Download TL260 / TL265

Transcript
Figure 1 Communicator Mounting Bracket
TL260 Mounting Bracket
Mounting Holes
Insert plastic standoffs
from back of bracket.
DG009386
2. To install the TL260 module into the panel, do the following. (see Figure 2).
a. Attach one end of the supplied PC-LINK cable to the panel PC-LINK header
on the panel (red wire goes on left (Pin 1) of the panel PC-LINK header).
NOTE: On the panel, the red wire is on the left,whereas on the TL260 the red
wire is on the right.
b. Insert the assembled Communicator into the panel cabinet.
c. Locate the screw hole in the right side wall of the panel. (See Figure 2 ). Line
up the assembled Communicator with the side wall of the panel and, using
the screw provided, secure the assembled module to the panel.
3. To electrically wire the Communicator to the panel, do the following:
(See Figure 3).
WARNING: ALL CONNECTIONS TO THE TL260 MODULE ARE POWER LIMITED. DO NOT ROUTE
ANY WIRING OVER THE CIRCUIT BOARDS. MAINTAIN AT LEAST 25.4 MM (1”) SEPARATION
BETWEEN CIRCUIT BOARD AND WIRING. A MINIMUM OF 7 MM (¼”) SEPARATION MUST BE MAINTAINED AT ALL POINTS BETWEEN NON-POWER LIMITED AND POWER LIMITED WIRING.
a. Attach a wire from the Communicator’s left PWR terminal to the panel’s
BELL+ terminal.
DG009387
NOTE: For ULC Commercial Fire Monitoring applications, do NOT connect any other devices to the Bell+ terminal.
b. Attach a wire from the Communicator’s GND terminal to the panel’s AUX - terminal.
c. Attach a wire from the Communicator’s SHLD terminal to the panel’s EGND terminal. (Protective earth ground).
d. If a Bell/Siren is used, attach a wire from the Communicator’s right PWR terminal to the positive (+) terminal on the Bell/Siren.
(See Figure 3).
e. If a Bell/Siren is used, attach the panel’s BELL - terminal to the negative (-) terminal on the Bell/Siren.
NOTE: If a Bell/Siren is not used, install the 1KΩ ½ W 5% resistor (Brown, Black,
Figure 2 Control Panel Cabinet
Red, Gold) (supplied with the panel) between the panel’s Bell + and Bell - terminals, then only wire the BELL + to the right PWR terminal on the Communicator.
PC-LINK Connector
f. Insert the PC-LINK connector into the Communicator’s PC-LINK socket. (Red wire
on Pin 4 on the Communicator).
g. Route the CAT 5 Ethernet cable through back of the cabinet and plug it into the Communicator’s RJ45 jack.
NOTE: Before leaving the site the Ethernet communication lines must first be connected to an approved (acceptable to local authorities) type NIDs, (UL installations, UL 60950 listed NIDs, for ULC installations CAN/CSA C22.2. No. 60950-1
Certified NIDs).
4. Perform the following for initial power on of the panel with Communicator installed:
a. Reconnect the AC power and battery + connector to the panel. (the Communicator
and Panel will power up together).
b. Observe that the Communicator’s red and yellow LEDs are flashing together while it
Screw
initializes. The red and yellow LEDs will continue to flash until the unit has successfully communicated to all programmed receivers.
c. Observe that the yellow Ethernet Network Link LED on the Communicator is ON.
(See Figure 3).
d. At the keypad, enter [*][8][Installer Code][382] and confirm that Toggle Option [5]
is ON (Ethernet Module Enabled). If this option is OFF, the yellow trouble LED indicates ‘Panel Supervision Trouble’ (2 flashes) and
the unit can not be programmed via PC-LINK cable.
NOTE: Initialization may take several minutes. Do not leave the installation until the red and yellow LEDs have stopped flashing.
PC1616/1832/1864 Programming
1. Perform the following panel programming steps to ensure that the Communicator and the panel work together as intended.
These Sections must be programmed at the panel keypad. Enter [*][8][Installer Code][Section Number]. Record any values that
are modified from their default, in the appropriate Worksheets for the Panel or Communicator.
NOTE: A toggle is ON when the number is displayed. A toggle is OFF when the number is not displayed. (e.g., [1---5---], Toggle
Options 1 and 5 are ON, all others are OFF). Press the number on the keypad to turn toggle ON/OFF.
2. In Section [167] program 060 (seconds).
3. In Sections [301], [302], and [303] Program the central station telephone number that will be used for the Ethernet Communicator. Valid
entries are:
a. Any valid telephone number. Signals will be routed to the central station using the Public Switched Telephone Network (PSTN).
b. DCAA (Receiver 0); signals will be routed to Ethernet Receivers 1 and 2 depending on programming in Section [851][006].
c. Section [301] sets the Primary communication path, and may be configured as either PSTN or Communicator routing. Panel Section
[302] is redundant, and Section [303] is the backup telephone number for Section [301].
NOTE: The leading digit D (dial tone detection) in the telephone number is pre-programmed.
4. In Section [350] program the communication format as Contact ID (03) or SIA FSK (04). Program the same value in Section [851][022].
NOTE: If any of the panel telephone numbers have been set to DCAA, Section [350] must be set to [04].
5. In Sections [351] - [376], program the Communicator call direction options. Refer to the Panel Installation Manual for these options.
6. In Section [401] set Toggle Option [1] Downloading Answer Enable to ON to perform panel DLS session through Ethernet.
NOTE: Before leaving the premises, the installer should verify all programmed communications paths are working. Use
[*][8][Installer Code][851][901] Toggle Options [1] and [2] to send diagnostic test transmission to both Ethernet Receivers.
3