Download Black Box SYH6K6RMT-P1

Transcript
© 2005. All rights reserved.
Black Box Corporation.
Black Box Corporation • 1000 Park Drive • Lawrence, PA 15055-1018 • Tech Support: 724-746-5500 • www.blackbox.com • e-mail: [email protected]
SYMMETRA RM
Bringing all the time-tested advantages
of Symmetra to your rack.
Key Features
The first rackmount
enterprise-level
power protector with
redundancy!
Flexible range of
capacity and runtimes.
Integrated Web/SNMP
management features.
Easy-to-manage, menubased diagnostics.
Occupies 8 or 10U of
rack space.
Built-in automatic and
manual bypass feature.
NEMA L6-30 plug
makes installation
easy in 208-VAC
environments.
ith more servers, storage
products, and other missioncritical networking equipment
becoming rack-based, there’s a
growing need for innovative rackmounted power protectors. The
Symmetra RM provides 2-, 4-, or
6-kVA power increments that
provide N+1 redundancy in just 8
or 10U of rack space.
Like the Symmetra, the
Symmetra RM lets multiple power
modules share the power array’s
connected load. All modules run
in parallel and share the load
evenly. If a module fails or is
removed, there’s nothing to worry
about: The Symmetra has one
more module than is necessary
for full-load operation. So you’re
still functioning at full power.
This load-sharing is what’s
known as N+1 redundancy. It
ensures maximum uptime and
continuous availability. The
W
Symmetra RM is the first
rackmount enterprise-level power
protector to offer redundancy.
And you won’t experience any
downtime when you upgrade your
Symmetra RM: hot-swappable
components keep your network
up and running.
To set up your Symmetra
system, choose the Symmetra
model that you need based on
your current VA load and future
expansion needs. All Symmetra
RM units are available with 208VAC output. Three units also
feature a stepdown transformer
that converts 208-VAC output into
120-VAC output. This conversion
enables you to power the data
center or rack enclosure from a
single high-powered circuit while
providing UPS-protected 120 VAC
to each piece of equipment. Add
an additional power module for
N+1 redundancy. Choose
additional battery modules for
longer run times if needed; these
hot-swappable modules fit into
any vacant slot in the Symmetra
RM.
To expand your power
capacity, add more power
modules in increments of 2 kVA,
up to a maximum of 6 kVA per
Symmetra RM unit.
If there’s an extended power
outage, included PowerChute
Network Shutdown software
helps you save data and shut
down multiple servers over the
network. In addition, units with up
to 6 kVA are optimized for eight
minutes, allowing you to perform
orderly shutdowns.
And with Symmetra’s menubased remote display, power and
UPS information is always
available at the touch of a button.
You can monitor parameters such
(continued on page 2)
1
11/30/2000
#25041
Specifications
Input
Conformance
Nominal Voltage: 208 or 240 VAC
Approvals: FCC, CSA, UL 1778
Output
Frequency: 50/60 Hz ±5 Hz
(autosensing); SYH2K6RMT-P1:
60 Hz ±3 Hz
Environmental
Capacity:
SYH2K6RMT: 2 kVA/1.4 kW;
SYH4K6RMT: 4 kVA/2.8 kW;
SYH6K6RMT: 6 kVA/4.2 kW;
SYH2K6RMT-P1: 2 kVA/1.4 kW;
SYH4K6RMT-P1: 4 kVA/2.8 kW;
SYH6K6RMT-P1: 6 kVA/4.2 kW
Voltage: SYH2K6RMT, SYH4K6RMT,
SYH6K6RMT: 208 VAC (240-VAC
configurable); SYH2K6RMT-P1,
