Download BCP-8 Hydronic Manual - Weil
Transcript
BCP-8W BCP-8X AND +<'521,&6(48(1&,1*%2,/(5&21752/$1'(;7(16,21 ,167$//$7,21$1'23(5$7,21,16758&7,2160$18$/ 86(523(5$7,21,16758&7,2160$18$/ BCP-8W HYDRONIC SEQUENCING CONTROL SYS=144F OD=35F Stage A Stage E SYSTEM Stage B Stage F DHW PUMP Stage C Stage G COMB. AIR Stage D Stage H ENCLOSED ENERGY MANAGEMENT EQUIPMENT OUTPUT RATING: 2A, 120VAC. MAXIMUM 15A TOTAL FOR ALL CIRCUITS LISTED 99RA C <AB > DE HI LO STAGE GH JK -- OFF MENU US INPUT RATINGS: 120VAC 60Hz, 12VA MAX CAUTION: Risk of Electric Shock. PWR Use Copper Conductors Only. PROGRAM L N Stage A Stage B Stage C Stage D Stage E Stage F DHW COMB. Stage G Stage H SYSTEM PUMP AIR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 :$51,1* DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS RUN AUX 1 SHUTDOWN /TSTAT PROVE TEMP OUTDOORRETURN DHW TEMP TEMP /SETBACK RS485 25 26 27 28 29 30 31 32 33 34 35 36 37 38 7KLV:HLO0F/DLQFRQWUROLVVWULFWO\DQRSHUDWLQJFRQWUROLWVKRXOGQHYHUEHXVHGDVD SULPDU\OLPLWRUVDIHW\FRQWURO$OOHTXLSPHQWPXVWKDYHLWVRZQFHUWLILHGOLPLWDQGVDIHW\ FRQWUROVUHTXLUHGE\ORFDOFRGHV7KHLQVWDOOHUPXVWYHULI\SURSHURSHUDWLRQDQGFRUUHFWDQ\ VDIHW\SUREOHPVSULRUWRWKHLQVWDOODWLRQRIWKLV:HLO0F/DLQFRQWURO Part Number 550-100-071/0408 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO &RQWHQWV %&3:/$<287 3 %&3:29(59,(: 4 81'(567$1',1*23(5$7,21&21&(37 5 Reset Ratio/Outdoor Reset . . . . . . . . . . . . . . . . 5 PID Operation . . . . . . . . . . . . . . . . . . . . . . . 6 OSS Operation . . . . . . . . . . . . . . . . . . . . . . 6 0DNH6XUH<RX+DYHWKH5LJKW&RQWURO 7 ,1,7,$/6(783 7 6HOHFWLQJWKH6\VWHP)HDWXUHV 7 ,167$//$7,21 0RXQWLQJWKH(QFORVXUH ,QVWDOOWKH6HQVRUV 9 System Sensor Installation . . . . . . . . . . . . . . . . 9 Outdoor Sensor Installation . . . . . . . . . . . . . . . . 9 :LULQJ 10 Wiring the Power (Terminals 1, 2) . . . . . . . . . . . . 10 Wiring the Sensors . . . . . . . . . . . . . . . . . . . 10 Wiring the Domestic Hot Water (DHW) Sensor (Terminals 33, 34) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Wiring the Shutdown (Terminals 35, 36) . . . . . . . . 11 Wiring the T-STAT (Terminals 35, 36) . . . . . . . . . . 11 Wiring the Setback (Terminals 35, 36) . . . . . . . . . 11 Connecting to the BCP-8X Panels and 420MOD Interface13 Selecting the BCP-8X Panel Letter . . . . . . . . . . . 13 ,167$//(50(186(48(1&( 14 6WDUWXS6HWWLQJV 17 Program Change Settings . . . . . . . . . . . . . . . . 17 Startup Sequence . . . . . . . . . . . . . . . . . . . . 17 Control Mode . . . . . . . . . . . . . . . . . . . . . . 17 Display Unit . . . . . . . . . . . . . . . . . . . . . . . 17 Setting the 4mA and 20mA Set Points (Available in 4-20mA EMS only) . . . . . . . . . . . . . . . . . . . . . . . . 17 DHW Piping . . . . . . . . . . . . . . . . . . . . . . . 18 DHW Pump Output . . . . . . . . . . . . . . . . . . . 18 Combustion Air Damper Output . . . . . . . . . . . . . 18 External Input Mode . . . . . . . . . . . . . . . . . . . 18 Burner Type . . . . . . . . . . . . . . . . . . . . . . . 19 Boiler Output . . . . . . . . . . . . . . . . . . . . . . 19 Total Boilers . . . . . . . . . . . . . . . . . . . . . . . 19 Staging . . . . . . . . . . . . . . . . . . . . . . . . . 19 Sequence . . . . . . . . . . . . . . . . . . . . . . . . 19 Control Logic . . . . . . . . . . . . . . . . . . . . . . 19 Sensor Fault . . . . . . . . . . . . . . . . . . . . . . . 20 6HWWLQJWKH&RQWUROWR)DFWRU\'HIDXOWV 20 2SHUDWLQJ6HWWLQJV 20 Program Change Settings . . . . . . . . . . . . . . . . 20 Season . . . . . . . . . . . . . . . . . . . . . . . . . 21 Reset Ratio . . . . . . . . . . . . . . . . . . . . . . . 21 Customized Reset Ratio. . . . . . . . . . . . . . . . . 21 Set Point (Not Adjustable in EMS Mode) . . . . . . . . 22 Outdoor Cutoff Temperature. . . . . . . . . . . . . . . 22 Target Offset. . . . . . . . . . . . . . . . . . . . . . . 22 Minimum Target . . . . . . . . . . . . . . . . . . . . . 23 2 Maximum Target. . . . . . . . . . . . . . . . . . . . . 23 %RLOHU0LQLPXP5HWXUQ 23 Minimum Return . . . . . . . . . . . . . . . . . . . . . 23 Return Lag. . . . . . . . . . . . . . . . . . . . . . . . 24 6\VWHP6HWWLQJV 24 Program Change Settings . . . . . . . . . . . . . . . . 24 6WDJH6HWWLQJV 24 Reaction Time . . . . . . . . . . . . . . . . . . . . . . 24 Purge Delay . . . . . . . . . . . . . . . . . . . . . . . 24 Minimum Runtime . . . . . . . . . . . . . . . . . . . . 24 Standby Delay . . . . . . . . . . . . . . . . . . . . . . 25 Last Stage Hold . . . . . . . . . . . . . . . . . . . . . 