Download Husqvarna GTH2254XP Lawn Mower User Manual
Transcript
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRV1426EH SAP-CMRV1926EH SAP-CMRV1936EH SAP-CMRV2446EH SAP-CMRV3146EH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity Product Code No. SAP-CMRV1926EH-F 1 852 355 44 SAP-CMRV1426EH-F 5.6kW SAP-CMRV1936EH-F 5.6kW 6.8kW 8.0kW SAP-CMRV1426EH Outdoor Model No. 4.0kW SAP-CMRV2446EH-F SAP-CMRV3146EH-F 1 852 355 43 1 852 355 45 1 852 355 46 1 852 355 47 SAP-CMRV1926EH SAP-CMRV1936EH SAP-CMRV2446EH < Applicable Indoor Units > Wall mounted type SAP-KRV96EHDSA SAP-KRV126EHDS SAP-CMRV3146EH NOTE SAP-KMRV76EH SAP-KMRV96EH SAP-KMRV126EH SAP-KRV186EH SAP-KRV246EH For details about the combination, refer to "Unit Combination Table" in the Appendix of this manual. RoHS • This product does not contain any hazardous substances prohibited by the RoHS Directive. WARNING • You are requested to use RoHS compliant parts for maintenance or repair. • You are requested to use lead-free solder. F-GAS REGULATION (EC) No 842 / 2006 Do not vent R410A into atmosphere : R410A is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975. REFERENCE NO. SM700846 Important! Please Read Before Starting When Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. When Installing For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or unsafe practice which can WARNING result in severe personal injury or death. CAUTION In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support. In a Room Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. When Connecting Refrigerant Tubing • Use the flare method for connecting tubing. • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. • Check carefully for leaks before starting the test run. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIONS WARNING When Servicing When Wiring • Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. • Keep your fingers and clothing away from any moving parts. • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. • Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. • Ground the unit following local electrical codes. • Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. • Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur. Others CAUTION • Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. • Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas. 2 Table of Contents Page APPLICABLE INDOOR UNITS .................................................................................................... 5 1. OPERATING RANGE ................................................................................................................... 6 2. SPECIFICATIONS 2-1. Unit Specifications ............................................................................................................. 2-2. Major Component Specifications ....................................................................................... 2-3. Other Component Specifications ....................................................................................... 7 12 17 3. DIMENSIONAL DATA ................................................................................................................... 18 4. REFRIGERANT FLOW DIAGRAM 4-1. Refrigerant Flow Diagram ................................................................................................... 23 5. PERFORMANCE DATA 5-1. Temperature Charts ............................................................................................................ 28 6. ELECTRICAL DATA 6-1. Electric Wiring Diagrams .................................................................................................... 59 7. FUNCTIONS 7-1. Explanation of Functions .................................................................................................... 7-2. Protective Functions ........................................................................................................... 64 68 8. TROUBLESHOOTING 8-1. Precautions before Performing Inspection or Repair ........................................................... 8-2. Trouble Diagnosis by Error Monitor Lamps ......................................................................... 8-3. Checking the Outdoor System ............................................................................................ 8-4. Trouble Diagnosis of Each Part .......................................................................................... 8-5. Trouble Diagnosis of Fan Motor .......................................................................................... 71 72 73 74 77 9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 9-1. Characteristics of New Refrigerant R410A ......................................................................... 9-2. Checklist before Servicing ................................................................................................... 9-3. Tools Specifically for R410A ................................................................................................ 9-4. Tubing Installation Procedures ............................................................................................ 9-5. In Case of Compressor Malfunction .................................................................................... 9-6. In Case Refrigerant is Leaking ............................................................................................ 9-7. Charging Additional Refrigerant .......................................................................................... 9-8. Retro-Fitting Existing Systems ............................................................................................ 78 78 80 80 81 83 84 84 3 Page APPENDIX A INSTALLATION INSTRUCTIONS ............................................................................. A-1 (SAP-CMRV1426EH) APPENDIX B INSTALLATION INSTRUCTIONS ............................................................................. A-2 SAP-CMRV1926EH, SAP-CMRV1936EH SAP-CMRV2446EH, SAP-CMRV3146EH ( ) APPENDIX C UNIT COMBINATION TABLES ................................................................................. A-3 4 APPLICABLE INDOOR UNITS Indoor Unit Multi-Outdoor Unit SAPKRV126EHDS 2-Room SAP-CMRV1426EH YES YES 2-Room SAP-CMRV1926EH YES YES 3-Room SAP-CMRV1936EH YES YES 4-Room SAP-CMRV2446EH YES YES 4-Room SAP-CMRV3146EH YES YES SAPKMRV76EH SAPKMRV96EH SAPKMRV126EH SAPKRV186EH SAPKRV246EH Indoor Unit Multi-Outdoor Unit NOTE SAPKRV96EHDSA 2-Room SAP-CMRV1426EH YES YES YES NO NO 2-Room SAP-CMRV1926EH YES YES YES YES NO 3-Room SAP-CMRV1936EH YES YES YES YES NO 4-Room SAP-CMRV2446EH YES YES YES YES YES 4-Room SAP-CMRV3146EH YES YES YES YES YES 1. The table lists the wall-mounted type of indoor units as representative models. 2. For details on the applicable indoor units other than the wall-mounted type, refer to the catalog. 5 1. OPERATING RANGE Outdoor Unit : SAP-CMRV1426EH, SAP-CMRV1926EH, SAP-CMRV1936EH SAP-CMRV2446EH, SAP-CMRV3146EH Indoor Unit : SAP-KRV96EHDSA, SAP-KRV126EHDS SAP-KMRV76EH, SAP-KMRV96EH, SAP-KMRV126EH SAP-KRV186EH, SAP-KRV246EH Temperature Cooling Heating Maximum Minimum Maximum Minimum Indoor Air Intake Temp. 32 °C D.B. / 23 °C W.B. 19 °C D.B. / 14 °C W.B. 27 °C D.B. 16 °C D.B. Outdoor Air Intake Temp. 43 °C D.B. -5 °C W.B. 24 °C D.B. / 18 °C W.B. _ D.B. / -15 °C W.B. (*1) 0 °C D.B. : When combined with SAP-KRV186EH or SAP-KRV246EH. 6 (*1) 2. SPECIFICATIONS 2-1. Unit Specifications Outdoor Unit Indoor Unit SAP-CMRV1426EH SAP-KMRV96EH × 2 Type 2-Room Multi Outdoor Unit Number of Connectable Indoor Units 2 Number of Operatable Indoor Units 2 Max. Capacity of Operating Indoor Units kW 6.15 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Capacity Air Circulation (High) Electrical Rating Available Voltage Range Running Amperes Power Input Power Factor E.E.R. C.O.P. Compressor Locked Rotor Amperes Features (Outdoor Unit) Controls Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound Hi Refrigerant Tubing Connections Max. allowable tubing length per unit Refrigerant Narrow tube Tube Diameter Wide tube Dimensions & Weight (Outdoor Unit) Unit Dimensions Height × Width × Depth Package Dimensions Height × Width × Depth Weight Net Shipping Shipping Volume Cooling 4.0 ( 2.0 to 5.0 ) 13,600 ( 6,800 to 17,100 ) 1,900 kW BTU/h m3/h Cooling V A W % W/W W/W A 4.1 925 98 4.32 - kg 47 dB-A m mm (in.) mm (in.) Heating 4.5 ( 2.2 to 5.5 ) 15,400 ( 7,500 to 18,800 ) 1,900 198 to 264 Heating 10.0 Microprocessor Auto (Hi, Me, Lo) DC Twin Rotary (Inverter) R410A / 1.7 Electric Expansion Valve Flare Type 20 6.35 (1/4") × 2 9.52 (3/8") × 2 mm 569 × 790 × 285 mm kg kg m3 645 × 920 × 385 42.0 45.0 0.22 4.1 925 98 4.86 48 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: 1. The values shown in perfromance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Table" in this manual. Indoor Unit: SAP-KMRV96EH 2units Outdoor Unit: SAP-CMRV1426EH 1unit 2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B. Outdoor air temp. 35°C D.B. / 24°C W.B. 7 Heating: Indoor air temp. 20°C D.B. Outdoor air temp. 7°C D.B. / 6°C W.B. Outdoor Unit Indoor Unit SAP-CMRV1926EH SAP-KMRV96EH × 1 + SAP-KRV186EH × 1 Type 2-Room Multi Outdoor Unit Number of Connectable Indoor Units 2 Number of Operatable Indoor Units 2 Max. Capacity of Operating Indoor Units kW 8.65 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Capacity Air Circulation (High) Electrical Rating Available Voltage Range Running Amperes Power Input Power Factor E.E.R. C.O.P. Compressor Locked Rotor Amperes Features (Outdoor Unit) Controls Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound Hi Refrigerant Tubing Connections Max. allowable tubing length per unit Refrigerant Narrow tube Tube Diameter Wide tube Dimensions & Weight (Outdoor Unit) Unit Dimensions Height × Width × Depth Package Dimensions Height × Width × Depth Weight Net Shipping Shipping Volume Cooling 5.6 ( 2.1 to 6.8 ) 19,100 ( 7,200 to 23,200 ) 2,500 kW BTU/h m3/h Cooling V A W % W/W W/W A 7.52 1,695 98 3.30 - kg 46 dB-A m mm (in.) mm (in.) Heating 7.3 ( 2.4 to 8.4 ) 24,900 ( 8,200 to 28,700 ) 2,500 198 to 264 Heating 14.5 Microprocessor Auto (Hi, Me, Lo) DC Twin Rotary (Inverter) R410A / 2.8 Electric Expansion Valve Flare Type 25 6.35 (1/4") × 2 9.52 (3/8") × 2 mm 740 × 900 × 320 mm kg kg m3 868 × 1,050 × 423 65.0 69.0 0.38 7.70 1,735 98 4.21 47 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: 1. The values shown in perfromance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Table" in this manual. Indoor Unit: SAP-KMRV96EH 1unit + SAP-KRV186EH 1unit Outdoor Unit: SAP-CMRV1926EH 1unit 2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B. Outdoor air temp. 35°C D.B. / 24°C W.B. 8 Heating: Indoor air temp. 20°C D.B. Outdoor air temp. 7°C D.B. / 6°C W.B. Outdoor Unit Indoor Unit SAP-CMRV1936EH SAP-KMRV96EH × 3 Type 3-Room Multi Outdoor Unit Number of Connectable Indoor Units 3 Number of Operatable Indoor Units 3 Max. Capacity of Operating Indoor Units kW 10.5 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Capacity Air Circulation (High) Electrical Rating Available Voltage Range Running Amperes Power Input Power Factor E.E.R. C.O.P. Compressor Locked Rotor Amperes Features (Outdoor Unit) Controls Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound Hi Refrigerant Tubing Connections Max. allowable tubing length per unit Refrigerant Narrow tube Tube Diameter Wide tube Dimensions & Weight (Outdoor Unit) Unit Dimensions Height × Width × Depth Package Dimensions Height × Width × Depth Weight Net Shipping Shipping Volume Cooling 5.6 ( 2.9 to 6.8 ) 19,100 ( 9,900 to 23,200 ) 2,500 kW BTU/h m3/h Cooling V A W % W/W W/W A 6.88 1,550 98 3.61 - kg 46 dB-A m mm (in.) mm (in.) Heating 7.3 ( 3.4 to 8.4 ) 24,900 ( 11,600 to 28,700 ) 2,500 198 to 264 Heating 14.5 Microprocessor Auto (Hi, Me, Lo) DC Twin Rotary (Inverter) R410A / 2.8 Electric Expansion Valve Flare Type 25 6.35 (1/4") × 3 9.52 (3/8") × 3 mm 740 × 900 × 320 mm kg kg m3 868 × 1,050 × 423 65.0 69.0 0.38 7.70 1,735 98 4.21 47 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: 1. The values shown in perfromance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Table" in this manual. Indoor Unit: SAP-KMRV96EH 3units Outdoor Unit: SAP-CMRV1936EH 1unit 2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B. Outdoor air temp. 35°C D.B. / 24°C W.B. 9 Heating: Indoor air temp. 20°C D.B. Outdoor air temp. 7°C D.B. / 6°C W.B. Outdoor Unit Indoor Unit SAP-CMRV2446EH SAP-KMRV96EH × 4 Type 4-Room Multi Outdoor Unit Number of Connectable Indoor Units 4 Number of Operatable Indoor Units 4 Max. Capacity of Operating Indoor Units kW 13.1 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Capacity Air Circulation (High) Electrical Rating Available Voltage Range Running Amperes Power Input Power Factor E.E.R. C.O.P. Compressor Locked Rotor Amperes Features (Outdoor Unit) Controls Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Operation Sound Hi Refrigerant Tubing Connections Max. allowable tubing length per unit Refrigerant Narrow tube Tube Diameter Wide tube Dimensions & Weight (Outdoor Unit) Unit Dimensions Height × Width × Depth Package Dimensions Height × Width × Depth Weight Net Shipping Shipping Volume Cooling 6.8 ( 2.9 to 8.1 ) 23,200 ( 9,900 to 27,600 ) 2,700 kW BTU/h m3/h Cooling V A W % W/W W/W A 8.87 2,000 98 3.40 - kg 47 dB-A Heating 8.6 ( 3.4 to 9.0 ) 29,300 ( 11,600 to 30,700 ) 2,700 198 to 264 Heating 14.5 Microprocessor Auto (Hi, Me, Lo) DC Twin Rotary (Inverter) R410A / 2.8 Electric Expansion Valve 8.87 2,000 98 4.30 49 Flare Type 25 6.35 (1/4") × 4 9.52 (3/8") × 3 + 12.7 (1/2") × 1 m mm (in.) mm (in.) mm 740 × 900 × 320 mm kg kg m3 868 × 1,050 × 423 65.0 69.0 0.38 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: 1. The values shown in perfromance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Table" in this manual. Indoor Unit: SAP-KMRV96EH 4units Outdoor Unit: SAP-CMRV2446EH 1unit 2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B. Outdoor air temp. 35°C D.B. / 24°C W.B. 10 Heating: Indoor air temp. 20°C D.B. Outdoor air temp. 7°C D.B. / 6°C W.B. Outdoor Unit Indoor Unit SAP-CMRV3146EH SAP-KMRV96EH × 4 Type 4-Room Multi Outdoor Unit Number of Connectable Indoor Units 4 Number of Operatable Indoor Units 4 Max. Capacity of Operating Indoor Units kW 14.7 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Capacity Air Circulation (High) Electrical Rating Available Voltage Range Running Amperes Power Input Power Factor E.E.R. C.O.P. Compressor Locked Rotor Amperes Features (Outdoor Unit) Controls Fan Speeds Compressor Refrigerant / Amount charged at shipment Refrigerant Control Hi Operation Sound Refrigerant Tubing Connections Max. allowable tubing length per unit Refrigerant Narrow tube Tube Diameter Wide tube Dimensions & Weight (Outdoor Unit) Unit Dimensions Height × Width × Depth Package Dimensions Height × Width × Depth Weight Net Shipping Shipping Volume Cooling 8.0 ( 2.9 to 9.2 ) 27,200 ( 9,900 to 31,400 ) 3,030 kW BTU/h m3/h Cooling V A W % W/W W/W A 7.58 1,725 99 4.64 - kg 48 dB-A Heating 9.4 ( 3.4 to 9.8 ) 32,000 ( 11,600 to 33,400 ) 3,030 198 to 264 Heating 17.0 Microprocessor Auto (Hi, Me, Lo) DC Twin Rotary (Inverter) R410A / 3.8 Electric Expansion Valve 8.96 2,040 99 4.61 50 Flare Type 30 6.35 (1/4") × 4 9.52 (3/8") × 2 + 12.7 (1/2") × 2 m mm (in.) mm (in.) mm 890 × 900 × 320 mm kg kg m3 1,019 × 1,050 × 423 82.0 86.0 0.45 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: 1. The values shown in perfromance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Table" in this manual. Indoor Unit: SAP-KMRV96EH 4units Outdoor Unit: SAP-CMRV3146EH 1unit 2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B. Outdoor air temp. 35°C D.B. / 24°C W.B. 11 Heating: Indoor air temp. 20°C D.B. Outdoor air temp. 7°C D.B. / 6°C W.B. 2-2. Major Component Specifications 2-2-1. Outdoor Unit Outdoor Unit SAP-CMRV1426EH Control PCB Part No. Controls Control Circuit Fuse CB-CMRV1426EH Microprocessor 250V 25A Compressor Type Compressor Model / Nominal Output Compressor Oil ... Amount Coil Resistance (Ambient Temp. 20 °C) DC Twin Rotary (Hermetic) C-6RVN93H0M / 1,000W FV50S ... 350 R - S : 0.482 S - T : 0.482 T - R : 0.482 CC Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Model Overload Relay Operation Temp. Micro F Run Capacitor VAC Crankcase Heater Fan Type Q'ty ... Dia. Yes Yes Yes CS-7L115 Open : 115 °C, Close : 95 °C Propeller 1 ... D420 mm Fan Motor Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 20 °C) Safety Device Type Over- Current Protection Run Capacitor DC Motor DAJ12-55J71-CR ... 1 8 750 / 750 50 RED - WHT : 77.5 WHT - BLU : 77.5 BLU - RED : 77.5 W Ohm Internal Controller Yes - Micro F VAC Heat Exchanger Coil Coil Rows Fin Pitch Face Area Aluminum Plate Fin / Copper Tube 2 1.3 0.452 mm m2 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 12 Outdoor Unit SAP-CMRV1926EH Control PCB Part No. Controls Control Circuit Fuse CB-CMRV1926EH Microprocessor 250V 25A Compressor Type Compressor Model / Nominal Output Compressor Oil ... Amount Coil Resistance (Ambient Temp. 20 °C) DC Twin Rotary (Hermetic) 5KD240XAB21 / 1,700W FV50S ... 900 U - V : 0.720 V - W : 0.708 W - U : 0.726 CC Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Model Overload Relay Operation Temp. Micro F Run Capacitor VAC Crankcase Heater Fan Type Q'ty ... Dia. Yes Yes Yes CS-7LN115 Open : 115 °C, Close : 100 °C 230V 25W mm Propeller 1 ... D460 W Ohm DC Motor SIC-71FW-D490-1 ... 1 8 650 / 650 90 - Fan Motor Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 20 °C) Safety Device Type Over- Current Protection Over- Heat Protection Run Capacitor Internal Controller Yes Yes - Micro F VAC Heat Exchanger Coil Coil Rows Fin Pitch Face Area Aluminum Plate Fin / Copper Tube 2 1.4 0.595 mm m2 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 13 Outdoor Unit SAP-CMRV1936EH Control PCB Part No. Controls Control Circuit Fuse CB-CMRV1935EHFA Microprocessor 250V 25A Compressor Type Compressor Model / Nominal Output Compressor Oil ... Amount Coil Resistance (Ambient Temp. 20 °C) DC Twin Rotary (Hermetic) 5KD240XAB21 / 1,700W FV50S ... 900 U - V : 0.720 V - W : 0.708 W - U : 0.726 CC Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Model Overload Relay Operation Temp. Micro F Run Capacitor VAC Crankcase Heater Fan Type Q'ty ... Dia. Yes Yes Yes CS-7LN115 Open : 115 °C, Close : 100 °C 230V 25W mm Propeller 1 ... D460 W Ohm DC Motor SIC-71FW-D490-1 ... 1 8 650 / 650 90 - Fan Motor Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 20 °C) Safety Device Type Over- Current Protection Over- Heat Protection Run Capacitor Internal Controller Yes Yes - Micro F VAC Heat Exchanger Coil Coil Rows Fin Pitch Face Area Aluminum Plate Fin / Copper Tube 2 1.4 0.595 mm m2 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 14 Outdoor Unit SAP-CMRV2446EH Control PCB Part No. Controls Control Circuit Fuse CB-CMRV2445EHFA Microprocessor 250V 25A Compressor Type Compressor Model / Nominal Output Compressor Oil ... Amount Coil Resistance (Ambient Temp. 20 °C) DC Twin Rotary (Hermetic) 5KD240XAB21 / 1,700W FV50S ... 900 U - V : 0.720 V - W : 0.708 W - U : 0.726 CC Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Model Overload Relay Operation Temp. Micro F Run Capacitor VAC Crankcase Heater Fan Type Q'ty ... Dia. Yes Yes Yes CS-7LN115 Open : 115 °C, Close : 100 °C 230V 25W mm Propeller 1 ... D460 W Ohm DC Motor SIC-71FW-D490-1 ... 1 8 700 / 700 90 - Fan Motor Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 20 °C) Safety Device Type Over- Current Protection Over- Heat Protection Run Capacitor Internal Controller Yes Yes - Micro F VAC Heat Exchanger Coil Coil Rows Fin Pitch Face Area Aluminum Plate Fin / Copper Tube 2 1.4 0.595 mm m2 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 15 Outdoor Unit SAP-CMRV3146EH Control PCB Part No. Controls Control Circuit Fuse CB-CMRV3145EHFA Microprocessor 250V 25A Compressor Type Compressor Model / Nominal Output Compressor Oil ... Amount Coil Resistance (Ambient Temp. 20 °C) DC Twin Rotary (Hermetic) 5JD420XAB22 / 3,000W FV50S ... 1,200 U - V : 0.435 V - W : 0.441 W - U : 0.452 CC Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Model Overload Relay Operation Temp. Micro F Run Capacitor VAC Crankcase Heater Fan Type Q'ty ... Dia. Yes Yes Yes CS-7LN115 Open : 115 °C, Close : 100 °C 230V 25W mm Propeller 1 ... D460 W Ohm DC Motor SIC-71FW-D490-1 ... 1 8 750 / 750 90 - Fan Motor Type Model ... Q'ty No. of Poles Rough Measure RPM (Cool:Hi / Heat:Hi) Nominal Output Coil Resistance (Ambient Temp. 20 °C) Safety Device Type Over- Current Protection Over- Heat Protection Run Capacitor Internal Controller Yes Yes - Micro F VAC Heat Exchanger Coil Coil Rows Fin Pitch Face Area Aluminum Plate Fin / Copper Tube 2 1.4 0.723 mm m2 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 16 2-3. Other Component Specifications Model No. of sensor Sensor Name Quantity of Sensor SAPSAPSAPSAPSAPCMRV1426EH CMRV1926EH CMRV1936EH CMRV2446EH CMRV3146EH Outdoor air temp sensor TKS295B 1 1 1 1 1 Outdoor heat exchanger sensor TKS292B 1 1 1 1 1 AW / AN sensor TKS292B 1/1 1/1 1/1 1/1 1/1 BW / BN sensor TKS292B 1/1 1/1 1/1 1/1 1/1 CW / CN sensor TKS292B 0 0 1/1 1/1 1/1 DW / DN sensor TKS292B 0 0 0 1/1 1/1 Resistance (k ohm) 40 35 30 25 20 15 10 5 0 -20 -15 -10 -5 0 5 10 Temperature (°C) Model No. of sensor Sensor Name Compressor temp sensor TKS293B 15 20 Quantity of Sensor SAPSAPSAPSAPSAPCMRV1426EH CMRV1926EH CMRV1936EH CMRV2446EH CMRV3146EH 1 1 Resistance (k ohm) 200 180 160 140 120 100 80 60 40 20 0 0 10 20 30 40 50 60 70 80 90 Temperature (°C) 17 1 1 1 3. DIMENSIONAL DATA Outdoor Unit SAP-CMRV1426EH 608 :23 ID: 336 310 285 .6 18 2 D:1 2-I 4-ID 295 Narrow tube service valve dia.6.35 (1/4") × 2 Wide tube service valve dia.9.52 (3/8") × 2 70 122 158 70 70 569 790 15 46 85 46 142 Unit: mm (852-0-0010-10700-0) 18 Outdoor Unit SAP-CMRV1926EH D:2 18 12 369 345 320 5-I ID: Narrow tube service valve dia.6.35 (1/4") × 2 Wide tube service valve dia.9.52 (3/8") × 2 85 113 150 75 72 740 900 18 35 293 136 3.6 608 51 114 Unit: mm (852-0-0010-13400-0) 19 Outdoor Unit SAP-CMRV1936EH 608 136 3.6 12 D:2 18 369 345 320 5-I ID: Narrow tube service valve dia.6.35 (1/4") × 3 Wide tube service valve dia.9.52 (3/8") × 3 85 113 150 72 75 70 70 740 900 18 35 293 51 114 Unit: mm (852-0-0010-10900-0) 20 Outdoor Unit SAP-CMRV2446EH 608 136 3.6 12 D:2 18 369 345 320 5-I ID: Wide tube service valve dia.12.70 (1/2") × 1 Narrow tube service valve dia.6.35 (1/4") × 4 Wide tube service valve dia.9.52 (3/8") × 3 113 150 72 75 70 70 70 70 85 740 900 18 35 293 51 114 Unit: mm (852-0-0010-11000-0) 21 Outdoor Unit SAP-CMRV3146EH 608 136 3.6 12 D:2 18 369 345 320 5-I ID: Wide tube service valve dia.12.70 (1/2") × 2 Narrow tube service valve dia.6.35 (1/4") × 4 Wide tube service valve dia.9.52 (3/8") × 2 85 113 150 73 75 70 70 70 70 890 900 18 35 293 51 114 Unit: mm (852-0-0010-11100-0) 22 4. REFRIGERANT FLOW DIAGRAM 4-1. Refrigerant Flow Diagram Outdoor Unit SAP-CMRV1426EH Outdoor unit Wide tube O.D.9.52mm Sub accumulator Service valve on wide tube BW AW O.D.9.52mm Main accumulator Compressor Indoor unit Muffler Defrost valve for hot gas bypass Narrow tube O.D.6.35mm Service valve on narrow tube BN O.D.6.35mm Heat exchanger 4-way valve S Capillary tube for split flow Electric expansion valve M Cooling cycle M AN Heating cycle Strainer Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 23 Insulation Thickness: Min. 8 mm Wide tube Thickness: Min. 8 mm Narrow tube Outdoor Unit SAP-CMRV1926EH Outdoor unit Wide tube O.D.9.52mm Sub accumulator Service valve on wide tube BW Main accumulator AW O.D.9.52mm Compressor Indoor unit Header Defrost valve for hot gas bypass Narrow tube O.D.6.35mm Service valve on narrow tube BN O.D.6.35mm S Heat exchanger 4-way valve Electric expansion valve M Cooling cycle M AN Strainer Heating cycle Header Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 24 Insulation Thickness: Min. 8 mm Wide tube Thickness: Min. 8 mm Narrow tube Outdoor Unit SAP-CMRV1936EH Outdoor unit Main accumulator BW O.D.9.52mm AW O.D.9.52mm Header 4-way valve Defrost valve for hot gas bypass Narrow tube O.D.6.35mm Service valve on narrow tube CN O.D.6.35mm O.D.6.35mm Electric expansion valve S Heat exchanger Wide tube O.D.9.52mm Sub accumulator Service valve on wide tube CW Compressor Indoor unit M M BN Cooling cycle M AN Strainer Heating cycle Header Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 25 Insulation Thickness: Min. 8 mm Wide tube Thickness: Min. 8 mm Narrow tube Outdoor Unit SAP-CMRV2446EH Outdoor unit Main accumulator CW O.D.9.52mm BW O.D.9.52mm AW O.D.12.7mm Narrow tube O.D.6.35mm Sub accumulator Header Service valve on narrow tube DN O.D.6.35mm O.D.6.35mm O.D.6.35mm 4-way valve Electric expansion valve Defrost valve for hot gas bypass S Heat exchanger Wide tube O.D.9.52mm Service valve on wide tube DW Compressor Indoor unit M M CN M BN Cooling cycle M AN Strainer Heating cycle Header Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 26 Insulation Thickness: Min. 8 mm Wide tube Thickness: Min. 8 mm Narrow tube Outdoor Unit SAP-CMRV3146EH Outdoor unit Main accumulator CW O.D.9.52mm BW O.D.12.7mm AW O.D.12.7mm Narrow tube O.D.6.35mm Sub accumulator Header Service valve on narrow tube DN O.D.6.35mm O.D.6.35mm O.D.6.35mm 4-way valve Electric expansion valve Defrost valve for hot gas bypass S Heat exchanger Wide tube O.D.9.52mm Service valve on wide tube DW Compressor Indoor unit M M CN M BN Cooling cycle M AN Strainer Heating cycle Header Defrosting cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 27 Insulation Thickness: Min. 8 mm Wide tube Thickness: Min. 8 mm Narrow tube 5. PERFORMANCE DATA 5-1. Temperature Charts 5-1-1. Temperature Charts (SAP-CMRV1426EH) Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KMRV76EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) 1.6 (16.2) Lo fan Hi fan 1.4 (14.2) temp.30°C Indoor air 27°C 1.2 (12.2) 1.0 (10.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 24°C 30 25 35 3.5 (35.7) 3.0 (30.6) o Ind 2.0 (20.4) 0 (2) Operating current performance chart °C mp.30 r air te Indoo 27°C 24°C 2 1 30 25 35 3 25 20 25 2 1 40 -5 0 5 10 15 Outdoor air temperature (°C) (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart 55 Lo fan Indoor discharge air temperature (°C) 25 Indoor discharge air temperature (°C) 20 °C r temp.23 Indoor ai 20°C 17°C Outdoor air temperature (°C) Hi fan 20 °C r temp.30 Indoor ai 27°C 15 24°C 10 5 15 4 Hi fan 3 10 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 5 Outdoor air temperature (°C) Outdoor air temperature (°C) 4 3°C p.2 tem C 20° C ° 17 2.5 (25.5) 1.5 (15.3) -5 40 ir or a 25 30 35 50 40 Outdoor air temperature (°C) C 17° 35 30 25 20 40 °C .23 mp r te r ai o o C Ind 20° 45 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 28 Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KMRV96EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) 1.6 (16.2) Lo fan (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart Hi fan 1.4 (14.2) C r air temp.30° Indoo 1.2 (12.2) 27°C 24°C 1.0 (10.2) 25 30 35 3.5 (35.7) Ind 17°C 2.5 (25.5) 0 Outdoor air temperature (°C) °C mp.30 r air te C 27° 24°C Indoo 2 1 30 25 35 6 5 25 20 25 4 3 40 -5 0 5 10 15 Outdoor air temperature (°C) (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart 60 Lo fan Indoor discharge air temperature (°C) 25 Indoor discharge air temperature (°C) 20 temp.23°C Indoor air 20°C 17°C Outdoor air temperature (°C) Hi fan 20 °C r temp.30 Indoor ai 27°C 15 24°C 10 5 15 7 Hi fan 3 10 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 5 Outdoor air temperature (°C) (2) Operating current performance chart 4 °C p.23 tem 20°C 3.0 (30.6) 2.0 (20.4) -5 40 air oor 25 30 35 55 45 40 35 30 25 40 Outdoor air temperature (°C) 3°C .2 temp or air Indo 20°C 17°C 50 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 29 Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KMRV126EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) 1.4 (14.2) Lo fan Hi fan 1.2 (12.2) mp.30°C Indoor air te 27°C 1.0 (10.2) 0.8 (8.