Download Kidde Fire Systems FM-200 User's Manual

Transcript
FM-200® Component Description
A UTC Fire & Security Company
Pressure Operated Switch
Effective: September 2010
K-90-5180
FEATURES
•
For Use with UL Listed, ULC Listed and
FM Approved Systems
P/N:
•
See Kidde® Manual 90-FM200M-021 for
USCG Approval
81-486536-000
OPERATED
OPERATED
SET
SET
STEM SHOWN IN SET POSITIONPULL UP ON STEM TO MANUALLY
OPERATE SWITCH
0.375"
WIRING
SCREW
TERMINALS
4.00"
PRESSURE OPERATED SWITCH
3P.D.T.
8 COVER SCREWS
TO RESET
PUSH STEM TO SET POSITION
U
15 AMP.— 125 V.AC L 10 AMP.—250 V.AC
3/4HP—250 VAC
PT. NO. 486536
FM
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
TO RESET
PUSH STEM TO SET POSITION
15 AMP 125 VAC
10 AMP 250 VAC
3/4 HP 1-2-3 PH 125-480 VAC
4.00"
FRONT VIEW
COVER REMOVED
1/2” SUPPLY PIPE WITH UNION
FRONT VIEW
OPERATED
SET
NC
BOX 3 EACH SIDE
1/2” CONDUIT
KNOCKOUTS
SWITCH 3PDT
NC
C
C
NC
C
COVER
NO
GASKET
½” NPT FEMALE,
CONNECT TO SYSTEM
PIPING
SIDE SECTION
NOTES:
• The switch may be mounted in any position; however, the preferred installation is upright, as shown.
• Any load connection to the switch must not exceed
the switch rating, and shall utilize a suitable protection device (i.e., circuit breaker, fuse).
•
NO
NO
PRESSURE INLET
WIRING DIAGRAM
Contact Ratings (3 PDT):
– 15 Amp @125 Vac
– 10 Amp @ 250 Vac
– 3/4 HP @ 250 Vac
– 1, 2 or 3 Phase
FM-200 is a registered trademark of the Great Lakes Chemical Corporation.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes
no responsibility for the product’s suitability for a particular application. The product must be
properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-90-5180 Rev AC
© 2010 Kidde-Fenwal Inc.
Printed in USA
Kidde Fire Systems
A UTC Fire & Security Company
400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com