Sensor 1 Trouble Time March 4, 2005 Units FIX EGU (1,2,3 or 4) (1,2,3 or 4) (1,2,3 or 4) (1,2,3 or 4) (1,2,3 or 4) (1,2,3 or 4) (1,2,3 or 4) (1,2,3 or 4) Month Day Hr Min Page: 9 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40224 40225 40226 40227 40228 40229 40230 40231 Sensor 1 Input Value - Multiplex 0 Sensor 1 Input Value - Multiplex 1 Sensor 1 Input Value - Multiplex 2 Sensor 1 Input Value - Multiplex 3 Sensor 1 Input Value - Multiplex 4 Sensor 1 Input Value - Multiplex 5 Sensor 1 Input Value - Multiplex 6 Sensor 1 Input Value - Multiplex 7 40232 Sensor 1 Calibration Due Days 40233 40234 40235 40236 Sensor 2 High Alarm Time Sensor 2 High Alarm Time Sensor 2 High Alarm Time Sensor 2 High Alarm Time Month Day Hr Min 40237 40238 40239 40240 Sensor 2 Low Alarm Time Sensor 2 Low Alarm Time Sensor 2 Low Alarm Time Sensor 2 Low Alarm Time Month Day Hr Min 40241 40242 40243 40244 Sensor 2 Calibration Time Month Sensor 2 Calibration Time Day Sensor 2 Calibration Time Hr Sensor 2 Calibration Time Min 40245 40246 40247 40248 Sensor 2 High Conc. Time Sensor 2 High Conc. Time Sensor 2 High Conc. Time Sensor 2 High Conc. Time Month Day Hr Min 40249 40250 40251 40252 Sensor 2 Low Conc. Time Sensor 2 Low Conc. Time Sensor 2 Low Conc. Time Sensor 2 Low Conc. Time Month Day Hr Min 40253 40254 40255 40256 Sensor 2 Trouble Time Sensor 2 Trouble Time Sensor 2 Trouble Time Sensor 2 Trouble Time 40257 40258 40259 40260 40261 40262 40263 40264 Sensor 2 Input Value - Multiplex 0 Sensor 2 Input Value - Multiplex 1 Sensor 2 Input Value - Multiplex 2 Sensor 2 Input Value - Multiplex 3 Sensor 2 Input Value - Multiplex 4 Sensor 2 Input Value - Multiplex 5 Sensor 2 Input Value - Multiplex 6 Sensor 2 Input Value - Multiplex 7 40265 Sensor 2 Calibration Due Days March 4, 2005 Units FIX EGU 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Month Day Hr Min 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Page: 10 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40266 40267 40268 40269 Sensor 3 High Alarm Time Sensor 3 High Alarm Time Sensor 3 High Alarm Time Sensor 3 High Alarm Time Month Day Hr Min 40270 40271 40272 40273 Sensor 3 Low Alarm Time Sensor 3 Low Alarm Time Sensor 3 Low Alarm Time Sensor 3 Low Alarm Time Month Day Hr Min 40274 40275 40276 40277 Sensor 3 Calibration Time Month Sensor 3 Calibration Time Day Sensor 3 Calibration Time Hr Sensor 3 Calibration Time Min 40278 40279 40280 40281 Sensor 3 High Conc. Time Sensor 3 High Conc. Time Sensor 3 High Conc. Time Sensor 3 High Conc. Time Month Day Hr Min 40282 40283 40284 40285 Sensor 3 Low Conc. Time Sensor 3 Low Conc. Time Sensor 3 Low Conc. Time Sensor 3 Low Conc. Time Month Day Hr Min 40286 40287 40288 40289 Sensor 3 Trouble Time Sensor 3 Trouble Time Sensor 3 Trouble Time Sensor 3 Trouble Time 40290 40291 40292 40293 40294 40295 40296 40297 Sensor 3 Input Value - Multiplex 0 Sensor 3 Input Value - Multiplex 1 Sensor 3 Input Value - Multiplex 2 Sensor 3 Input Value - Multiplex 3 Sensor 3 Input Value - Multiplex 4 Sensor 3 Input Value - Multiplex 5 Sensor 3 Input Value - Multiplex 6 Sensor 3 Input Value - Multiplex 7 40298 Sensor 3 Calibration Due Days 40299 40300 40301 40302 Sensor 4 High Alarm Time Sensor 4 High Alarm Time Sensor 4 High Alarm Time Sensor 