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 24°C 25 30 35 4.0 (40.8) C 17° 0 Outdoor air temperature (°C) °C p.30 ir tem or a 27°C 24°C Indo 4 3 30 25 35 25 20 25 3°C .2 temp or air 20°C 17°C 6 5 4 40 -5 0 5 10 15 Outdoor air temperature (°C) (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart 65 Lo fan Indoor discharge air temperature (°C) 25 Indoor discharge air temperature (°C) 20 Indo 7 Outdoor air temperature (°C) Hi fan 20 Indoor air 15 temp.30°C 27°C 24°C 10 5 15 8 Hi fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 5 Outdoor air temperature (°C) (2) Operating current performance chart 6 C 20° 3.0 (30.6) 2.5 (25.5) -5 40 In °C .23 mp ir te ra doo 3.5 (35.7) 25 30 35 60 55 50 Outdoor air temperature (°C) 3°C mp.2 air te C ° 20 17°C 45 40 35 30 40 or Indo -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 30 Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KRV96EHDSA × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) 1.4 (14.2) Lo fan (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart Hi fan p.30°C Indoor air tem 1.2 (12.2) 27°C 24°C 1.0 (10.2) 0.8 (8.2) 25 30 35 3.5 (35.7) Ind 17°C 2.5 (25.5) 0 Outdoor air temperature (°C) °C mp.30 r air te 27°C 24°C Indoo 2 1 30 25 35 6 5 25 20 25 4 3 40 -5 0 5 10 15 Outdoor air temperature (°C) (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart 60 Lo fan Indoor discharge air temperature (°C) 25 Indoor discharge air temperature (°C) 20 temp.23°C Indoor air 20°C 17°C Outdoor air temperature (°C) Hi fan 20 °C r temp.30 Indoor ai 15 27°C 24°C 10 5 15 7 Hi fan 3 10 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 5 Outdoor air temperature (°C) (2) Operating current performance chart 4 °C p.23 tem 20°C 3.0 (30.6) 2.0 (20.4) -5 40 air oor 25 30 35 55 Outdoor air temperature (°C) Indo 45 40 35 30 25 40 3°C .2 temp or air 20°C 17°C 50 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 31 Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KRV126EHDS × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) 1.4 (14.2) Lo fan Hi fan 1.2 (12.2) mp.30°C Indoor air te 27°C 1.0 (10.2) 0.8 (8.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 24°C 25 30 35 4.0 (40.8) C 17° 0 Outdoor air temperature (°C) °C p.30 ir tem or a 27°C 24°C Indo 4 3 30 25 35 25 20 25 3°C .2 temp or air 20°C 17°C 6 5 4 40 -5 0 5 10 15 Outdoor air temperature (°C) (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart 65 Lo fan Indoor discharge air temperature (°C) 25 Indoor discharge air temperature (°C) 20 Indo 7 Outdoor air temperature (°C) Hi fan 20 Indoor air 15 temp.30°C 27°C 24°C 10 5 15 8 Hi fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 5 Outdoor air temperature (°C) (2) Operating current performance chart 6 C 20° 3.0 (30.6) 2.5 (25.5) -5 40 In °C .23 mp ir te ra doo 3.5 (35.7) 25 30 35 60 55 50 45 Outdoor air temperature (°C) 3°C mp.2 air te C ° 20 17°C 40 35 30 40 or Indo -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 32 5-1-2. Temperature Charts (SAP-CMRV1926EH) Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KMRV76EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) (1) High pressure performance chart Hi fan HH fan oor Ind 1.2 (12.2) High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart air C 30° . p tem C 27° C 24° 1.1 (11.2) 1.0 (10.2) 25 30 35 3.5 (35.7) Indoo 2.5 (25.5) 2.0 (20.4) -5 40 0 Outdoor air temperature (°C) Hi fan 15 20 25 20 25 8 HH fan 4 °C r temp.30 Indoor ai °C 7 2 24°C 3 10 (2) Operating current performance chart Operating current (A) Operating current (A) 5 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan °C mp.23 r air te 20°C 17°C 3.0 (30.6) 7 °C r temp.23 Indoor ai 20°C 17°C 6 5 2 30 25 35 40 -5 0 Outdoor air temperature (°C) 20 Hi fan Indoor p.30°C air tem 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) 55 50 45 Outdoor air temperature (°C) 23°C . emp air t 20°C 17°C 40 35 30 25 40 or Indo -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 33 Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KMRV96EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) Hi fan HH fan 0°C mp.3 r air te C ° 27 1.2 (12.2) Indoo 24°C 1.1 (11.2) 1.0 (10.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) 17°C 2.5 (25.5) 2.0 (20.4) -5 40 23°C mp. ir te or a Indo 20°C 3.0 (30.6) 0 Outdoor air temperature (°C) (2) Operating current performance chart Operating current (A) 6 Hi fan C 30° 3 mp. ir te or a Indo C 27° 24°C 30 25 35 6 -5 0 15 25 60 HH fan °C mp.30 air te Indoor 14 27°C 12 24°C 35 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) Hi fan 30 5 Outdoor air temperature (°C) 18 25 20 °C mp.23 r air te C ° 20 17°C Indoo 40 20 10 25 5 (3) Indoor discharge air performance chart 16 20 7 Outdoor air temperature (°C) Lo fan 15 8 HH fan 5 4 10 (2) Operating current performance chart Operating current (A) Lo fan 5 Outdoor air temperature (°C) 55 50 45 40 Outdoor air temperature (°C) p.23°C air tem 20°C 17°C 35 30 25 40 Indoor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 34 Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KMRV126EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart Hi fan High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart HH fan Indoor 1.1 (11.2) p.30°C air tem 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) 40 -5 0 Outdoor air temperature (°C) Hi fan 9 °C p.30 ir tem or a Indo 27°C 24°C 4 15 20 25 20 25 10 HH fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) 6 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan 3°C p.2 em ir t ra oo 0°C Ind 2 C 17° °C .23 p em ir t ra o o C Ind 20° C 17° 8 7 6 5 4 3 30 25 35 3 40 -5 0 Outdoor air temperature (°C) 20 Hi fan C 30°°C r temp.30 Indoor ai 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) 55 Outdoor air temperature (°C) Ind 45 40 35 30 25 40 i ra C ° 20 °C 7 1 oo 50 3°C p.2 m r te -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 35 Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KRV186EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart HH fan Hi fan or Indo 1.1 (11.2) High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart °C p.30 m air te 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) -5 40 0 HH fan Ind °C p.30 tem C 27° 24°C 30 25 11 ir or a o Ind 10 20 25 20 25 3°C p.2 tem C 20° C ° 7 1 9 8 35 6 40 -5 0 Outdoor air temperature (°C) Hi fan HH fan 18 16 Indoor air 14 temp.30°C 27°C 12 24°C 10 25 30 35 10 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Lo fan 20 5 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) 15 7 5 8 10 12 7 6 5 (2) Operating current performance chart Operating current (A) Operating current (A) Hi fan air oor C Outdoor air temperature (°C) (2) Operating current performance chart Lo fan C 20° 17° Outdoor air temperature (°C) 8 ra oo Ind 3°C p.2 em ir t 60 55 Outdoor air temperature (°C) Ind 50 °C p.23 tem 20°C 17°C 45 40 35 30 40 air oor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 36 Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KRV96EHDSA × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) Hi fan HH fan 0°C mp.3 r air te C ° 27 1.2 (12.2) Indoo 24°C 1.1 (11.2) 1.0 (10.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) 17°C 2.5 (25.5) 2.0 (20.4) -5 40 23°C mp. ir te or a Indo 20°C 3.0 (30.6) 0 Outdoor air temperature (°C) (2) Operating current performance chart Operating current (A) 6 Hi fan C 30° 3 mp. ir te or a Indo C 27° 24°C 30 25 35 6 -5 0 Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) 8 p.30°C 27°C 24°C 25 30 35 15 25 60 air tem 10 10 (3) Indoor discharge air performance chart HH fan 12 5 Outdoor air temperature (°C) 18 14 20 °C mp.23 r air te C ° 20 17°C Indoo 40 Hi fan Indoor 25 5 (3) Indoor discharge air performance chart 16 20 7 Outdoor air temperature (°C) Lo fan 15 8 HH fan 5 4 10 (2) Operating current performance chart Operating current (A) Lo fan 5 Outdoor air temperature (°C) 55 50 45 Outdoor air temperature (°C) p.23°C air tem 20°C 17°C 40 35 30 25 40 Indoor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 37 Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KRV126EHDS × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart Hi fan High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart HH fan Indoor 1.1 (11.2) p.30°C air tem 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) 40 -5 0 Outdoor air temperature (°C) Hi fan 9 °C p.30 ir tem or a Indo 27°C 24°C 4 15 20 25 20 25 10 HH fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) 6 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan 3°C p.2 em ir t ra oo 0°C Ind 2 C 17° °C .23 p em ir t ra o o C Ind 20° C 17° 8 7 6 5 4 3 30 25 35 3 40 -5 0 Outdoor air temperature (°C) 20 Hi fan C 30°°C r temp.30 Indoor ai 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) Outdoor air temperature (°C) em ir t ra oo 0°C d 2 In °C 17 50 45 40 35 30 25 40 3°C p.2 55 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 38 5-1-3. Temperature Charts (SAP-CMRV1936EH) Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KMRV76EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) (1) High pressure performance chart Hi fan HH fan oor Ind 1.2 (12.2) High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart air C 30° . p tem C 27° C 24° 1.1 (11.2) 1.0 (10.2) 25 30 35 3.5 (35.7) 2.5 (25.5) 2.0 (20.4) -5 40 0 Outdoor air temperature (°C) Hi fan 15 20 25 20 25 8 HH fan 4 °C r temp.30 Indoor ai °C 7 2 24°C 3 10 (2) Operating current performance chart Operating current (A) Operating current (A) 5 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan °C mp.23 r air te 20°C 17°C Indoo 3.0 (30.6) 7 °C r temp.23 Indoor ai 20°C 17°C 6 5 2 30 25 35 40 -5 0 Outdoor air temperature (°C) 20 Hi fan Indoor p.30°C air tem 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) 55 50 45 Outdoor air temperature (°C) 23°C . emp air t 20°C 17°C 40 35 30 25 40 or Indo -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 39 Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KMRV96EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) Hi fan HH fan 0°C mp.3 r air te 27°C 1.2 (12.2) Indoo 24°C 1.1 (11.2) 1.0 (10.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) 17°C 2.5 (25.5) 2.0 (20.4) -5 40 23°C mp. ir te or a Indo 20°C 3.0 (30.6) 0 Outdoor air temperature (°C) (2) Operating current performance chart Operating current (A) 6 Hi fan C 30° 3 mp. ir te or a Indo C 27° 24°C 30 25 35 6 -5 0 15 25 60 HH fan °C mp.30 air te Indoor 14 27°C 12 24°C 35 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) Hi fan 30 5 Outdoor air temperature (°C) 18 25 20 °C mp.23 r air te C ° 20 17°C Indoo 40 20 10 25 5 (3) Indoor discharge air performance chart 16 20 7 Outdoor air temperature (°C) Lo fan 15 8 HH fan 5 4 10 (2) Operating current performance chart Operating current (A) Lo fan 5 Outdoor air temperature (°C) 55 50 45 40 Outdoor air temperature (°C) p.23°C air tem 20°C 17°C 35 30 25 40 Indoor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 40 Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KMRV126EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart Hi fan High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart HH fan Indoor 1.1 (11.2) p.30°C air tem 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) 40 -5 0 Outdoor air temperature (°C) Hi fan 9 °C p.30 ir tem or a Indo 27°C 24°C 4 15 20 25 20 25 10 HH fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) 6 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan 3°C p.2 em ir t ra oo 0°C Ind 2 C 17° °C .23 p em ir t ra o o C Ind 20° C 17° 8 7 6 5 4 3 30 25 35 3 40 -5 0 Outdoor air temperature (°C) 20 Hi fan C 30°°C r temp.30 Indoor ai 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) 55 Outdoor air temperature (°C) Ind 45 40 35 30 25 40 i ra C ° 20 °C 7 1 oo 50 3°C p.2 m r te -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 41 Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KRV186EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart HH fan Hi fan or Indo 1.1 (11.2) High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart °C p.30 m air te 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) -5 40 0 HH fan Ind °C p.30 tem C 27° 24°C 30 25 11 ir or a o Ind 10 20 25 20 25 3°C p.2 tem C 20° C ° 7 1 9 8 35 6 40 -5 0 Outdoor air temperature (°C) Hi fan HH fan 18 16 Indoor air 14 temp.30°C 27°C 12 24°C 10 25 30 35 10 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Lo fan 20 5 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) 15 7 5 8 10 12 7 6 5 (2) Operating current performance chart Operating current (A) Operating current (A) Hi fan air oor C Outdoor air temperature (°C) (2) Operating current performance chart Lo fan C 20° 17° Outdoor air temperature (°C) 8 ra oo Ind 3°C p.2 em ir t 60 55 Outdoor air temperature (°C) Ind 50 °C p.23 tem 20°C 17°C 45 40 35 30 40 air oor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 42 Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KRV96EHDSA × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) Hi fan HH fan 0°C mp.3 r air te 27°C 1.2 (12.2) Indoo 24°C 1.1 (11.2) 1.0 (10.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) 17°C 2.5 (25.5) 2.0 (20.4) -5 40 23°C mp. ir te or a Indo 20°C 3.0 (30.6) 0 Outdoor air temperature (°C) (2) Operating current performance chart Operating current (A) 6 Hi fan C 30° 3 mp. ir te or a Indo C 27° 24°C 30 25 35 6 -5 0 Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) 8 p.30°C 27°C 24°C 25 30 35 15 25 60 air tem 10 10 (3) Indoor discharge air performance chart HH fan 12 5 Outdoor air temperature (°C) 18 14 20 °C mp.23 r air te C ° 20 17°C Indoo 40 Hi fan Indoor 25 5 (3) Indoor discharge air performance chart 16 20 7 Outdoor air temperature (°C) Lo fan 15 8 HH fan 5 4 10 (2) Operating current performance chart Operating current (A) Lo fan 5 Outdoor air temperature (°C) 55 50 45 Outdoor air temperature (°C) p.23°C air tem 20°C 17°C 40 35 30 25 40 Indoor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 43 Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KRV126EHDS × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart Hi fan High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart HH fan Indoor 1.1 (11.2) p.30°C air tem 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) 40 -5 0 Outdoor air temperature (°C) Hi fan 9 °C p.30 ir tem or a Indo 27°C 24°C 4 15 20 25 20 25 10 HH fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) 6 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan 3°C p.2 em ir t ra oo 0°C Ind 2 C 17° °C .23 p em ir t ra o o C Ind 20° C 17° 8 7 6 5 4 3 30 25 35 3 40 -5 0 Outdoor air temperature (°C) 20 Hi fan C 30°°C r temp.30 Indoor ai 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) Outdoor air temperature (°C) em ir t ra oo 0°C d 2 In °C 17 50 45 40 35 30 25 40 3°C p.2 55 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 44 5-1-4. Temperature Charts (SAP-CMRV2446EH) Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KMRV76EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) (1) High pressure performance chart Hi fan HH fan oor Ind 1.2 (12.2) High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart air C 30° . p tem C 27° C 24° 1.1 (11.2) 1.0 (10.2) 25 30 35 3.5 (35.7) Indoo 2.5 (25.5) 2.0 (20.4) -5 40 0 Outdoor air temperature (°C) Hi fan 15 20 25 20 25 8 HH fan 4 °C r temp.30 Indoor ai °C 7 2 24°C 3 10 (2) Operating current performance chart Operating current (A) Operating current (A) 5 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan °C mp.23 r air te 20°C 17°C 3.0 (30.6) 7 °C r temp.23 Indoor ai 20°C 17°C 6 5 2 30 25 35 40 -5 0 Outdoor air temperature (°C) 20 Hi fan Indoor p.30°C air tem 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) 55 50 45 Outdoor air temperature (°C) 23°C . emp air t 20°C 17°C 40 35 30 25 40 or Indo -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 45 Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KMRV96EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) Hi fan HH fan 0°C mp.3 r air te C ° 27 1.2 (12.2) Indoo 24°C 1.1 (11.2) 1.0 (10.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) 17°C 2.5 (25.5) 2.0 (20.4) -5 40 23°C mp. ir te or a Indo 20°C 3.0 (30.6) 0 Outdoor air temperature (°C) (2) Operating current performance chart Operating current (A) 6 Hi fan C 30° 3 mp. ir te or a Indo C 27° 24°C 30 25 35 6 -5 0 15 25 60 HH fan °C mp.30 air te Indoor 14 27°C 12 24°C 35 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) Hi fan 30 5 Outdoor air temperature (°C) 18 25 20 °C mp.23 r air te C ° 20 17°C Indoo 40 20 10 25 5 (3) Indoor discharge air performance chart 16 20 7 Outdoor air temperature (°C) Lo fan 15 8 HH fan 5 4 10 (2) Operating current performance chart Operating current (A) Lo fan 5 Outdoor air temperature (°C) 55 50 45 40 Outdoor air temperature (°C) p.23°C air tem 20°C 17°C 35 30 25 40 Indoor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 46 Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KMRV126EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart Hi fan High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart HH fan Indoor 1.1 (11.2) p.30°C air tem 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) 40 -5 0 Outdoor air temperature (°C) Hi fan 9 °C p.30 ir tem or a Indo 27°C 24°C 4 15 20 25 20 25 10 HH fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) 6 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan 3°C p.2 em ir t ra oo 0°C Ind 2 C 17° °C .23 p em ir t ra o o C Ind 20° C 17° 8 7 6 5 4 3 30 25 35 3 40 -5 0 Outdoor air temperature (°C) 20 Hi fan C 30°°C r temp.30 Indoor ai 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) 55 Outdoor air temperature (°C) Ind 45 40 35 30 25 40 i ra C ° 20 °C 7 1 oo 50 3°C p.2 m r te -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 47 Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV186EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart HH fan Hi fan or Indo 1.1 (11.2) High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart °C p.30 m air te 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) -5 40 0 Ind °C p.30 tem C 27° 24°C 30 25 11 ir or a o Ind 10 20 25 20 25 3°C p.2 tem C 20° C ° 7 1 9 8 35 6 40 -5 0 Outdoor air temperature (°C) Hi fan HH fan 18 16 Indoor air 14 temp.30°C 27°C 12 24°C 10 25 30 35 10 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Lo fan 20 5 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) 15 7 5 8 10 12 Operating current (A) Operating current (A) HH fan 7 6 5 (2) Operating current performance chart Hi fan air oor C Outdoor air temperature (°C) (2) Operating current performance chart Lo fan C 20° 17° Outdoor air temperature (°C) 8 ra oo Ind 3°C p.2 em ir t 60 55 Outdoor air temperature (°C) Ind 50 °C p.23 tem 20°C 17°C 45 40 35 30 40 air oor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 48 Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV246EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart Hi fan High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart HH fan Indoor 1.1 (11.2) °C mp.30 air te 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) -5 40 1 0 or ndo I p tem air C 27° C 24° 20 25 20 25 14 Operating current (A) Operating current (A) °C .30 13 o ir or a Ind 12 11 3°C p.2 tem C 20° C ° 7 1 10 9 6 30 25 35 8 40 -5 0 Outdoor air temperature (°C) Hi fan HH fan 18 16 14 0°C mp.3 air te door In 27°C 12 24°C 10 25 30 35 10 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Lo fan 20 5 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) 15 (2) Operating current performance chart 7 8 10 HH fan Hi fan 8 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan C 20° 7°C Outdoor air temperature (°C) 9 r oo Ind °C .23 mp te air 60 55 45 Outdoor air temperature (°C) C 20° C ° 17 40 35 30 40 Ind 50 °C .23 mp r te ai oor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 49 Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV96EHDSA × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.3 (13.2) Hi fan HH fan 0°C mp.3 r air te C ° 27 1.2 (12.2) Indoo 24°C 1.1 (11.2) 1.0 (10.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) 17°C 2.5 (25.5) 2.0 (20.4) -5 40 23°C mp. ir te or a Indo 20°C 3.0 (30.6) 0 Outdoor air temperature (°C) (2) Operating current performance chart Operating current (A) 6 Hi fan C 30° 3 mp. ir te or a Indo C 27° 24°C 30 25 35 6 -5 0 Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) 8 p.30°C 27°C 24°C 25 30 35 15 25 60 air tem 10 10 (3) Indoor discharge air performance chart HH fan 12 5 Outdoor air temperature (°C) 18 14 20 °C mp.23 r air te C ° 20 17°C Indoo 40 Hi fan Indoor 25 5 (3) Indoor discharge air performance chart 16 20 7 Outdoor air temperature (°C) Lo fan 15 8 HH fan 5 4 10 (2) Operating current performance chart Operating current (A) Lo fan 5 Outdoor air temperature (°C) 55 45 Outdoor air temperature (°C) p.23°C air tem 20°C 17°C 40 35 30 25 40 Indoor 50 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 50 Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV126EHDS × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) (1) High pressure performance chart Hi fan High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart HH fan Indoor 1.1 (11.2) p.30°C air tem 27°C 24°C 1.0 (10.2) 0.9 (9.2) 25 30 35 4.0 (40.8) 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) 40 -5 0 Outdoor air temperature (°C) Hi fan 9 °C p.30 ir tem or a Indo 27°C 24°C 4 15 20 25 20 25 10 HH fan 5 10 (2) Operating current performance chart Operating current (A) Operating current (A) 6 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan 3°C p.2 em ir t ra oo 0°C Ind 2 C 17° °C .23 p em ir t ra o o C Ind 20° C 17° 8 7 6 5 4 3 30 25 35 3 40 -5 0 Outdoor air temperature (°C) 20 Hi fan C 30°°C r temp.30 Indoor ai 14 27°C 12 24°C 10 8 25 30 35 15 60 HH fan 18 16 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) (3) Indoor discharge air performance chart Lo fan 5 Outdoor air temperature (°C) 50 45 40 35 30 25 40 Outdoor air temperature (°C) 3°C p.2 em ir t ra oo 0°C d 2 In °C 17 55 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 51 5-1-5. Temperature Charts (SAP-CMRV3146EH) Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KMRV76EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) Hi fan 1.0 (10.2) Hi fan Indoor air HH fan temp.30°C 27°C 24°C 0.8 (8.2) 0.6 (6.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) 2.5 (25.5) 2.0 (20.4) 1.5 (15.3) -5 40 C 3° p.2 m e ir t °C ra 20 oo d n I °C 17 3.0 (30.6) 0 Outdoor air temperature (°C) (2) Operating current performance chart 5 Lo fan Hi fan 5 Hi fan Operating current (A) Operating current (A) or 20 25 20 25 9 HH fan 0°C p.3 o Ind 15 (2) Operating current performance chart 8 4 10 Outdoor air temperature (°C) tem air °C 27 C ° 4 2 C 3° p.2 m e ir t °C r a 20 oo °C d In 17 7 6 5 3 25 30 35 4 40 -5 0 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Lo fan Hi fan Hi fan p.30°C tem Indoor air 27°C 10 5 24°C 25 30 35 15 55 HH fan 20 15 10 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) 25 5 Outdoor air temperature (°C) Outdoor air temperature (°C) p tem air or o d C In 20° C ° 7 1 45 40 35 30 25 20 40 °C .23 50 -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 52 Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KMRV96EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) Hi fan 1.0 (10.2) Hi fan HH fan temp.30°C Indoor air 27°C 24°C 0.8 (8.2) 0.6 (6.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) In 0 Hi fan 0°C p.3 3 25 30 35 7 I Hi fan Indoor air temp.30°C 27°C 10 5 24°C 25 30 35 20 25 °C 20 C ° 7 1 5 -5 0 5 10 15 55 HH fan 20 15 air °C 23 p. m te (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) Hi fan 25 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Lo fan 20 6 4 40 or o nd Outdoor air temperature (°C) 25 15 8 HH fan em ir t ra oo 7°C d n I 2 C 24° 4 10 (2) Operating current performance chart Operating current (A) Operating current (A) Hi fan 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan °C 20 °C 17 2.0 (20.4) Outdoor air temperature (°C) 5 t 2.5 (25.5) 1.5 (15.3) -5 40 ir ra o do 3.0 (30.6) °C 23 p. em 50 45 Outdoor air temperature (°C) C 17° 40 35 30 25 20 40 r oo Ind 3°C p.2 em C 20° t air -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 53 Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KMRV126EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) Hi fan 1.0 (10.2) Hi fan HH fan temp.30°C Indoor air 27°C 0.8 (8.2) 0.6 (6.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 24°C 25 30 35 3.5 (35.7) 3.0 (30.6) ra oo Ind °C 20 °C 7 1 2.5 (25.5) 2.0 (20.4) 1.5 (15.3) -5 40 0 5 Outdoor air temperature (°C) Hi fan Hi fan 13 HH fan 12 °C 30 mp. ir te or a 27°C o d In C 24° 5 15 20 25 20 25 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 10 Outdoor air temperature (°C) (2) Operating current performance chart 6 C 3° p.2 em ir t 4 r oo d In 11 rt °C 20 °C 7 1 ai °C 23 p. em 10 9 8 3 25 30 35 7 40 -5 0 5 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Lo fan Hi fan Hi fan 55 HH fan 20 15 temp.30°C Indoor air 27°C 10 5 24°C 25 30 35 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) 25 10 Outdoor air temperature (°C) Outdoor air temperature (°C) oo Ind 50 45 3°C p.2 tem C 20° C ° 7 1 40 35 30 25 20 40 ir ra -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 54 Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV186EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) 1.0 (10.2) Hi fan mp.30°C Indoor air te 27°C 0.8 (8.2) 0.6 (6.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 24°C 25 30 35 3.5 (35.7) 3.0 (30.6) 2.5 (25.5) 2.0 (20.4) 1.5 (15.3) -5 40 °C .23 mp r te r ai o o C Ind 20° C 17° 0 Outdoor air temperature (°C) 30 35 13 0 Outdoor air temperature (°C) 60 Hi fan 20 15 30°C or air temp. Indo 27°C 10 5 24°C 25 30 35 10 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) Lo fan 5 Outdoor air temperature (°C) (3) Indoor discharge air performance chart 25 25 12 11 -5 40 do or 20 air °C tem 14 5 25 20 p. Hi fan 6 4 25 17 °C °C .30 mp r te r ai C o o 27° Ind C 24° 7 20 (2) Operating current performance chart Operating current (A) Operating current (A) 8 15 In Lo fan 10 23 °C (2) Operating current performance chart 9 5 Outdoor air temperature (°C) 55 50 Outdoor air temperature (°C) C C 17° 45 40 35 30 25 40 23° p. tem r air o o Ind C 20° -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 55 Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV246EH × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (1) High pressure performance chart Lo fan 1.2 (12.2) High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart Hi fan 1.0 (10.2) 0.8 (8.2) 0.6 (6.2) 0°C Indoor air temp.3 27°C 24°C 25 30 35 3.5 (35.7) 3.0 (30.6) Ind C 20° 2.5 (25.5) 2.0 (20.4) 0 5 Outdoor air temperature (°C) 8 25 30 35 p. 12 11 -5 40 0 5 Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) 60 Hi fan 15 10 temp.30°C 27°C 24°C 5 25 30 35 15 (3) Indoor discharge air performance chart 20 Indoor air 10 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Lo fan 25 °C 13 Outdoor air temperature (°C) 25 20 23 °C 9 do or 20 air °C tem 14 °C 27 C ° 24 10 25 17 i ra oo Ind Hi fan p m r te 20 In 11 °C .30 15 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 10 Outdoor air temperature (°C) (2) Operating current performance chart 12 C 17° 1.5 (15.3) -5 40 °C .23 mp r te ai oor 55 Outdoor air temperature (°C) C 20° C ° 17 45 40 35 30 25 40 Ind 50 3°C .2 mp r te ai oor -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 56 Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV96EHDSA × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) Hi fan 1.0 (10.2) Hi fan HH fan temp.30°C Indoor air 27°C 24°C 0.8 (8.2) 0.6 (6.