Download Panasonic CU-4KE31NBU Data Sheet

Transcript
Split System Submittal Data
Outdoor: CU-4KE31NBU
MultiSystem - Outdoor
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit#:
Drawing#:
General Data
Power (V/P/Hz)
Circuit Ampacity (A)
Fuse Size, Max.(A)
208/230/1/60
17
20
Compressor
No. Used
R.L. Amps - L.R. (A)
Crankcase Heater (W)
DC Twin Rotary
1
12.3/10.3 - 17
30
Outdoor Unit
Fan Type
Dia & Length (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles (RPM)
No. Motors (W)
CFM (High)
F.L. Amps (A)
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area (sq.ft.)
Tube Size (in)
Propeller
D18-1/8 - 1
DC Motor
8 - (800)
1-(90)
1942
0.55
Aluminum Fin & Copper Pipe
Corrugated Plate - Inner Riffeled
2 - 18.1
7.75
3/8”
Refrigerant
Lbs. - R410a
Control
Line Size (in. O.D. Discharge)
Line Size (in. O.D. Suction)
R410A
8.38
Electronic Expansion Valve
1/4” x 4 (Flare)
3/8” x 2 + 1/2” x 2 (Flare)
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity (BTU/H)
Sensible Capacity (BTU/H)
Latent Capacity (BTU/H)
SEER
Amps (A)
Max. Amps (A)
Power Inputs (W)
Max. Inputs (W)
Outdoor Sound Rating (dB-A) High
30,600 (9,800 - 30,600)
25,800
4,800
17.2
12.3
17
2,800
4,000
53
32,000 (11,600 - 32,000)
9.3
10.3
17
2,350
4,000
55
Dimensions (HxWxD)
Indoor Unit (Crated) (in.)
Indoor Unit (Uncrated) (in.)
40 1/8 x 41 11/32 x 16 21/32
35-1/32 x 35-7/16 x 12-19/32
Weight (lbs.)
Net
Shipping
180.8
189.6
Heating
Total Capacity (BTU/H)
HSPF
Amps (A)
Max. Amps (A)
Power Inputs (W)
Max Inputs (W)
Outdoor Sound Rating (dB-A) High
Shipping Volume (cu.ft.)
15.88
Operating Range
Indoor Air Intake Temp
Outdoor Air Intake Temp
Cooling (Max)
Cooling (Min)
Cooling (Max)
Cooling (Min)
95F DB/71F WB
67 DB/57F WB
80F DB/67F WB
115 F DB
14 F DB
75F DB/65F WB
0F DB
3. DIMENSIONAL DATA
Outdoor Unit CU-3KS19NBU
Outdoor Dimensions
15/32
13-19/32
12-19/32(320)
35-7/16(900)
14-17/32
2-I
D
23
/32
ID:
1-3/8
11-17/32
5-11/32
:15
/16
23-15/16
2-15/16
Wide tube service valve
dia.3/8" (9.52) × 3
1-13/16
4-7/16 2-15/16 2-3/4
5-29/32 2-27/32 2-3/4
23/32
29-1/8(740)
Narrow tube service valve
dia.1/4" (6.35) × 3
2-1/32
4-1/2
2-1/16
Unit: inch(mm)
(852-0-0010-11500-0)
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144
http://www.panasonic.com/aircon
21