4 High Alarm Time Month Day Hr Min 40303 40304 40305 40306 Sensor 4 Low Alarm Time Sensor 4 Low Alarm Time Sensor 4 Low Alarm Time Sensor 4 Low Alarm Time Month Day Hr Min 40307 40308 40309 40310 Sensor 4 Calibration Time Month Sensor 4 Calibration Time Day Sensor 4 Calibration Time Hr Sensor 4 Calibration Time Min March 4, 2005 Units FIX EGU Month Day Hr Min 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Page: 11 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40311 40312 40313 40314 Sensor 4 High Conc. Time Sensor 4 High Conc. Time Sensor 4 High Conc. Time Sensor 4 High Conc. Time Month Day Hr Min 40315 40316 40317 40318 Sensor 4 Low Conc. Time Sensor 4 Low Conc. Time Sensor 4 Low Conc. Time Sensor 4 Low Conc. Time Month Day Hr Min 40319 40320 40321 40322 Sensor 4 Trouble Time Sensor 4 Trouble Time Sensor 4 Trouble Time Sensor 4 Trouble Time 40323 40324 40325 40326 40327 40328 40329 40330 Sensor 4 Input Value - Multiplex 0 Sensor 4 Input Value - Multiplex 1 Sensor 4 Input Value - Multiplex 2 Sensor 4 Input Value - Multiplex 3 Sensor 4 Input Value - Multiplex 4 Sensor 4 Input Value - Multiplex 5 Sensor 4 Input Value - Multiplex 6 Sensor 4 Input Value - Multiplex 7 40331 Sensor 4 Calibration Due Days 40332 40333 40334 40335 Sensor 5 High Alarm Time Sensor 5 High Alarm Time Sensor 5 High Alarm Time Sensor 5 High Alarm Time Month Day Hr Min 40336 40337 40338 40339 Sensor 5 Low Alarm Time Sensor 5 Low Alarm Time Sensor 5 Low Alarm Time Sensor 5 Low Alarm Time Month Day Hr Min 40340 40341 40342 40343 Sensor 5 Calibration Time Month Sensor 5 Calibration Time Day Sensor 5 Calibration Time Hr Sensor 5 Calibration Time Min 40344 40345 40346 40347 Sensor 5 High Conc. Time Sensor 5 High Conc. Time Sensor 5 High Conc. Time Sensor 5 High Conc. Time Month Day Hr Min 40348 40349 40350 40351 Sensor 5 Low Conc. Time Sensor 5 Low Conc. Time Sensor 5 Low Conc. Time Sensor 5 Low Conc. Time Month Day Hr Min 40352 40353 40354 40355 Sensor 5 Trouble Time Sensor 5 Trouble Time Sensor 5 Trouble Time Sensor 5 Trouble Time March 4, 2005 Units FIX EGU Month Day Hr Min 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Month Day Hr Min Page: 12 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40356 40357 40358 40359 40360 40361 40362 40363 Sensor 5 Input Value - Multiplex 0 Sensor 5 Input Value - Multiplex 1 Sensor 5 Input Value - Multiplex 2 Sensor 5 Input Value - Multiplex 3 Sensor 5 Input Value - Multiplex 4 Sensor 5 Input Value - Multiplex 5 Sensor 5 Input Value - Multiplex 6 Sensor 5 Input Value - Multiplex 7 40364 Sensor 5 Calibration Due Days 40365 40366 40367 40368 Sensor 6 High Alarm Time Sensor 6 High Alarm Time Sensor 6 High Alarm Time Sensor 6 High Alarm Time Month Day Hr Min 40369 40370 40371 40372 Sensor 6 Low Alarm Time Sensor 6 Low Alarm Time Sensor 6 Low Alarm Time Sensor 6 Low Alarm Time Month Day Hr Min 40373 40374 40375 40376 Sensor 6 Calibration Time Month Sensor 6 Calibration Time Day Sensor 6 Calibration Time Hr Sensor 6 Calibration Time Min 40377 40378 40379 40380 Sensor 6 High Conc. Time Sensor 6 High Conc. Time Sensor 6 High Conc. Time Sensor 6 High Conc. Time Month Day Hr Min 40381 40382 40383 40384 Sensor 6 Low Conc. Time Sensor 6 Low Conc. Time Sensor 6 Low Conc. Time Sensor 6 Low Conc. Time