Installation examples B-C-E: Boiler control via 0-10VDC + cascade via plate heat exchanger B-C-E: Boiler control via 0-10VDC + cascade via plate heat exchanger Description R40 with plate heat exchanger Cascade control Tips Complete accessory kits with plate heat exchanger are available for ∆T=10-20K (see chapter "Accessories"). The primary circuit should be designed for ∆T=20K, this guarantees a high boiler efficiency. When the secondary circuit is designed for a ∆T smaller than 20K, the flow temperature of the plate heat exchanger will be lower than the flow temperature of the boiler. This should be taken in to consideration during the design stage. The plate heat exchanger should be positioned close to the boiler, to avoid a negative influence on the temperature control quality. In case of a boiler room installed on the roof, the boiler may never be hydraulically connected at the highest point of the installation. 51