25 Throttle Range. . . . . . . . . . . . . . . . . . . . . . 25 /HDG6HWWLQJV 25 Lead Boiler . . . . . . . . . . . . . . . . . . . . . . . 26 Rotate Mode. . . . . . . . . . . . . . . . . . . . . . . 26 6HWEDFN6FKHGXOH 26 Setback . . . . . . . . . . . . . . . . . . . . . . . . . 26 Boost . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Boost Period. . . . . . . . . . . . . . . . . . . . . . . 27 Day/Night Schedules . . . . . . . . . . . . . . . . . . 27 Set Present Time . . . . . . . . . . . . . . . . . . . . 27 '+:6HWWLQJV 2 DHW Priority Timer (Available with Parallel DHW Piping)28 DHW Set Point (Requires an Optional DHW Temperature Sensor) . . . . . . . . . . . . . . . . . . . . . . . . . 28 3XPS9DOYHDQG&RPEXVWLRQ$LU'DPSHU2SHUDWLRQ 29 Run-On . . . . . . . . . . . . . . . . . . . . . . . . . 29 Pump Exercise . . . . . . . . . . . . . . . . . . . . . 29 0DLQWHQDQFH 30 System & Outdoor Sensor Trim . . . . . . . . . . . . . 30 +LVWRU\ 30 &RQ¿JXUDWLRQ . . . . . . . . . . . . . . . . . . . . . . 30 Display and Buttons . . . . . . . . . . . . . . . . . . . 30 %RLOHU6HWWLQJV 32 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 32 RunTime. . . . . . . . . . . . . . . . . . . . . . . . . 32 7528%/(6+227,1* 33 08/7,3/(%2,/(56:,7+380363,3,1*:,5,1* ',$*5$06 34 86(50(186(48(1&( 35 Program Change Settings . . . . . . . . Season . . . . . . . . . . . . . . . . . Set Point (Not Adjustable in EMS Mode) Reset Ratio . . . . . . . . . . . . . . . Customized Reset Ratio. . . . . . . . . Outdoor Cutoff Temperature. . . . . . . Setback . . . . . . . . . . . . . . . . . Day/Night Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 35 36 36 36 37 37 37 63(&,),&$7,216 40 %&3:6SHFL¿FDWLRQV 40 %&3;6SHFL¿FDWLRQV 40 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO %&3:/$<287 Program Switch to restrict access to function changes. This Switch is covered with Enclosure Wiring Cover. LEDs indicate associated relay’s status Button function is presented on bottom row of the display. BCP-8W HYDRONIC SEQUENCING CONTROL SYS=144F Stage A Stage E SYSTEM Stage B Stage F DHW PUMP Stage C Stage G COMB. AIR Stage D Stage H C OUTPUT RATING: 2A, 120VAC. MAXIMUM 15A TOTAL FOR ALL CIRCUITS PWR L N 1 2 Use Copper Conductors Only. STAGE PROGRAM DHW PUMP DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS RUN COMB. AIR 3 4 15 16 17 18 19 20 21 22 23 24 Output Relays to manage the stages. MENU LISTED 99RA Stage G Stage H SYSTEM 9 10 11 12 13 14 JK OFF US Stage A Stage B Stage C Stage D Stage E Stage F 5 6 7 8 GH -- ENCLOSED ENERGY MANAGEMENT EQUIPMENT INPUT RATINGS: 120VAC 60Hz, 12VA MAX CAUTION: Risk of Electric Shock. <AB > DE HI LO OD=35F PRESS + - TEMP OUTDOOR RETURN TEMP TEMP DHW SHUTDOWN /TSTAT /SETBACK RS485 PROVE 25 26 27 28 29 30 31 32 33 34 35 36 37 38 When connecting Temperature Sensors, no Polarity is observed. Prove terminals must be connected for BCP-8 to operate stages. System Output controls pumps, valves, or other system components. DHW Pump and Comb. Air relays are controlled when configured. Connect to Extension panels to add additional stages or connect to 420MOD Interface for external set point. 3 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO %&3:29(59,(: 6(48(1&(6837267$*(6:,7+38036259$/9(6 The BCP-8W is the perfect control whenever multiple boiler stages are required for Hydronic heating applications. The BCP-8W controls the stages and their pumps or valves to maintain a precise system set point. 3,'2529(56,=('6<67(0266/2*,& The BCP-8W’s control algorithm allows it to look at the rate of change in the system. If the load is changing quickly, the BCP-8W can be set to OSS sequencing where it will react based on load changes. If the system oscillation is minimal as in heating applications, the %&3:ZLOOPDNHVORZDQGJUDGXDORXWSXWDGMXVWPHQWV7KHUHIRUHWKH%&3:DGDSWVWRVSHFL¿FV\VWHPUHTXLUHPHQWVDQGPLQLPL]HV oscillation around the set point. ',*,7$/',63/$<2)$//6<67(06(77,1*6 The BCP-8W’s alphanumeric digital display names each system parameter in simple English and shows its precise value. The easy to IROORZPHQXV\VWHPDOORZVXVHUVWRTXLFNO\PDNHFKDQJHVWRDQ\V\VWHPVHWWLQJZLWKRXWKDYLQJWROHDUQDQ\VSHFLDOL]HGFRGHVRUNH\ commands. $8720$7,&527$7,21$021*67$*(6 5RWDWLQJWKH¿UVWVWDJHWREHDFWLYDWHGRQDFDOOIRURXWSXWSURPRWHVHYHQZHDURQHDFKERLOHU7KH%&3:KDVWKUHHPRGHVRIURWDWLRQ Manual, First-On/First-Off (FOFO), or Time. The Time rotates the lead stage every selected period from every hour to every 41 days. 287'2255(6(7:,7+&86720,=$%/(&859( With its Outdoor reset feature, the BCP-8W