Month Day Hr Min 40385 40386 40387 40388 Sensor 6 Trouble Time Sensor 6 Trouble Time Sensor 6 Trouble Time Sensor 6 Trouble Time 40389 40390 40391 40392 40393 40394 40395 40396 Sensor 6 Input Value - Multiplex 0 Sensor 6 Input Value - Multiplex 1 Sensor 6 Input Value - Multiplex 2 Sensor 6 Input Value - Multiplex 3 Sensor 6 Input Value - Multiplex 4 Sensor 6 Input Value - Multiplex 5 Sensor 6 Input Value - Multiplex 6 Sensor 6 Input Value - Multiplex 7 40397 Sensor 6 Calibration Due Days March 4, 2005 Units FIX EGU 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Month Day Hr Min 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Page: 13 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40398 40399 40400 40401 Sensor 7 High Alarm Time Sensor 7 High Alarm Time Sensor 7 High Alarm Time Sensor 7 High Alarm Time Month Day Hr Min 40402 40403 40404 40405 Sensor 7 Low Alarm Time Sensor 7 Low Alarm Time Sensor 7 Low Alarm Time Sensor 7 Low Alarm Time Month Day Hr Min 40406 40407 40408 40409 Sensor 7 Calibration Time Month Sensor 7 Calibration Time Day Sensor 7 Calibration Time Hr Sensor 7 Calibration Time Min 40410 40411 40412 40413 Sensor 7 High Conc. Time Sensor 7 High Conc. Time Sensor 7 High Conc. Time Sensor 7 High Conc. Time Month Day Hr Min 40414 40415 40416 40417 Sensor 7 Low Conc. Time Sensor 7 Low Conc. Time Sensor 7 Low Conc. Time Sensor 7 Low Conc. Time Month Day Hr Min 40418 40419 40420 40421 Sensor 7 Trouble Time Sensor 7 Trouble Time Sensor 7 Trouble Time Sensor 7 Trouble Time 40422 40423 40424 40425 40426 40427 40428 40429 Sensor 7 Input Value - Multiplex 0 Sensor 7 Input Value - Multiplex 1 Sensor 7 Input Value - Multiplex 2 Sensor 7 Input Value - Multiplex 3 Sensor 7 Input Value - Multiplex 4 Sensor 7 Input Value - Multiplex 5 Sensor 7 Input Value - Multiplex 6 Sensor 7 Input Value - Multiplex 7 40430 Sensor 7 Calibration Due Days 40431 40432 40433 40434 Sensor 8 High Alarm Time Sensor 8 High Alarm Time Sensor 8 High Alarm Time Sensor 8 High Alarm Time Month Day Hr Min 40435 40436 40437 40438 Sensor 8 Low Alarm Time Sensor 8 Low Alarm Time Sensor 8 Low Alarm Time Sensor 8 Low Alarm Time Month Day Hr Min 40439 40440 40441 40442 Sensor 8 Calibration Time Month Sensor 8 Calibration Time Day Sensor 8 Calibration Time Hr Sensor 8 Calibration Time Min March 4, 2005 Units FIX EGU Month Day Hr Min 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Page: 14 Sentry MODBUS I/O Memory Map Modbus Address Parameter 40443 40444 40445 40446 Sensor 8 High Conc. Time Sensor 8 High Conc. Time Sensor 8 High Conc. Time Sensor 8 High Conc. Time Month Day Hr Min 40447 40448 40449 40450 Sensor 8Low Conc. Time Sensor 8 Low Conc. Time Sensor 8 Low Conc. Time Sensor 8 Low Conc. Time Month Day Hr Min 40451 40452 40453 40454 Sensor 8 Trouble Time Sensor 8 Trouble Time Sensor 8 Trouble Time Sensor 8 Trouble Time 40455 40456 40457 40458 40459 40460 40461 40462 Sensor 8 Input Value - Multiplex 0 Sensor 8 Input Value - Multiplex 1 Sensor 8 Input Value - Multiplex 2 Sensor 8 Input Value - Multiplex 3 Sensor 8 Input Value - Multiplex 4 Sensor 8 Input Value - Multiplex 5 Sensor 8 Input Value - Multiplex 6 Sensor 8 Input Value - Multiplex 7 40463 Sensor 8 Calibration Due Days 40466 40467 40468 40469 40470 40471 40472 