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 25 30 35 3.5 (35.7) In 0 Hi fan 0°C p.3 3 25 30 35 7 I Hi fan Indoor air 5 temp.30°C 27°C 10 24°C 25 30 35 20 25 °C 20 C ° 7 1 5 -5 0 5 10 55 HH fan 20 15 air °C 23 p. m te 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) Hi fan 25 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Lo fan 20 6 4 40 or o nd Outdoor air temperature (°C) 25 15 8 HH fan em ir t ra oo 7°C d n I 2 C 24° 4 10 (2) Operating current performance chart Operating current (A) Operating current (A) Hi fan 5 Outdoor air temperature (°C) (2) Operating current performance chart Lo fan °C 20 °C 17 2.0 (20.4) Outdoor air temperature (°C) 5 t 2.5 (25.5) 1.5 (15.3) -5 40 ir ra o do 3.0 (30.6) °C 23 p. em Outdoor air temperature (°C) Ind 45 C 17° 40 35 30 25 20 40 r oo 50 °C .23 mp C 20° te air -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 57 Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV126EHDS × 1 Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 50Hz) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) Lo fan 1.2 (12.2) Hi fan 1.0 (10.2) Hi fan HH fan temp.30°C Indoor air 27°C 0.8 (8.2) 0.6 (6.2) (1) High pressure performance chart High pressure at wide tube service valve MPaG (kgf/cm2G) Low pressure at wide tube service valve MPaG (kgf/cm2G) (1) Low pressure performance chart 24°C 25 30 35 3.5 (35.7) ra oo Ind 3.0 (30.6) °C 20 °C 7 1 2.5 (25.5) 2.0 (20.4) 1.5 (15.3) -5 40 0 5 Outdoor air temperature (°C) Hi fan Hi fan 13 HH fan 12 °C 30 mp. ir te or a 27°C o d In C 24° 5 15 20 25 20 25 (2) Operating current performance chart Operating current (A) Operating current (A) Lo fan 10 Outdoor air temperature (°C) (2) Operating current performance chart 6 C 3° p.2 em ir t 4 r oo d In 11 rt °C 20 °C 7 1 ai °C 23 p. em 10 9 8 3 25 30 35 7 40 -5 0 5 Outdoor air temperature (°C) (3) Indoor discharge air performance chart Lo fan Hi fan Hi fan 55 HH fan 20 15 Indoor air temp.30°C 27°C 10 24°C 5 25 30 35 15 (3) Indoor discharge air performance chart Indoor discharge air temperature (°C) Indoor discharge air temperature (°C) 25 10 Outdoor air temperature (°C) 50 45 Outdoor air temperature (°C) C 20° C ° 7 1 40 35 30 25 20 40 oor Ind °C .23 mp te air -5 0 5 10 15 20 25 Outdoor air temperature (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary. 58 COMPRESSOR THERMISTOR BLK BLK CM FERRITE CORE YEL YEL BLK BLK 1 1 RED (PNK) 2 2 WHT 3 3 BLU WHT W OLR1 W U OLR0 W W V 1 2 3 4 COIL/OUTDOOR 1 2 COMP (3P)CONNECTOR (2P) CONNECTOR RED (PNK) WHT BLU GRN/YEL C R S COMPRESSOR MOTOR (OLR) OVERLOAD RELAY WHT 1 1 BLK 2 2 BLK (2P) CONNECTOR RED 1 1 WHT WHT 2 2 WHT WHT W W (4P) CONNECTOR COIL WHT THERMISTOR YEL YEL BLK BLK OUTDOOR THERMISTOR (4P) CONNECTOR RED AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR 1 2 3 4 A-TH YEL YEL YEL YEL 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 2 1 2 1 W W DEF1 DEF0 CONTROLLER CN04 DCFM 1 2 3 4 5 6 7 1 2 3 4 B-TH 1 2 3 4 5 6 7 1 2 3 4 5 6 7 (7P) CONNECTOR WHT WHT 1 2 3 4 1 2 3 4 (4P) CONNECTOR BLU BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR YEL YEL YEL YEL BLK RED BLU YEL WHT FAN MOTOR FM BLK RED BLU YEL 2 1 2 1 RV COIL 4WAY VALVE W MV1 1 2 3 4 5 W RV1 RV0 1 2 3 4 5 1 2 3 4 5 2 1 2 1 REACTANCE W E-1 W E-2 MV0 1 2 3 4 5 W L1 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV0 MAGNETIC COIL 1 2 3 4 5 1 2 3 4 5 MV1 MAGNETIC COIL W L2 GRN/YEL DEF (2P) CONNECTOR BLK BLU BLU BLK BLK (5P) CONNECTOR (2P) CONNECTOR WHT BLU BLU BLK BLK ORG RED YEL BLK GRY ORG RED YEL BLK GRY BLU (2P) CONNECTOR WHT WHT WHT WHT WHT (5P) CONNECTOR GRN/YEL ORG RED YEL BLK GRY ORG RED YEL BLK GRY RED 25A E GRN/YEL W W W SI-A SI-B BLK BLK BLK BLU RED WHT REACTANCE ACIN2 W W ACIN1 WHT WHT BLK 8 7 6 5 4 3 2 1 TERMINAL PLATE A INDDOR UNIT L 59 GND N WARNING B INDDOR UNIT Outdoor Unit SAP-CMRV1426EH TO INDDOR UNIT POWER SUPPLY COIL DEFROST VALVE 6. ELECTRICAL DATA 6-1. Electric Wiring Diagrams To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-56900-2 (OLR) OVERLOAD RELAY (2P) CONNECTOR WHT WHT COMPRESSOR THERMISTOR BLK BLK RED 1 1 2 2 W OLR1 W U OLR0 W COMP W V W W 1 2 3 1 2 3 CM 1 2 3 4 1 2 3 4 B-TH WHT (2P) CONNECTOR W W HEATER1 HEATER0 2 2 1 1 HEATER CRANKCASE C/W GRN/YEL COMPRESSOR MOTOR S/U (3P) CONNECTOR WHT WHT 1 1 2 2 1 2 3 4 1 2 3 4 A-TH 2 1 2 1 W W DEF1 DEF0 1 2 3 4 5 6 7 1 2 3 4 5 6 7 FAN MOTOR FM RV 2 1 2 1 W L2 W L1 1 2 3 4 5 1 2 3 4 5 MV0 MAGNETIC COIL MV1 MAGNETIC COIL W E-1 1 2 3 4 5 1 2 3 4 5 W E-2 MV0 1 2 3 4 5 1 2 3 4 5 CONTROLLER W 2 1 2 1 MV1 1 2 3 4 5 1 2 3 4 5 W RV1 RV0 REACTANCE (2P) CONNECTOR WHT COIL 4WAY VALVE BLK BLK WHT WHT WHT WHT DEF CN04 DCFM 1 2 3 4 5 6 7 RED 1 2 3 4 1 2 3 4 COIL/OUTDOOR WHT WHT RED (PNK) WHT BLU FERRITE CORE WHT RED (PNK) R/V WHT BLU WHT (2P) CONNECTOR BLK BLU BLU RED GRN/YEL ORG RED YEL BLK GRY BLK BLK BLU BRN WHT ORG GRN/YEL ORG RED YEL BLK GRY COIL THERMISTOR YEL YEL BLK BLK OUTDOOR THERMISTOR AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR WHT (2P) CONNECTOR WHT BLU BLU BLU BRN WHT ORG 25A E GRN/YEL W W SI-B REACTANCE W SI-A ACIN2 W W ACIN1 BLK BLK BLK BLU RED WHT FERRITE CORE WHT WHT BLK 8 7 6 5 4 3 2 1 TERMINAL PLATE A INDDOR UNIT L GND N 60 B INDDOR UNIT WARNING TO INDDOR UNIT POWER SUPPLY COIL DEFROST VALVE Outdoor Unit SAP-CMRV1926EH To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-84200-0 COMPRESSOR THERMISTOR BLK BLK 1 2 3 1 2 3 CM C/W OLR1 U V W W W W W CN04 DCFM 1 2 3 4 5 6 7 OLR0 W 1 2 3 4 5 6 7 1 2 3 4 5 6 7 RED 2 2 WHT WHT 1 1 WHT WHT (2P) CONNECTOR OVERLOAD RELAY (OLR) FAN MOTOR FM 2 1 2 1 DEF W W DEF1 DEF0 RV 2 1 2 1 C-TH 1 2 3 4 1 2 3 4 MV2 1 2 3 4 5 1 2 3 4 5 MAGNETIC COIL MV2 1 2 3 4 5 1 2 3 4 5 W SI-C SICOM2 W 1 2 3 4 5 6 1 2 3 4 5 6 CN02 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CN03 1 2 3 4 1 2 3 4 CN01 W SICOM2 KS10 1 2 3 4 W KS22 1 2 3 4 5 6 W RV1 RV0 CRANKCASE HEATER WHT W W WHT REACTANCE 2 1 2 1 W L1 W E-2 W E-1 BRN MAGNETIC COIL MV0 MV1 MAGNETIC COIL 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV0 1 2 3 4 5 1 2 3 4 5 W L2 MV1 1 2 3 4 5 1 2 3 4 5 HEATER1 HEATER0 1 1 2 2 (2P) CONNECTOR WHT (2P) CONNECTOR WHT COIL 4WAY VALVE KS23 1 2 3 4 5 6 7 8 CONTROLLER 1 2 3 4 1 2 3 4 COIL/OUTDOOR COMPRESSOR MOTOR S/U RED (PNK) R/V WHT BLU WHT FERRITE CORE (2P) CONNECTOR BLK BLU BLU BLK BLK BLK WHT RED BLU BLK WHT RED BLU COMP RED RED 1 1 2 2 1 2 3 4 1 2 3 4 B-TH 1 2 3 4 1 2 3 4 A-TH COIL THERMISTOR YEL YEL BLK BLK OUTDOOR THERMISTOR GRN/YEL (3P) CONNECTOR AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR BLU BRN WHT ORG RED (PNK) WHT BLU BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR CW THERMISTOR YEL YEL YEL YEL CN THERMISTOR BLU BRN WHT ORG (2P) CONNECTOR WHT BLK WHT RED BLU BLK WHT WHT WHT WHT WHT BLU BLU BLK BLK BLK WHT RED BLU GRN/YEL ORG RED YEL BLK GRY 25A E GRN/YEL W W SI-B REACTANCE W SI-A ACIN2 W W ACIN1 BLK BLK BLU RED WHT BLK FERRITE CORE WHT WHT BLK BLK 3 2 1 9 8 7 6 5 4 3 2 1 TERMINAL PLATE L GND N A INDDOR UNIT GRN/YEL ORG RED YEL BLK GRY POWER SUPPLY TO INDDOR UNIT WHT WHT WHT ORG RED YEL BLK GRY 61 B INDDOR UNIT GND WARNING C INDDOR UNIT COIL DEFROST VALVE Outdoor Unit SAP-CMRV1936EH To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-57000-0 CM C/W COMPRESSOR MOTOR S/U RED (PNK) WHT BLU 1 2 3 1 2 3 1 1 2 2 OLR1 U V W W W W W CN04 DCFM 1 2 3 4 5 6 7 OLR0 W 1 2 3 4 5 6 7 1 2 3 4 5 6 7 FM RED 2 2 WHT WHT 1 1 WHT WHT (2P) CONNECTOR OVERLOAD RELAY (OLR) FAN MOTOR 2 1 2 1 DEF W DEF1 DEF0 W RV 2 1 2 1 D-TH 1 2 3 4 1 2 3 4 C-TH 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 MV2 MAGNETIC COIL MV3 MAGNETIC COIL MV2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV3 1 2 3 4 5 1 2 3 4 5 SI-C W SI-D W W SICOM2 1 2 3 4 5 6 1 2 3 4 5 6 CN02 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CN03 1 2 3 4 1 2 3 4 CN01 W SICOM2 KS10 1 2 3 4 KS22 1 2 3 4 5 6 W RV1 RV0 W CRANKCASE HEATER WHT W W WHT REACTANCE 2 1 2 1 L1 W E-2 W E-1 W GRY BRN MAGNETIC COIL MV0 MV1 MAGNETIC COIL 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV0 1 2 3 4 5 1 2 3 4 5 L2 W GRN/YEL MV1 1 2 3 4 5 1 2 3 4 5 HEATER1 HEATER0 1 1 2 2 (2P) CONNECTOR WHT (2P) CONNECTOR WHT COIL 4WAY VALVE KS23 1 2 3 4 5 6 7 8 CONTROLLER 1 2 3 4 1 2 3 4 B-TH 1 2 3 4 1 2 3 4 A-TH 1 2 3 4 1 2 3 4 COIL/OUTDOOR FERRITE CORE WHT COMP RED COMPRESSOR THERMISTOR BLK BLK (3P) CONNECTOR COIL THERMISTOR YEL YEL BLK BLK OUTDOOR THERMISTOR RED RED (PNK) WHT BLU AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR BLK WHT RED BLU BLK WHT RED BLU DW THERMISTOR YEL YEL YEL YEL DN THERMISTOR R/V BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR GRN/YEL (2P) CONNECTOR BLK BLU BLU BLK BLK BLK WHT RED BLU BLK WHT CW THERMISTOR YEL YEL YEL YEL CN THERMISTOR BLU BRN WHT ORG (2P) CONNECTOR WHT ORG RED YEL BLK GRY WHT WHT WHT WHT BLU BLU BLK BLK BLK WHT RED BLU ORG RED YEL BLK GRY BLU BRN WHT ORG WHT WHT WHT GRN/YEL ORG RED YEL BLK GRY 25A E GRN/YEL W W SI-B REACTANCE W SI-A ACIN2 W ACIN1 W BLK BLK BLU RED WHT BLK FERRITE CORE WHT WHT WHT 12 11 10 9 8 7 6 5 BLK 4 WHT 3 2 1 BLK BLK 3 2 1 TERMINAL PLATE L GND N B INDDOR UNIT ORG RED YEL BLK GRY POWER SUPPLY A INDDOR UNIT TO INDDOR UNIT 62 C INDDOR UNIT GND WARNING D INDDOR UNIT COIL DEFROST VALVE Outdoor Unit SAP-CMRV2446EH To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-57100-0 COMPRESSOR THERMISTOR BLK BLK CM C/W W W W W W CN04 DCFM 1 2 3 4 5 6 7 W V U OLR1 OLR0 1 2 3 4 5 6 7 1 2 3 4 5 6 7 FM FAN MOTOR OVERLOAD RELAY (OLR) RED 2 2 WHT WHT 1 1 WHT WHT (2P) CONNECTOR COMPRESSOR MOTOR S/U RED (PNK) WHT BLU 1 2 3 1 2 3 1 1 2 2 2 1 2 1 W DEF1 DEF0 W 2 1 2 1 RV D-TH 1 2 3 4 1 2 3 4 C-TH 1 2 3 4 1 2 3 4 MV3 1 2 3 4 5 1 2 3 4 5 MV2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV2 MAGNETIC COIL 1 2 3 4 5 1 2 3 4 5 MV3 MAGNETIC COIL WHT SI-C W W W REACTANCE (2P) CONNECTOR WHT 2 1 2 1 L1 W E-2 W E-1 GRY BRN MAGNETIC COIL MV0 MV1 MAGNETIC COIL 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 W W SI-A SI-B ACIN2 W ACIN1 W REACTANCE 25A E W W MV0 1 2 3 4 5 1 2 3 4 5 L2 W MV1 1 2 3 4 5 1 2 3 4 5 W WHT HEATER1 HEATER0 SI-D W SICOM2 1 2 3 4 5 6 1 2 3 4 5 6 CN02 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CN03 1 2 3 4 1 2 3 4 CN01 W SICOM2 KS10 1 2 3 4 KS22 1 2 3 4 5 6 KS23 1 2 3 4 5 6 7 8 W RV1 RV0 W CRANKCASE HEATER 1 1 2 2 (2P) CONNECTOR WHT WHT WHT WHT WHT COIL 4WAY VALVE GRN/YEL DEF CONTROLLER 1 2 3 4 1 2 3 4 B-TH 1 2 3 4 1 2 3 4 A-TH 1 2 3 4 1 2 3 4 COIL/OUTDOOR RED WHT FERRITE CORE COMP RED (7P) CONNECTOR GRN/YEL (3P) CONNECTOR COIL THERMISTOR YEL YEL BLK BLK OUTDOOR THERMISTOR DW THERMISTOR YEL YEL YEL YEL DN THERMISTOR RED (PNK) WHT BLU AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR BLK WHT RED BLU BLK WHT RED BLU CW THERMISTOR YEL YEL YEL YEL CN THERMISTOR BLU BRN WHT ORG (2P) CONNECTOR BLK BLU BLU BLK BLK BLK WHT RED BLU BLK WHT ORG RED YEL BLK GRY WHT (2P) CONNECTOR WHT BLU BLU BLK BLK BLK WHT RED BLU ORG RED YEL BLK GRY R/V BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR BLU BRN WHT ORG WHT WHT WHT GRN/YEL FERRITE CORE GRN/YEL ORG RED YEL BLK GRY BLK BLK BLU RED WHT BLK FERRITE CORE WHT WHT WHT 12 11 10 9 8 7 6 5 BLK 4 WHT 3 2 1 BLK BLK 3 2 1 TERMINAL PLATE L GND N B INDDOR UNIT ORG RED YEL BLK GRY POWER SUPPLY A INDDOR UNIT TO INDDOR UNIT 63 C INDDOR UNIT GND WARNING D INDDOR UNIT COIL DEFROST VALVE Outdoor Unit SAP-CMRV3146EH To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-89000-0 7. FUNCTIONS 7-1. Explanation of Functions NOTE The numerical values such as temperature, frequency, time and current in parentheses are an example of SAP-CMRV3146EH and the values are different from the other models. Control/conditions INITIAL Unit operation Breaker is ON. The ON/OFF operation button on the remote controller is pressed. Explanation Power is supplied to the indoor and outdoor unit control circuits, however the unit remains stopped. Positioning of the outdoor unit electric expansion valve is performed. If automatic operation mode has been selected with the remote controller, operation begins in HEAT, SENSOR DRY, or COOL mode depending on the room temperature and outdoor temperature at the time operation starts. This applies in the case of automatic HEAT/COOL operation. Depending on the operational mode, refer to the HEAT, SENSOR DRY, or COOL item. HEAT The ON/OFF operation button on the remote controller is pressed. Operation lamp illuminates. Indoor fan is stopped to prevent cold air from being emitted. Outdoor unit begins operating after forced-stop is canceled. The unit is forced to stop for 3 minutes after the power is turned ON, or 3 minutes after the compressor stops, in order to protect the compressor. The frequency is increased at the rate of 1 Hz every 0.5 seconds. When the indoor coil temperature rises, the compressor starts, the outdoor fan starts, and the indoor fan changes from "LL" to the set fan speed. Depending on the relationship between the remote controller temperature setting and the room temperature, the compressor may stop temporarily (in other words, the thermostat may turn OFF). When the frequency reaches Hz,frequency increases are stopped for a period of seconds. (Refor to Table 2 "Freguency control".) This is in order to stabilize the return of oil to the compressor. The frequency then increases. If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. The room temperature has reached the desired temperature. The indoor temperature and the remote controller temperature setting are approximately equal. The thermostat turns OFF. The indoor fan is stopped. The indoor and outdoor temperatures are high. The outdoor unit stops. (It does not stop if the thermostat for another indoor unit is ON.) Approximately 30 seconds after the thermostat turns OFF, the indoor fan is stopped. In order to protect the compressor, the outdoor unit will not operate for 3 minutes after the thermostat turns OFF, even if the room temperature drops below the desired temperature. The frequency is not increased, even if there is a difference between the room temperature and the desired temperature. In some cases, the frequency may be decreased. The thermostat turns ON. Operating frequency is stabilized in order to maintain a comfortable environment. The indoor unit is stopped. 64 The outdoor unit starts automatically after 3 minutes. During these 3 minutes, a low-pressure pressure balance is achieved, allowing the compressor to start more easily. The amount of heat pump exceeds the amount of heat radiation from the room. Therefore, there is no need to further increase the compressor capacity, and the frequency is stabilized or lowered. The unit operated before, and the temperature of the indoor heat exchanger is relatively warm. Therefore,the fan speed may start at the set fan speed at the same time that the thermostat turns ON. Control/conditions HEAT When defrost operation begins, frost has formed on the outdoor unit (when the ambient air temperature is low). Unit operation Non-stop defrost Indoor fan : Stopped Outdoor fan : Stopped Compressor : 80 Hz Solenoid valve (for hot gas bypass): ON 4-way valve : Remains ON Operation lamp : Red and orange ON alternately Explanation Defrost operation begins based on outdoor heat exchanger temperature and outdoor air temperature conditions. Non-stop defrost (Refer to Fig. 1) 1. After HEAT operation begins, the temperature of the outdoor heat exchanger is at or below the L1 line for 35 minutes. (If outdoor air temperature is less than –3 °C, the time is 48 minutes) 2. After HEAT operation begins, the temperature of the outdoor heat exchanger is at or below the L2 line for 120 minutes. The 4-way valve remains ON during defrost. The outdoor fan stops and the solenoid valve turns ON, allowing the refrigerant to bypass the indoor unit. The operating frequency during defrost is 80 Hz. (Frequency is lowered if the current peak cut-off function is activated.) The maximum length of a single defrost operation is 12 minutes. For the outdoor heat exchanger temperature conditions for ending defrost, refer to Table 1. Defrost release Indoor fan turns ON. After 10 seconds, the solenoid valve (for hot gas bypass) turns OFF. When the cold air feel has disappeared, the indoor fan starts and gradually increases speed until it reaches the set speed. STOP [Clean defrost] Defrost is performed when the outdoor unit is stopped, and the temperature of the outdoor unit coil is at or below the L1 line. (Refer to Fig. 1.) All indicator lamps turn OFF. The indoor and outdoor units stop. Operation is restarted within 4 hours (only when AUTO mode is selected with the remote controller). Starts operating in the same operating mode (HEAT) and with the same temperature settings as before operation was stopped. Operation starts after 4 hours or more have passed. New operation begins based on the temperature conditions at the time the ON/OFF button is pressed. Temperature of releasing Outdoor heat exchanger temperature (–20) 0 (– 6) (– 7) L2 L1 Within 4 hours after operation was stopped, it is assumed that there has been no significant change in the indoor and outdoor temperatures, and the previous conditions (HEAT) are stored. (– 24) (– 25) Outdoor air temperature Defrost operation time Heat exchanger temperature for releasing defrosting Less than 2 minutes 2 minutes or more No releasing 14 °C or higher (*1) *1 The temperature for releasing of defrosting is (20 °C) or higher when the outdoor air temperature is less than 0 °C. Fig. 1 Table 1 65 Control/conditions COOL The ON/OFF operation button on the remote controller is pressed. Unit operation Explanation The operation lamp illuminates. The indoor fan operates at the set fan speed. The outdoor unit stops. The outdoor unit starts. The outdoor unit does not operate for 3 minutes even after the breaker is turned ON. The frequency is increased at the rate of 0.5 Hz every 1 seconds. (Compressor and the outdoor fan start.) The room temperature has reached the desired temperature. When the frequency reaches Hz, frequency increases are stopped for a period of seconds. (Refer to Table 2.) This is in order to stabilize the return of oil to the compressor. The frequency then increases. If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. The indoor temperature and the desired temperature are approximately equal. Operating frequency is stabilized in order to maintain a comfortable environment. The thermostat turns OFF. The thermostat turns ON again. Freeze prevention The outdoor unit stops. (It does not stop if the thermostart for another indoor unit is ON.) After the thermostat turns ON again, the outdoor unit will not operate for 3 minutes, even if the room temperature increases above the desired temperature. After 3 minutes, the outdoor unit begins operating automatically. During these 3 minutes, a pressure balance is achieved, allowing the compressor to start more easily. When the temperature of the indoor heat exchanger drops to approximately 2 °C or below, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan continues operating with no changes. In order to protect against freezing, the compressor stops temporarily, until the temperature of the indoor heat exchanger has risen. Approximately 3 minutes later, if the temperature of the indoor heat exchanger is adove 8 °C, the system returns to its original conditions. Stop All indicator lamps turn OFF. The indoor and outdoor units stop. Operation is restarted within 4 hours (only when AUTO mode is selected with the remote controller). Starts operating in the same operating mode (COOL) and with the same temperature settings as before operation was stopped. Operation starts after 4 hours or more have passed. New operating mode is determined based on the temperature conditions at the time the ON/OFF operation button is pressed. Within 4 hours after operation was stopped, it is assumed that there has been no significant change in the indoor and outdoor temperatures, and the previous conditions (COOL) are stored. Frequency control (Hz) (senconds) Outdoor air temperature is below 0 °C. Outdoor air temperature is 0 °C or higher. (25) Hz (120) seconds (60) seconds (35) Hz (60) seconds (30) seconds (45) Hz (60) seconds (30) seconds (55) Hz (180) seconds (90) seconds Table 2 66 (1/f fluctuation fan) Control/conditions SENSOR The ON/OFF operation button on the remote DRY controller is pressed. Unit operation The operation lamp illuminates. The indoor fan operates at the set fan speed. The outdoor unit stops. The outdoor unit starts. Explanation The outdoor unit does not operate for 3 minutes even after the breaker is turned ON. The frequency is increased at the rate of 0.5 Hz every 1 seconds. (Compressor and the outdoor fan start.) The room temperature reaches the desired temperature, and there is no need for further cooling. The room temperature is 15 °C or higher, and is slightly too cold. When the frequency reaches Hz, frequency increases are stopped for a period of seconds. (Refer to Table 2.) This is in order to stabilize the return of oil to the compressor. The frequency then increases. If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any increases in frequency. DRY operation starts Operating frequency is stabilized in order to maintain a comfortable environment. DRY A operation The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is 1/f fluctuation fan operation. (Refer to Fig. 2.) Operates to effectively dehumidify the air while not excessively reducing the indoor temperature. The indoor unit operates at 1/f fluctuation fan operation, at a fan speed that does not cause a chilly feeling. DRY B operation (1) The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is 1/f fluctuation fan operation. The compressor operates on a 3-minutes ON, 6-minutes OFF cycle, to prevent the room temperature from dropping too much. (2) After appoximately 3 minutes, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan turns OFF. (3) After approximately 6 minutes, the conditions return to (1). The room temperature is below 15 °C. Monitoring operation begins. 1/f fluctuation fan 250 200 (Step) 150 100 50 0 6-minute cycle Fig. 2 67 When monitoring operation begins, the compressor stops, and the indoor fan operates at "LL" (very low) speed. 7-2. Protective Functions NOTE The numerical values such as temperature, frequency, time and current in parentheses are an example of SAP-CMRV3146EH and the values are different from the other models. 7-2-1. Defrost Detection and Release (1) Non-stop defrosting Defrosting sequence Heating operation 4-way valve ON Defrost detection occurs in either of the following cases: • The temperature of the heat exchanger remains at or below the L1 line for 35 minutes after the start of HEAT operation. • The temperature of the heat exchanger remains at or below the L2 line for 120 minutes after the start of HEAT operation. Outdoor heat exchanger temperature (–20) Frost detection Non-stop defrosting Releasing of defrosting 0 L2 L1 Outdoor air (– 6) temperature (– 7) (– 24) (– 25) (80 Hz) operation (4-way valve ON) OFF ON • Compressor • Outdoor fan • Solenoid valve (for hot gas bypass) • Indoor fan OFF • Temperature of the outdoor heat exchanger is at or above the temperature shown in the table below. • Defrost operation has continued for 12 minutes (max. length). Temperature of releasing Defrost operation time Heat exchanger temperature for releasing defrosting Less than 2 minutes 2 minutes or more No releasing 14 °C or higher (*1) *1 The temperature for releasing of defrosting is (20 °C) or higher when the outdoor air temperature is less than 0 °C. NOTE Defrost does not occur during HIGH POWER operation. If other stopped indoor units are started during defrost operation, they begin operating in defrost mode. (2) Clean defrost If all indoor units are stopped during HEAT operation, and frost is detected at the L1 line, and the conditions for defrost are met, then defrost operation occurs, and the unit stops after defrost is completed. 68 7-2-2. Current Control The operating current may rise as a result of causes including increasing heating or cooling loads or decreases in power voltage. In these cases, the operating frequency is automatically reduced, or operation is stopped, in order to control the operating current so that it is (20 A) or less. As a result: • Power breakers and fuses will not be tripped. • Operation can continue during this period with somewhat reduced heating or cooling capacity. • Operation at normal capacity is restored when the cause of the current rise is eliminated. Description of function Example of operation for heating Power Point C Point B Point A Frequency Current (20A) (17A) (16.6A) Target frequency Frequency Stops operation Approx.3 minutes • • • • Operates at the target frequency at Point A and below. Stops increases to the frequency between Points A and B. Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded. Stops operation, and restarts it appoximately 3 minutes later, if Point C is exceeded. (May operate when sudden voltage fluctuations occur. Indicates trouble.) (1) Automatic frequency control The operating frequency is reduced automatically, or operation is stopped, in order to control the operating current so that it is at or below the values shown in the table below. (20A) HEAT COOL Point C (peak cut trip) Point B (Hz reduction) Point A (Hz increase prohibit) NOTE (20.0) (20.0) (16.6) (16.6) (17.0) (17.0) During defrost operation, the COOL current setting value is used. (2) Current control The operating frequency upper limits shown in the figure below are established for frequency reduction and increase-prohibit. Current(A) Example of operation during cooling Trip Hz reduction Hz increase prohibit Hz reduction Hz increase prohibit Hz reduction Hz increase prohibit (16) (15.6) 0 (30) Frequency (Hz) 69 7-2-3. Low Start Current Operation starts at (8 Hz), and the start current is less than the normal operating current. This prevents the flickering of fluorescent lights or television screens that occurs when ordinary A/C units start. 7-2-4. Compressor Temperature Control To protect the compressor coil from overheating, the operating frequency is controlled based on the compressor discharge temperature. Compressor discharge temperature (°C) Trip (110) 5Hz every 30 sec. reduction (106) 2Hz every 30 sec. reduction (100) No control Increase prohibit range (Hz reduction) (90) * Within the increase-prohibit range, the range changes to the Hz reduction range (2 Hz every 30 seconds) if the compressor temperature rises by 2 °C. 7-2-5. Control at HEAT Start-up If HEAT operation is started when the outdoor air temperature is 15 °C or below, the unit operates at the HEAT start-up frequency (70 Hz or above). Reset conditions (1) The compressor frequency exceeds the start-up frequency of (70 Hz). (2) The compressor thermostat is OFF. (3) Frequency reduction for indoor high-load control has occurred. (4) The outdoor air temperature is above 15 °C. (5) The main-unit switch on one or more indoor units is set to TEST run. 70 8. TROUBLESHOOTING 8-1. Precautions before Performing Inspection or Repair Both the indoor unit and outdoor unit include electronic control circuits. Be sure to pay attention to the following before inspecting or repairing the outdoorside electronic circuits. High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 311 V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the control circuit board Power Lamp (red) turns OFF. If the outdoor control circuit board is normal, approximately 180 seconds will be required for the charge to dissipate. However, allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble with the outdoor control circuit board. For example, if the outdoor control circuit board fuse has blown, approximately 30 minutes will be required to discharge the high-capacity electrolytic capacitors. 