Troubleshooting
Table 5
Battery run times
Internal Battery
(minutes)
Internal Battery
+ 1 External Battery
Cabinet (minutes)
Internal Battery
+ 2 External Battery
Cabinets (minutes)
Internal Battery
+ 3 External Battery
Cabinets (minutes)
Internal Battery
+ 4 External Battery
Cabinets (minutes)
Load%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
6000VA
94
46
29
21
17
13
11
9
8
7
222
124
81
60
49
39
33
28
24
21
350
197
135
105
85
70
58
50
43
38
478
269
185
145
123
101
85
73
63
55
606
341
235
184
156
131
113
97
85
75
Using the configuration program, the user may specify the number of GXT2-240VBATTUL external
battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 5 above shows the estimated run times at different loads.
34