40473 Contrived alarm - Sensor 1 - 0 = no alarm, 1 = Low alarm, 2 = High alarm Contrived alarm - Sensor 2 - 0 = no alarm, 1 = Low alarm, 2 = High alarm Contrived alarm - Sensor 3 - 0 = no alarm, 1 = Low alarm, 2 = High alarm Contrived alarm - Sensor 4 - 0 = no alarm, 1 = Low alarm, 2 = High alarm Contrived alarm - Sensor 5 - 0 = no alarm, 1 = Low alarm, 2 = High alarm Contrived alarm - Sensor 6 - 0 = no alarm, 1 = Low alarm, 2 = High alarm Contrived alarm - Sensor 7 - 0 = no alarm, 1 = Low alarm, 2 = High alarm Contrived alarm - Sensor 8 - 0 = no alarm, 1 = Low alarm, 2 = High alarm March 4, 2005 Units FIX EGU Month Day Hr Min 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 0 - 6553.5 Page: 15 Sentry MODBUS I/O Memory Map Read/Write Parameters High Alarm Limits Modbus Address Parameter Units FIX EGU 40501 40502 40503 40504 40505 40506 40507 40508 Sensor 1 Sensor 2 Sensor 3 Sensor 4 Sensor 5 Sensor 6 Sensor 7 Sensor 8 % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 Sensor 1 Sensor 2 Sensor 3 Sensor 4 Sensor 5 Sensor 6 Sensor 7 Sensor 8 % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM % / PPM 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 0 - 65535 Low Alarm Limits 40511 40512 40513 40514 40515 40516 40517 40518 H2S/CH4/Oxy/CO 40520 40521 40522 40523 40524 40525 40526 40527 40528 Sensor 1 Calib. 40530 40521 40532 40533 40534 40535 40536 40537 40538 Sensor 2 Calib. 40540 40541 40542 40543 40544 40545 40546 40547 40548 Sensor 3 Calib. March 4, 2005 Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - - - - ccn vmax - ccn vmin vmax - ccn vmax - ccn vmin vmax - ccn vmax - ccn vmin vmax - Page: 16 Sentry MODBUS I/O Memory Map 40550 40551 40552 40553 40554 40555 40556 40557 40558 Sensor 4 Calib. 40560 40561 40562 40563 40564 40565 40566 40567 40568 Sensor 5 Calib. 40570 40571 40572 40573 40574 40575 40576 40577 40578 Sensor 6 Calib. 40580 40581 40582 40583 40584 40585 40586 40587 40588 Sensor 7 Calib. 40590 40591 40592 40593 40594 40595 40596 40597 40598 Sensor 8 Calib. March 4, 2005 Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - Coeff. 1 2 3 4 5 6 7 8 9 k1 k2 k3 n1 n2 n3 bp12 bp23 ccn ccn vmin vmax gasfac - - - - - - ccn vmax - ccn vmin vmax - ccn vmax - ccn vmin vmax - ccn vmax - ccn vmin vmax - ccn vmax - ccn vmin vmax - ccn vmax - ccn vmin vmax - Page: 17 Sentry MODBUS I/O Memory Map Control Bits Modbus Address Parameter 40601 40602 40603 System Reset Alarm Reset History Reset 40610 40611 40612 40613 System Time Month System Time Day System Time Hr System Time Min 40614 40615 40616 40617 40618 40619 40620 40621 Latch High Alarms - Sensor 1 Latch High Alarms - Sensor 2 Latch High Alarms - Sensor 3 Latch High Alarms - Sensor 4 Latch High Alarms - Sensor 5 Latch High Alarms - Sensor 6 Latch High Alarms - Sensor 7 Latch High Alarms - Sensor 8 40622 40623 40624 40625 40626 40627 40628 40629 Latch Low Alarms - Sensor 1 Latch Low Alarms - Sensor 2 Latch Low Alarms - Sensor 3 Latch Low Alarms - Sensor 4 Latch Low Alarms - Sensor 5 Latch Low Alarms - Sensor 6 Latch Low Alarms - Sensor 7 Latch Low Alarms - Sensor 8 40631 40632 40633 Calibration Concentration Comb (Type 2) Calibration Concentration Oxy (Type 3) Calibration Concentration Toxic (Type 4) March 4, 2005 Units FIX EGU Page: 18