71 8-2. Trouble Diagnosis by Error Monitor Lamps WARNING To prevent electric shock, do not inspect or repair until the Power Lamp on the P.C.Board is turned off. 8-2-1. Location of the Error Monitor Lamps Remove the top plate of outdoor unit and the cover of Electrical Component Box. The Power Lamp and Error Monitor Lamps are located on the P.C.Board of Electrical Component Box. (Fig.1) Heat Exchanger Rear side P.C.Board of Electrical Component Box. Error Monitor Lamps Power Lamp Front side Fig.1 View from top ERR0 ERR1 ERR2 ERR3 8-2-2. Display of the Error Monitor Lamps If a protective device has activated or there is a sensor failure in the outdoor unit, the 4 error monitor lamps on the outdoor control circuit board will indicate the nature of the trouble. : ON Error Monitor Lamp ERR0 ERR1 ERR2 : OFF Error Contents ERR3 Sensor for compressor discharge temp Sensor for heat excharge temp Sensor for branch pipe A (Narrow tube) Sensor for branch pipe B (Narrow tube) Sensor for branch pipe C (Narrow tube) Sensor for branch pipe D (Narrow tube) Outdoor temp sensor Sensor for branch pipe A (Wide tube) Sensor for branch pipe B (Wide tube) Sensor for branch pipe C (Wide tube) Sensor for branch pipe D (Wide tube) HIC circuit trouble (current, temp) Actuation of comp over load relay Actuation of freeze protection function Outdoor unit error. Detail of error message indicate on indoor LED 72 8-3. Checking the Outdoor System 8-3-1. Checking the outdoor unit No. Work procedure Check items (unit operation) 1 • Apply 220 V AC between terminals L and N on the • The LED (red) on the control board must illuminate. 2 • Short-circuit the T-RUN terminal to the COM terminal • The compressor, fan motor, 4-way valve, and solenoid outdoor unit terminal plate. of TEST/T-RUN terminals. valve (for the hot gas bypass) must turn ON. (They turn ON about (70) seconds later after the power is turned ON.) NOTE If the above check items are okay, but the outdoor unit does not operate, there may be a faulty connection between the indoor unit and the outdoor unit. 8-3-2. Checking the defrost operation Using forced defrost operation to check this function. No. 1 Work procedure Check items (unit operation) • Connect a dummy resistor of 39 k ohm to the outdoor coil temperature sensor connector. Non-stop defrost Indoor fan 30 sec. Setting LL Stop CM Solenoid valve (for hot gas bypass) Outdoor fan Setting (80 Hz) ON 5 sec. 10 sec. OFF ON ON OFF Defrost start OFF ON Release • The maximum length of defrost operation is 12 minutes. Defrost can also be released based on the below conditions for the outdoor heat exchanger sensor. Less than 2 minutes Not released 2 minutes or more 14 °C or higher (*1) *1 However, the condition is (20 °C) or higher when the outdoor air temperature is below 0 °C. 73 8-4. Trouble Diagnosis of Each Part 8-4-1. Problems of Each Part and Inspection Points For details about the inspection points, refer to the Inspection Points for Each Part. Does not heat or heating performance is inadequate. Does not cool or cooling performance is inadequate. The electric expansion valve does not operate. Defrost operation does not occur. Others The outdoor air temperature is high, however defrost operation occurs. The compressor speed does not increase. The compressor stops on occasion. 4-way valve does not operate. Outdoor fan dose not turn. Outdoor unit does not operate. Indoor fan dose not turn. Operation lamp does not illuminate. Operation lamp blinking. Inspection points Indoor unit does not operate. Problems The compressor (only) does not operate. Outdoor unit Indoor unit No. of Inspection Points for Each part Self-Diagnostics check Indoor controller (control unit) Indoor unit Indoor fan motor Room temperature sensor Heat exchanger temperature sensor Inter-unit cable Switch circuit board Outdoor control circuit board (1) Diode module HIC Outdoor unit Electrolytic capacitor Fuse (2) Compressor (3) Compressor protective sensor (4) Others Outdoor fan motor 4-way valve (5) Coil thermistor (6) Electric expansion valve (7) Branch tubing temperature sensor (8) Breaker (9) Refrigerant gas pressure (10) 74 8-4-2. Inspection Points for Each Part (1) Outdoor control circuit board Refer to 8-3-1. Checking the outdoor unit. NOTE Do not remove or insert the outdoor control circuit board connector when power is being supplied to it. (The controller will be damaged.) (2) Fuse Check it visually or the continuity with a tester. (3) Compressor Check for an open circuit in the compressor coil winding. (4) Compressor protective sensor (compressor discharge temperature thermistor) Check that the senseor is securely contained in the thermostart holder. (5) 4-way valve Short-circuit the T-RUN terminal to the COM terminal of TEST/T-RUN terminals. Perfrom a test run of the unit alone, and check whether the 4-way valve inside the outdoor unit produces a click sound. (6) Coil thermistor Check that the sensor is securely contained in the thermostat holder. (7) Electric expansion valve When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions. Labels are applied to the valve body and coil, corresponding to the connector colors, to identify them. Use a multi-meter to measure the voltage (12 V). When the power is turned ON, the needle will move in the following seguence in approximately 10 to 20 seconds for each point. Controller check Voltage varies No voltage on circuit board Model No. SAP-CMRV1426EH SAP-CMRV1926EH Check the illumination of the red Power Lamp. MV0 MV1 SAP-CMRV1936EH MV0 MV1 MV2 SAP-CMRV2446EH SAP-CMRV3146EH MV0 MV1 MV2 Check the coil resistance. 0 ohm Sequence MV3 Check the resistance between the gray lead wire and the other wires. Resistance is OK if it is 46 +/– 4ohm at 20 °C Approx. 46 +/– 4 ohm Replace the controller. NOTE Cool the main unit with a damp cloth or other means while welding. When applying vacuum, use the special service magnet and rotate at least 5 revolutions counterclockwise to fully open the electric expansion valve. Replace the coil. *1 Open and close the electric expansion valve by hand to check it. No temperature change Temperature changes Replace the electric expansion valve. This part is normal. Check elsewhere. Use the special service magnet and rotate 5 revolutions clockwise to fully close the valve. Then start the unit and measure the temperature at the inlet and outlet tubes of the electric expansion valve. If the temperature difference is large, the valve is closed. Then rotate 5 revolutions counterclockwise to open the valve. Operation is normal if the temperature difference between the 2 tubes drops. *1 If you have manually checked the electric expansion valve, be sure to reapply the outdoor power after you have replaced the wiring. (The position of the elecric expansion valve will changed.) 75 (8) Branch tubing temperature sensor Check that the sensor is securely contained in the thermostat holder. (9) Breaker Check whether or not the breaker has been tripped. Check that the breakers and fuses used are of the specified capacity. Check that the breaker and its line are exclusive for A/C use. (10) Refrigerant gas pressure Start a COOL test run, and messure the temperatures of the A/C intake air and discharge air. Compare the values with the performance charts. If the values are higher than the performance charts: Check for refrigerant shortage or blockage of the refrigerant circuit. < Assessment of refrigerant shortage > 1. The pressure in the low-pressure section is 5 MPa or more below the value in the performance charts. 2. There is little condensation on the indoor heat exchanger, which overall appears dry. < Distinguishing between refrigerant shortage and refrigerant circuit blockage > If the pressure in the low-pressure section does not change when the circuit is charged 2 to 3 times with refrigerant gas (0.44 lbs each time), or if the change is small, then the problem may not be refrigerant shortage. The problem may be a blockage of the refrigerant circuit. 1. Check that there is no internal leakage inside the 4-way valve: At the low-pressure side tubing, check that there is no temperature difference between the intake and discharge of the 4-way valve. 2. Check that the electric expansion valve is not blocked. Check as described on the preceding page. 76 8-5. Trouble Diagnosis of Fan Motor This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor. Perform the trouble diagnosis by Test Run mode described on Installation Instructions of indoor unit. Important: (A) Turn OFF the power before connecting or disconnecting the motor connectors. (B) When performing voltage measurement at the outdoor controller connector for (3) in the table below, the DC motor will trip and voltage output will stop approximately 10 seconds after operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor unit power, then, measure the voltage in Test Run mode. [Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble [Trouble symptom 2] The fan motor does not rotate when the outdoor unit is operating. (Diagnostic procedure) * Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor unit controller (3 locations). Measurement location (1) Vs-Gnd : Between pin 1 and pin 4 or Vm-Gnd : Between pin 1 and pin 4 (2) Vcc-Gnd : Between pin 5 and pin 4 (3) Vsp-Gnd : Between pin 7 and pin 4 Normal value DC 230V or more DC 14V or more After fluctuating 4 times between DC 1.7 to 6.1V (1 sec. ON) and DC 0 V (1 sec. OFF), the DC motor trips. (Diagnostic results) All of the above measured values are normal. Fan motor trouble (Replace the motor.) Any one of the above measured values is not normal. Outdoor unit controller trouble (Replace the controller .) (Reference) DC motor connector pin arrangement SAP-CMRV1426EH SAP-CMRV1926EH / -CMRV1936EH SAP-CMRV2446EH / -CMRV3146EH Pin 1: Vs (white) Pin 2: Not used Pin 3: Not used Pin 4: Gnd (black) Pin 5: Vcc (red) Pin 6: FG (blue) Pin 7: Vsp (yellow) Pin 1: Vm (red) Pin 2: Not used Pin 3: Not used Pin 4: Gnd (blue) Pin 5: Vcc (brown) Pin 6: PG (white) Pin 7: Vsp (orange) [Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor unit operates. (There is trouble in the system that provides feedback of motor rotation speed from the motor to the outdoor unit controller.) [Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation. [Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation. (Remedy for symptom 3 to 5) It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble. Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor. 77 9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 9-1. Characteristics of New Refrigerant R410A 9-1-1. What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22. 9-1-2. Components (mixing proportions) HFC32 (50%) / HFC125 (50%) 9-1-3. Characteristics Less toxic, more chemically stable refrigerant The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase). When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state. Thus, always charge the refrigerant while it is in liquid phase. CAUTION Ether-type oil is used for compressor oil for R410A-type units, which is different from the mineral oil used for R22. Thus more attention to moisture prevention and faster replacement work compared with conventional models are required. 9-2. Checklist before Servicing Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of extrusion) by using the flare spacer. Diameter of tube D Dia.6.35 mm (1/4") Flare tool for R410A Dia.9.52 mm (3/8") Specification A Conventional flare tool (for R22) 0 to 0.5 mm Dia.12.7 mm (1/2") 1.2 mm Dia.15.88 mm (5/8") Size of flare D D A Spacer A Flare tool for R410A Conventional flare tool (R22) 78 Tubing precautions Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation. Never use 0.7mm-thick copper tubing or tubing which is less than 0.8mm in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C. No addition of compressor oil for R410A No additional charge of compressor oil is permitted. No use of refrigerant other than R410A Never use a refrigerant other than R410A. If refrigerant R410A is exposed to fire Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure to provide ample ventilation during installation work. Caution in case of R410A leak Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room, immediately provide thorough ventilation. 79 9-3. Tools Specifically for R410A For servicing, use the following tools for R410A Tool Distinction Tool Name Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Tools specifically for R410A Vacuum pump with anti-reverse flow (*1) (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2)...can be used if the following adapter is attached. Vacuum pump adapter (reverse-flow prevention adapter) (*3). (Solenoid valve-installed adapter attached to a conventional vacuum pump.) Electronic scale for charging refrigerant Flare tool Tools which can be commonly used for R22, R407C, and R410A CAUTION Bender Torque wrench Cutter, reamer Welding tool, nitrogen gas cylinder The above tools specifically for R410A must not be used for R22 and R407C. Doing so will cause malfunction of the unit. For the above vacuum pump (*1, *2) and vacuum pump adapter (*3), those for R22-type units can be used for R410A-type. However, they must be used exclusively for R410A and never alternately with R22 and R407C. To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, shape and external diameter of the service port screw has been altered. <External diameter of service port> R410A : 7.94 mm (5/16") R22, R407C : 6.35 mm (1/4") 9-4. Tubing Installation Procedures When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of tubing. The following is the HAB oil generally used: Esso: ZERICE S32 NOTE For details on tubing installation procedures, refer to the installation manuals attached to the indoor unit and outdoor unit. 80 9-5. In Case of Compressor Malfunction CAUTION Should the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as possible. Use only the tools indicated exclusively for R410A. for R410A." See "9-3. Tools Specifically 9-5-1. Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R410A. (1) Recover refrigerant OK Do not reuse the recovered refrigerant, since it will contain impurities. (2) Replacing Compressor Soon after removing seals of both discharge and suction tubes of the new compressor, replace it quickly. (2) Replace compressor OK (3) Checking for sealing Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas. (3) Check for sealing OK (4) Evacuation Use a solenoid valve-installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back. (4) Evacuation OK The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly. When using a vacuum pump with exhaust air volume more than 25L/min. and ultimate vacuum pressure rate of 0.05Torr. Standard time for evacuation Length of tubing Evacuation time Less than 10 meters More than 10 minutes More than 10 meters More than 15 minutes 81 (5) Recharge (5) Recharging Configuration and characteristics of cylinders Be sure to charge the specified amount of refrigerant in liquid state using the service port of the wide tube service valve. The proper amount is listed on the unit's nameplate. Valve When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation. CAUTION Liquid Never charge a large amount of liquid refrigerant at once to the unit. This may cause damage to the compressor. Single valve Charge liquid refrigerant with cylinder in up-side-down position. When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus, do not use the refrigerant if the amount in the charging cylinder is less than 20%. Fig. 1 Valve Also, charge the minimum necessary amount to the charging cylinder before using it to charge the air conditioning unit. Liquid Example: In case of charging refrigerant to a unit requiring 0.76Kg using a capacity of a 10Kg cylinder, the minimum necessary amount for the cylinder is: 0.76 + 10 Single valve (with siphon tube) Charge with cylinder in normal position. 0.20 = 2.76Kg Fig. 2 For the remaining refrigerant, refer to the instructions of the refrigerant manufacturer. If using a charging cylinder, transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder. Prepare an evacuated charging cylinder beforehand. CAUTION To prevent the composition of R410A from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant. (Fig. 3) NO! Charging cylinder Liquid Open Do not use the refrigerant if the amount in the charging cylinder is less than 20%. 82 Refrigerant cylinder Fig. 3 9-6. In Case Refrigerant is Leaking CAUTION Never attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points. (2) Recovering refrigerant (1) Detect leaks OK Never release the gas to the atmosphere; recover residual refrigerant using the refrigerant recovery unit for R410A, instead. Do not reuse the recovered refrigerant because its composition will have been altered. (2) Recover refrigerant OK (3) Welding leaking points Confirm again that no residual refrigerant exists in the unit before starting welding. Weld securely using flux and wax for R410A. (3) Weld leaking points OK Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen (N2) in the refrigerant circuit of the unit. Leave ends of tubes open during welding. (4) Checking for sealing (4) Check for sealing Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas. (5) Evacuation Use a solenoid valve-installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back. The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly. When using a vacuum pump with exhaust air volume more than 25L/min. and ultimate vacuum pressure rate of 0.05Torr. Standard time for evacuation Length of tubing Evacuation time Less than 10 meters More than 10 minutes More than 10 meters More than 15 minutes (6) Recharging Recharge unit in the same manner explained on the previous page "(5) Recharging." 83 OK (5) Evacuation OK (6) Recharge 9-7. Charging Additional Refrigerant 9-7-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. CAUTION Never charge additional refrigerant if refrigerant is leaking from the unit. Follow instructions given in "9-6. In Case Refrigerant is Leaking" and completely carry out repairs. Only then should you recharge the refrigerant. 9-8. Retro-Fitting Existing Systems 9-8-1. Use of Existing Units Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to operate improperly and may result in a hazardous condition. 9-8-2. Use of Existing Tubing If replacing an older unit that used refrigerant R22 with a R410A unit, do not use its existing tubing. Instead, completely new tubing must be used. 84 APPENDIX A INSTALLATION INSTRUCTIONS SAP-CMRV1426EH (II-852-6-4190-456-00-1) NOTE The specifications of SAP-KRV96EHDSA are the same as those of SAP-KRV96EHDS described in the Installation Instruction. A-1 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page a For Outdoor Unit INSTALLATION INSTRUCTIONS – Inverter Multi Split System Air Conditioner – COOL / DRY/ HEAT Model This air conditioner uses the new refrigerant R410A. Page IMPORTANT! Please Read Before Starting .................................. 2 2. GENERAL .......................................................... 3 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation Indoor Unit Outdoor Unit SAP-KMRV74EH SAP-CMRV1426EH SAP-KMRV94EH SAP-KMRV124EH SAP-KMRV76EH SAP-KMRV96EH SAP-KMRV126EH SAP-KRV96EHDS SAP-KRV126EHDS Combine indoor and outdoor units only as listed in the combination tables for 2-room outdoor unit as shown in its respective manual. Power Source: 3. WIRING INSTRUCTIONS ................................ 14 5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Diameter 5-3. Wiring System Diagram 5-4. How to Connect Wiring to the Terminal 5-5. Wiring Instructions for the Outdoor Unit 6. TEST RUN......................................................... 18 7. CONNECTING A HOME AUTOMATION DEVICE ............................................................. 19 8. INSTALLATION CHECK SHEET ...................... 19 9. ELECTRIC WIRING DIAGRAM ........................ 19 85264190456001 © SANYO 2008 Indoor unit B Indoor unit A Outdoor unit NOTE The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing. SANYO Electric Co., Ltd. Osaka, Japan EÏÏËÓÈο 5. Combination example Português AIR PURGING................................................... 11 I Air Purging with a Vacuum Pump (for Test Run) I Pump Down Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A. Italiano 4. 50 Hz, single-phase, 220 – 240 VAC Deutsch INSTALLATION PROCESS ............................... 8 3-1. Embedding the Tubing and Wiring 3-2. Drain Cap and Drain Elbow 3-3. Use of the Flaring Method 3-4. Flaring Procedure with a Flare Tool 3-5. Caution Before Connecting Tubes Tightly 3-6. Tubing Connections 3-7. Insulation of Refrigerant Tubing 3-8. Taping the Tubes 3-9. Finishing the Installation Français INSTALLATION SITE SELECTION ................... 4 2-1. Indoor Unit 2-2. Connecting Indoor Units 2-3. Outdoor Unit 2-4. Outer Dimensions of Outdoor Unit 2-5. Diagram of Outdoor Unit Installation Combine indoor and outdoor units only as listed below. Español 1. Model Combinations English Contents 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 2 IMPORTANT! Please Read Before Starting outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. English This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. When Installing… For safe installation and trouble-free operation, you must: G Carefully read this instruction booklet before beginning. G Follow each installation or repair step exactly as shown. G Observe all local, state, and national electrical codes. G Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or unsafe practice which WARNING can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which CAUTION can result in personal injury or product or property damage. …In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support. …In a Room Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors. …In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. …In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. …In a Snowy Area (for Heat Pump-type Systems) • Position the outdoor unit in a protected location If Necessary, Get Help where snow will not blow into it. These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. • Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. When Connecting Refrigerant Tubing In Case of Improper Installation • Use the flare method for connecting tubing. • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. • Check carefully for leaks before starting the test run. The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIONS WARNING • • • • • When Wiring When Servicing ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur. • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. • Keep your fingers and clothing away from any moving parts. • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. CAUTION Others • Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. • Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas. • Do not install only a single indoor unit. When Transporting Be careful when picking up and moving the indoor and 2 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 3 1. General 1-1. Tools Required for Installation (not supplied) 1. Standard screwdriver 2. Phillips head screwdriver 3. Knife or wire stripper 4. Tape measure Carpenter’s level Sabre saw or key hole saw Hacksaw Core bits Hammer Drill Tube cutter Tube flaring tool Torque wrench Adjustable wrench Reamer (for deburring) Vacuum pump (For R410A) Manifold valve English 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. If the electric wiring diagram does not appear in this manual, please check for the diagram on the indoor unit. 1-2. Accessories Supplied with Unit Table 1 Parts Figure Labels for inter-unit cable and tube A B C D Q’ty Parts Figure Q’ty Parts 4 Drain elbow 4 each Cushion rubber Drain cap Figure Q’ty 1 Packed in the outdoor unit. 4 1-3. Optional Copper Tubing Kit 2. Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 8 mm. 3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 5. Wiring Instructions for details. 1-4. Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source, you will need: 1. Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2. CAUTION Cut each tube to the appropriate lengths +30 cm to 40 cm to dampen vibration between units. Table 2 Narrow Tube Wide Tube Model Outer Dia. Thickness Outer Dia. Thickness KMRV74/76 6.35 mm 0.8 mm 9.52 mm 0.8 mm KMRV94/96 6.35 mm 0.8 mm 9.52 mm 0.8 mm KMRV124/126 6.35 mm 0.8 mm 9.52 mm 0.8 mm KRV96/126 6.35 mm 0.8 mm 9.52 mm 0.8 mm 3 Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations. 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 4 1-5. Additional Materials Required for Installation English 1. 2. Refrigeration (armored) tape Insulated staples or clamps for connecting wire (See local codes) Putty Refrigeration lubricant Clamps or saddles to secure refrigerant tubing 3. 4. 5. Indoor unit 2. Installation Site Selection 2-1. Indoor Unit WARNING To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow. Drain hose AVOID: Outside drainage G direct sunlight. G nearby heat sources that may affect performance of the unit. G areas where leakage of flammable gas may be expected. Fig. 1 G placing or allowing any obstructions near the Air Conditioner inlet or outlet. G installing in rooms that contain instant-on (rapid-start) fluorescent lamps. (These may prevent the Air Conditioner from receiving signals.) G places where large amounts of oil mist exist. G installing in locations where there are devices that generate high-frequency emissions. G select an appropriate position from which every corner of the room can be uniformly cooled. (High on a wall is best.) G select a location that will hold the weight of the unit. G select a location where tubing and drain hose have the shortest run to the outside. (Fig. 1) G allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 2) G install the unit within the maximum elevation difference (H1, H2) above or below the outdoor unit and within a total tubing length (L1+L2) from the outdoor unit as detailed in Table 3 and Fig. 3a. 5 cm min. Front View Fig. 2 INDOOR UNIT (1) DO: 15 cm min. 5 cm min. Elevation difference (H1) Tubing length (L1) INDOOR UNIT (2) L2 OUTDOOR UNIT H2 Fig. 3a CAUTION Indoor unit For stable operation of the air conditioner, do not install wall-mounted type indoor Minimum height units less than 1.5 m from from floor level floor level. 