Transcript
g 7.1.4 GE Complete UPS shutdown (No Load supply) The Load must be disconnected. Initial status: Load supplied from Inverter. 1. Press “total off” button. • Load is disconnected from UPS. • Rectifier is shut down and all output and input contactors will be opened. • LED’s, Rectifier, Inverter and Load are OFF. 2. Open Q1 (Pos. O). • LED service check lights up. 3. Disconnect the Battery from the UPS in case of External Battery. • Wait 5 minutes for DC-Link Capacitors discharge. 4. Disconnect the Utility. • All LED’s are OFF. End of procedure OPM_SGS_USM_10K_40K_0US_V010.doc 46/88 Operating Manual SG Series 10, 20, 30 & 40 kVA