is capable of changing its temperature target based on the outdoor temperature. It offers VHYHUDOSDUDPHWHUVWKDWFDQEHXVHGWR¿QHWXQHWKHUHVHWFXUYHOffset, Minimum, and Maximum Targets, and Night Setback Schedule or Setback using an External Signal. )XUWKHUPRUHDFXVWRPL]DEOHRXWGRRUUHVHWFXUYHKDVEHHQLQFRUSRUDWHGIRUXQLTXHDSSOLFDWLRQV ZKHUHVWDQGDUGUHVHWUDWLRVZLOOQRWVXI¿FH 67$1'%<%2,/(5237,21 $Q\RIWKH%&3:KHDWLQJERLOHUVFDQEHFRQ¿JXUHGDVD6WDQGE\ZLWKDQDGMXVWDEOH6WDQGE\GHOD\$VVLJQLQJDVSHFL¿FERLOHUWR work in standby mode will remove it from the rotation. In this mode, the boiler will be used for backup in large demand periods where WKHSULPDU\ERLOHUVZLOOQRWVXI¿FH 6<67(0$1'&20%867,21$,5'$03(52873876:,7+3529(,1387 These outputs work with the control logic to operate a primary system pump and a combustion air damper. In addition, a System Prove LQSXWFDQEHZLUHGLQWRFKHFNWKHVWDWXVRIHLWKHURIWKHFRPSRQHQWVHQHUJL]HGE\WKHRXWSXWVEHIRUHWKHVWDJHVFDQEHDFWLYDWHG 1250$//2+,/2+,253$5$//(//2/2+,+,6(48(1&,1* The BCP-8W can sequence boilers as needed)RUKHDWLQJV\VWHPVZKHUHKLJKHUHI¿FLHQF\LVDFKLHYHGXVLQJORZHU¿ULQJVWDJHVWKH %&3:RIIHUVWKH3DUDOOHO6HTXHQFLQJRSWLRQ,WVHTXHQFHVDOOWKHORZ¿ULQJVWDJHV¿UVWEHIRUHEULQJLQJWKHUHVWRIWKHVWDJHVRQ)RU other types of boilers, using the Normal Sequencing option brings the lower operating stage followed by the higher one of the lead boiler. That will be repeated for each of the lag boilers. 08/7,3/(256,1*/(67$*,1* 8QOLNHPDQ\ERLOHUVZKHUHWR¿UHDPXOWLVWDJHERLOHUERWKORZDQGKLJKVWDJHUHOD\VPXVWEHHQHUJL]HGVRPHRIWKHDYDLODEOHHTXLSPHQW require that the operation of the higher stages turn off the lower operating stages. This can be achieved by selecting Single from the Startup Staging menu. $''837267$*(6 As a stand-alone, the BCP-8W-8 is designed to control eight stages. However, it has the capability of expanding its control to two extension panels (BCP-8X) each with eight stages. Thus, the BCP-8W can control a total of up to 24 stages. 021,7256<67(05(78517(03(5$785( Using a smart algorithm, the BCP-8W can monitor the boiler return temperature using an optional return sensor mounted on the return line. Then, sequence the boilers to raise the return temperature above an adjustable Minimum Return. '+:3803&21752/:,7+08/7,3/(35,25,7<237,216 Having a DHW input either as a dry contact to be used with an external aquastat or as a temperature sensor that can be ordered separately, the BCP-8W can control a DHW pump using its built-in DHW Pump output relay. The user will have different priority options that varies based on the DHW piping design. 4 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 81'(567$1',1*23(5$7,21&21&(37 1:4 1:3 1:2 1:1.5 In Outdoor Reset, the BCP-8W controls a hot water heating system to provide a building with comfortable and even heat levels. The BCP-8W varies the Target temperature of the circulating heating water in response to changes in the outdoor temperature. The BCP-8W also controls the system circulating pump with an adjustable Outdoor Cutoff. When the outdoor temperature is above the Outdoor Cutoff, the System Pump will be off and no heating water is circulated through the system. When the outdoor temperature drops EHORZWKH2XWGRRU&XWRIIWKHV\VWHPSXPSUHOD\LVHQHUJL]HGDQGWKHKHDWLQJZDWHUVWDUWVWR circulate through the system. The temperature of the heating water is controlled by the Reset Ratio parameters or the Set Point. (S) Water Temperature (in °F) 220 The BCP-8W has multiple operating modes that satisfy most hydronic systems. When the Outdoor Reset is selected, it can change the System Set Point based on outdoor temperature. Or, it can be set to Set Point and sequence stages to achieve a manually adjusted Set Point. 1:1.25 210 200 1:1 190 180 1.25:1 170 1.5:1 160 150 2:1 140 3:1 130 4:1 120 8:1 110 100 70 60 50 40 30 20 10 0 -10 -20 (O) Outdoor Temperature (in °F) Reset Ratio is Presented as Outdoor Temp.(O) : Water Temp.(S) Ratio 5(6(75$7,2287'2255(6(7 Each building has different heat loss characteristics. A very well insulated building will QRWORVHPXFKKHDWWRWKHRXWVLGHDLUDQGPD\QHHGD5HVHW5DWLRRI2' 6<62XWGRRU:DWHU7KLVPHDQVWKHRXWGRRUWHPSHUDWXUHZRXOGKDYHWRGURS degrees to increase the water temperature 1 degree. On the other hand, a poorly insulated EXLOGLQJZLWKLQVXI¿FLHQWUDGLDWLRQPD\QHHGD5HVHW5DWLRRI2'6<6 This means that for each degree the outdoor temperature dropped the water temperature will increase 2 degrees. The BCP-8W has a full range of Reset Ratios to match any buildings heat loss characteristics. A heating curve that relies not only on Outdoor temperature but also on the type of radiation will improve heat comfort. The following are suggested initial settings for different types of radiation based on average building insulation and heat loss. The FRQWUDFWRUFDQ¿QHWXQHWKHVHDGMXVWPHQWVEDVHGRQWKHVSHFL¿FEXLOGLQJQHHG Water Tem perature With a -20° Offset, the ratio curves begin at 80° Water Temperature. 