1.5 m Floor level Fig. 3b 4 Wall 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 5 install the indoor unit more than 1 meter away from any antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation. G install in a sturdy manner to avoid increased operating noise. Table 3 Model Max. Allowable Tubing Length per unit (m) Max. Allowable Total Tubing Length at Shipment (L1+L2) (m) Limit of Total Tubing Length (L1+L2) (m) Limit of Elevation Difference (H1, H2) (m) Required Amount of Additional Refrigerant (g/m)* CMRV1426 20 30 (L1+L2) 30 (L1+L2) 15 – 2-2. Connecting Indoor Units (1) Connecting indoor unit for SAP-CMRV1426 Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH,KMRV94EH,KMRV124EH) (SAP-KMRV76EH,KMRV96EH,KMRV126EH) (SAP-KRV96EHDS,KRV126EHDS) ø9.52 (SAP-KMRV74EH,KMRV94EH,KMRV124EH) (SAP-KMRV76EH,KMRV96EH,KMRV126EH) (SAP-KRV96EHDS,KRV126EHDS) B ø9.52 ø6.35 A ø9.52 ø6.35 Fig. 4 unit: mm 5 English G 10:35 AM Page 6 2-3. Outdoor Unit NO AVOID: G heat sources, exhaust fans, etc. (Fig. 5a) G damp, humid or uneven locations. Hot air Heat source Outdoor unit English DO: G position the outdoor unit in a protected location where snow will not blow into it. G choose a place as cool as possible. G choose a place that is well ventilated. install in a location where at least two sides are unobstructed, so that the flow of air at the intake port or exhaust port is not blocked, and so that sufficient space is ensured for maintenance to be carried out without trouble. In general the top also must be unobstructed. (Fig. 5b) G G G Exhaust fan Fig. 5a Obstacle above Air intake provide a solid base (level concrete pad, concrete block, 10 × 40 cm beams or equal), a minimum of 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 5c) Min. 5 cm Min. 10 cm Air discharge Valve side Min. 25 cm Min. 40 cm Ground Fig. 5b install cushion rubber under unit’s feet to reduce vibration and noise. (Fig. 5d) G use lug bolts or equal to bolt down unit, reducing vibration and noise. G install in a location where no antenna of a television or radio exists within 3 meters. Min. 2m Min. 2m Obstacle 9/22/08 Air discharge 08-245 CMRV1426EH_OU EN Min. 10 cm Air intake Anchor bolts (4 pcs.) Min. 10 cm Air intake Concrete or equal t 10 Abou Ab ou t4 cm 0c m Fig. 5c Cushion rubber Fig. 5d 6 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 7 2-4. Outer Dimensions of Outdoor Unit A 85 70 Service valve on narrow tube side (Outer diameter ø6.35) 122 70 158 70 569 15 Service valve on wide tube side (Outer diameter ø9.52) 142 46 unit: mm Fig. 6a 2-5. Diagram of Outdoor Unit Installation Never install only a single indoor unit. Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit. (Use caution. Connecting any other model may result in operation failure and malfunction.) The dimensions indicated by in the figure below are spaces that are required in order to maintain performance. Install in a location where the dimensions indicated by are ensured, and where 2 or more faces of the unit are unobstructed. In principle, the top direction should be unobstructed. Indoor unit B Indoor unit A Ov er er Ov 5c cm 10 Power breaker m Service space Ensure 15cm of space if a drain hose is to be used. m 0c 4 er Ov Ov er 25 cm Access panel C B A Base (not provided) (concrete or similar material) Ground wire (not provided) Fasten with anchor bolts (not provided) (3/8" or M10, 4 locations) Fig. 6b 7 English A 790 285 310 336 608 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 8 3. Installation Process English 3-1. Embedding the Tubing and Wiring G Do not connect tubes to locations that are embedded. G Be sure to bind refrigerant tubing and inter-unit cables together with vinyl tape. G The power cable must be obtained on-site. (ø3.5: Less than 26 m) G Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring. G Securely seal the end of embedded tubing with vinyl tape in order to prevent dirt or moisture entry. G In order to prevent insulation breakdown and ground faults, do not allow the wire ends to contact rainwater, or be subject to dew condensation. 3-2. Drain Cap and Drain Elbow First refer to Section 2. Installation Site Selection. NOTE Outdoor unit The drain hole at the bottom of the outdoor unit was not plugged at the time of factory shipment. If necessary, plug the drain hole with the accessory drain cap or mount the accessory drain elbow before installing the outdoor unit. (Fig. 7) CAUTION When installing in a cold area where drainage water may freeze, do not attach the provided drain cap or drain elbow to the bottom plate of the unit. Accessory drain cap Accessory drain elbow Accessory drain cap Fig. 7 3-3. Use of the Flaring Method Deburring Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts. After Before 3-4. Flaring Procedure with a Flare Tool (1) Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 30 – 50 cm longer than the tubing length you estimate. (2) Remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 8) Fig. 8 8 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 9 NOTE Copper tubing When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9) (3) Remove the flare nut from the unit and be sure to mount it on the copper tube. Reamer (*Use “RIDGID” or equivalent.) Fig. 9 If the previous flare tool (clutch-type) is used: If the special R410A flare tool is used: NOTE A good flare should have the following characteristics: G inside surface is glossy and smooth. G edge is smooth. G tapered sides are of uniform length. 1.2 mm 0 – 0.5 mm Adjust so that the amount of tube protrusion is as shown in the figure. Fig. 10 3-5. Caution Before Connecting Tubes Tightly a) b) c) Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used. Flare nut Copper tubing Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 12) Flare tool Fig. 11 For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 13) Apply refrigerant lubricant here and here 3-6. Tubing Connections Fig. 12 a) Temporary connection: Screw in 3 – 5 rotations by hand. (Fig.14) b) To fasten the flare nuts, apply specified torque as: Table 4 Tube Dia. Tightening Torque 6.35 mm 14 – 18 N·m (140 – 180 kgf · cm) 9.52 mm 34 – 42 N·m (340 – 420 kgf · cm) 12.70 mm 49 – 61 N·m (490 – 610 kgf · cm) 15.88 mm 68 – 82 N·m (680 – 820 kgf · cm) Union Flare nut Fig. 13 Service valve on narrow tube side B A Service valve on wide tube side Fig. 14 9 Apply the provided labels to the indoor and outdoor unit tubing connectors to prevent errors in connections. English (4) Make a flare at the end of copper tube with a flare tool.* (Figs. 10 and 11) 08-245 CMRV1426EH_OU EN 9/22/08 English CAUTION 10:35 AM Page 10 Torque wrench Be sure to match refrigerant tubing and electric wiring between indoor and outdoor units. Spanner Indoor unit Outdoor unit Fig. 15 3-7. Insulation of Refrigerant Tubing IMPORTANT To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a minimum 8 mm. (Fig. 17) Insulation Fig. 16 Insulation 3-8. Taping the Tubes CAUTION After a tube has been insulated, never try to bend it into a narrow curve, as this may cause the tube to break or crack. Thickness: min. 8 mm Min. 8 mm Fig. 17 (1) At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing. Clamp (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 18) (3) Clamp the tubing bundle to wall, using 1 clamp approx. every 120 cm. Insulated tubes Fig. 18 NOTE Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing. Apply putty here 3-9. Finishing the Installation Tubing After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 19) 10 Fig. 19 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 11 4. Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. pressure in the system rises G operating current rises G cooling efficiency drops G moisture in the air may freeze and block capillary tubing G I G water may lead to corrosion of parts in the refrigerant system Air Purging with a Vacuum Pump (for Test Run) In order to protect the earth’s environment, be sure to use a vacuum pump to perform the air purge. (Never perform an air purge by using the refrigerant gas cylinder or other external gas, or by using the gas inside the outdoor unit.) Perform the air purge for tubes A and B. Use the same procedures for all tubes. CAUTION Service valve on narrow tube side B A With push-pin Hex wrench (nominal size 4mm, not provided) Charging hose (special for R410A) Vacuum pump Fig. 20 In order to prevent charging errors with the air conditioner that uses R410A, the screw diameter at the service valve charging port has been changed. When recharging or performing other servicing, use the special charging hose and manifold gauge. Stopper Spindle Screw diameter: 1/2 UNF 20 threads Cap tightening torque: 20 – 25 N·m (200 – 250 kgf·cm) (Tighten by hand, then use a wrench to turn.) Valve core (2) Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both narrow and wide tubes. Cap nut tightening torque: 7 – 11 N·m (70 – 110 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 30 .) (3) Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig. 20). CAUTION Manifold gauge (special for R410A) High-pressure valve Low-pressure Vacuum pump valve adapter Lo Hi (for preventing Leave the reverse flow) valve open. (special for Open R410A) Service valve on wide tube side (1) Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage. CAUTION English G <Structure of service valve on wide tube side> Before using the vacuum pump adapter, read the vacuum pump adapter manual, and use the adapter correctly. Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The “Hi” knob of the manifold valve must always be kept closed. 11 Fig. 21 G When using a hex wrench to open the spindle, an extremely small amount of refrigerant may leak. This does not indicate a problem. G Use a hex wrench of a type to which force can be easily applied. English 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 12 (4) With the “Lo” knob of the manifold valve open and high-pressure valve (“Hi”) closed completely, run the vacuum pump. Run the pump until the pressure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time required for evacuation: Table 5 Required time for evacuation when capacity of 100 liter/h vacuum pump is used 20 min. or more NOTE The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs. (5) With the vacuum pump still running, close the “Lo” knob of the manifold valve. Then stop the vacuum pump. Fully close the low-pressure valve and stop the vacuum pump. (Wait 1 – 2 minutes and check that the manifold gauge pointer does not return. If it does return, find and repair the leak, then apply the vacuum again.) (6) With a hex wrench, turn the valve stem on the narrow tube service valve counter-clockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again. CAUTION Be sure to completely insert the hex wrench before attempting to turn the valve. (7) With a standard screwdriver, turn the wide tube service valve stem counterclockwise to fully open the valve. (8) Turn the narrow tube service valve stem counterclockwise to fully open the valve. (9) Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure. Then, remove the hose. (10) Leak test all joints at the tubing (both indoor and outdoors) with liquid soap. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth. CAUTION If a CFC gas detector is used, use a special detector for HFC refrigerant (such as R410A and R134a). 12 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 13 (11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 20 N·m (200 kgf · cm)). This process is very important to prevent gas from leaking from the system. (12) Test run the air conditioner. (See page 18.) (13) While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps. English (14) If there is no leakage, stop the air conditioner. (15) Wipe off the soap on the tubing. This completes air purging with a vacuum pump and the air conditioner is ready for actual operation. I Pump Down In order to protect the earth’s environment, be sure to perform pump-down to recover refrigerant gas without releasing it into the atmosphere. G When relocating or disposing of the Air Conditioner, request this service from the dealer where the unit was purchased, or from an appropriate agent. Perform pump-down as described below. Close Charging port B What is pump-down? G Pump-down refers to recovering the refrigerant gas from the refrigerant cycle at the outdoor unit. This work must be performed during cooling operation. The refrigerant gas cannot be recovered during heating operation. G During winter, or if the temperature sensor prevents cooling operation, perform “forced cooling operation.” Narrow tube side Close A Fig. 22 Pump-down procedure (1) Fully close the spindles at the valves on the narrow tube side of tubes A and B. (Refer to Fig. 22.) (2) Connect the manifold gauge to the charging port at the valve on the wide tube side of tube B. Purge the air from the charging hose. (Refer to Fig. 23.) A (3) Perform cooling operation or forced cooling operation. When the pressure at the low-pressure side is 0.15 – 0.2 MPa (0.5 – 1 kg/cm2G), fully close the spindles at the valves on the wide tube side of tubes A and B, and immediately stop operation. (Refer to Fig. 23.) In the winter, the outdoor unit may stop after 5 – 10 minutes of operation. This is in order to protect the indoor unit heat exchanger from freezing and does not indicate a problem. (4) Disconnect the manifold gauge and the inter-unit tubes, and attach the caps and flare nuts. At this point, pumpdown is completed. (If the caps and flare nuts are not reattached, there is the danger of gas leakage.) (Refer to Fig. 24.) If pump-down is not possible If the Air Conditioner cannot be operated because of a malfunction or other cause, use a refrigerant recovery device to recover the refrigerant. B Wide tube side Manifold gauge Fig. 23 Cap After disconnecting the inter-unit tubes, attach the flare nuts with flare bonnets. Cap Fig. 24 13 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 14 5. Wiring Instructions 5-1. General Precautions on Wiring English (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line. (3) To prevent possible hazard due to insulation failure, the unit must be grounded. (4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged. (5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. (6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes. 5-2. Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation. Table 6 shows maximum wire lengths for control line and power line and fuse or circuit capacity. NOTE Refer to the wiring system diagram (Fig. 25) for the meaning of (A), (B), and (C) in Table 6. Table 6 Cross-Sectional Area (mm2) Model SAP-CMRV1426 Max. Power Line Length (m) (A) Max. Control Line Length (m) (B) (C) 3.5 1.0 26 25 14 Fuse or Circuit Capacity 15 A 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 15 WARNING G G G G Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.). Each wire must be firmly connected. No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part. Be sure to connect power wires correctly matching up numbers on terminals of the outdoor unit and respective indoor units A – B. G G G CAUTION G G Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit. Do not run wiring for antenna, signal, or power lines of television, radio, stereo, telephone, security system, or intercom any closer than 1 meter from the power cable and wires between the indoor and outdoor units. Electrical noise may affect the operation. 5-3. Wiring System Diagram OUTDOOR UNIT Grounding line (A) Terminal (8P) 7 Grounding line (B) (B) 6 (C) 2 5 1 4 3 UNIT B 4 3 8 Grounding line (B) (B) 3 (C) 2 2 1 1 UNIT A A INDOOR UNIT Terminal B 4 INDOOR UNIT Terminal Single-phase 220-240VAC 50Hz 220VAC 60Hz Power supply Fig. 25 15 To avoid the risk of electric shock, each air conditioner unit must be grounded. For the installation of a grounding device, please observe local electrical codes. Grounding is necessary, especially for units using inverter circuits, in order to release charged electricity and electrical noise caused by high tension. Otherwise, electrical shock may occur. Place a dedicated ground more than 2 meters away from other grounds and do not have it shared with other electric appliances. English G WARNING 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 16 5-4. How to Connect Wiring to the Terminal Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected. When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate. STRIP SIZE How to connect wiring to the terminal 7 mm (ACTUAL SIZE) Fig. 26 a) For Indoor Unit Solid wire 25 mm (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the wire about 7 mm. See the label (Fig. 26) near the terminal plate. (2) Using a screwdriver, loosen the terminal screw on the terminal plate. Loop Insulation (3) Insert the wire and tighten the terminal screw completely using a screwdriver. Fig. 27 Stranded wire b) For Outdoor Unit 10 mm English WARNING I For solid core wiring (or F-cable) Ring connector (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the solid wire about 25 mm. (Fig. 27) Fig. 28 (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate. (3) Using the pliers, bend the solid wire to form a loop suitable for the terminal screw. Twist wire ends (4) Shape the loop wire properly, place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver. I For stranded wiring Fig. 29 (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Figs. 28 and 29) Special washer (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate. Screw Ring connector (3) Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring connector. (Fig. 28) Wire Terminal plate Wire (4) Place the ring connector wire, and replace and tighten the removed terminal screw using a screwdriver. (Fig. 30) Fig. 30 16 Screw and special washer Ring connector 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 17 5-5. Wiring Instructions for the Outdoor Unit CAUTION G Be sure to correctly align inter-unit cables A and B. English Outdoor unit A Terminal board 1 2 3 4 5 6 7 8 Power: Single-phase, 220/240VAC 50HZ Power switch (not provided) Indoor unit A A is the indoor unit with refrigerant tubing that is 12 3 connected to service valve A (bottom) of the outdoor unit. Terminal board Inter-unit cables ø1.0 (not provided) Ground Power cable (not provided) (ø3.5 mm: Less than 26 m) Label A Indoor unit B B is the indoor unit with refrigerant tubing that is connected to service valve 1 2 3 B (top) of the outdoor unit. A Be sure to perform grounding. Attach a ground wire to either the outdoor unit or indoor unit. If there is a grounding terminal inside the room, use the grounding screw inside the indoor unit. Terminal board Inter-unit cables ø1.0 (not provided) Label B B Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring. The units will not function if the wiring connections are incorrect. Fig. 31 G G G G G Use a dedicated air conditioner circuit for power. To make connections to the outdoor unit, remove the inspection panel and tubing panel. Do not bring the inter-unit cables or power cable into contact with tubing or service valves. Use outdoor unit cable fasteners and fasten the inter-unit cables at the location where the cables are double-sheathed. Arrange the wiring so that the inter-unit cables are contained in the inspection panel and tubing panel, as shown in Fig. 31. 17 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 18 Regulations on wire size differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Make sure that the installation fully complies with all local and national regulations. Cabinet English (1) Remove access panel “C”. (Fig. 32) (2) Connect the inter-unit wiring and power line according to the drawing on the panel side. Access panel “C” (3) Be sure to size each wire allowing approx. 10 cm longer than the required length for wiring. Store excess wiring inside the cabinet. (4) When connections are completed, check that all connections are correct as shown in the wiring system diagram on panel side. (5) Be sure to ground the unit according to your local codes. 6. Test Run Fig. 32 Performing a test run G Refer to the test run procedures in the indoor unit installation manual. G Perform the test run separately for each connected indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring. G If the room temperature is 15°C or below, it may not be possible to check for tubing errors with cooling operation. If this occurs, perform heating operation for each unit individually, and check that warm air is discharged from each unit. If there is cold air mixed in with the warm air, check the tubing connections again. Checking tubing and wiring Perform the test run and check that operation is normal. If there is an error in tubing or wiring, the refrigerant may flow to indoor unit B when indoor unit A is operated (for example). CAUTION G Stop operation immediately if there is an error in tubing or wiring. Turn the power (breaker) OFF, and check whether the inter-unit cables are connected incorrectly, or whether the narrow tubes A and B are connected in reverse. Correct the connections. G If there is an error in tubing, pump-down must be performed. Be sure to perform pump-down. After making corrections, again purge the air from the tubes. 18 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 19 7. Connecting a Home Automation Device The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal. Also, refer to Section 9. Electric Wiring Diagram in the outdoor unit installation manual. The strength of the installation location is sufficient to support the Air Conditioner weight. The indoor and outdoor units are installed level and vertically. The power and voltage are as specified. Inter-unit cables are securely fastened to the terminal board. Inter-unit cables are securely fixed. The power cord and inter-unit cables are not connected anywhere along their paths. The ground wire is securely connected. An air purge of the refrigerant circuit has been conducted. A leak test of the tubing connections has been performed. Thermal insulation has been applied to the tubing connections. Drain connections are secure and water drains properly. Putty has been used to close the hole in the wall. All service valves are fully open. Remote controller signals are being positively received. 9. Electric Wiring Diagram Indoor Unit SAP-KMRV74/94/124EH EVAPORATOR TO OUTDOOR UNIT YEL/GRN TERMINAL BASE BLK 1 WHT 2 RED 3 4 1 2 3 4 5 AC1 AC2 SI 1 1 2 2 1 3 3 2 FLAP 3 5P(WHT) LAMP 4 4 4 10P(WHT) 5 5 6 6 5 7 7 8 8 9 9 10 10 RED WHT WHT WHT WHT WHT WHT WHT WHT WHT 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 IND LAMP ASSY CONNECTOR RED 1 1 PNK 2 2 BLU 3 3 FLAP BRN 4 4 YEL 5 5 FLAP MOTOR CONTROLLER RED FM FAN MOTOR BLK WHT YEL BLU 1 2 3 4 5 6 1 ROOM/COIL 2 4P(WHT) 3 DCM 4 6P(BLU) 5 6 1 2 3 4 1 2 3 4 1 1 ION 2 2 3P(WHT) 3 3 1 1 WHT 2 2 RED 3 3 BLK CONNECTOR WHT RED BLK BLK BLK HA JEM-A 4P(WHT) 1 2 3 4 ROOM THERMISTOR BLK BLK BLK BLK COIL THERMISTOR 1 2 3 4 1 2 3 4 ION TERMINAL Fig. 33a ION ASSY 8FA-2-5257-72600-1 19 English 8. Installation Check Sheet 08-245 CMRV1426EH_OU EN 9/22/08 10:35 AM Page 20 SAP-KRV96/126EHDS SAP-KMRV76/96/126EH 3 GRN/YEL 2 + + + + 7 5 3 1 UV UNIT 1 2 1 2 THERMISTOR (HUM) WHT BLK PANEL SW WHT BLU BLU BLU BLU (WHT) IND LAMP ASSY 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 SW ASSY 1 2 3 4 5 1 2 3 4 5 (BLU) BLK BLK 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 LAMP (WHT) BLK WHT YEL BLU THERMISTOR (ROOM) THERMISTOR (COIL) 1 2 1 2 1 2 1 2 HUM SW2 (RED) (BLU) 8FA-2-5250-29700-2 Fig. 33b RED 1 2 3 4 5 6 1 2 3 4 5 6 FM BLK WHT YEL BLU DCM (BLU) 1 2 3 4 5 6 1 2 3 4 5 6 DC FAN MOTOR RED 1 2 1 2 UV (RED) (WHT) BLK BLK ORG ORG 1 2 3 4 5 1 2 3 4 5 SW1 (WHT) 3 DC OUT 2 (WHT) 1 BLK BLK ORG ORG RED COIL THERMISTOR BLK CONTROLLER 1 1 ROOM/COIL/UV 2 2 6P(WHT) 3 3 4 4 HA 5 5 JEM-A 6 6 4P(WHT) 1 2 3 4 WHT GRY GRY GRY GRY RED BLK (RED) WHT GRY GRY GRY GRY GRY GRY GRY GRY GRY (WHT) PANEL MOTOR PANEL (WHT) 1 2 3 4 5 1 2 3 4 5 E UV ASSY ROOM THERMISTOR FLAP3 GRN/YEL FLAP MOTOR (LOWER) HA JEM-A (WHT) 1 2 3 4 1 2 3 DCM 4 6P(BLU) 5 6 1 2 3 4 5 1 2 3 4 5 BLK WHT YEL BLU 1 2 3 4 5 6 RED BLK 1 2 3 4 1 2 3 4 ROOM /COIL (WHT) (WHT) (WHT) FLAP1 (WHT) 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 WHT GRY GRY GRY GRY WHT BLU BLU BLU BLU 7 5 ELEC-JB1 3 (WHT) 1 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 (WHT) (RED) RED YEL ORG RED BRN RED WHT WHT WHT WHT WHT WHT WHT WHT FLAP2 1 2 3 4 5 6 7 8 9 + + EARTH PLATE 1 2 3 4 5 1 2 3 4 5 8FA-2-5250-07400-1 Fig. 33c DEF RV (2P) CONNECTOR WHT BLU BLU w w RV1 RV0 w L2 w L1 w E-2 w E-1 1 COMP 2 GRN/YEL GRN/YEL w w DEF1 DEF0 GRN/YEL w w E ACIN1 w ACIN2 25A BLK WHT CONTROLLER 1 2 3 4 5 1 2 3 4 5 BLK WHT BLK 3 4 5 6 WHT 7 8 TO INDOOR UNIT 2 BLK REACTANCE RED 1 2 3 4 5 1 2 3 4 5 1 L BLU ORG RED YEL BLK GRY S1-B w ORG RED YEL BLK GRY (5P) CONNECTOR ORG RED YEL BLK GRY 1 2 3 4 5 1 2 3 4 5 BLU WHT (5P) CONNECTOR BLK RED BLU YEL WHT 1 2 3 4 5 6 7 1 2 3 4 5 6 7 MV0 1 2 3 4 5 MV1 1 2 3 4 5 BLK RED BLU YEL RED(PNK) WHT BLU CN04 DCFM 1 2 3 4 5 6 7 ORG RED YEL BLK GRY W w (7P) CONNECTOR V w WHT U w RED N w OLR1 S1-A w B INDOOR A INDOOR UNIT UNIT TERMINAL PLATE w OLR0 POWER SUPPLY 1 2 3 4 B-TH 2 1 2 1 WHT WHT BLK BLK 2 1 2 1 BLK BLK 2 1 2 1 1 2 3 4 1 2 3 4 REACTANCE (2P) CONNECTOR WHT WHT WHT COIL 4WAY VALVE (2P) CONNECTOR BLK BLU BLU YEL YEL YEL YEL BN THERMISTOR BW THERMISTOR (4P) CONNECTOR BLU COIL DEFROST VALVE YEL YEL YEL YEL YEL YEL YEL YEL AN THERMISTOR 1 2 3 4 A-TH (3P) CONNECTOR 1 1 RED(PNK) C 2 2 WHT CM R 3 3 BLU S FERRITE WHT CORE GRN/YEL 1 2 3 4 1 2 3 4 YEL YEL YEL YEL OUTDOOR THERMISTOR AW THERMISTOR COIL THERMISTOR 1 2 3 4 COIL/OUTDOOR (OLR) OVERLOAD RELAY COMPRESSOR MOTOR (4P) CONNECTOR RED 1 2 3 4 1 2 3 4 YEL YEL BLK BLK (4P) CONNECTOR WHT BLK BLK WHT 1 1 BLK 2 2 BLK (2P) CONNECTOR RED WHT 1 1 WHT WHT 2 2 WHT (2P) CONNECTOR YEL YEL BLK BLK Electric wiring diagram for 2-room multi outdoor unit (CMRV1426EH) COMPRESSOR THERMISTOR English 1 + FLAP MOTOR (UPPER) SI FAN MOTOR FM + GRN/YEL EVAPORATOR SI-2 1 2 3 4 LAMP 9P(WHT) 5 6 7 8 CONTROLLER 9 CONNECTOR 3 + TERMINAL BASE AC IN AC IN-2 1 2 FLAP 3 5P(WHT) 4 5 2 FLAP1 1 2 3 4 5 WHT WHT RED IND LAMP ASSY RED PNK BLU BRN YEL 1 1 2 3 4 5 1 2 3 4 5 FLAP 1 2 3 4 5 BLK TO OUTDOOR UNIT 1 2 3 4 5 TERMINAL BASE FERRITE CORE FLAP MOTOR TO OUTDOOR UNIT EVAPORATOR GND 1 2 3 4 5 1 2 3 4 5 FM MV1 MV0 MAGNETIC COIL MAGNETIC COIL FAN MOTOR 8FA-2-5257-56900-2 Fig. 34 Meaning of Abbreviations ABBREV. WARNING To prevent electric shock, do not inspect or repair until the Power Lamp on the P.C.Board is turned off. 20 MEANING 1 BLK BLACK 2 BLU BLUE 3 BRN BROWN 4 GRN/YEL GREEN/YELLOW 5 GRY GREY 6 ORG ORANGE 7 PNK PINK 8 RED RED 9 VLT VIOLET 10 WHT WHITE 11 YEL YELLOW APPENDIX B INSTALLATION INSTRUCTIONS SAP-CMRV1926EH SAP-CMRV1936EH SAP-CMRV2446EH SAP-CMRV3146EH (II-852-6-4190-442-00-2) NOTE The specifications of SAP-KRV96EHDSA are the same as those of SAP-KRV96EHDS described in the Installation Instruction. A-2 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page a For Outdoor Unit INSTALLATION INSTRUCTIONS – Inverter Multi Split System Air Conditioner – COOL / DRY/ HEAT Model This air conditioner uses the new refrigerant R410A. Model Combinations Page Combine indoor and outdoor units only as listed below. IMPORTANT! Please Read Before Starting .................................. 2 2. SAP-KRV96EHDS SAP-KRV126EHDS SAP-KRV184EH SAP-KRV244EH SAP-KRV186EH SAP-KRV246EH Combine indoor and outdoor units only as listed in the combination tables for 2-room, 3-room or 4-room outdoor unit as shown in its respective manual. Power Source: 50 Hz, single-phase, 220 – 240 VAC Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A. AIR PURGING................................................... 16 I Air Purging with a Vacuum Pump (for Test Run) I Pump Down 6. TEST RUN......................................................... 23 7. CONNECTING A HOME AUTOMATION DEVICE ............................................................. 24 8. INSTALLATION CHECK SHEET ...................... 