SYH4K6RMT-P1, SYH6K6RMTP1: 208 VAC↔120 VAC (240-VAC
configurable)
Max. Configurable Power with
Additional Power Modules:
SYH2K6RMT, SYH4K6RMT,
SYH6K6RMT: 6 kVA/4.2 kW;
SYH2K6RMT-P1, SYH4K6RMTP1, SYH6K6RMT-P1: 6 kVA/
4.2 kW (max. 5 kVA of 120 VAC)
Connections (Always check with
local electrical requirement and
regulations): SYH2K6RMT,
SYH4K6RMT, SYH6K6RMT:
(2) NEMA L6-20R, (1) NEMA L630R; SYH2K6RMT-P1,
SYH4K6RMT-P1, SYH6K6RMTP1: (2) NEMA L6-20R, (12) NEMA
5-15R
Efficiency at Full Load:
SYH2K6RMT, SYH4K6RMT,
SYH6K6RMT: 91%; SYH2K6RMTP1, SYH4K6RMT-P1,
SYH6K6RMT-P1: 86%
Bypass: Internal bypass (automatic
and manual)
Voltage Distortion: <5% at full load
Frequency (Sync): 57–63 Hz
Frequency (Not Sync): 60 Hz
Connection (Always check with
local electrical requirements and
regulations): (1) NEMA L6-30P
Voltage Range: 155–276 V
Power Factor: 0.98
Cord Length: 6 feet (1.8 m)
Batteries
Battery Type: Maintenance-free,
sealed lead-acid battery with
suspended electrolyte; leakproof
Typical Recharge Time (Recharge
time to 90 after full discharge):
4 hours
Replacement Battery Module:
SYH2K6RMT, SYH2K6RMT-P1:
(1) SYBT2; SYH4K6RMT,
SYH4K6RMT-P1: (2) SYBT2;
SYH6K6RMT, SYH6K6RMT-P1:
(3) SYBT2
Physical
®
Operating Temperature: 32 to 104°F
(0 to 40°C)
Operating Relative Humidity: Up to
95%
Operating Elevation: Up to
10,000 feet (3048 m)
Storage Temperature: 5 to 113°F
(-15 to +45°C)
Storage Relative Humidity: Up to
95%
Storage Elevation: Up to 50,000 feet
(15,240 m)
Audible Noise at 3 ft. (0.9 m):
60 dBA
On-Line Thermal Dissipation:
SYH2K6RMT: 430 BTU/hr.;
SYH4K6RMT: 860 BTU/hr.;
SYH6K6RMT: 1290 BTU/hr.;
SYH2K6RMT-P1: 590 BTU/hr.;
SYH4K6RMT-P1: 1542 BTU/hr.;
SYH6K6RMT-P1: 2143 BTU/hr.
Size: SYH2K6RMT, SYH4K6RMT,
SYH6K6RMT: 14"H (8U) x 19"W x
28.75"D (35.6 x 48.3 x 73 cm);
SYH2K6RMT-P1, SYH4K6RMTP1, SYH6K6RMT-P1: 17.5"H
(10U) x 19"W x 28.75"D (44.5 x
48.3 x 73 cm)
Weight: SYH2K6RMT: 164 lb.
(74.4 kg); SYH4K6RMT: 229 lb.
(103.9 kg); SYH6K6RMT: 294 lb.
(133.4 kg); SYH2K6RMT-P1:
259 (117.5 kg); SYH4K6RMT-P1:
324 lb. (147 kg); SYH6K6RMT-P1:
389 (176.5 kg)
Shipping Weight: SYH2K6RMT:
185 lb. (83.9 kg); SYH4K6RMT:
256 lb. (116.1 kg); SYH6K6RMT:
327 lb. (148.3 kg); SYH2K6RMTP1: 295 lb. (133.8 kg);
SYH4K6RMT-P1: 366 lb. (166 kg);
SYH6K6RMT-P1: 437 lb. (198.2 kg)
Communications/
Management
Interface Port: (1) DB9 RS-232,
(1) RJ-45 10BASE-T Ethernet for
Web, (2) SmartSlot™
Control Panel: Multi-function LCD
status and control console
Management Software:
PowerChute Network
Shutdown, Web/SNMP
Management Card included with
each unit
®
Audible Alarm: Distinctive lowbattery alarm
Emergency Power Off (EPO): Yes
Crest Factor: Up to 5:1
What the package includes
•
•
•
•
•
2
(1) Symmetra RM
Rackmounting brackets
Rackmounting support rails
CD with software
Users’ manual
(continued from page 1)
as input voltage, temperature,
level of redundancy, and humidity.
The power-factor correction
feature also eliminates power-line
harmonics and neutral overloads
that can cause building wiring to
overheat. Symmetra RM also
performs self-diagnosis. In the
event of an internal failure, the
unit sends you an alert via
network, SNMP, or Web-based
commands. Because of
Symmetra RM’s redundancy, the
system remains up, running, and
protected during repairs.
3000
1950
—
12 min.
25 min.
—
13 min.
26 min.
2500
1625
—
17 min.
34 min.
—
18 min.
34 min.