1:4 130 1:1 120 110 100 4:1 70 60 50 40 Outdoor Temperature 1:4 110 1:1 100 90 -20 Offset 4:1 80 70 60 50 40 Outdoor Temperature With a +20° Offset, the ratio curves begin at 120° Water Temperature. Water Temperature 7KHVWDUWLQJSRLQWIRUPRVWV\VWHPVLVWKH2'6<62XWGRRU7HPSHUDWXUH +HDWLQJ:DWHU7HPSHUDWXUHUDWLR7KLVPHDQVWKDWIRUHYHU\GHJUHHWKHRXWGRRU temperature drops, the temperature of the heating water will increase one degree. The starting point of the curves is adjustable, but comes factory selected at 70°F Outdoor Temp. and 100°):DWHU7HPS)RUH[DPSOHZLWKD2'6<6UDWLRLIWKH outdoor temperature is 50°F, this means the temperature has fallen 20° from the starting point of 70°F. Therefore, the heating water temperature will increase 20° to 120°F. With a 0° Offset, the ratio curves begin at 100° Water Temperature. Water Temperature Reset Ratio Curves When a building is being heated, heat escapes through the walls, doors, and windows to the colder outside air. The colder the outside temperature, the more heat escapes. If you can input heat into the building at the same rate that it is lost out of the building, then the building temperatures will remain constant. The Reset Ratio is an adjustment that lets you achieve this equilibrium between heat input and heat loss. 150 1:4 1:1 140 130 4:1 120 90 +20 Offset 100 70 60 50 40 Outdoor Temperature 7\SHRI5DGLDWLRQLQ%XLOGLQJ 5HVHW5DWLR 2IIVHW Radiators (Steel & Cast Iron) 1.00 (OD) : 1.00 (SYS) Û) Baseboard (Finned copper tube& Cast Iron) 1.00 (OD) : 1.00 (SYS) Û) Radiant (High Mass/Concrete) 4.00 (OD) : 1.00 (SYS) Û) Radiant (Low Mass/Joists) 2.00 (OD) : 1.00 (SYS) Û) Fan Coils & Air Handlers 1.00 (OD) : 1.00 (SYS) Û) :$51,1* :KHQFRQWUROOLQJDQRQFRQGHQVLQJ ERLOHUWKH0LQLPXP7DUJHW WHPSHUDWXUHPXVWEHVHWWRWKHERLOHU PDQXIDFWXUHUVSHFL¿FDWLRQV,QWKDW FDVHV\VWHPWHPSHUDWXUHPXVWQRW JREHORZVXFKWHPSHUDWXUH 5 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO The BCP-8W has multiple operating modes that satisfy most hydronic systems. It can sequence stages to achieve an adjustable Set Point or an Outdoor Reset Ratio. Moreover, when used with the 420MOD Interface it can accept a 4-20mA signal as a set point. The 420MOD Interface must be purchased separately. This gives the BCP-8W the capability of being controlled remotely. 3,'23(5$7,21 3,'FRQWUROORJLFLVSULPDULO\XVHGIRUEXLOGLQJKHDWLQJ7KHORJLFZLOOXWLOL]HWZRSULPDU\VHWWLQJVWRDGGRUVXEWUDFWVWDJHV7KH5HDFWLRQ 7LPHLVXVHGWRWXUQRQHQHUJL]HVWDJHV2QWKHRWKHUKDQGWKH0LQLPXP5XQWLPHLVXVHGWRWXUQRIIGHHQHUJL]HVWDJHV$FDOOIRUKHDW by either closing the TSTAT input or opening the SHUTDOWN input, and when the outdoor temperature is below the Outdoor Cutoff, the %&3:ZLOOWXUQRQHQHUJL]HWKHORZHVW¿ULQJVWDJHRIWKH/HDG%RLOHUWRVWDUWWKH3XUJH'HOD\$IWHUWKHHODSVHRIWKHSXUJHSHULRGWKH BCP-8W will start calculating the Reaction Period. If after a full Reaction Time the control logic foresee additional stages are needed, WKH%&3:ZLOOHQHUJL]HWKHIROORZLQJVWDJH,IWKDWVWDJHZDVDQRWKHUERLOHUWKDWERLOHUKDVWRJRWKURXJKDIXOO3XUJH'HOD\EHIRUH VWDUWLQJWRFDOFXODWHWKH5HDFWLRQ7LPHIRUWKDWVWDJH2WKHUZLVHLIWKHQH[WVWDJHZDVWKHKLJKHU¿ULQJVWDJHRQWKHVDPHERLOHUWKH 5HDFWLRQ7LPHZLOOVWDUWIURPWKHPRPHQWWKHKLJKHU¿ULQJVWDJHUHOD\LVHQHUJL]HG When the BCP-8W PID logic foresees that the system will overshoot, regardless of the current system and target values, it will make sure WKDWWKHODVWVWDJHWXUQHGRQHQHUJL]HGHODSVHGDIXOO0LQLPXP5XQWLPHEHIRUHLWLVWXUQHGRIIGHHQHUJL]HG([FHSWIRUWKHOHDGVWDJH QRDGGLWLRQDOVWDJHVZLOOEHWXUQHGRIIGHHQHUJL]HGXQWLODQRWKHUIXOO0LQLPXP5XQWLPHLVHODSVHG2QWKHRWKHUKDQGLIWKHODVWVWDJH LVDOHDGVWDJHLWZLOOUHPDLQHQHUJL]HGXQWLOWKHV\VWHPUHDGLQJH[FHHGVWKHWDUJHWVHWSRLQWE\WKH/DVW6WDJH+ROGYDOXHLQDGGLWLRQWR satisfying the Minimum Runtime condition. That is, if the Set Point was 150°)DQGWKH/DVW6WDJH+ROGZDVVHWWR°F, the lead stage ZLOOUHPDLQHQHUJL]HGXQWLOWKHV\VWHPUHDFKHV°F and a full Minimum Runtime elapses. This is useful in protecting the lead stages from short cycling. 