24 9. ELECTRIC WIRING DIAGRAM......................... 24 85264190442002 © SANYO 2008 Indoor unit B Indoor unit A Indoor unit C Outdoor unit Indoor unit D NOTE The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing. SANYO Electric Co., Ltd. Osaka, Japan EÏÏËÓÈο WIRING INSTRUCTIONS ................................. 19 5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Diameter 5-3. Wiring System Diagram 5-4. How to Connect Wiring to the Terminal 5-5. Wiring Instructions for the Outdoor Unit Combination example Português 5. SAP-CMRV3146EH Italiano INSTALLATION PROCESS .............................. 13 3-1. Embedding the Tubing and Wiring 3-2. Drain Cap and Drain Elbow 3-3. Use of the Flaring Method 3-4. Flaring Procedure with a Flare Tool 3-5. Caution Before Connecting Tubes Tightly 3-6. Tubing Connections 3-7. Insulation of Refrigerant Tubing 3-8. Taping the Tubes 3-9. Finishing the Installation SAP-CMRV2446EH Deutsch 4. INSTALLATION SITE SELECTION ................... 4 2-1. Indoor Unit 2-2. Connecting Indoor Units 2-3. Outdoor Unit 2-4. Outer Dimensions of Outdoor Unit 2-5. Diagram of Outdoor Unit Installation SAP-KMRV76EH SAP-KMRV96EH SAP-KMRV126EH SAP-CMRV1936EH Français 3. GENERAL .......................................................... 3 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation Outdoor Unit SAP-CMRV1926EH Español 1. Indoor Unit SAP-KMRV74EH SAP-KMRV94EH SAP-KMRV124EH English Contents English 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 2 IMPORTANT! Please Read Before Starting when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. When Installing… …In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support. …In a Room Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors. …In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration. …In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. …In a Snowy Area (for Heat Pump-type Systems) • Position the outdoor unit in a protected location For safe installation and trouble-free operation, you must: G Carefully read this instruction booklet before beginning. G Follow each installation or repair step exactly as shown. G Observe all local, state, and national electrical codes. G Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or unsafe practice which WARNING can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which CAUTION can result in personal injury or product or property damage. where snow will not blow into it. • Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. If Necessary, Get Help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions. When Connecting Refrigerant Tubing • Use the flare method for connecting tubing. • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. • Check carefully for leaks before starting the test run. In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. When Servicing SPECIAL PRECAUTIONS WARNING • • • • • • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. • Keep your fingers and clothing away from any moving parts. • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur. CAUTION Others • Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. • Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas. • Do not install only a single indoor unit. When Transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees 2 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 3 1. General 1-1. Tools Required for Installation (not supplied) 1. Standard screwdriver 2. Phillips head screwdriver 3. Knife or wire stripper 4. Tape measure Carpenter’s level Sabre saw or key hole saw Hacksaw Core bits Hammer Drill Tube cutter Tube flaring tool Torque wrench Adjustable wrench Reamer (for deburring) Vacuum pump (For R410A) Manifold valve English 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. If the electric wiring diagram does not appear in this manual, please check for the diagram on the indoor unit. 1-2. Accessories Supplied with Unit Table 1 Parts Reducer (ø9.52 ø12.70) Labels for inter-unit cable and tube Figure Q’ty Parts 1 Reducer (ø12.70 ø9.52) CMRV1926 CMRV1936 A B C D Figure Q’ty CMRV2446 1 CMRV3146 2 4 each Cushion rubber 4 Parts Figure Q’ty Drain elbow 1 Drain cap 5 Packed in the outdoor unit. 1-3. Optional Copper Tubing Kit 2. Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 8 mm. 3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 5. Wiring Instructions for details. 1-4. Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source, you will need: 1. Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2. CAUTION Cut each tube to the appropriate lengths +30 cm to 40 cm to dampen vibration between units. Table 2 Narrow Tube Wide Tube Model Outer Dia. Thickness Outer Dia. Thickness KMRV74/76 6.35 mm 0.8 mm 9.52 mm 0.8 mm KMRV94/96 6.35 mm 0.8 mm 9.52 mm 0.8 mm KMRV124/126 6.35 mm 0.8 mm 9.52 mm 0.8 mm KRV184/186 6.35 mm 0.8 mm 12.70 mm 0.8 mm KRV244/246 6.35 mm 0.8 mm 15.88 mm 1.0 mm KRV96/126 6.35 mm 0.8 mm 9.52 mm 0.8 mm 3 Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations. 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 4 1-5. Additional Materials Required for Installation English 1. 2. Refrigeration (armored) tape Insulated staples or clamps for connecting wire (See local codes) Putty Refrigeration lubricant Clamps or saddles to secure refrigerant tubing 3. 4. 5. Indoor unit 2. Installation Site Selection 2-1. Indoor Unit WARNING To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow. Drain hose AVOID: Outside drainage G direct sunlight. G nearby heat sources that may affect performance of the unit. G areas where leakage of flammable gas may be expected. Fig. 1 G placing or allowing any obstructions near the Air Conditioner inlet or outlet. G installing in rooms that contain instant-on (rapid-start) fluorescent lamps. (These may prevent the Air Conditioner from receiving signals.) G places where large amounts of oil mist exist. G installing in locations where there are devices that generate high-frequency emissions. Fig. 2 INDOOR UNIT (1) Tubing length (L1) Elevation difference (H1) select an appropriate position from which every corner of the room can be uniformly cooled. (High on a wall is best.) G select a location that will hold the weight of the unit. G select a location where tubing and drain hose have the shortest run to the outside. (Fig. 1) G allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 2) G install the unit within the maximum elevation difference (H1, H2, H3, H4) above or below the outdoor unit and within a total tubing length (L1+L2, L1+L2+L3, L1+L2+L3+L4) from the outdoor unit as detailed in Table 3 and Fig. 3a. 5 cm min. Front View DO: G 15 cm min. 5 cm min. INDOOR UNIT (2) L2 OUTDOOR UNIT H2 L3 H4 INDOOR UNIT (4) L4 INDOOR UNIT (3) H3 Fig. 3a CAUTION Indoor unit For stable operation of the air conditioner, do not install wall-mounted type indoor Minimum height units less than 1.5 m from from floor level floor level. 1.5 m Floor level Fig. 3b 4 Wall 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 5 install the indoor unit more than 1 meter away from any antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation. G install in a sturdy manner to avoid increased operating noise. Table 3 Max. Allowable Tubing Length per unit (m) Model Max. Allowable Total Tubing Length at shipment (L1+L2) or (L1+L2+L3) or (L1+L2+L3+L4) (m) Limit of Total Tubing Length (L1+L2) or (L1+L2+L3) or (L1+L2+L3+L4) (m) Limit of Elevation Difference (H1, H2, H3, H4) (m) Required Amount of Additional Refrigerant (g/m)* CMRV1926 25 45 (L1+L2) 45 (L1+L2) 15 – CMRV1936 25 45 (L1+L2+L3) 45 (L1+L2+L3) 15 – CMRV2446 25 45 (L1+L2+L3+L4) 60 (L1+L2+L3+L4) 15 20 CMRV3146 30 45 (L1+L2+L3+L4) 70 (L1+L2+L3+L4) 15 20 * If total tubing length becomes 45 to 60 m (max.) or 45 to 70 m (max.), charge additional refrigerant (R410A) by 20 g/m. No additional charge of compressor oil is necessary. 2-2. Connecting Indoor Units (1) Connecting indoor unit for SAP-CMRV1926 (A) Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) B ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) A ø9.52 ø6.35 Fig. 4 (B) Outdoor unit Indoor unit ø9.52 B ø9.52 ø6.35 ø12.70 (SAP-KRV184EH) (SAP-KRV186EH) A ø9.52 Flare ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø6.35 Union ø12.70 A joint for connecting tubes of different sizes (ø9.52 ø12.70) Supplied Reducer Fig. 4a unit: mm 5 English G 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 6 (2) Connecting indoor unit for SAP-CMRV1936 (A) Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) English C ø9.52 ø6.35 B ø9.52 ø6.35 A ø9.52 ø6.35 Fig. 4b (B) Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) C ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) B ø9.52 ø6.35 ø12.70 (SAP-KRV184EH) (SAP-KRV186EH) A ø9.52 Flare ø9.52 ø6.35 Union ø12.70 A joint for connecting tubes of different sizes (ø9.52 ø12.70) Supplied Reducer Fig. 4c (3) Connecting indoor unit for SAP-CMRV2446 (A) Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) D ø9.52 ø6.35 C ø9.52 ø6.35 ø9.52 B ø9.52 ø6.35 ø9.52 A ø12.70 ø6.35 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) Flare ø12.70 Union ø9.52 (ø12.70 ø9.52) Supplied Reducer Fig. 4d unit: mm 6 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 7 (B) Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) D ø9.52 ø6.35 ø9.52 ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) B ø9.52 ø6.35 ø12.70 (SAP-KRV184EH) (SAP-KRV186EH) A ø12.70 ø6.35 Fig. 4e (C) Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) D ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) C ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) B ø9.52 ø6.35 ø15.88 (SAP-KRV244EH) (SAP-KRV246EH) A ø12.70 ø6.35 Flare ø12.70 Union ø15.88 (ø12.70 ø15.88) Locally purchased Fig. 4f (D) Outdoor unit Indoor unit ø9.52 D ø9.52 ø6.35 ø9.52 C ø9.52 ø6.35 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø12.70 (SAP-KRV184EH) (SAP-KRV186EH) B ø9.52 ø6.35 ø15.88 (SAP-KRV244EH) (SAP-KRV246EH) A ø12.70 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø6.35 Flare ø12.70 Union ø15.88 Flare ø9.52 Union ø12.70 (ø12.70 ø15.88) Locally purchased (ø9.52 ø12.70) Locally purchased Fig. 4g unit: mm 7 English (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) C 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 8 (4) Connecting indoor unit for SAP-CMRV3146 (A) Outdoor unit Indoor unit ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) D English ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) C ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) B ø12.70 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) A ø12.70 ø6.35 Flare ø12.70 Union ø9.52 (ø12.70 ø9.52) Supplied Reducer Fig. 4h (B) Outdoor unit Indoor unit ø9.52 D ø9.52 ø6.35 ø9.52 C ø9.52 ø6.35 ø9.52 B ø12.70 ø6.35 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø12.70 (SAP-KRV184EH) (SAP-KRV186EH) A ø12.70 ø6.35 Flare ø12.70 Union ø9.52 (ø12.70 ø9.52) Supplied Reducer Fig. 4i (C) Outdoor unit Indoor unit ø9.52 D ø9.52 ø6.35 ø9.52 C ø9.52 ø6.35 (SAP-KRV184EH) (SAP-KRV186EH) ø6.35 ø12.70 A ø12.70 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø12.70 B ø12.70 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) (SAP-KRV184EH) (SAP-KRV186EH) ø6.35 Fig. 4j unit: mm 8 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 9 (D) Outdoor unit Indoor unit ø9.52 ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) C ø9.52 ø6.35 ø9.52 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) B ø12.70 ø6.35 ø15.88 (SAP-KRV244EH) (SAP-KRV246EH) A ø12.70 ø6.35 Flare ø12.70 Union ø15.88 Flare ø12.70 Union ø9.52 (ø12.70 ø15.88) Locally purchased (ø12.70 ø9.52) Supplied Reducer Fig. 4k (E) Outdoor unit Indoor unit ø9.52 D ø9.52 ø6.35 ø9.52 C ø9.52 ø6.35 (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) ø12.70 (SAP-KRV184EH) (SAP-KRV186EH) B ø12.70 ø6.35 ø15.88 (SAP-KRV244EH) (SAP-KRV246EH) A ø12.70 ø6.35 Flare ø12.70 Union ø15.88 (ø12.70 ø15.88) Locally purchased Fig. 4l unit: mm 9 English (SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS) D 2:39 PM Page 10 2-3. Outdoor Unit NO AVOID: G heat sources, exhaust fans, etc. (Fig. 5a) G damp, humid or uneven locations. Hot air Heat source Outdoor unit English DO: G position the outdoor unit in a protected location where snow will not blow into it. G choose a place as cool as possible. G choose a place that is well ventilated. G install in a location where at least two sides are unobstructed, so that the flow of air at the intake port or exhaust port is not blocked, and so that sufficient space is ensured for maintenance to be carried out without trouble. In general the top also must be unobstructed. (Fig. 5b) G Fig. 5a Obstacle above Air intake Min. provide a solid base (level concrete pad, concrete block, 15 × 40 cm beams or equal), a minimum of 15 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 5c) G install cushion rubber under unit’s feet to reduce vibration and noise. (Fig. 5d) G use lug bolts or equal to bolt down unit, reducing vibration and noise. G install in a location where no antenna of a television or radio exists within 3 meters. Exhaust fan 10 cm Min. 20 cm Air discharge Valve side Min. 25 cm Min. 2m Min. 50 cm Ground Fig. 5b Min. 2m Obstacle 10/14/08 Air discharge 08-253 CMRV3146EH_OU EN Min. 20 cm Air intake Anchor bolts (4 pcs.) Min. 15 cm Air intake Concrete or equal Ab t 15 ou Abou t4 cm 0c m Fig. 5c Cushion rubber Fig. 5d 10 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 11 2-4. Outer Dimensions of Outdoor Unit (1) SAP-CMRV1926 A 136 12 85 113 75 18 150 72 740 Service valve on narrow tube side (Outer diameter ø6.35) Service valve on wide tube side (Outer diameter ø9.52) 51 Fig. 6a English A 900 320 345 369 608 114 (2) SAP-CMRV1936 A 136 12 85 Service valve on narrow tube side (Outer diameter ø6.35) 740 A 900 320 345 369 608 113 75 70 18 150 72 70 Service valve on wide tube side (Outer diameter ø9.52) 51 Fig. 6b 114 (3) SAP-CMRV2446 A 136 12 85 Service valve on narrow tube side (Outer diameter ø6.35) Service valve on wide tube side (Outer diameter ø9.52) 113 75 70 70 150 72 70 70 18 740 A 900 320 345 369 608 51 Fig. 6c Service valve on wide tube side (Outer diameter ø12.70) 114 (4) SAP-CMRV3146 A 136 12 Service valve on narrow tube side (Outer diameter ø6.35) Service valve on wide tube side (Outer diameter ø9.52) 113 75 70 70 150 73 70 70 890 18 A 85 900 320 345 369 608 51 Fig. 6d 11 114 Service valve on wide tube side (Outer diameter ø12.70) unit: mm 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 12 2-5. Diagram of Outdoor Unit Installation Never install only a single indoor unit. English Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit. (Use caution. Connecting any other model may result in operation failure and malfunction.) Indoor unit D The dimensions indicated by in the figure below are spaces that are required in order to maintain performance. Install in a location where the dimensions indicated by are ensured, and where 2 or more faces of the unit are unobstructed. In principle, the top direction should be unobstructed. er Ov Indoor unit C Indoor unit B cm 20 Indoor unit A Service space Ov er 10 Power breaker cm Ov er Ensure 15cm of space if a drain hose is to be used. m 0c r5 e Ov 25 cm Access panel C D C B A Base (not provided) (concrete or similar material) Ground wire (not provided) Fasten with anchor bolts (not provided) (3/8" or M10, 4 locations) Fig. 6e 12 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 13 3. Installation Process 3-1. Embedding the Tubing and Wiring Do not connect tubes to locations that are embedded. G Be sure to bind refrigerant tubing and inter-unit cables together with vinyl tape. G The power cable must be obtained on-site. (ø3.5: Less than 26 m) G Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring. G Securely seal the end of embedded tubing with vinyl tape in order to prevent dirt or moisture entry. G In order to prevent insulation breakdown and ground faults, do not allow the wire ends to contact rainwater, or be subject to dew condensation. English G 3-2. Drain Cap and Drain Elbow First refer to Section 2. Installation Site Selection. NOTE Outdoor unit The drain hole at the bottom of the outdoor unit was not plugged at the time of factory shipment. If necessary, plug the drain hole with the accessory drain cap or mount the accessory drain elbow before installing the outdoor unit. (Fig. 7) CAUTION Accessory drain cap When installing in a cold area where drainage water may freeze, do not attach the provided drain cap or drain elbow to the bottom plate of the unit. Accessory drain elbow Accessory drain cap Fig. 7 3-3. Use of the Flaring Method Deburring Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts. After Before 3-4. Flaring Procedure with a Flare Tool (1) Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 30 – 50 cm longer than the tubing length you estimate. (2) Remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 8) Fig. 8 13 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 14 NOTE Copper tubing When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9) English (3) Remove the flare nut from the unit and be sure to mount it on the copper tube. Reamer (4) Make a flare at the end of copper tube with a flare tool.* (Figs. 10 and 11) Fig. 9 (*Use “RIDGID” or equivalent.) If the previous flare tool (clutch-type) is used: If the special R410A flare tool is used: NOTE A good flare should have the following characteristics: G inside surface is glossy and smooth. G edge is smooth. G tapered sides are of uniform length. 1.2 mm 0 – 0.5 mm Adjust so that the amount of tube protrusion is as shown in the figure. Fig. 10 3-5. Caution Before Connecting Tubes Tightly a) b) c) Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used. Flare nut Copper tubing Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 12) Flare tool Fig. 11 For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 13) Apply refrigerant lubricant here and here 3-6. Tubing Connections Fig. 12 a) Temporary connection: Screw in 3 – 5 rotations by hand. (Fig.14) b) To fasten the flare nuts, apply specified torque as: Table 4 Tube Dia. Tightening Torque 6.35 mm 14 – 18 N·m (140 – 180 kgf · cm) 9.52 mm 34 – 42 N·m (340 – 420 kgf · cm) 12.70 mm 49 – 61 N·m (490 – 610 kgf · cm) 15.88 mm 68 – 82 N·m (680 – 820 kgf · cm) Union Flare nut Fig. 13 Service valve on narrow tube side Service valve on wide tube side Fig. 14 14 D C B A Apply the provided labels to the indoor and outdoor unit tubing connectors to prevent errors in connections. 08-253 CMRV3146EH_OU EN 10/14/08 CAUTION 2:39 PM Page 15 Torque wrench Be sure to match refrigerant tubing and electric wiring between indoor and outdoor units. Spanner Indoor unit English Outdoor unit Fig. 15 3-7. Insulation of Refrigerant Tubing IMPORTANT To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a minimum 8 mm. (Fig. 17) Insulation Fig. 16 Insulation 3-8. Taping the Tubes CAUTION After a tube has been insulated, never try to bend it into a narrow curve, as this may cause the tube to break or crack. Thickness: min. 8 mm Min. 8 mm Fig. 17 (1) At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing. Clamp (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 18) (3) Clamp the tubing bundle to wall, using 1 clamp approx. every 120 cm. Insulated tubes Fig. 18 NOTE Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing. Apply putty here 3-9. Finishing the Installation Tubing After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 19) 15 Fig. 19 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 16 4. Air Purging English Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. G pressure in the system rises G operating current rises G cooling efficiency drops G moisture in the air may freeze and block capillary tubing G water may lead to corrosion of parts in the refrigerant system I G Service valve on narrow tube side D C B A Service valve on wide tube side Air Purging with a Vacuum Pump (for Test Run) With push-pin Manifold gauge (special for R410A) High-pressure valve Low-pressure Vacuum pump valve adapter Lo Hi (for preventing Leave the reverse flow) valve open. (special for Open R410A) Hex wrench (nominal size 4mm, not provided) In order to protect the earth’s environment, be sure to use a vacuum pump to perform the air purge. (Never perform an air purge by using the refrigerant gas cylinder or other external gas, or by using the gas inside the outdoor unit.) Perform the air purge for tubes A, B, C and D. Use the same procedures for all tubes. CAUTION In order to prevent charging errors with the air conditioner that uses R410A, the screw diameter at the service valve charging port has been changed. When recharging or performing other servicing, use the special charging hose and manifold gauge. Stopper Spindle Screw diameter: 1/2 UNF 20 threads Cap tightening torque: 20 – 25 N·m (200 – 250 kgf·cm) (Tighten by hand, then use a wrench to turn.) Valve core (2) Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both narrow and wide tubes. Cap nut tightening torque: 7 – 11 N·m (70 – 110 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 30 .) (3) Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig. 20). CAUTION Vacuum pump Fig. 20 (1) Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage. CAUTION Charging hose (special for R410A) <Structure of service valve on wide tube side> Before using the vacuum pump adapter, read the vacuum pump adapter manual, and use the adapter correctly. Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The “Hi” knob of the manifold valve must always be kept closed. 16 Fig. 21 G When using a hex wrench to open the spindle, an extremely small amount of refrigerant may leak. This does not indicate a problem. G Use a hex wrench of a type to which force can be easily applied. 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 17 English (4) With the “Lo” knob of the manifold valve open and high-pressure valve (“Hi”) closed completely, run the vacuum pump. Run the pump until the pressure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time required for evacuation: Table 5 Required time for evacuation when capacity of 100 liter/h vacuum pump is used 20 min. or more NOTE The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs. (5) With the vacuum pump still running, close the “Lo” knob of the manifold valve. Then stop the vacuum pump. Fully close the low-pressure valve and stop the vacuum pump. (Wait 1 – 2 minutes and check that the manifold gauge pointer does not return. If it does return, find and repair the leak, then apply the vacuum again.) (6) With a hex wrench, turn the valve stem on the narrow tube service valve counter-clockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again. CAUTION Be sure to completely insert the hex wrench before attempting to turn the valve. (7) With a standard screwdriver, turn the wide tube service valve stem counterclockwise to fully open the valve. (8) Turn the narrow tube service valve stem counterclockwise to fully open the valve. (9) Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure. Then, remove the hose. (10) Leak test all joints at the tubing (both indoor and outdoors) with liquid soap. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth. CAUTION If a CFC gas detector is used, use a special detector for HFC refrigerant (such as R410A and R134a). 17 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 18 (11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 20 N·m (200 kgf · cm)). This process is very important to prevent gas from leaking from the system. (12) Test run the air conditioner. (See page 23.) English (13) While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps. (14) If there is no leakage, stop the air conditioner. (15) Wipe off the soap on the tubing. This completes air purging with a vacuum pump and the air conditioner is ready for actual operation. I Pump Down In order to protect the earth’s environment, be sure to perform pump-down to recover refrigerant gas without releasing it into the atmosphere. G Close When relocating or disposing of the Air Conditioner, request this service from the dealer where the unit was purchased, or from an appropriate agent. Perform pump-down as described below. D Narrow tube side Close C What is pump-down? G Pump-down refers to recovering the refrigerant gas from the refrigerant cycle at the outdoor unit. This work must be performed during cooling operation. The refrigerant gas cannot be recovered during heating operation. G During winter, or if the temperature sensor prevents cooling operation, perform “forced cooling operation.” Close B Charging port Close A Fig. 22 Pump-down procedure D (1) Fully close the spindles at the valves on the narrow tube side of tubes A, B, C and D. (Refer to Fig. 22.) C (2) Connect the manifold gauge to the charging port at the valve on the wide tube side of tube D. Purge the air from the charging hose. (Refer to Fig. 23.) (3) Perform cooling operation or forced cooling operation. When the pressure at the low-pressure side is 0.15 – 0.2 MPa (0.5 – 1 kg/cm2G), fully close the spindles at the valves on the wide tube side of tubes A, B, C and D, and immediately stop operation. (Refer to Fig. 23.) In the winter, the outdoor unit may stop after 5 - 10 minutes of operation. This is in order to protect the indoor unit heat exchanger from freezing and does not indicate a problem. (4) Disconnect the manifold gauge and the inter-unit tubes, and attach the caps and flare nuts. At this point, pumpdown is completed. (If the caps and flare nuts are not reattached, there is the danger of gas leakage.) (Refer to Fig. 24.) Wide tube side B A Manifold gauge Fig. 23 Cap Cap After disconnecting the inter-unit tubes, attach the flare nuts with flare bonnets. Cap Cap If pump-down is not possible If the Air Conditioner cannot be operated because of a malfunction or other cause, use a refrigerant recovery device to recover the refrigerant. Fig. 24 18 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 19 5. Wiring Instructions 5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. English (2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line. (3) To prevent possible hazard due to insulation failure, the unit must be grounded. (4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged. (5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. (6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes. 5-2. Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation. Table 6 shows maximum wire lengths for control line and power line and fuse or circuit capacity. NOTE Refer to the wiring system diagram (Figs. 25a, 25b or 25c) for the meaning of (A), (B) and (C) in Table 6. Table 6 Max. Power Line Length (m) (A) Max. Control Line Length (m) (B) (C) 3.5 1.0 SAP-CMRV1926 26 25 20 A SAP-CMRV1936 26 25 20 A SAP-CMRV2446 26 25 20 A SAP-CMRV3146 26 30 20 A Cross-Sectional Area (mm2) Model 19 Fuse or Circuit Capacity 10/14/08 2:39 PM Page 20 WARNING G G CAUTION G G Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit. Do not run wiring for antenna, signal, or power lines of television, radio, stereo, telephone, security system, or intercom any closer than 1 meter from the power cable and wires between the indoor and outdoor units. Electrical noise may affect the operation. 