2200
1430
—
22 min.
40 min.
—
22 min.
41 min.
1600
1040
11 min.
35 min.
59 min.
11 min.
36 min.
1 hr.
900
585
29 min.
1 hr., 10 min.
1 hr., 46 min.
30 min.
1 hr., 13 min.
1 hr., 50 min.
VA
Watts
SYH2K6RMT-P1
SYH4K6RMT-P1
SYH6K6RMT-P1
SYH2K6RMT
SYH4K6RMT
SYH6K6RMT
1000
650
24 min.
1 hr., 2 min.
1 hr., 36 min.
25 min.
1 hr., 5 min.
1 hr., 39 min.
1200
780
18 min.
51 min.
1 hr., 21 min.
19 min.
52 min.
1 hr., 23 min.
1400
910
14 min.
42 min.
1 hr., 9 min.
14 min.
43 min.
1 hr., 10 min.
2000
1300
7 min.
25 min.
45 min.
7 min.
26 min.
46 min.
34 min.
1 hr., 19 min.
1 hr., 57 min.
35 min.
1 hr., 22 min.
2 hr., 2 min.
40 min.
1 hr., 29 min.
2 hr., 11 min.
42 min.
1 hr., 34 min.
2 hr., 16 min.
48 min.
1 hr., 43 min.
2 hr., 27 min.
51 min.
1 hr., 48 min.
2 hr., 34 min.
59 min.
2 hr.
2 hr., 46 min.
1 hr., 3 min.
2 hr., 7 min.
2 hr., 55 min.
1 hr., 13 min.
2 hr., 21 min.
3 hr., 11 min.
1 hr., 20 min.
2 hr., 31 min.
3 hr., 23 min.
1 hr., 35 min.
2 hr., 50 min.
3 hr., 43 min.
1 hr., 45 min.
3 hr., 5 min.
3 hr., 59 min.
3 hr., 49 min.
5 hr., 18 min
6 hr., 5 min.
4 hr., 45 min.
6 hr., 8 min.
6 hr., 47 min.
SYH2K6RMT-P1
SYH4K6RMT-P1
SYH6K6RMT-P1
SYH2K6RMT
SYH4K6RMT
SYH6K6RMT
3 hr., 3 min.
4 hr., 34 min.
5 hr., 25 min.
3 hr., 38 min.
5 hr., 10 min.
5 hr., 58 min.
2 hr., 7 min.
3 hr., 31 min.
4 hr., 26 min.
2 hr., 24 min.
3 hr., 53 min.
4 hr., 48 min.
400
260
50
33
VA
Watts
100
65
200
130
300
195
500
325
600
390
700
455
800
520
Runtime by Load for Symmetra RM
3
Why Buy From Black Box? Exceptional
Value. Exceptional Tech Support. Period.
Recognize any of these
situations?
• You wait more than 30
minutes to get through to a
vendor’s tech support.
• The so-called “tech” can’t
help you or gives you the
wrong answer.
• You don’t have a purchase
order number and the tech
refuses to help you.
• It’s 9 p. m. and you need help,
but your vendor’s tech
support line is closed.
According to a survey by Data
Communications magazine, 90%
of network managers surveyed
say that getting the technical
support they need is extremely
important when choosing a
vendor. But even though network
managers pay anywhere from 10
to 20% of their overall purchase
price for a basic service and
support contract, the technical
support and service they receive
falls far short of their
expectations—and certainly isn’t
worth what they paid.
At Black Box, we guarantee
the best value and the best
support. You can even consult our
Technical Support Experts before
you buy if you need help selecting
just the right component for your
application.
Don’t waste time and
money—call Black Box today.
Ordering Information
ITEM
CODE
Symmetra RM
208-VAC Output
2 kVA (Expandable to 6 kVA) ...................SYH2K6RMT
4 kVA (Expandable to 6 kVA) ...................SYH4K6RMT
6 kVA .............................................................SYH6K6RMT
208-VAC Output with 120-Volt Transformer
2 kVA (Expandable to 6 kVA) .............SYH2K6RMT-P1
4 kVA (Expandable to 6 kVA) .............SYH4K6RMT-P1
6 kVA .......................................................SYH6K6RMT-P1
Add optional Power Modules for N+1 redundancy…
2-kVA Power Module ........................................SYPM2KU
Choose single Battery Modules for longer run times (if
needed)…
Battery Module..........................................................SYBT2