High Pressure
Control Closed?
NO
NO
Line Voltage To
Compressor
Contactor Coil?
Resets?
NO
NO
Replace HPCO
Resets
&
Trips
YES
Refrigerant Pressure
Above Cut-out?
YES
Clean Condenser,
Check Fan Motor
Check Fan Cycle Control
NO
Clean Condenser,
Check Fan Motor,
Check Fan Cycle Control &
Refrigeration System
Replace Relay
Low Pressure
Control Closed?
NO
YES
YES
Repair Wiring
Verify:
Refrigerant Pressure is Higher Than
LPCO Cut-in
Both Shut-off Valves are Open
Repair/Replace Liquid Line Solenoid
Locate and Repair Refrigerant Leak
Replace LPCO Switch
Line Voltage At
Liquid Line Solenoid
Valve?