2 indoor units with SAP-CMRV1926 OUTDOOR UNIT (A) Grounding line Terminal (8P) Single-phase 220-240VAC 50Hz 220VAC 60Hz Power supply B A 5-3. Wiring System Diagram 4 4 3 8 7 Grounding line (B) (B) 6 (C) 2 5 1 4 3 UNIT B G G To avoid the risk of electric shock, each air conditioner unit must be grounded. For the installation of a grounding device, please observe local electrical codes. Grounding is necessary, especially for units using inverter circuits, in order to release charged electricity and electrical noise caused by high tension. Otherwise, electrical shock may occur. Place a dedicated ground more than 2 meters away from other grounds and do not have it shared with other electric appliances. INDOOR UNIT Terminal G Grounding line (B) (B) 3 (C) 2 2 1 1 Fig. 25a 1 3 4 Grounding line (B) (B) 3 (C) 2 2 1 1 Terminal (2P) C 1 (B) 4 (C) 3 8 (B) 2 7 UNIT D 1 (B) B 9 4 3 Grounding line (B) 6 5 4 (C) 2 1 Grounding line 2 A (A) (B) 4 3 3 (C) (B) 2 1 2 1 1 Fig. 25b Terminal (2P) Power supply Single-phase 220-240VAC 50Hz 220VAC 60Hz Grounding line 5 10 1 L N 2 4 6 (C) 11 2 UNIT C (B) 12 (C) UNIT B 3 (B) (B) Grounding line Grounding line (B) 3 OUTDOOR UNIT Terminal (12P) Grounding line UNIT A 4 INDOOR UNIT Terminal 7 INDOOR UNIT Terminal 1 INDOOR UNIT Terminal 8 INDOOR UNIT Terminal (C) 2 D Power supply Single-phase 220-240VAC 50Hz 220VAC 60Hz Grounding line (B) 9 UNIT C (B) UNIT B 3 4 L N A 4 4 indoor units with SAP-CMRV2446, CMRV3146 OUTDOOR UNIT Terminal (9P) Grounding line UNIT A B INDOOR UNIT Terminal C INDOOR UNIT Terminal 3 indoor units with SAP-CMRV1936 INDOOR UNIT Terminal English G G Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.). Each wire must be firmly connected. No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part. Be sure to connect power wires correctly matching up numbers on terminals of the outdoor unit and respective indoor units A – D. INDOOR UNIT Terminal G WARNING UNIT A 08-253 CMRV3146EH_OU EN 2 (A) Fig. 25c 20 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 21 5-4. How to Connect Wiring to the Terminal WARNING When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate. STRIP SIZE How to connect wiring to the terminal English Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected. 7 mm (ACTUAL SIZE) Fig. 26 a) For Indoor Unit Solid wire 25 mm (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the wire about 7 mm. See the label (Fig. 26) near the terminal plate. (2) Using a screwdriver, loosen the terminal screw on the terminal plate. Loop Insulation (3) Insert the wire and tighten the terminal screw completely using a screwdriver. Fig. 27 Stranded wire 10 mm b) For Outdoor Unit I For solid core wiring (or F-cable) Ring connector (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the solid wire about 25 mm. (Fig. 27) Fig. 28 (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate. (3) Using the pliers, bend the solid wire to form a loop suitable for the terminal screw. Twist wire ends (4) Shape the loop wire properly, place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver. I For stranded wiring Fig. 29 (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Figs. 28 and 29) Special washer (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate. Screw Ring connector (3) Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring connector. (Fig. 28) Wire Terminal plate Wire (4) Place the ring connector wire, and replace and tighten the removed terminal screw using a screwdriver. (Fig. 30) Fig. 30 21 Screw and special washer Ring connector 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 22 5-5. Wiring Instructions for the Outdoor Unit CAUTION Be sure to correctly align inter-unit cables A, B, C and D. English G Outdoor unit Terminal board 1 Indoor unit A A is the indoor unit with refrigerant tubing that is 12 3 connected to service valve A (bottom) of the outdoor unit. “B” is the indoor unit with refrigerant tubing that is connected to service valve B (second from 1 2 3 the bottom) of the outdoor unit. 3 1 2 3 4 5 6 7 8 9 10 11 12 Power: Single-phase, 220/240VAC 50HZ Terminal board Inter-unit cables ø1.0 (not provided) Power switch (not provided) Label A Indoor unit B 2 A Ground Power cable (not provided) (ø3.5 mm: Less than 26 m) Terminal board Inter-unit cables ø1.0 (not provided) Label B Indoor unit C C is the indoor unit with refrigerant tubing that is connected to service valve C (third from the 1 2 3 bottom) of the outdoor unit. B Terminal board Label C Indoor unit D D is the indoor unit with refrigerant tubing that is connected to service valve 1 2 3 D (top) of the outdoor unit. Be sure to perform grounding. Attach a ground wire to either the outdoor unit or indoor unit. If there is a grounding terminal inside the room, use the grounding screw inside the indoor unit. Inter-unit cables ø1.0 (not provided) C Terminal board Label D Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring. The units will not function if the wiring connections are incorrect. Inter-unit cables ø1.0 (not provided) D Fig. 31 G G G G G Use a dedicated Air Conditioner circuit for power. To make connections to the outdoor unit, remove the inspection panel and tubing panel. Do not bring the inter-unit cables or power cable into contact with tubing or service valves. Use outdoor unit cable fasteners and fasten the inter-unit cables at the location where the cables are double-sheathed. Arrange the wiring so that the inter-unit cables are contained in the inspection panel and tubing panel, as shown in Fig. 31. 22 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 23 Regulations on wire size differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Make sure that the installation fully complies with all local and national regulations. Cabinet (1) Remove access panel “C”. (Fig. 32) Access panel C (3) Be sure to size each wire allowing approx. 10 cm longer than the required length for wiring. Store excess wiring inside the cabinet. (4) When connections are completed, check that all connections are correct as shown in the wiring system diagram on panel side. (5) Be sure to ground the unit according to your local codes. 6. Test Run Fig. 32 Performing a test run G Refer to the test run procedures in the indoor unit installation manual. G Perform the test run separately for each connected indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring. G If the room temperature is 15°C or below, it may not be possible to check for tubing errors with cooling operation. If this occurs, perform heating operation for each unit individually, and check that warm air is discharged from each unit. If there is cold air mixed in with the warm air, check the tubing connections again. Checking tubing and wiring Perform the test run and check that operation is normal. If there is an error in tubing or wiring, the refrigerant may flow to indoor unit B when indoor unit A is operated (for example). CAUTION G Stop operation immediately if there is an error in tubing or wiring. Turn the power (breaker) OFF, and check whether the inter-unit cables are connected incorrectly, or whether the narrow tubes A and B are connected in reverse. Correct the connections. G If there is an error in tubing, pump-down must be performed. Be sure to perform pump-down. After making corrections, again purge the air from the tubes. 23 English (2) Connect the inter-unit wiring and power line according to the drawing on the panel side. 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 24 7. Connecting a Home Automation Device English The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal. Also, refer to Section 9. Electric Wiring Diagram in the outdoor unit installation manual. 8. Installation Check Sheet The strength of the installation location is sufficient to support the Air Conditioner weight. The indoor and outdoor units are installed level and vertically. The power and voltage are as specified. Inter-unit cables are securely fastened to the terminal board. Inter-unit cables are securely fixed. The power cord and inter-unit cables are not connected anywhere along their paths. The ground wire is securely connected. An air purge of the refrigerant circuit has been conducted. A leak test of the tubing connections has been performed. Thermal insulation has been applied to the tubing connections. Drain connections are secure and water drains properly. Putty has been used to close the hole in the wall. All service valves are fully open. Remote controller signals are being positively received. 9. Electric Wiring Diagram Diagrama de cableado eléctrico Diagramme de câblage électrique Elektrisches Schaltbild Diagramma dei circuiti elettrici Diagrama da fiação elétrica ¢È¿ÁÚ·ÌÌ· ËÏÂÎÙÚÈ΋˜ ηψ‰›ˆÛ˘ SAP-KMRV74/94/124EH EVAPORATOR Indoor Unit Unidad interior Appareil intérieur Innenraumgerät Unità Interna Unidade interior ∂Û ˆÙÂÚÈ΋ ÌÔÓ¿‰· TO OUTDOOR UNIT YEL/GRN TERMINAL BASE BLK 1 WHT 2 RED 3 4 AC1 AC2 SI 1 2 3 4 5 1 2 FLAP 3 5P(WHT) LAMP 4 10P(WHT) 5 1 2 3 4 5 6 1 ROOM/COIL 2 4P(WHT) 3 DCM 4 6P(BLU) 5 6 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 RED WHT WHT WHT WHT WHT WHT WHT WHT WHT 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 IND LAMP ASSY CONNECTOR RED 1 1 PNK 2 2 BLU 3 3 FLAP BRN 4 4 YEL 5 5 FLAP MOTOR CONTROLLER RED FM FAN MOTOR BLK WHT YEL BLU 1 2 3 4 1 2 3 4 1 1 ION 2 2 3P(WHT) 3 3 1 1 WHT 2 2 RED 3 3 BLK CONNECTOR WHT RED BLK BLK BLK HA JEM-A 4P(WHT) 1 2 3 4 ROOM THERMISTOR BLK BLK BLK BLK COIL THERMISTOR 1 2 3 4 1 2 3 4 ION TERMINAL Fig. 33a 24 ION ASSY 8FA-2-5257-72600-1 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 25 SAP-KRV184/244EH SAP-KMRV76/96/126EH EVAPORATOR EVAPORATOR WHT 2 RED 3 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 RED WHT WHT WHT WHT WHT WHT WHT WHT WHT 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 FLAP MOTOR FLAP 1 2 3 4 5 RED PNK BLU BRN YEL 1 2 3 4 5 1 2 3 4 5 AC IN AC IN-2 1 2 FLAP 3 5P(WHT) 4 5 1 2 3 4 5 6 1 2 3 DCM 4 6P(BLU) 5 6 CONTROLLER RED BLK WHT YEL BLU FM 1 2 3 4 5 6 1 2 3 4 1 ROOM/COIL 2 4P(WHT) 3 DCM 4 6P(BLU) 5 6 FAN MOTOR 1 2 3 4 ROOM THERMISTOR BLK BLK BLK BLK COIL THERMISTOR RED BLK WHT YEL BLU FM E WHT RED BLK BLK BLK HA JEM-A 4P(WHT) 1 2 3 4 3 SI 1 2 3 4 5 6 7 8 9 RED WHT WHT WHT WHT WHT WHT WHT WHT 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 FAN MOTOR 1 1 ION 2 2 3P(WHT) 3 3 GRN/YEL 2 SI-2 1 2 3 4 LAMP 9P(WHT) 5 6 7 8 CONTROLLER 9 CONNECTOR 1 WHT WHT RED IND LAMP ASSY 1 2 FLAP 3 5P(WHT) LAMP 4 10P(WHT) 5 BLK E GRN/YEL UV ASSY ROOM THERMISTOR 1 1 ROOM/COIL/UV 2 2 6P(WHT) 3 3 4 4 HA 5 5 JEM-A 6 6 4P(WHT) 1 2 3 4 BLK BLK ORG ORG RED COIL THERMISTOR BLK 1 2 3 4 1 2 3 4 ION TERMINAL ION ASSY 8FA-2-5257-68200-0 Fig. 33b SAP-KRV186/246EH SAP-KRV96/126EHDS GRN/YEL 4 FLAP MOTOR (UPPER) UV UNIT THERMISTOR (ROOM) THERMISTOR (COIL) 1 2 1 2 1 2 1 2 HUM SW2 (RED) (BLU) BLK BLK THERMISTOR (HUM) WHT BLK PANEL SW IND LAMP ASSY 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 LAMP (WHT) 1 2 3 4 5 1 2 3 4 5 SW1 (WHT) 3 DC OUT 2 (WHT) 1 SW ASSY 1 2 3 4 5 1 2 3 4 5 Fig. 33e 25 1 2 1 2 1 2 1 2 UV (RED) BLK BLK ORG ORG WHT BLU BLU BLU BLU (WHT) CONTROLLER (BLU) RED BLK WHT YEL BLU DCM (BLU) 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 FM 8FA-2-5250-27700-1 BLK WHT YEL BLU RED BLK (RED) 1 2 3 4 1 2 3 4 ROOM /COIL (WHT) (WHT) DC FAN MOTOR RED Fig. 33d HA JEM-A HA JEM-A 4P(WHT) 1 2 3 4 WHT GRY GRY GRY GRY RED BLK WHT GRY GRY GRY GRY GRY GRY GRY GRY GRY (WHT) PANEL MOTOR COIL THERMISTOR FLAP3 E (WHT) (RED) FLAP MOTOR (LOWER) PANEL (WHT) 1 2 3 4 5 1 2 3 4 5 RED BLK ROOM THERMISTOR (WHT) 1 2 3 4 UV 1 1 2P(RED) 2 2 UV ASSY 1 2 3 4 5 1 2 3 4 5 GRN/YEL BLK BLK ORG ORG FLAP2 FAN MOTOR 1 2 3 DCM 4 6P(BLU) 1 1 5 6 ROOM/COIL 2 2 4P(WHT) 3 3 4 4 1 2 3 4 5 1 2 3 4 5 FM BLK WHT YEL BLU 1 2 3 4 5 6 FLAP1 (WHT) 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 (WHT) (WHT) CONTROLLER RED WHT GRY GRY GRY GRY WHT BLU BLU BLU BLU 7 5 ELEC-JB1 3 (WHT) 1 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 7 5 3 1 WHT BLK BLK BLK BLK BLK BLK BLK BLK BLK YEL ORG RED BRN FLAP MOTOR 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 FLAP1 1 2 FLAP 3 5P(WHT) 4 LAMP 10P(WHT) 5 + + + + + EARTH PLATE 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 IND LAMP ASSY CONNECTOR 1 1 RED 2 2 PNK 3 3 BLU FLAP 4 4 BRN 5 5 YEL + + GRN/YEL EVAPORATOR AC1 AC2 SI + 3 3 + 2 RED 1 2 TERMINAL BASE 1 WHT TO OUTDOOR UNIT BLK TO OUTDOOR UNIT TERMINAL BASE EVAPORATOR 8FA-2-5250-29700-2 Fig. 33c 8FA-2-5250-07400-1 English AC1 AC2 SI 1 2 3 4 5 IND LAMP ASSY CONNECTOR RED 1 1 PNK 2 2 BLU 3 3 FLAP BRN 4 4 YEL 5 5 FLAP MOTOR TERMINAL BASE FERRITE CORE GRN/YEL 1 TO OUTDOOR UNIT TO OUTDOOR UNIT YEL/GRN TERMINAL BASE BLK 10/14/08 2:39 PM Page 26 Outdoor Unit Unidad exterior Appareil extérieur Außengerät Unità Esterna Unidade exterior ∂Í ˆÙÂÚÈ΋ ÌÔÓ¿‰· SAP-CMRV1926EH COIL COIL DEFROST VALVE 4WAY VALVE W W DEF1 DEF0 GRN/YEL GRN/YEL WHT WHT GRN/YEL 2P-CONNECTOR WHT WHT WHT 2P-CONNECTOR WHT BLU BLU OUTDOOR THERMISTOR 2 1 2 1 2 1 2 1 W W W W W W W RV1 RV0 L2 L1 E-2 E-1 E COMP WHT W ACIN2 R / V TERMINAL PLATE 1 REACTANCE BLK BLK 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV1 MV0 WHT 3 4 5 6 BLK WHT 7 8 MAGNETIC COIL MAGNETIC COIL 2 2 1 1 TO INDOOR UNIT BLU B INDOOR A INDOOR UNIT UNIT MV0 1 2 3 4 5 1 2 3 4 5 2 1 2 3 4 5 6 7 1 2 3 4 5 6 7 WHT WHT MV1 1 2 3 4 5 1 2 3 4 5 RED W L HEATER CRANKCASE 1 2 3 1 2 3 S/U CN04 DCFM 1 2 3 4 5 6 7 W W S1-B N 3P-CONNECTOR RED(PNK) RED(PNK) WHT WHT BLU BLU WHT FERRITE CORE W S1-A POWER SUPPLY HEATER1 HEATER0 W ORG RED YEL BLK GRY W ORG RED YEL BLK GRY V W W BLU BRN WHT ORG U RED OLR1 BLU BRN WHT ORG W FERRITE CORE CONTROLLER RED OLR0 WHT W (OLR) OVERLOAD RELAY BLK W ACIN1 25A WHT COMPRESSOR THERMISTOR BLK BLK 1 1 2 2 RED WHT 1 1 WHT WHT 2 2 WHT 2P-CONNECTOR 2 1 2 1 BLK BLK 1 2 3 4 1 2 3 4 B-TH 2P-CONNECTOR BLK BLU BLU BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR 1 2 3 4 1 2 3 4 A-TH REACTANCE RV BLK BLK AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR 1 2 3 4 1 2 3 4 COIL/OUTDOOR COIL THERMISTOR YEL YEL BLK BLK DEF GND FM WHT 2P-CONNECTOR FAN MOTOR C/W GRN/YEL CM COMPRESSOR MOTOR 8FA-2-5257-84200-0 Fig. 34a SAP-CMRV1936EH W W E-2 E-1 W W E ACIN1 W U W V W TERMINAL PLATE BLK WHT ACIN2 FERRITE CORE 3 GND KS23 1 2 3 4 5 6 7 8 KS22 1 2 3 4 5 6 KS10 1 2 3 4 SICOM2 W MV1 1 2 3 4 5 1 2 3 4 5 S1-A W RED MV0 S1-B 1 2 3 4 5 1 2 3 4 5 W BLU 1 2 3 4 1 2 3 4 CNO1 ORG RED YEL BLK GRY BLK WHT RED BLU 1 2 3 4 5 6 1 2 3 4 5 6 CNO2 ORG RED YEL BLK GRY BLK WHT RED BLU BLK WHT 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CNO3 WHT BLK WHT RED BLU BLK WHT RED BLU BLU BRN WHT ORG RED BLK BLU BRN WHT ORG FAN MOTOR OVERLOAD RELAY (OLR) MV2 1 2 3 4 5 1 2 3 4 5 ORG RED YEL BLK GRY GRN/YEL FM C-TH 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 W 3 1 2 3 4 5 1 2 3 4 5 SICOM2 SI-C W BLK 4 WHT 5 BLK MV1 MV0 MAGNETIC COIL MAGNETIC COIL 1 2 REACTANCE 1 2 3 4 5 6 7 1 2 3 4 5 6 7 RED WHT 2 2 WHT WHT 1 1 WHT 2P-CONNECTOR 2 CONTROLLER W CNO4 DCFM 1 2 3 4 5 6 7 CM 1 L W L1 N W L2 GRN/YEL WHT 2P-CONNECTOR WHT WHT WHT WHT WHT W POWER SUPPLY W HEATER1 HEATER0 GRN/YEL W RV0 GRN/YEL W RV1 6 BLK 7 WHT 8 9 BRN C INDOOR B INDOOR A INDOOR UNIT UNIT UNIT TO INDOOR UNIT OLR1 C/W COMPRESSOR MOTOR W CRANKCASE HEATER CW THERMISTOR YEL YEL YEL YEL CN THERMISTOR S/U WHT WHT COIL THERMISTOR W W 2 1 2 1 2 1 2 1 DEF1 DEF0 COMP OLR0 1 2 3 1 2 3 R / V W REACTANCE 25A W RED COMPRESSOR THERMISTOR BLK BLK 1 1 2 2 2P-CONNECTOR WHT BLU BLU 1 2 3 4 1 2 3 4 B-TH 2 1 2 1 BLK BLK BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR 1 2 3 4 1 2 3 4 A-TH RV 2P-CONNECTOR BLK BLK BLU BLK BLU AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR 1 2 3 4 1 2 3 4 COIL/OUTDOOR OUTDOOR THERMISTOR YEL YEL BLK BLK DEF 2P-CONNECTOR WHT 1 1 2 2 WHT COIL COIL DEFROST VALVE 4WAY VALVE 3P-CONNECTOR RED(PNK) RED(PNK) WHT WHT BLU BLU WHT FERRITE CORE English 08-253 CMRV3146EH_OU EN GND 1 2 3 4 5 1 2 3 4 5 MV2 MAGNETIC COIL Fig. 34b 26 8FA-2-5257-57000-0 08-253 CMRV3146EH_OU EN 10/14/08 2:39 PM Page 27 English SAP-CMRV2446EH W W W L2 L1 W GRN/YEL W E-2 E-1 W ACIN1 FERRITE CORE 3 GND S1-A W RED MV1 1 2 3 4 5 1 2 3 4 5 MV0 S1-B 1 2 3 4 5 1 2 3 4 5 W BLU V KS10 1 2 3 4 BLK WHT RED BLU BLK WHT RED BLU BLK WHT RED BLU BLK WHT BLK WHT RED BLU SICOM2 W WHT KS22 1 2 3 4 5 6 BLU BRN WHT ORG KS23 1 2 3 4 5 6 7 8 BLK FAN MOTOR OVERLOAD RELAY (OLR) RED WHT 2 2 WHT WHT 1 1 WHT 2P-CONNECTOR 1 2 3 4 5 1 2 3 4 5 W 3 1 2 3 4 5 1 2 3 4 5 SICOM2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV3 MV2 W BLK 4 WHT 5 BLK MV1 SI-D SI-C MV2 1 2 3 4 5 1 2 3 4 5 ORG RED YEL BLK GRY FM 1 2 3 4 1 2 3 4 CNO1 MV3 1 2 3 4 5 1 2 3 4 5 C-TH 1 2 3 4 1 2 3 4 DW THERMISTOR YEL YEL YEL YEL DN THERMISTOR CW THERMISTOR YEL YEL YEL YEL CN THERMISTOR D-TH 1 2 3 4 1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 CNO2 ORG RED YEL BLK GRY 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CNO3 BLU BRN WHT ORG RED 1 2 3 4 5 6 7 1 2 3 4 5 6 7 W 1 2 REACTANCE GRN/YEL 2 CONTROLLER W CNO4 DCFM 1 2 3 4 5 6 7 CM 1 D INDOOR C INDOOR B INDOOR A INDOOR UNIT UNIT UNIT UNIT TO INDOOR UNIT U WHT ACIN2 ORG RED YEL BLK GRY W W TERMINAL PLATE BLK ORG RED YEL BLK GRY OLR1 W W E L W HEATER1 HEATER0 N W RV0 POWER SUPPLY W RV1 GRN/YEL CRANKCASE HEATER GRN/YEL WHT 2P-CONNECTOR WHT WHT WHT WHT WHT WHT WHT 2P-CONNECTOR WHT BLU BLU OUTDOOR THERMISTOR W C/W COMPRESSOR MOTOR W DEF1 DEF0 COMP OLR0 W 2 1 2 1 25A W 1 2 3 1 2 3 S/U W REACTANCE 2 1 2 1 RED COMPRESSOR THERMISTOR BLK BLK 3P-CONNECTOR RED(PNK) RED(PNK) WHT WHT BLU BLU WHT FERRITE CORE 1 1 2 2 R / V 2 1 2 1 BLK BLK 1 2 3 4 1 2 3 4 B-TH 2P-CONNECTOR BLK BLU BLU BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR 1 2 3 4 1 2 3 4 A-TH RV BLK BLK AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR 1 2 3 4 1 2 3 4 COIL/OUTDOOR COIL THERMISTOR YEL YEL BLK BLK DEF WHT 2P-CONNECTOR WHT 1 1 2 2 COIL COIL DEFROST VALVE 4WAY VALVE MV0 6 BLK BLK MAGNETIC COIL MAGNETIC COIL WHT 7 8 9 10 BRN WHT WHT GRY 11 12 GND MAGNETIC COIL MAGNETIC COIL 8FA-2-5257-57100-0 Fig. 34c SAP-CMRV3146EH W U GRN/YEL FERRITE CORE W W W W W W L2 L1 E-2 E-1 E ACIN1 FAN MOTOR OVERLOAD RELAY (OLR) RED WHT 2 2 WHT WHT 1 1 WHT (2P) CONNECTOR WHT ACIN2 FERRITE CORE 1 2 3 GND 1 2 3 4 1 2 3 4 CNO1 MV1 1 2 3 4 5 1 2 3 4 5 S1-A W RED MV0 S1-B 1 2 3 4 5 1 2 3 4 5 W BLU ORG RED YEL BLK GRY 1 2 3 4 5 6 1 2 3 4 5 6 CNO2 W ORG RED YEL BLK GRY BLK WHT RED BLU 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CNO3 SICOM2 WHT BLK WHT RED BLU BLK WHT KS10 1 2 3 4 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 BLK W SICOM2 3 D-TH 1 2 3 4 1 2 3 4 C-TH 1 2 3 4 1 2 3 4 MV0 MV3 1 2 3 4 5 1 2 3 4 5 SI-D SI-C MV2 W W MAGNETIC COIL MAGNETIC COIL 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 MV3 MV2 BLK 4 WHT 5 BLK MV1 6 BLK BLK 7 WHT 8 9 10 BRN WHT GRY 1 2 REACTANCE ORG RED YEL BLK GRY GRN/YEL FM KS22 1 2 3 4 5 6 BLK WHT RED BLU BLK WHT RED BLU WHT BLU BRN WHT ORG KS23 1 2 3 4 5 6 7 8 BLU BRN WHT ORG 1 2 3 4 5 6 7 1 2 3 4 5 6 7 CM W TERMINAL PLATE BLK L GRN/YEL GRN/YEL (2P) CONNECTOR WHT WHT WHT WHT WHT WHT W N W HEATER1 HEATER0 POWER SUPPLY W RV0 ORG RED YEL BLK GRY W CNO4 DCFM 1 2 3 4 5 6 7 C/W COMPRESSOR MOTOR W RV1 CONTROLLER DW THERMISTOR YEL YEL YEL YEL DN THERMISTOR CW THERMISTOR YEL YEL YEL YEL CN THERMISTOR S/U R / V W DEF1 DEF0 CRANKCASE HEATER V RED 1 2 3 1 2 3 2 1 2 1 2 1 2 1 WHT 11 12 D INDOOR C INDOOR B INDOOR A INDOOR UNIT UNIT UNIT UNIT TO INDOOR UNIT OLR1 W WHT WHT COIL THERMISTOR COMP W (3P) CONNECTOR RED(PNK) RED(PNK) WHT WHT BLU BLU WHT FERRITE CORE (7P) CONNECTOR OLR0 W W REACTANCE 25A W RED COMPRESSOR THERMISTOR BLK BLK 1 1 2 2 (2P) CONNECTOR WHT BLU BLU 1 2 3 4 1 2 3 4 B-TH 2 1 2 1 BLK BLK BW THERMISTOR YEL YEL YEL YEL BN THERMISTOR 1 2 3 4 1 2 3 4 A-TH RV (2P) CONNECTOR BLK BLK BLU BLK BLU AW THERMISTOR YEL YEL YEL YEL AN THERMISTOR 1 2 3 4 1 2 3 4 COIL/OUTDOOR OUTDOOR THERMISTOR YEL YEL BLK BLK DEF (2P) CONNECTOR WHT 1 1 2 2 WHT COIL COIL DEFROST VALVE 4WAY VALVE GND MAGNETIC COIL MAGNETIC COIL Fig. 34d 27 8FA-2-5257-89000-0 28 GRY ORG PNK RED VLT WHT YEL 5 6 7 8 9 10 11 YELLOW WHITE VIOLET RED PINK ORANGE GREY GREEN/YELLOW GRN/YEL GRY ORG PNK RED 4 5 6 7 8 11 10 YEL WHT VLT BRN 3 9 BLU 2 AMARILLO BLANCO VIOLETA ROJO ROSA NARANJA GRIS VERDE/AMARILLO MARRÓN AZUL BLK BLU BRN GRN/YEL GRY ORG PNK RED VLT WHT YEL 1 2 3 4 5 6 7 8 9 10 11 ABBREV. GIALLO BIANCO VIOLA ROSSO ROSA ARANCIONE GRIGIO VERDE/GIALLO MARRONE BLU NERO SIGNIFICATO BLK BLU BRN GRN/YEL GRY ORG PNK RED VLT WHT YEL 1 2 3 4 5 6 7 8 9 10 11 ABREV. AMARELO BRANCO VIOLETA ENCARNADO COR-DE-ROSA COR-DE-LARANJA CINZENTO VERDE/AMARELO CASTANHO AZUL PRETO SIGNIFICADO Significado das abreviaturas GRN/YEL 4 BROWN BLUE SIGNIFICADO NEGRO Significato delle abbreviazioni BRN 3 ABREV. BLK 1 11 10 9 8 7 6 5 4 3 2 1 11 10 9 8 7 6 5 4 3 2 1 ABREV. SIGNIFICATION EÏÏËÓÈο JAUNE BLANC VIOLET ROUGE ROSE ORANGE GRIS VERT/JAUNE MARRON BLEU NOIR YEL WHT VLT RED PNK ORG GRY GRN/YEL BRN BLU BLK ™À¡∆ª∏™∏ ∫π∆ƒπ¡√ ∞™¶ƒ√ μπ√§∂∆A ∫√∫∫π¡√ ƒ√∑ ¶√ƒ∆√∫∞§π °∫ƒπ∑√ ¶ƒ∞™π¡√ / ∫π∆ƒπ¡√ ∫∞º∂∆H™ ª¶§∂ ª∞Àƒ√ ∂¶∂•∏°∏™∏ ∂ÂÍ‹ÁËÛË ÙˆÓ Û˘ÓÙÌ‹ÛÂˆÓ YEL WHT VLT RED PNK ORG GRY GRN/YEL BRN BLU BLK ABKÜRZUNG 11 YEL WHT VLT 9 10 RED 8 PNK ORG 7 GRY GRN/YEL 4 6 BRN 5 BLU 3 BLK 2 1 BEDEUTUNG GELB WEISS VIOLETT ROT ROSA ORANGE GRAU GRÜN/GELB BRAUN BLAU SCHWARZ 2:39 PM Português BLU 2 BLACK Bedeutung der Abkürzungen Deutsch 10/14/08 Italiano BLK 1 MEANING Signification des abréviations Significado de las abreviaturas Meaning of Abbreviations ABBREV. Français Español English English 08-253 CMRV3146EH_OU EN Page 28 APPENDIX C UNIT COMBINATION TABLES < List of Combination Table > Name of Combination Table Model No. of Outdoor Unit Remarks 2-Room Outdoor Unit Combination Table SAP-CMRV1426EH OI-852-6-4181-076-00-1 2-Room Outdoor Unit Combination Table SAP-CMRV1926EH OI-852-6-4181-040-00-2 3-Room Outdoor Unit Combination Table SAP-CMRV1936EH OI-852-6-4181-041-00-2 4-Room Outdoor Unit Combination Table SAP-CMRV2446EH OI-852-6-4181-042-00-2 4-Room Outdoor Unit Combination Table SAP-CMRV3146EH OI-852-6-4181-043-00-2 NOTE Be sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with only a single unit installed, the returning fluid to the compressor may cause a malfunction. NOTE The specifications of SAP-KRV96EHDSA are the same as those of SAP-KRV96EHDS described in the Unit Combination Tables. A-3 CombinationTable-1426EH.fm Page 2 Thursday, October 2, 2008 11:03 AM Save this Combination Table! Please be sure to hand over this sheet to the user. 2-Room Outdoor Unit Combination Table SAP-CMRV1426EH <Combinations of Connectable Indoor Units> The combinations of the indoor units listed in Table 1 and 2 on the next page are combinations solely of those units which can be operated concurrently. In addition to the combinations listed in the table, other combinations of indoor units are possible provided that the following conditions are satisfied. Conditions: 1. At least two or more indoor units must be connected to the multi outdoor unit. It is not acceptable for only one indoor unit to be connected. 2. The total rated cooling capacity of the indoor units to be connected must be no more than 200% of the rated cooling capacity of the outdoor unit. CAUTION In this case, all the indoor units installed must not be operated concurrently under any circumstances. Otherwise, the air conditioner may not run properly and trouble may occur. Example: When two indoor units are connected If the following holds true • Rated cooling capacity of SAP-CMRV1426EH outdoor unit: C=4 (kW) • Rated cooling capacity of indoor units: K1, K2, ... (kW) Then: C x 2 (200%) K1 + K2 + ....... 4 x 2 3.5 + 3.5 8 7 It is therefore possible to connect two units with respective capacities of 3.5 + 3.5. However, since this combination is not found in the 2-room operation column of Table 1, operating all these units concurrently may result in trouble. At a time like this, shut down at least one of the two indoor units to match one of the combinations found in the single-room operation column of Table 1. NOTE Be sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with only a single unit installed, the returning fluid to the compressor may cause a malfunction. Pub. OI-85264181076001 © SANYO 2008 CombinationTable-1426EH.fm Page 3 Thursday, October 2, 2008 11:03 AM < Combinations of operatable indoor units > SAP-CMRV1426EH (Rated cooling capacity: 4.0 kW) NOTE 2.2: SAP-KMRV74/76EH 2.65: SAP-KMRV94/96EH 3.5: SAP-KMRV124/126EH Table 1 Indoor Unit Combination 2.2 Single-room 2.65 Operation 3.5 2.2 2.2 2-room 2.2 Operation 2.65 2.65 + + + + + 2.2 2.65 3.5 2.65 3.5 Room Room A B = 2.2 2.20 = 2.65 2.65 = 3.5 3.50 = 4.4 1.80 1.80 = 4.85 1.68 2.02 = 5.7 1.51 2.39 = 5.3 2.00 2.00 = 6.15 1.72 2.28 Indoor Unit Capacity COOLING Room Total Performance Capacity ( Min. - Max. ) A 2.2 ( 1.2 2.6 ) 2.50 2.65 ( 1.2 3.2 ) 3.60 3.5 ( 1.3 3.6 ) 4.20 3.6 ( 2.0 4.5 ) 2.10 3.7 ( 2.0 4.8 ) 1.72 3.9 ( 2.0 4.9 ) 1.64 4.0 ( 2.0 5.0 ) 2.25 4.0 ( 2.1 5.0 ) 2.08 (kW) HEATING Room Total Performance B Capacity ( Min. - Max. 2.5 ( 1.4 3.5 3.6 ( 1.4 4.0 4.2 ( 1.5 4.2 2.10 4.2 ( 2.0 5.0 2.48 4.2 ( 2.0 5.0 2.76 4.4 ( 2.2 5.3 2.25 4.5 ( 2.2 5.5 2.42 4.5 ( 2.4 5.5 ) ) ) ) ) ) ) ) ) NOTE 2.65: SAP-KRV96EHDS 3.5: SAP-KRV126EHDS Table 2 Indoor Unit Combination Single-room 2.65 Operation 3.5 2-room Operation 2.65 + 2.65 + 2.65 3.5 Indoor Unit Capacity (kW) COOLING HEATING Room Room Room Room Total Performance Total Performance A B Capacity ( Min. - Max. ) A B Capacity ( Min. - Max. ) = 2.65 = 3.5 2.65 3.50 = 5.3 = 6.15 1.90 1.64 1.90 2.16 2.65 ( 3.5 ( 1.2 1.3 - 3.2 ) 3.6 ) 3.60 4.20 3.8 ( 3.8 ( 2.0 2.1 - 4.8 ) 4.8 ) 2.15 1.98 2.15 2.32 3.6 ( 4.2 ( 1.4 1.5 - 4.0 ) 4.2 ) 4.3 ( 4.3 ( 2.2 2.4 - 5.2 ) 5.2 ) • When one or more SAP-KRVxxEHDS indoor units are operated concurrently with one or more SAP-KMRVxxEH indoor units, the performance specifications of the SAP-KRVxxEHDS models will decrease by 5% from those listed in the Table 2. • The table lists the wall-mounted type of indoor units as representative models. • For details on the connection of indoor units other than the wall-mounted type, refer to the catalog. CombinationTable-1926EH.fm Page 2 Friday, September 26, 2008 10:07 AM Save this Combination Table! Please be sure to hand over this sheet to the user. 2-Room Outdoor Unit Combination Table SAP-CMRV1926EH <Combinations of Connectable Indoor Units> The combinations of the indoor units listed in Table 1 and 2 on the next page are combinations solely of those units which can be operated concurrently. In addition to the combinations listed in the table, other combinations of indoor units are possible provided that the following conditions are satisfied. Conditions: 1. At least two or more indoor units must be connected to the multi outdoor unit. It is not acceptable for only one indoor unit to be connected. 2. The total rated cooling capacity of the indoor units to be connected must be no more than 200% of the rated cooling capacity of the outdoor unit. CAUTION In this case, all the indoor units installed must not be operated concurrently under any circumstances. Otherwise, the air conditioner may not run properly and trouble may occur. Example: When two indoor units are connected If the following holds true • Rated cooling capacity of SAP-CMRV1926EH outdoor unit: C=5.6 (kW) • Rated cooling capacity of indoor units: K1, K2, ... (kW) Then: C x 2 (200%) K1 + K2 + ....... 