Hardwiring the UPS Input WARNING: Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. The Dell Online Rack hardwired models require a dedicated branch circuit that meets the following requirements: S Protection device requires a two-pole disconnection device between the UPS input and the mains S Breaker must be wall-mounted and be readily accessible to the operator S For Europe. Breaker must meet the IEC/EN 60934 standard and at least 3 mm contact air gap S 200–240 Vac S Single-phase S 50/60 Hz S Flexible metal conduit (recommended for ease of service and maintenance) Wall 2-pole Breaker Line AC Mains UPS Neutral/L2 18 | Installation and Startup