26623(5$7,21 266LVXVHGLQIDVWUHDFWLQJDSSOLFDWLRQDVLQSURFHVVDSSOLFDWLRQVZKHUHPDLQWDLQLQJDVHWSRLQWLVFULWLFDO7KH266XWLOL]HVWKH7KURWWOH setting, as a mean to calculate the number of stages the BCP-8W shall have on at any point. For every Throttle Range below the set SRLQWDQDGGLWLRQDOVWDJHVKDOOEHWXUQHGRQHQHUJL]HG7KDWLVLIWKHVHWSRLQWZDV°F and the Throttle setting was 5°F, if the System dropped below 175°F (180°F - 5°)WKHOHDGVWDJHZLOOHQHUJL]H:LWKIXUWKHUGHFUHDVHLQWKHV\VWHPYDOXHWR°F (180°F - 5°F - 5°F), WKHVHFRQGVWDJHZLOOHQHUJL]H As the system temperature rises towards the set point, stages will turn off. Using the previous example, when the system rise to 175°F ERLOHU%ZLOOGHHQHUJL]HOHDYLQJRQO\ERLOHU$RQ%RLOHU$ZLOOUHPDLQRQXQWLOWKHV\VWHPULVHVDRQHIXOO7KURWWOHUDQJHDERYHWKHVHW point. This will leave the lead boiler A on until the temperature rises to 185°)WKHQWXUQRIIGHHQHUJL]H 7KURWWOLQJ([DPSOH 6HW3RLQW °) 7KURWWOLQJ °) %RLOHU6WDJHV$%&DQG' )DOOLQJ7HPSHUDWXUH 6 7HPSHUDWXUH &DOFXODWLRQ 6WDJH7XUQHG2Q 6WDJHV2Q 185°F 180 + (1)THR --- 180°F 180 - (0)THR --- 5LVLQJ7HPSHUDWXUH 6WDJH7XUQHG2II 6WDJHV2Q None A None None --- A 175°F 180 - (1)THR A A B A 171 to 174°F --- --- A --- A,B 170°F 180 - (2)THR B A,B C A,B 166 to 169°F --- --- A,B --- A,B,C 165°F 180 - (3)THR C A,B,C D A,B,C 161 to 165°F --- --- A,B,C --- A,B,C,D 160°F 180 - (4)THR D A,B,C,D --- A,B,C,D %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 0$.(685(<28+$9(7+(5,*+7&21752/ ,I\RXQHHGWKH%&3:WRGRDGGLWLRQDOWDVNVWKDWHLWKHUDUHQRWOLVWHGRUGRQRWNQRZKRZWRVHWWKHPFRQWDFW:HLO0F/DLQ ,1,7,$/6(783 +DYLQJDQ,QLWLDO6HWXS3URJUDPZLOOHDVHWKHFRQ¿JXUDWLRQRIWKH%&3:DQGZLOOSURYLGHWKHRSSRUWXQLW\WRXWLOL]HPDQ\RIWKHHQHUJ\ saving features and give more comfortable heat when needed. 7KHSURJUDPVKRXOGFRQVLVWRIWKHIROORZLQJ HOHFWLQJWKHIHDWXUHVWKDW\RXUV\VWHPFDQXWLOL]H 6 ,QVWDOODWLRQ,QVWDOOWKH&RQWUROVZLWFKHVDQGVHQVRUV 6HWWLQJWKH6\VWHP6WDUWXS 6HWWLQJWKH6\VWHP6HWWLQJV 6HWWLQJWKH6WDJHV $GMXVWLQJ5HVHW5DWLRDQG:DWHU2IIVHW,Q5HVHW0RGH2QO\ 6(/(&7,1*7+(6<67(0)($785(6 The BCP-8W has been designed with Hydronic heating as the primary purpose. With this in mind, many of the BCP-8W features can EHXWLOL]HGWRHDVHHQKDQFHDQGLPSURYH\RXUV\VWHPSHUIRUPDQFH6RPHRIWKHVHIHDWXUHVDUHOLVWHGLQWKLVVHFWLRQ +($7,1*:,7+08/7,3/(256,1*/(287387$7$7,0( 7KH%&3:LVHTXLSSHGWRFRQWUROPXOWLSOHPXOWLVWDJHERLOHUVZLWKRUZLWKRXWSXPSVRUYDOYHVIRUKHDWLQJDSSOLFDWLRQV 7KDWFRPELQHGZLWKWKHFDSDELOLW\RIHQHUJL]LQJRQO\DVLQJOHVWDJHRIDPXOWLVWDJHERLOHUZKHQLQKLJKGHPDQGPDNHVWKH%&3 8W versatile for many industries. 287'2255(6(76(732,1725(;7(51$/0$6(732,17 7KH%&3:FDQFRQWUROWKH6\VWHP7HPSHUDWXUHHLWKHUE\DGMXVWLQJWKHWDUJHWDFFRUGLQJWRWKH2XWGRRU7HPSHUDWXUH2XWGRRU Reset) or by maintaining an adjustable Set Point. The Outdoor Reset option uses an Outdoor Sensor (supplied with the control) and achieves better fuel savings in addition to better comfort. 8VLQJWKHRSWLRQDO02',QWHUIDFHWKH%&3:FDQUHFHLYHDQH[WHUQDOVHWSRLQWWKURXJKDQ(06V\VWHP 3,'25266&21752//2*,& 7KH%&3:3,'FDQEHXVHGIRUDSSOLFDWLRQVZKHUHV\VWHPUHDFWLRQis slow and requires a long period to achieve or measure the results. However, OSS, can be used for applications where the load changes frequently and the sequencing must match the load and its immediate change. 180%(52)67$*(6 7KH%&3:FDQEHFRQ¿JXUHGWRFRQWUROXSWRHLJKWVWDJHV,WFDQFRQWUROXSWRVWDJHVXVLQJDPD[LPXPRIWZR%&3; Extension Panels, each with eight stages. 67$*(38036259$/9(6 7KH%&3:FDQFRQWUROPXOWLSOHVWDJHVLQDGGLWLRQWR boiler pumps or valves. &21752/'+:3803$1'&20%867,21$,5'$03(5 The control of the DHW is based on either a temperature sensor, can be purchased separately, on the DHW source or using a dry contact from an aquastat. The BCP-8W provides multiple DHW Priority options based on the DHW piping. The Combustion Air Damper output can be used in conjunction with the PROVE input to check the status of the Combustion Air Damper's End Switch, 6\VWHP3XPS V)ORZ6ZLWFKRUDQ\RWKHURSHUDWLQJGHYLFHEHIRUHDQ\VWDJHLVHQHUJL]HG 021,725%2,/(55(7851 The optional return line sensor, is purchased separately, can be connected to monitor and help protect the boilers from thermal shock and condensation caused by cool returns. 7 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO $8720$7,&527$7,21$021*%2,/(56 5RWDWLQJWKHOHDGERLOHUWREHDFWLYDWHGRQDFDOOIRURXWSXWSURPRWHVHYHQZHDURQDOOERLOHUV7KH%&3:KDVWKUHHPRGHVRI URWDWLRQ0DQXDO)LUVW2Q)LUVW2IIRU7LPHG5RWDWLRQ7KLVRSWLRQDXWRPDWLFDOO\URWDWHVWKHERLOHUVHYHU\VHOHFWHGSHULRGIURP one hour to every 41 days (999 hours). 6(7%$&.