5.6 x 2 5.15 + 5.15 11.2 10.3 It is therefore possible to connect two units with respective capacities of 5.15 + 5.15. However, since this combination is not found in the 2-room operation column of Table 1, operating all these units concurrently may result in trouble. At a time like this, shut down at least one of the two indoor units to match one of the combinations found in the single-room operation column of Table 1. NOTE Be sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with only a single unit installed, the returning fluid to the compressor may cause a malfunction. Pub. OI-85264181040002 © SANYO 2008 CombinationTable-1926EH.fm Page 3 Friday, September 26, 2008 10:07 AM < Combinations of operatable indoor units > NOTE SAP-CMRV1926EH SAP-CMRV1924EH 2.2: SAP-KMRV74EH SAP-KMRV74/76EH 2.65: SAP-KMRV94EH SAP-KMRV94/96EH 3.5: SAP-KMRV124EH SAP-KMRV124/126EH 5.15: SAP-KRV184EH SAP-KRV184/186EH (Rated cooling capacity: 5.6 kW) Table 1 Indoor Unit Combination Single-room Operation 2-room Operation 2.2 2.65 3.5 5.15 2.2 2.2 2.2 2.2 2.65 2.65 2.65 3.5 3.5 + + + + + + + + + 2.2 2.65 3.5 5.15 2.65 3.5 5.15 3.5 5.15 = = = = = = = = = = = = = 2.2 2.65 3.5 5.15 4.4 4.85 5.7 7.35 5.3 6.15 7.8 7 8.65 Room Room A B 2.20 2.65 3.50 5.15 2.20 2.20 2.20 2.65 1.97 3.13 1.65 3.85 2.50 2.50 2.24 2.96 1.90 3.70 2.70 2.70 2.27 3.33 Indoor Unit Capacity (kW) COOLING HEATING Total Performance Room Room Total Performance Capacity ( Min. - Max. ) Capacity ( Min. - Max. A B 2.2 ( 1.4 2.6 ) 2.50 2.5 ( 1.8 4.3 2.65 ( 1.4 3.2 ) 3.60 3.6 ( 1.8 4.7 3.5 ( 1.5 3.6 ) 4.20 4.2 ( 1.9 5.1 5.15 ( 1.6 5.8 ) 6.00 6.0 ( 2.0 7.8 4.4 ( 2.0 5.1 ) 2.50 2.50 5.0 ( 2.0 6.4 4.85 ( 2.0 5.8 ) 2.50 3.60 6.1 ( 2.1 7.5 5.1 ( 2.0 6.7 ) 2.35 3.95 6.3 ( 2.1 8.3 5.5 ( 2.1 6.8 ) 2.03 4.87 6.9 ( 2.4 8.4 3.23 3.23 5.0 ( 2.0 6.3 ) 6.45 ( 2.3 8.4 3.07 3.58 5.2 ( 2.0 6.8 ) 6.65 ( 2.3 8.4 5.6 ( 2.1 6.8 ) 2.74 4.56 7.3 ( 2.4 8.4 5.4 ( 2.0 6.8 ) 3.45 3.45 6.9 ( 2.3 8.4 5.6 ( 2.1 6.8 ) 3.01 4.29 7.3 ( 2.4 8.4 ) ) ) ) ) ) ) ) ) ) ) ) ) ) NOTE 2.65: SAP-KRV96EHDS 3.5: SAP-KRV126EHDS Table 2 Indoor Unit Combination Single-room Operation 2-room Operation 2.65 3.5 2.65 + 2.65 2.65 + 3.5 3.5 + 3.5 = 2.65 = 3.5 = 5.3 = 6.15 = 7 Indoor Unit Capacity (kW) COOLING HEATING Room Room Total Performance Room Room Total Performance Capacity ( Min. - Max. ) Capacity ( Min. - Max. A B A B 2.65 3.50 2.35 2.11 2.53 2.35 2.79 2.53 2.65 3.5 4.7 4.9 5.05 ( ( ( ( ( 1.4 1.5 2.0 2.0 2.0 - 3.2 3.6 6.0 6.4 6.4 ) ) ) ) ) 3.60 4.20 3.20 3.02 3.45 3.20 3.53 3.45 3.6 4.2 6.4 6.55 6.9 ( ( ( ( ( 1.8 1.9 2.3 2.3 2.3 - 4.7 5.1 8.3 8.3 8.3 • When one or more SAP-KRVxxEHDS indoor units are operated concurrently with one or more SAP-KMRVxxEH indoor units, the performance specifications of the SAP-KRVxxEHDS models will decrease by 5% from those listed in the Table 2. • The table lists the wall-mounted type of indoor units as representative models. • For details on the connection of indoor units other than the wall-mounted type, refer to the catalog. ) ) ) ) ) ) CombinationTable-1936EH.fm Page 2 Friday, September 26, 2008 10:11 AM Save this Combination Table! Please be sure to hand over this sheet to the user. 3-Room Outdoor Unit Combination Table SAP-CMRV1936EH <Combinations of Connectable Indoor Units> The combinations of the indoor units listed in Table 1 and 2 on the next page are combinations solely of those units which can be operated concurrently. In addition to the combinations listed in the table, other combinations of indoor units are possible provided that the following conditions are satisfied. Conditions: 1. At least two or more indoor units must be connected to the multi outdoor unit. It is not acceptable for only one indoor unit to be connected. 2. The total rated cooling capacity of the indoor units to be connected must be no more than 200% of the rated cooling capacity of the outdoor unit. CAUTION In this case, all the indoor units installed must not be operated concurrently under any circumstances. Otherwise, the air conditioner may not run properly and trouble may occur. Example: When three indoor units are connected If the following holds true • Rated cooling capacity of SAP-CMRV1936EH outdoor unit: C=5.6 (kW) • Rated cooling capacity of indoor units: K1, K2, ... (kW) Then: C x 2 (200%) K1 + K2 + ....... 5.6 x 2 2.2 + 3.5 + 5.15 11.2 10.85 It is therefore possible to connect three units with respective capacities of 2.2 + 3.5 + 5.15. However, since this combination is not found in the 3-room operation column of Table 1, operating all these units concurrently may result in trouble. At a time like this, shut down at least one of the three indoor units to match one of the combinations found in the 2-room operation column of Table 1. NOTE Be sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with only a single unit installed, the returning fluid to the compressor may cause a malfunction. Pub. OI-85264181041002 © SANYO 2008 CombinationTable-1936EH.fm Page 3 Friday, September 26, 2008 10:11 AM < Combinations of operatable indoor units > NOTE SAP-CMRV1934EH SAP-CMRV1936EH 2.2: SAP-KMRV74EH 2.2: SAP-KMRV74/76EH 2.65: SAP-KMRV94EH 2.65: SAP-KMRV94/96EH 3.5: SAP-KMRV124EH 3.5: SAP-KMRV124/126EH 5.15: SAP-KRV184EH 5.15: SAP-KRV184/186EH (Rated cooling capacity: 5.6 kW) Table 1 Indoor Unit Combination Single-room Operation 2-room Operation 3-room Operation 2.2 2.65 3.5 5.15 2.2 2.2 2.2 2.2 2.65 2.65 2.65 3.5 3.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 3.5 + + + + + + + + + + + + + + + + + + + + + 2.2 2.65 3.5 5.15 2.65 3.5 5.15 3.5 5.15 2.2 2.2 2.2 2.2 2.65 2.65 2.65 3.5 2.65 2.65 3.5 3.5 + + + + + + + + + + + + 2.2 2.65 3.5 5.15 2.65 3.5 5.15 3.5 2.65 3.5 3.5 3.5 = = = = = = = = = = = = = = = = = = = = = = = = = 2.2 2.65 3.5 5.15 4.4 4.85 5.7 7.35 5.3 6.15 7.8 7 8.65 6.6 7.05 7.9 9.55 7.5 8.35 10 9.2 7.95 8.8 9.65 10.5 Room Room A B 2.20 2.65 3.50 5.15 2.20 2.20 2.20 2.65 1.97 3.13 1.65 3.85 2.50 2.50 2.24 2.96 1.90 3.70 2.70 2.70 2.27 3.33 1.77 1.77 1.69 1.69 1.56 1.56 1.29 1.29 1.63 1.96 1.48 1.78 1.23 1.48 1.34 2.13 1.87 1.87 1.69 1.69 1.54 2.03 1.87 1.87 Indoor Unit Capacity (kW) COOLING HEATING Room Room Room Room Total Performance Total Performance Capacity ( Min. - Max. ) C Capacity ( Min. - Max. ) A B C 2.2 ( 1.4 - 2.6 ) 2.50 2.5 ( 1.8 - 4.3 ) 2.65 ( 1.4 - 3.2 ) 3.60 3.6 ( 1.8 - 4.7 ) 3.5 ( 1.5 - 3.6 ) 4.20 4.2 ( 1.9 - 5.1 ) 5.15 ( 1.6 - 5.8 ) 6.00 6.0 ( 2.0 - 7.8 ) 4.4 ( 2.0 - 5.1 ) 2.50 2.50 5.0 ( 2.0 - 6.4 ) 4.85 ( 2.0 - 5.8 ) 2.50 3.60 6.1 ( 2.1 - 7.5 ) 5.1 ( 2.0 - 6.7 ) 2.35 3.95 6.3 ( 2.1 - 8.3 ) 5.5 ( 2.1 - 6.8 ) 2.03 4.87 6.9 ( 2.4 - 8.4 ) 5.0 ( 2.0 - 6.3 ) 3.23 3.23 6.45 ( 2.3 - 8.4 ) 5.2 ( 2.0 - 6.8 ) 3.07 3.58 6.65 ( 2.3 - 8.4 ) 5.6 ( 2.1 - 6.8 ) 2.74 4.56 7.3 ( 2.4 - 8.4 ) 5.4 ( 2.0 - 6.8 ) 3.45 3.45 6.9 ( 2.3 - 8.4 ) 5.6 ( 2.1 - 6.8 ) 3.01 4.29 7.3 ( 2.4 - 8.4 ) 1.77 5.3 ( 2.5 - 6.8 ) 2.18 2.18 2.18 6.55 ( 2.7 - 8.4 ) 2.03 5.4 ( 2.9 - 6.8 ) 2.02 2.02 2.91 6.95 ( 3.0 - 8.4 ) 2.48 5.6 ( 2.9 - 6.8 ) 1.94 1.94 3.26 7.15 ( 3.2 - 8.4 ) 3.02 5.6 ( 2.9 - 6.8 ) 1.66 1.66 3.98 7.3 ( 3.4 - 8.4 ) 1.96 5.55 ( 2.9 - 6.8 ) 1.88 2.71 2.71 7.3 ( 3.4 - 8.4 ) 2.35 5.6 ( 2.9 - 6.8 ) 1.77 2.55 2.98 7.3 ( 3.4 - 8.4 ) 2.88 5.6 ( 2.9 - 6.8 ) 1.51 2.17 3.62 7.3 ( 3.4 - 8.4 ) 2.13 5.6 ( 2.9 - 6.8 ) 1.67 2.81 2.81 7.3 ( 3.4 - 8.4 ) 1.87 5.6 ( 2.9 - 6.8 ) 2.43 2.43 2.43 7.3 ( 3.4 - 8.4 ) 2.23 5.6 ( 2.9 - 6.8 ) 2.31 2.31 2.69 7.3 ( 3.4 - 8.4 ) 2.03 5.6 ( 2.9 - 6.8 ) 2.19 2.56 2.56 7.3 ( 3.4 - 8.4 ) 1.87 5.6 ( 2.9 - 6.8 ) 2.43 2.43 2.43 7.3 ( 3.4 - 8.4 ) NOTE 2.65: SAP-KRV96EHDS 2.65:3.5: SAP-KRV96EHDS SAP-KRV126EHDS Table 2 Indoor Unit Capacity (kW) COOLING HEATING Room Room Room Total Performance Room Room Room Total Performance Capacity ( Min. - Max. ) A B C Capacity ( Min. - Max. ) A B C Indoor Unit Combination Single-room Operation 2-room Operation 3-room Operation 2.65 3.5 2.65 2.65 3.5 2.65 2.65 2.65 3.5 + + + + + + + 2.65 3.5 3.5 2.65 2.65 3.5 3.5 + + + + 2.65 3.5 3.5 3.5 = = = = = = = = = 2.65 3.5 5.3 6.15 7 7.95 8.8 9.65 10.5 2.65 3.50 2.35 2.11 2.53 1.77 1.60 1.46 1.77 2.35 2.79 2.53 1.77 1.60 1.92 1.77 1.77 2.11 1.92 1.77 2.65 3.5 4.7 4.9 5.05 5.3 5.3 5.3 5.3 ( ( ( ( ( ( ( ( ( 1.4 1.5 2.0 2.0 2.0 2.9 2.9 2.9 2.9 - 3.2 3.6 6.0 6.4 6.4 6.4 6.4 6.4 9.4 ) ) ) ) ) ) ) ) ) 3.60 4.20 3.20 3.02 3.45 2.40 2.27 2.16 2.40 3.20 3.53 3.45 2.40 2.27 2.52 2.40 2.40 2.65 2.52 2.40 3.6 4.2 6.4 6.55 6.9 7.2 7.2 7.2 7.2 ( ( ( ( ( ( ( ( ( 1.8 1.9 2.3 2.3 2.3 3.4 3.4 3.4 3.4 - 4.7 5.1 8.3 8.3 8.3 8.3 8.3 8.3 8.3 • When one or more SAP-KRVxxEHDS indoor units are operated concurrently with one or more SAP-KMRVxxEH indoor units, the performance specifications of the SAP-KRVxxEHDS models will decrease by 5% from those listed in the Table 2. • The table lists the wall-mounted type of indoor units as representative models. • For details on the connection of indoor units other than the wall-mounted type, refer to the catalog. ) ) ) ) ) ) ) ) ) CombinationTable-2446EH.fm Page 1 Friday, September 26, 2008 10:20 AM Save this Combination Table! Please be sure to hand over this sheet to the user. 4-Room Outdoor Unit Combination Table SAP-CMRV2446EH <Combinations of Connectable Indoor Units> The combinations of the indoor units listed in Table 1 on page 2 and Table 2 on page 3 are combinations solely of those units which can be operated concurrently. In addition to the combinations listed in the table, other combinations of indoor units are possible provided that the following conditions are satisfied. Conditions: 1. At least two or more indoor units must be connected to the multi outdoor unit. It is not acceptable for only one indoor unit to be connected. 2. The total rated cooling capacity of the indoor units to be connected must be no more than 200% of the rated cooling capacity of the outdoor unit. CAUTION In this case, all the indoor units installed must not be operated concurrently under any circumstances. Otherwise, the air conditioner may not run properly and trouble may occur. Example: When four indoor units are connected If the following holds true • Rated cooling capacity of SAP-CMRV2446EH outdoor unit: C=6.8 (kW) • Rated cooling capacity of indoor units: K1, K2, ... (kW) Then: C x 2 (200%) K1 + K2 + ....... 6.8 x 2 2.2 + 2.65 + 3.5 + 5.15 13.6 13.5 It is therefore possible to connect four units with respective capacities of 2.2 + 2.65 + 3.5 + 5.15. However, since this combination is not found in the 4-room operation column of Table 1, operating all these units concurrently may result in trouble. At a time like this, shut down at least one of the four indoor units to match one of the combinations found in the 3-room operation column of Table 1. NOTE Be sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with only a single unit installed, the returning fluid to the compressor may cause a malfunction. Pub. OI-85264181042002 © SANYO 2008 CombinationTable-2446EH.fm Page 2 Friday, September 26, 2008 10:20 AM < Combinations of operatable indoor units > NOTE NOTE SAP-CMRV2446EH SAP-CMRV2444EH (Rated cooling capacity: 6.8 kW) 2.2: 2.2: SAP-KMRV74/76EH SAP-KMRV74EH 2.65:2.65: SAP-KMRV94/96EH SAP-KMRV94EH 3.5: 3.5: SAP-KMRV124/126EH SAP-KMRV124EH SAP-KRV184EH 5.15:5.15: SAP-KRV184/186EH SAP-KRV244EH 7.1: 7.1: SAP-KRV244/246EH Table 1 Indoor Unit Capacity (kW) COOLING Indoor Unit Combination Single-room Operation 2-room Operation 3-room Operation 4-room Operation 2.2 2.65 3.5 5.15 7.1 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 3.5 3.5 3.5 5.15 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 2.65 3.5 3.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + 2.2 2.65 3.5 5.15 7.1 2.65 3.5 5.15 7.1 3.5 5.15 7.1 5.15 2.2 2.2 2.2 2.2 2.65 2.65 2.65 3.5 3.5 2.65 2.65 2.65 3.5 3.5 3.5 3.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 3.5 2.65 2.65 2.65 2.65 + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + 2.2 2.65 3.5 5.15 2.65 3.5 5.15 3.5 5.15 2.65 3.5 5.15 3.5 5.15 3.5 5.15 2.2 2.2 2.2 2.2 2.65 2.65 2.65 3.5 3.5 2.65 2.65 2.65 3.5 3.5 2.65 2.65 2.65 3.5 + + + + + + + + + + + + + + + + + + 2.2 2.65 3.5 5.15 2.65 3.5 5.15 3.5 5.15 2.65 3.5 5.15 3.5 3.5 2.65 3.5 5.15 3.5 = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = 2.2 2.65 3.5 5.15 7.1 4.4 4.85 5.7 7.35 9.3 5.3 6.15 7.8 9.75 7 8.65 10.6 10.3 6.6 7.05 7.9 9.55 7.5 8.35 10 9.2 10.9 7.95 8.8 10.5 9.65 11.3 10.5 12.2 8.8 9.25 10.1 11.75 9.7 10.55 12.2 11.4 13.05 10.15 11 12.65 11.85 12.7 10.6 11.45 13.1 12.3 A 2.20 2.65 3.50 5.15 6.80 2.20 2.20 2.20 1.95 1.57 2.65 2.54 2.28 1.85 3.23 2.69 2.25 3.40 2.17 2.06 1.88 1.57 1.97 1.79 1.50 1.63 1.38 2.27 2.05 1.72 1.87 1.59 2.27 1.96 1.70 1.62 1.48 1.27 1.54 1.42 1.23 1.31 1.15 1.47 1.36 1.18 1.26 1.18 1.70 1.57 1.38 1.47 B 2.20 2.65 3.50 4.55 5.08 2.65 3.36 4.42 4.95 3.23 3.96 4.55 3.40 2.17 2.06 1.88 1.57 2.37 2.16 1.80 2.59 2.19 2.27 2.05 1.72 2.47 2.11 2.27 1.96 1.70 1.62 1.48 1.27 1.54 1.42 1.23 1.31 1.15 1.78 1.64 1.42 1.52 1.87 1.70 1.57 1.38 1.47 C 2.17 2.48 2.99 3.67 2.37 2.85 3.50 2.59 3.23 2.27 2.70 3.35 2.47 3.10 2.27 2.88 1.70 1.62 1.48 1.27 1.86 1.71 1.48 2.09 1.82 1.78 1.64 1.42 2.01 1.87 1.70 1.57 1.38 1.93 D 1.70 1.95 2.36 2.98 1.86 2.26 2.87 2.09 2.68 1.78 2.16 2.77 2.01 1.87 1.70 2.08 2.67 1.93 HEATING Total Performance Room Room Room Room Capacity 2.2 2.65 3.5 5.15 6.8 4.4 4.85 5.7 6.5 6.65 5.3 5.9 6.7 6.8 6.45 6.65 6.8 6.8 6.5 6.6 6.75 6.8 6.7 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 ( Min. - Max. ) ( 1.4 - 2.6 ) ( 1.4 - 3.2 ) ( 1.5 - 3.6 ) ( 1.6 - 5.8 ) ( 1.6 - 6.8 ) ( 2.0 - 5.1 ) ( 2.0 - 5.8 ) ( 2.0 - 6.7 ) ( 2.1 - 7.7 ) ( 2.1 - 7.9 ) ( 2.0 - 6.3 ) ( 2.0 - 6.8 ) ( 2.1 - 7.9 ) ( 2.1 - 7.9 ) ( 2.0 - 7.9 ) ( 2.1 - 7.9 ) ( 2.1 - 7.9 ) ( 2.1 - 7.9 ) ( 2.5 - 7.7 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 7.9 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) ( 2.9 - 8.1 ) Room Room Room Room A 2.50 3.60 4.20 6.00 8.00 2.50 2.50 2.50 2.38 2.01 3.60 3.51 3.08 2.64 4.00 3.42 2.96 4.28 2.50 2.33 2.26 1.95 2.16 2.06 1.78 1.97 1.69 2.87 2.72 2.35 2.58 2.24 2.87 2.51 2.15 1.94 1.84 1.59 1.76 1.68 1.47 1.60 1.41 1.62 1.55 1.37 1.48 1.42 2.15 2.06 1.84 1.98 B C D 2.50 3.60 4.20 5.72 6.44 3.60 4.09 5.13 5.86 4.00 4.88 5.64 4.28 2.50 2.33 2.26 1.95 3.12 2.97 2.56 3.31 2.84 2.87 2.72 2.35 3.01 2.62 2.87 2.51 2.15 1.94 1.84 1.59 1.76 1.68 1.47 1.60 1.41 2.33 2.23 1.97 2.14 2.39 2.15 2.06 1.84 1.98 2.50 3.35 3.79 4.69 3.12 3.47 4.26 3.31 4.06 2.87 3.17 3.91 3.01 3.74 2.87 3.58 2.15 1.94 1.84 1.59 2.54 2.42 2.12 2.70 2.38 2.33 2.23 1.97 2.49 2.39 2.15 2.06 1.84 2.32 2.15 2.79 3.09 3.82 2.54 2.82 3.53 2.70 3.39 2.33 2.60 3.29 2.49 2.39 2.15 2.41 3.07 2.32 • The table lists the wall-mounted type of indoor units as representative models. • For details on the connection of indoor units other than the wall-mounted type, refer to the catalog. –2– Total Performance Capacity 2.5 3.6 4.2 6.0 8.0 5.0 6.1 6.7 8.1 8.45 7.2 7.6 8.2 8.5 8.0 8.3 8.6 8.55 7.5 8.0 8.3 8.6 8.4 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 ( Min. - Max. ) ( 1.8 4.3 ) ( 1.8 4.7 ) ( 1.9 5.1 ) ( 2.0 7.8 ) ( 2.0 8.0 ) ( 2.0 6.4 ) ( 2.1 7.5 ) ( 2.1 8.3 ) ( 2.4 9.0 ) ( 2.4 9.0 ) ( 2.3 8.5 ) ( 2.3 8.5 ) ( 2.4 9.0 ) ( 2.4 9.0 ) ( 2.3 8.5 ) ( 2.4 9.0 ) ( 2.4 9.0 ) ( 2.4 9.0 ) ( 2.7 8.5 ) ( 3.0 9.0 ) ( 3.2 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) ( 3.4 9.0 ) CombinationTable-2446EH.fm Page 3 Friday, September 26, 2008 10:20 AM NOTE 2.65: SAP-KRV96EHDS 3.5: SAP-KRV126EHDS Table 2 Indoor Unit Capacity (kW) COOLING Indoor Unit Combination Single-room Operation 2-room Operation 3-room Operation 4-room Operation 2.65 3.5 2.65 2.65 3.5 2.65 2.65 2.65 3.5 2.65 2.65 2.65 + + + + + + + + + + 2.65 3.5 3.5 2.65 2.65 3.5 3.5 2.65 2.65 2.65 + 2.65 + 3.5 + 3.5 + 3.5 + 2.65 + 2.65 + 2.65 + 3.5 + 3.5 + 3.5 Room Room Room Room = 2.65 = 3.5 = 5.3 = 6.15 = 7 = 7.95 = 8.8 = 9.65 = 10.5 = 10.6 = 11.45 = 12.3 A 2.65 3.50 2.55 2.41 3.00 2.08 1.88 1.72 2.08 1.56 1.45 1.35 B 2.55 3.19 3.00 2.08 1.88 2.27 2.08 1.56 1.45 1.35 C 2.08 2.49 2.27 2.08 1.56 1.45 1.78 D HEATING Total Performance Capacity 2.65 3.5 5.1 5.6 6.0 6.25 6.25 6.25 6.25 1.56 6.25 1.91 6.25 1.78 6.25 ( Min. - Max. ) ( 1.4 - 3.2 ) ( 1.5 - 3.6 ) ( 2.0 - 5.8 ) ( 2.0 - 6.3 ) ( 2.0 - 6.3 ) ( 2.9 - 7.2 ) ( 2.9 - 7.2 ) ( 2.9 - 7.2 ) ( 2.9 - 7.2 ) ( 2.9 - 7.5 ) ( 2.9 - 7.5 ) ( 2.9 - 7.5 ) Room Room Room Room A 3.60 4.20 3.58 3.42 3.80 2.63 2.49 2.37 2.63 2.00 1.92 1.85 B C 3.58 3.98 3.80 2.63 2.49 2.77 2.63 2.00 1.92 1.85 2.63 2.91 2.77 2.63 2.00 1.92 2.15 D Total Performance Capacity 3.6 4.2 7.15 7.4 7.6 7.9 7.9 7.9 7.9 2.00 8.0 2.24 8.0 2.15 8.0 ( Min. - Max. ) ( 1.8 4.7 ) ( 1.9 5.1 ) ( 2.3 8.1 ) ( 2.3 8.1 ) ( 2.3 8.1 ) ( 3.4 8.5 ) ( 3.4 8.5 ) ( 3.4 8.5 ) ( 3.4 8.5 ) ( 3.4 8.5 ) ( 3.4 8.5 ) ( 3.4 8.5 ) • When one or more SAP-KRVxxEHDS indoor units are operated concurrently with one or more SAP-KMRVxxEH indoor units, the performance specifications of the SAP-KRVxxEHDS models will decrease by 5% from those listed in the Table 2. • The table lists the wall-mounted type of indoor units as representative models. • For details on the connection of indoor units other than the wall-mounted type, refer to the catalog. –3– CombinationTable-3146EH.fm Page 1 Friday, September 26, 2008 10:31 AM Save this Combination Table! Please be sure to hand over this sheet to the user. 4-Room Outdoor Unit Combination Table SAP-CMRV3146EH <Combinations of Connectable Indoor Units> The combinations of the indoor units listed in Table 1 on page 2 and Table 2 on page 3 are combinations solely of those units which can be operated concurrently. In addition to the combinations listed in the table, other combinations of indoor units are possible provided that the following conditions are satisfied. Conditions: 1. At least two or more indoor units must be connected to the multi outdoor unit. It is not acceptable for only one indoor unit to be connected. 2. The total rated cooling capacity of the indoor units to be connected must be no more than 200% of the rated cooling capacity of the outdoor unit. CAUTION In this case, all the indoor units installed must not be operated concurrently under any circumstances. Otherwise, the air conditioner may not run properly and trouble may occur. Example: When four indoor units are connected If the following holds true • Rated cooling capacity of SAP-CMRV3146EH outdoor unit: C=8 (kW) • Rated cooling capacity of indoor units: K1, K2, ... (kW) Then: C x 2 (200%) K1 + K2 + ....... 8 x 2 2.2 + 2.2 + 3.5 + 7.1 16 15 It is therefore possible to connect four units with respective capacities of 2.2 + 2.2 + 3.5 + 7.1. However, since this combination is not found in the 4-room operation column of Table 1, operating all these units concurrently may result in trouble. At a time like this, shut down at least one of the four indoor units to match one of the combinations found in the 3-room operation column of Table 1. NOTE Be sure to operate the air conditioning system only when 2 or more indoor units have been installed. If operated with only a single unit installed, the returning fluid to the compressor may cause a malfunction. Pub. OI-85264181043002 © SANYO 2008 CombinationTable-3146EH.fm Page 2 Friday, September 26, 2008 10:31 AM < Combinations of operatable indoor units > SAP-CMRV3146EH (Rated cooling capacity: 8.0 kW) NOTE 2.2: SAP-KMRV74/76EH 2.65: SAP-KMRV94/96EH 3.5: SAP-KMRV124/126EH 5.15: SAP-KRV184/186EH 7.1: SAP-KRV244/246EH Table 1 Indoor Unit Combination Single-room Operation 2-room Operation 3-room Operation 4-room Operation 2.2 2.65 3.5 5.15 7.1 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 3.5 3.5 3.5 5.15 5.15 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 2.65 2.65 2.65 2.65 3.5 3.5 3.5 3.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 2.65 2.65 3.5 + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + 2.2 2.65 3.5 5.15 7.1 2.65 3.5 5.15 7.1 3.5 5.15 7.1 5.15 7.1 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 3.5 3.5 3.5 5.15 5.15 2.65 2.65 2.65 2.65 3.5 3.5 3.5 5.15 3.5 3.5 3.5 5.15 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 2.65 3.5 3.5 2.65 2.65 2.65 2.65 2.65 3.5 3.5 + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + 2.2 2.65 3.5 5.15 7.1 2.65 3.5 5.15 7.1 3.5 5.15 7.1 5.15 7.1 2.65 3.5 5.15 7.1 3.5 5.15 7.1 5.15 3.5 5.15 7.1 5.15 2.2 2.2 2.2 2.2 2.2 2.65 2.65 2.65 2.65 3.5 3.5 5.15 2.65 2.65 2.65 3.5 3.5 3.5 3.5 2.65 2.65 2.65 3.5 3.5 3.5 3.5 + + + + + + + + + + + + + + + + + + + + + + + + + + 2.2 2.65 3.5 5.15 7.1 2.65 3.5 5.15 7.1 3.5 5.15 5.15 2.65 3.5 5.15 3.5 5.15 3.5 5.15 2.65 3.5 5.15 3.5 5.15 3.5 3.5 = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = 2.2 2.65 3.5 5.15 7.1 4.4 4.85 5.7 7.35 9.3 5.3 6.15 7.8 9.75 7 8.65 10.6 10.3 12.3 6.6 7.05 7.9 9.55 11.5 7.5 8.35 10 12 9.2 10.9 12.8 12.5 14.5 7.95 8.8 10.5 12.4 9.65 11.3 13.3 13 10.5 12.2 14.1 13.8 8.8 9.25 10.1 11.8 13.7 9.7 10.6 12.2 14.2 11.4 13.1 14.7 10.2 11 12.7 11.9 13.5 12.7 14.4 10.6 11.5 13.1 12.3 14 13.2 14 Room A 2.20 2.65 3.50 5.15 7.10 2.20 2.20 2.20 2.14 1.81 2.65 2.54 2.46 2.11 3.40 3.03 2.61 3.95 3.36 2.20 2.20 2.03 1.77 1.53 2.11 1.95 1.72 1.47 1.82 1.60 1.38 1.41 1.22 2.43 2.26 2.00 1.71 2.13 1.88 1.60 1.64 2.65 2.30 1.99 2.03 1.88 1.82 1.71 1.50 1.28 1.76 1.66 1.44 1.24 1.54 1.35 1.20 1.70 1.60 1.39 1.49 1.30 1.39 1.23 2.00 1.85 1.62 1.72 1.52 1.61 2.00 Room B 2.20 2.65 3.50 5.01 5.84 2.65 3.36 4.79 5.64 3.40 4.47 5.29 3.95 4.64 2.20 2.20 2.03 1.77 1.53 2.54 2.35 2.07 1.77 2.89 2.55 2.19 3.30 2.85 2.43 2.26 2.00 1.71 2.81 2.48 2.11 3.18 2.65 2.30 1.99 2.99 1.88 1.82 1.71 1.50 1.28 1.76 1.66 1.44 1.24 1.54 1.35 1.20 2.05 1.93 1.68 1.79 1.57 2.20 1.95 2.00 1.85 1.62 1.72 1.52 2.13 2.00 Room C 2.20 2.65 3.23 4.15 4.94 2.54 3.10 4.02 4.75 2.89 3.75 4.44 3.30 3.93 2.43 2.98 3.89 4.58 2.81 3.65 4.29 3.18 2.65 3.39 4.03 2.99 1.88 1.82 1.71 1.50 1.28 2.12 2.00 1.74 1.50 2.46 2.15 2.80 2.05 1.93 1.68 2.36 2.07 2.20 1.95 2.00 1.85 1.62 2.28 2.01 2.13 2.00 Indoor Unit Capacity (kW) COOLING Total Performance Room Room Room D Capacity ( Min. - Max. ) A B 2.2 ( 1.5 - 2.6 ) 2.50 2.65 ( 1.5 - 3.2 ) 3.60 3.5 ( 1.6 - 3.6 ) 4.20 5.15 ( 1.7 - 5.8 ) 6.00 8.50 7.1 ( 1.8 - 7.4 ) 4.4 ( 2.0 - 5.1 ) 2.50 2.50 4.85 ( 2.0 - 5.8 ) 2.50 3.60 5.7 ( 2.0 - 6.7 ) 2.50 4.20 7.15 ( 2.2 - 7.7 ) 2.50 6.00 7.65 ( 2.3 - 8.8 ) 2.01 6.84 5.3 ( 2.0 - 6.5 ) 3.60 3.60 5.9 ( 2.0 - 7.4 ) 3.51 4.09 7.25 ( 2.3 - 8.5 ) 3.24 5.41 7.75 ( 2.3 - 8.8 ) 2.68 6.32 6.8 ( 2.2 - 8.4 ) 4.00 4.00 7.5 ( 2.6 - 8.8 ) 3.60 5.15 7.9 ( 2.6 - 8.8 ) 3.01 6.09 7.9 ( 2.6 - 8.8 ) 4.50 4.50 3.89 5.51 8.0 ( 2.7 - 8.8 ) 6.6 ( 2.0 - 7.7 ) 2.50 2.50 7.05 ( 2.2 - 8.4 ) 2.47 2.47 7.3 ( 2.4 - 8.6 ) 2.34 2.34 7.7 ( 2.7 - 9.0 ) 2.01 2.01 8.0 ( 2.9 - 9.0 ) 1.71 1.71 7.2 ( 2.3 - 8.6 ) 2.23 3.21 7.4 ( 2.6 - 9.0 ) 2.12 3.06 7.8 ( 2.9 - 9.0 ) 1.86 2.68 8.0 ( 2.9 - 9.0 ) 1.61 2.32 7.6 ( 2.7 - 9.0 ) 2.03 3.41 7.9 ( 2.9 - 9.0 ) 1.79 3.01 8.0 ( 2.9 - 9.0 ) 1.55 2.60 8.0 ( 2.9 - 9.0 ) 1.62 3.89 8.0 ( 2.9 - 9.0 ) 1.38 3.32 7.3 ( 2.5 - 8.6 ) 2.95 2.95 7.5 ( 2.7 - 9.0 ) 2.81 2.81 7.9 ( 2.9 - 9.0 ) 2.51 2.51 8.0 ( 2.9 - 9.0 ) 2.16 2.16 7.75 ( 2.7 - 9.0 ) 2.70 3.15 8.0 ( 2.9 - 9.0 ) 2.43 2.83 8.0 ( 2.9 - 9.0 ) 2.08 2.42 8.0 ( 2.9 - 9.0 ) 2.17 3.62 7.95 ( 2.9 - 9.0 ) 3.03 3.03 8.0 ( 2.9 - 9.0 ) 2.73 2.73 8.0 ( 2.9 - 9.0 ) 2.34 2.34 2.44 3.48 8.0 ( 2.9 - 9.0 ) 1.88 7.5 ( 2.9 - 9.2 ) 2.18 2.18 2.19 7.65 ( 2.9 - 9.2 ) 1.99 1.99 2.72 7.85 ( 2.9 - 9.2 ) 1.91 1.91 3.51 8.0 ( 2.9 - 9.2 ) 1.71 1.71 4.15 8.0 ( 2.9 - 9.2 ) 1.47 1.47 2.12 7.75 ( 2.9 - 9.2 ) 1.85 1.85 2.64 7.95 ( 2.9 - 9.2 ) 1.79 1.79 3.38 8.0 ( 2.9 - 9.2 ) 1.61 1.61 4.01 8.0 ( 2.9 - 9.2 ) 1.37 1.37 2.46 8.0 ( 2.9 - 9.2 ) 1.72 1.72 3.16 8.0 ( 2.9 - 9.2 ) 1.55 1.55 2.80 8.0 ( 2.9 - 9.2 ) 1.38 1.38 2.05 7.85 ( 2.9 - 9.2 ) 1.73 2.49 2.55 8.0 ( 2.9 - 9.2 ) 1.67 2.41 3.26 8.0 ( 2.9 - 9.2 ) 1.50 2.16 2.36 8.0 ( 2.9 - 9.2 ) 1.62 2.33 3.05 8.0 ( 2.9 - 9.2 ) 1.44 2.08 2.20 8.0 ( 2.9 - 9.2 ) 1.56 2.61 2.87 8.0 ( 2.9 - 9.2 ) 1.39 2.34 2.00 8.0 ( 2.9 - 9.2 ) 2.35 2.35 2.45 8.0 ( 2.9 - 9.2 ) 2.26 2.26 3.15 8.0 ( 2.9 - 9.2 ) 2.01 2.01 2.28 8.0 ( 2.9 - 9.2 ) 2.17 2.17 2.95 8.0 ( 2.9 - 9.2 ) 1.94 1.94 2.13 8.0 ( 2.9 - 9.2 ) 2.09 2.44 2.35 2.35 2.00 8.0 ( 2.9 - 9.2 ) Room C 2.50 3.56 3.93 4.83 5.82 3.21 3.57 4.46 5.47 3.41 4.30 5.26 3.89 4.70 2.95 3.28 4.18 5.09 3.15 4.04 4.90 3.62 3.03 3.90 4.73 3.48 2.18 1.99 1.91 1.71 1.47 2.67 2.57 2.32 1.98 2.88 2.60 3.32 2.49 2.41 2.16 2.72 2.42 2.61 2.34 2.35 2.26 2.01 2.53 2.27 2.44 2.35 HEATING Total Performance Room D Capacity ( Min. - Max. 2.5 ( 1.8 - 4.3 3.6 ( 1.8 - 4.7 4.2 ( 1.9 - 5.1 6.0 ( 2.0 - 7.8 8.5 ( 2.0 - 8.8 5.0 ( 2.0 - 6.4 6.1 ( 2.1 - 7.5 6.7 ( 2.3 - 8.3 8.5 ( 3.0 - 9.4 8.85 ( 3.0 - 9.8 7.2 ( 2.4 - 8.5 7.6 ( 2.6 - 8.5 8.65 ( 3.3 - 9.4 9.0 ( 3.3 - 9.8 8.0 ( 2.9 - 8.5 8.75 ( 3.4 - 9.8 9.1 ( 3.4 - 9.8 9.0 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 7.5 ( 2.7 - 9.0 8.5 ( 3.0 - 9.2 8.6 ( 3.2 - 9.8 8.85 ( 3.4 - 9.8 9.25 ( 3.4 - 9.8 8.65 ( 3.3 - 9.3 8.75 ( 3.4 - 9.8 9.0 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 8.85 ( 3.4 - 9.8 9.1 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 8.85 ( 3.4 - 9.4 8.9 ( 3.4 - 9.8 9.2 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 9.0 ( 3.4 - 9.8 9.3 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 9.1 ( 3.4 - 9.8 9.35 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 9.4 ( 3.4 - 9.8 2.18 8.7 ( 3.4 - 9.8 2.87 8.85 ( 3.4 - 9.8 3.21 8.95 ( 3.4 - 9.8 4.11 9.25 ( 3.4 - 9.8 4.99 9.4 ( 3.4 - 9.8 2.67 9.05 ( 3.4 - 9.8 3.00 9.15 ( 3.4 - 9.8 3.86 9.4 ( 3.4 - 9.8 4.67 9.4 ( 3.4 - 9.8 2.88 9.2 ( 3.4 - 9.8 3.71 9.4 ( 3.4 - 9.8 3.32 9.4 ( 3.4 - 9.8 2.49 9.2 ( 3.4 - 9.8 2.81 9.3 ( 3.4 - 9.8 3.59 9.4 ( 3.4 - 9.8 2.72 9.4 ( 3.4 - 9.8 3.46 9.4 ( 3.4 - 9.8 2.61 9.4 ( 3.4 - 9.8 3.34 9.4 ( 3.4 - 9.8 2.35 9.4 ( 3.4 - 9.8 2.63 9.4 ( 3.4 - 9.8 3.36 9.4 ( 3.4 - 9.8 2.53 9.4 ( 3.4 - 9.8 3.24 9.4 ( 3.4 - 9.8 2.44 9.4 ( 3.4 - 9.8 2.35 9.4 ( 3.4 - 9.8 • The table lists the wall-mounted type of indoor units as representative models. • For details on the connection of indoor units other than the wall-mounted type, refer to the catalog. –2– ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) CombinationTable-3146EH.fm Page 3 Friday, September 26, 2008 10:31 AM NOTE 2.65: SAP-KRV96EHDS 3.5: SAP-KRV126EHDS Table 2 Indoor Unit Combination Single-room Operation 2-room Operation 3-room Operation 4-room Operation 2.65 3.5 2.65 2.65 3.5 2.65 2.65 2.65 3.5 2.65 2.65 2.65 2.65 3.5 + + + + + + + + + + + + 2.65 3.5 3.5 2.65 2.65 3.5 3.5 2.65 2.65 2.65 3.5 3.5 + 2.65 + 3.5 + 3.5 + 3.5 + 2.65 + 2.65 + 2.65 + 3.5 + 3.5 + 3.5 + 3.5 + 3.5 + 3.5 + 3.5 = = = = = = = = = = = = = = 2.65 3.5 5.3 6.15 7 7.95 8.8 9.65 10.5 10.6 11.5 12.3 13.2 14 Room Room Room A B C 2.65 3.50 2.60 2.60 2.43 3.22 3.18 3.18 2.30 2.30 2.30 2.14 2.14 2.82 2.02 2.67 2.67 2.52 2.52 2.52 1.90 1.90 1.90 1.76 1.76 1.76 1.64 1.64 2.16 1.53 2.02 2.02 1.90 1.90 1.90 Indoor Unit Capacity (kW) COOLING HEATING Total Performance Total Performance Room Room Room Room Room D Capacity ( Min. - Max. ) A B C D Capacity ( Min. - Max. 2.65 ( 1.5 - 3.2 ) 3.60 3.6 ( 1.8 - 4.7 3.5 ( 1.6 - 3.6 ) 4.20 4.2 ( 1.9 - 5.1 5.2 ( 2.0 - 6.0 ) 3.50 3.50 7.0 ( 2.4 - 8.3 5.65 ( 2.0 - 7.0 ) 3.44 4.01 7.5 ( 2.6 - 8.3 3.93 3.93 7.85 ( 2.9 - 8.3 6.35 ( 2.2 - 8.0 ) 6.9 ( 2.5 - 8.1 ) 2.88 2.88 2.88 8.65 ( 3.4 - 9.2 7.1 ( 2.7 - 8.5 ) 2.75 2.75 3.21 8.7 ( 3.4 - 9.6 7.35 ( 2.7 - 8.5 ) 2.64 3.08 3.08 8.8 ( 3.4 - 9.6 2.97 2.97 2.97 8.9 ( 3.4 - 9.6 7.55 ( 2.9 - 8.5 ) 1.90 7.6 ( 2.9 - 8.7 ) 2.30 2.30 2.30 2.30 9.2 ( 3.4 - 9.6 2.32 7.6 ( 2.9 - 8.7 ) 2.21 2.21 2.21 2.58 9.2 ( 3.4 - 9.6 2.16 7.6 ( 2.9 - 8.7 ) 2.12 2.12 2.48 2.48 9.2 ( 3.4 - 9.6 2.02 7.6 ( 2.9 - 8.7 ) 2.04 2.39 2.39 2.39 9.2 ( 3.4 - 9.6 2.30 2.30 2.30 2.30 9.2 ( 3.4 - 9.6 1.90 7.6 ( 2.9 - 8.7 ) • When one or more SAP-KRVxxEHDS indoor units are operated concurrently with one or more SAP-KMRVxxEH indoor units, the performance specifications of the SAP-KRVxxEHDS models will decrease by 5% from those listed in the Table 2. • The table lists the wall-mounted type of indoor units as representative models. • For details on the connection of indoor units other than the wall-mounted type, refer to the catalog. –3– ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) SANYO Electric Co., Ltd. Osaka, Japan Jan. / 2010 Printed in Japan (T)