PUMP CONTROL CONNECTIONS The water heater can be used to control a recirculation pump. Proper pump control helps to preserve the life of the system and saves energy as well. The water heater pump control port is a “normally-open dry contact”, and therefore needs additional components to properly control a recirculation pump. To control a recirculation pump, connect the pump to the “Pump connector” in the water heater as shown in the diagram below. (In a multi-unit system, connect the pump ONLY to the “PARENT” unit.) The pump is to be connected using suitable relays shown in the diagram below. Please make sure the relays are properly rated for the recirculation pump. Using the water heater’s internal thermistors as a temperature control, the recirculation pump will only turn on when recirculation is needed. CAUTION: In a multi-unit system, the pump must be connected to the “Pump” connector in the “PARENT” unit only. If the pump is connected to any of the “CHILD” units, the pump will not work. These components are NOT included with water heater and are external to the unit. They must be acquired separately. Connect to this “Pump connector”. Power supply for relay Power supply for pump 120 VAC 220 VAC etc 120 VAC 220 VAC etc for relay Thermal relay Recirculation pump - 21 -