%226725'$<1,*+76&+('8/,1* 7ZR6HWEDFNPRGHVDUHDYDLODEOHIRUWKH%&3: The Day/Night Scheduling provides an adjustable time-based schedule for the Setback. It will be available when Shutdown or Tstat is selected from the External Input Startup menu options. :hen Setback is selected from the External Input Startup menu options, an external signal can be used to switch the operation of the BCP-8W in and out of setback mode 7KH%RRVWFDQEHXVHGWREULQJWKHEXLOGLQJWRFRPIRUWDEOHWHPSHUDWXUHVHWWLQJVDIWHUD1LJKWRU6HWEDFNSHULRG,WGRHVWKDWE\ increasing the target temperature for an adjustable period that follows the setback. Enclosure Display Module ,167$//$7,21 Each of the BCP-8W and BCP-8X consists of three primary enclosure components. 7KH(QFORVXUH'LVSOD\0RGXOHFRQWDLQVWKHGLVSOD\EXWWRQV/('V and electric wiring terminals. It has two screws to hold it to the base. A SURJUDPFRQ¿JXUDWLRQVZLWFKXVHGWRDGMXVW%&3:VHWWLQJVLVSODFHG above the terminals. This switch is enclosed with the Enclosure Wiring Cover for security. The wiring terminals are of the plug-in type to ease installation and removal. 7KH(QFORVXUH%DVH contains the holes to mount and hold the control DJDLQVWWKHZDOORUDQ\ÀDWVXUIDFH$OORWKHUHQFORVXUHFRPSRQHQWVPRXQW on the base. The bottom section of the Enclosure Base contains the wiring chamber with knockouts on the bottom to ease installation. 7KH(QFORVXUH:LULQJ&RYHU seals the wires from the external environment. It has two screws to hold it to the base and a hole to secure a lock on the wiring enclosure. A plastic web that separates the wiring chamber into high and low volt sections has been provided. 02817,1*7+((1&/2685( Enclosure Wiring Cover Mounting Base HOHFWDORFDWLRQQHDUWKHHTXLSPHQWWREHFRQWUROOHG 6 7KHVXUIDFHVKRXOGEHÀDWDQGVXI¿FLHQWO\ZLGHDQGVWURQJWRKROGWKH%&3 8W or BCP-8X. .HHSWKHFRQWURODZD\IURPH[WUHPHKHDWFROGRUKXPLGLW\$PELHQW operating temperature is from 20 to 120°F. 5HPRYHWKH(QFORVXUH:LULQJ&RYHUIURPWKHFRQWUROHQFORVXUHE\ removing the two bottom screws. 5HPRYHWKH(QFORVXUH'LVSOD\0RGXOHE\UHPRYLQJWKHPLGGOHVFUHZV 6FUHZWKH(QFORVXUH%DVHWRWKHVXUIDFHWKURXJKWKHXSSHUDQGORZHU mounting holes on the back of the enclosure. 5HSODFHWKH(QFORVXUH'LVSOD\0RGXOHDQGUHSODFHWKHPLGGOHVFUHZV 'RQRWUHSODFHWKHHQFORVXUHZLULQJFRYHUXQWLODOOZLULQJLVGRQH :KHQSXUFKDVLQJDSDGORFNIRUWKHHQFORVXUHWKHPD[LPXPVKDQNGLDPHWHU should not exceed ¼" Display Mounting Scr ews 8 Enclosure Base Hole for optional Padlock (not supplied) Wiring Cover Mounting Scr ews %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO S ,167$//7+( 6(16256 Immersion Heating System Sensor Immersion Well 3/8" ID 1/2" NPT Common Supply Pipe 6<67(0 6(1625 ,167$//$7,21 Shield /2&$7,1*7+(6<67(0 6(1625 3XWWKH6\VWHPVHQVRUDSSUR[LPDWHO\ IHHWSDVWWKHODVWKHDWLQJERLOHURQWKH common supply header but before any takeoffs. 7KHVHQVRUPXVWEHORFDWHGZKHUHLWVHHVWKHRXWSXWRIDOOWKHVWDJHV,ID boiler is piped so that the sensor does not see its output, the BCP-8W will not sequence the boilers correctly. 2QO\XVHD6WDQGDUG%UDVV7XEHVHQVRU 7KHVHQVRUZLUHVFDQEHH[WHQGHGXSWR XVLQJDVKLHOGHGFRQGXFWRU FDEOH%HOGHQRUHTXLYDOHQW(#18/2)). Do not ground the shield at the sensor but at the panel using one of the terminals marked with an “O”. 'RQRWUXQVHQVRUZLUHVLQFRQGXLWZLWKOLQHYROWDJHZLULQJ Heating System Sensor Strap-On Heating System Sensor Shield 2QO\XVHWKH:HLO0F/DLQVHQVRULQFOXGHGZLWKWKHXQLW /RFDWHWKHVHQVRULQWKHVKDGHRQWKHQRUWKVLGHRIWKHEXLOGLQJ7KHVHQVRU should never be in direct sunlight. %HVXUHWKHORFDWLRQLVDZD\IURPGRRUVZLQGRZVH[KDXVWIDQVYHQWVRU other possible heat sources. 7KHVHQVRUVKRXOGEHPRXQWHGDSSUR[LPDWHO\ IHHWDERYHJURXQGOHYHO $GKHUHWKH2XWGRRU/DEHOSURYLGHGWRWKHEDFNRIWKHVHQVRUEDVH 8VHWKH(QFORVXUH%DVHERWWRPNQRFNRXWIRUWKHFRQGXLW8VHWKHORFNQXWWR hold the conduit and enclosure base together. Screw the cover to the base. ,IVFUHZVDUHXVHGWRDI¿[WKHHQFORVXUHWRWKHZDOOPDNHVXUHWRVHDODURXQG the sensor and wall except from the bottom. 7KHVHQVRUZLUHVFDQEHH[WHQGHGXSWR XVLQJVKLHOGHGFRQGXFWRUFDEOH (#18/2). Do not ground the shield at the sensor but at the control using the terminal marked with an “O”. 'RQRWUXQVHQVRUZLUHVLQFRQGXLWZLWKOLQHYROWDJHZLULQJ Sensor Probe $/(57 If the System Sensor can not sense the correct system water temperature being supplied to the building, the BCP-8W will not provide comfortable heat levels. Be sure that it is located on the main supply pipe which can not easily be isolated from the system. 287'225 6(1625 ,167$//$7,21 Pipe Insulation Common Supply Pipe ,00(56,21 +($7,1* 6<67(06(1625 +66 ,167$//$7,21 ,QVWDOOD,'LPPHUVLRQZHOO ,QVHUWWKHVHQVRUSUREHRIWKHVXSSOLHGVHQVRULQWRWKHZHOO 675$321+($7,1* 6<67(0 6(1625 +66 ,167$//$7,21 6WUDSWKHVHQVRUWRWKHSLSHXVLQJPHWDOFODPSV'RQRWRYHUWLJKWHQWKH clamp. The sensors's concave surface must be facing the pipe for better temperature reading. 6WUDSSLSHLQVXODWLRQDURXQGWKHVHQVRUDQGSLSH Sensor Probe Outdoor Sensor Seal around sensor and wall Outdoor Sensor snap-in location Mounting screws location Shield not connected Outdoor drip-hole Outdoor Label on back of Sensor Conduit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ine Neutral :,5,1*7+(32:(57(50,1$/6 120VAC Power Source :$51,1* &ODVVYROWDJHZLULQJPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJH ZLULQJ:HLO0F/DLQUHFRPPHQGVLQVWDOOLQJDVXUJHVXSSUHVVRURQWKHSRZHUVRXUFHWRWKH%&3: :$51,1* OUTDOOR TEMP TEMP 25 26 27 28 29 30 &RQQHFWWKH7HPSHUDWXUHVHQVRUVKLHOGDWWKHFRQWUROWRWKHVHQVRUWHUPLQDOPDUNHG2 'RQRWFRQQHFWWKH6KLHOGDWWKHVHQVRUHQG :,5,1*7+(6(16256 10 Sensor Shiled OUTDOOR RETURN TEMP TEMP D Sensor Shiled Outdoor Sensor 28 29 30 31 32 3 DOOR RETURN MP TEMP DHW 30 31 32 33 34 Sensor Shiled 5(78516(1625:,5,1*7(50,1$/6237,21$/$9$,/$%/(,1+($7,1*21/< ,IWKH5HWXUQ6HQVRULVFRQQHFWHGPXVWEHSXUFKDVHGVHSDUDWHO\WKH%&3:ZLOOUHFRJQL]HLWDQGDOWHUQDWHLWV temperature on the display with the Target temperature. If the Return is below the Minimum Return, the BCP8W will sequence stages based on the Return Sensor, Minimum Return, Calculated Target, and the actual System Temperature. 7KH5HWXUQRQWKH%&3:LVGHVLJQHGWREHFRQQHFWHGWRDWHPSHUDWXUHVHQVRUWKDWFDQEHSXUFKDVHGVHSDUDWHO\ IRULPPHUVLRQLQD,'ZHOO 7KHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶XVLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRUHTXLYDOHQW (#18/2)). 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHZLUHVIURPWKHRXWGRRUVHQVRUWRWKH%&3:WHUPLQDOV marked OUTDOOR TEMP - 31, 32. &RQQHFWWKHVKLHOGWRWKHFLUFOHGWHUPLQDO32 with one of the sensor wires. Do not connect it to the sensor. MP Return Sensor 287'2256(1625:,5,1*7(50,1$/6 :KHQ2XWGRRU5HVHWLVVHOHFWHGWKH%&3:ZLOOYDU\WKHV\VWHPWDUJHWEDVHGRQWKHRXWGRRUWHPSHUDWXUH :KHWKHULQ6HW3RLQWRU2XWGRRU5HVHWPRGHVWKHRXWGRRUVHQVRUFDQEHXVHGDVDQ2XWGRRU&XWRII7KH%&3 8W will disable all Boilers when the outdoor temperature is above the adjustable Outdoor Cutoff temperature. This feature will automatically be activated when an outdoor sensor is connected. )RUDQRXWGRRUVHQVRUXVHWKHSURYLGHG:HLO0F/DLQRXWGRRUVHQVRU 7KHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶XVLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRUHTXLYDOHQW (#18/2)). 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHZLUHVIURPWKHRXWGRRUVHQVRUWRWKH%&3:WHUPLQDOV marked OUTDOOR TEMP - 29, 30. Connect the shield to the circled terminal 30 with one of the sensor wires. Do not connect the shield at the sensor end. System Sensor 6<67(07(03(5$785(6(1625:,5,1*7(50,1$/6 7KH%&3:LVGHVLJQHGWREHFRQQHFWHGWRDWHPSHUDWXUHVHQVRUIRULPPHUVLRQLQD,'ZHOO located on the common header. Contact the factory for additional temperature sensor options. 7HPSHUDWXUHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶E\VSOLFLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRU equivalent (#18/2)). 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHWZRZLUHVIURPWKHVHQVRUWRWKH%&3:WHUPLQDOVPDUNHG SYSTEM TEMP 27, 28. &RQQHFWWKHVKLHOGWRWKHFLUFOHGWHUPLQDOZLWKRQHRIWKHVHQVRUZLUHV'RQRWFRQQHFWWKHVKLHOGDWWKH sensor end. %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO :,5,1*7+('20(67,&+27:$7(5'+:6(16257(50,1$/6 RN P 32 33 34 35 36 3 :,5,1*7+(6+87'2:17(50,1$/6 7KLVIHDWXUHZLOORQO\EHDYDLODEOHZKHQ6KXWGRZQLVVHOHFWHGDVWKH([WHUQDO,QSXW0RGHRQSDJH18. KLVIHDWXUHFDQEHXVHGZKHQHYHULWLVGHVLUDEOHWRWXUQRIIWKH%&3:VWDJHRXWSXWVIURPDUHPRWHORFDWLRQRU 7 another controller (i.e. EMS input). :KHQWKH6KXWGRZQLVHQDEOHGDOODFWLYHVWDJHVZLOOLPPHGLDWHO\WXUQRII7KH6\VWHP3XPS&RPEXVWLRQ$LU DQGERLOHUSXPSV RUYDOYHV UHOD\VZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2QGHOD\SHULRGDQGWKHQWXUQRII 7KH6KXWGRZQVLJQDOPXVWEHDGU\FRQWDFWLQSXW1RYROWDJHFDQEHSODFHGDFURVVWKHSHUTDOWN terminals. %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHSHUTDOWN- 35,36 terminals. :KHQ6KXWGRZQLVVHOHFWHG6HWEDFNZLOOEHDYDLODEOHXVLQJWKHSURJUDPPHG'D\1LJKWVFKHGXOH :,5,1*7+(767$77(50,1$/6 KLVIHDWXUHFDQEHXVHGZKHQHYHULWLVGHVLUDEOHWRVZLWFKWKH%&3:WRRSHUDWHIURPDUHPRWHORFDWLRQLH 7 EMS input or thermostat). It will only be available when Tstat is selected as the External Input Mode option from the Startup menu on page 18. :KHQWKH7VWDWLVHQDEOHGE\FORVLQJDGU\FRQWDFWWKH%&3:ZLOODFWLYDWHWKHKHDWLQJORJLF 7KH7VWDWVLJQDOPXVWEHDGU\FRQWDFWRQO\1RYROWDJHFDQEHSODFHGDFURVVWKHTSTAT terminals. %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHTSTAT- 35,36 terminals. $IDFWRU\LQVWDOOHGMXPSHUSURYLGHVWKH7VWDWVLJQDO'RQRWUHPRYHWKHMXPSHUXQOHVVLWZLOOEHUHSODFHGE\D Tstat signal. :KHQ7VWDWLVVHOHFWHGIURPWKH6WDUWXS([WHUQDO,QSXWPRGH6HWEDFNZLOOEHDYDLODEOHXVLQJWKHSURJUDPPHG Day/Night schedule. DHW Sensor Shiled DHW Sensor SHUTDOWN /TSTAT PROVE /SETBACK 3 34 35 36 37 38 Shutdown Dry Contact SHUTDOWN /TSTAT P /SETBACK Auxiliary Input3 SHUTDOWN /TSTAT /SETBACK PROVE 33 34 35 36 37 38 T-Stat Dry Contact KH'+:LQSXWFDQEHXVHGWRUDLVHV\VWHP6HW3RLQWWR)RU0D[LPXP7DUJHWZKLFKHYHULVORZHU7KH 7 DHW Piping on page 18 must be selected from the Startup Menu to determine the DHW Priority options. DHW Call terminals can be connected to either a dry-contact or a temperature sensor that can be purchased VHSDUDWHO\IRULPPHUVLRQLQD,'ZHOO ,IXVLQJDGU\FRQWDFWZLUHDQDTXDVWDWRURWKHUFRQWUROVWRSURYLGHGU\FRQWDFWFORVXUHRQWKHDHW terminals. ,IXVLQJDVHQVRUWKHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶XVLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRU equivalent (#18/2)). 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHZLUHVIURPWKH'+:VHQVRUWRWKH%&3:WHUPLQDOV marked DHW - 33, 34. Connect the sensor shield to the circled terminal 34 with one of the sensor wires. Do not connect the shield to the sensor. ,I6KXWGRZQZDVVHOHFWHGDVWKH([WHUQDO,QSXWDQ\'+:FDOOZLOOEHLJQRUHGZKHQWKH6KXWGRZQLVDFWLYH DHW :,5,1*7+(6(7%$&.7(50,1$/6 DHW 3 34 35 36 37 38 :,5,1*7+(3529(7(50,1$/6 KH3URYHIHDWXUHLVSURYLGHGWRFKHFNV\VWHPFRPSRQHQWRSHUDWLRQEHIRUHHQHUJL]LQJWKHVWDJHV,WFDQEH 7 used to check on the Combustion Air Damper by connecting it to the end switch of the damper. In this case, the Comb. Air Output option must be activated from the Startup Menu on page 18. ,IWKH&RPE$LU'DPSHU2XWSXWRSWLRQZDVQRWDFWLYDWHGWKHPROVE input can be used to check on the 6\VWHP2XWSXW$W\SLFDOXVHRIWKLVIHDWXUHLVWRFKHFNIRUV\VWHPSXPSÀRZEHIRUHHQHUJL]LQJDQ\VWDJH ,IWKHPROVE input is open on a call, the BCP-8W will enable only the System Output. All stage outputs will be off when the PROVE input is open. $IDFWRU\LQVWDOOHGMXPSHUSURYLGHVWKH6\VWHP3URYHVLJQDO'RQRWUHPRYHWKHMXPSHUXQOHVVLWZLOOEH replaced by a System Prove signal. %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHPROVE - 37, 38 terminals. No voltage can be placed across the PROVE terminals Setback Dry Contact DOWN TAT PROVE BACK RS485 36 37 38 Prove Dry Contact KLVIHDWXUHFDQEHXVHGZKHQHYHULWLVGHVLUDEOHWRVZLWFKWKH%&3:WRRSHUDWHLQ6HWEDFNIURPDUHPRWH 7 location (i.e. EMS input or external time clock). It will only be available when Setback is selected as the External Input Mode option from the Startup menu. See page 18. :KHQWKH6HWEDFNLVHQDEOHGE\FORVLQJDGU\FRQWDFWWKH7DUJHWZLOOFKDQJHE\WKH6HWEDFNYDOXH7KDWLVWKH Target will be reduced by the Setback value. 7KH6HWEDFNVLJQDOPXVWEHDGU\FRQWDFWRQO\1RYROWDJHFDQEHSODFHGDFURVVWKHSETBACK terminals. %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHSETBACK- 35,36 terminals. :KHQ6HWEDFNLVVHOHFWHG1R'D\1LJKW6FKHGXOLQJZLOOEHDYDLODEOH SHUTDOWN /TSTAT PROVE /SETBACK 11 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO :$51,1* 7KH3529(LQSXWFDQQRWEHXVHGDVDVDIHW\OLPLW$OOHTXLSPHQWPXVWKDYHLWVRZQFHUWL¿HGOLPLWDQGVDIHW\ controls as required by local codes. No boiler stage will start unless the Prove terminals are shorted. DO NOT remove the PROVE jumper supplied unless replacing it with a Prove signal. :,5,1*7+(6<67(02873877(50,1$/6 DHW ge G Stage H SYSTEM PUMP 16 17 18 19 20 21 22 KH6\VWHPRXWSXWKDVD1RUPDOO\2SHQ12UHOD\WKDWDFWVDVDGU\FRQWDFW,WGRHVQRWVRXUFHDQ\SRZHU 7 &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJHZLULQJ L 6\VWHP2XWSXW2SHUDWLRQLQ6HW3RLQW0RGH N 7KH6\VWHPRXWSXWUHOD\ZLOOHQHUJL]HZKHQHYHUWKHRXWGRRUWHPSHUDWXUHGURSVEHORZWKH2XWGRRU&XWRIIRU ZKHQHYHUDVWDJHRXWSXWLVDFWLYH,IQRRXWGRRUVHQVRULVFRQQHFWHGDQGWKHODVWERLOHUUHOD\KDVGHHQHUJL]HG System WKH6\VWHPUHOD\ZLOOUHPDLQHQHUJL]HGIRUDSHULRGVHWE\WKH5XQ2QDQGWKHQGHHQHUJL]H Pump ,IWKHPROVELQSXWLV2SHQWKH6\VWHPUHOD\ZLOOUHPDLQHQHUJL]HGKRZHYHUDOOVWDJHVZLOOEHGHHQHUJL]HG If a Prove is not required, the factory-installed jumper must remain connected for proper operation. $W\SLFDOXVHRIWKH6\VWHPRXWSXWLVWRDFWLYDWHDV\VWHPSXPSRULWVVWDUWHU7KHSXPSFDQUXQZKHQHYHUWKHUHLVDFDOOIRU KHDW:KHQVWDJHVDUHQRORQJHUUHTXLUHGWKHSXPSZLOOVWD\DFWLYHIRUDQDGMXVWDEOH5XQ2QGHOD\DQGWKHQGHHQHUJL]H 6\VWHP2XWSXW2SHUDWLRQLQ5HVHW0RGH 7KH6\VWHPRXWSXWUHOD\ZLOOHQHUJL]HZKHQHYHUWKHRXWGRRUWHPSHUDWXUHLVEHORZWKH2XWGRRU&XWRII :KHQWKHRXWGRRUWHPSHUDWXUHULVHV)DERYHWKH2XWGRRU&XWRIIWKH6\VWHPRXWSXWZLOOUHPDLQHQHUJL]HGIRUWKHSHULRGVHW by the System Run-OnDQGWKHQGHHQHUJL]H. :,5,1*7+('+:38037(50,1$/6 age H SYSTEM DHW COM PUMP AI 7 18 19 20 21 22 23 The BCP-8W can control the DHW Pump when the DHW Pump Output option is activated from the Startup Menu. See page 18. 7KH%&3:ZLOOHQHUJL]HWKH'+:3XPSZKHQHYHUWKHUHLVDFDOOIRU'+:XVLQJDGU\FRQWDFWRUZKHQWKH DHW temperature falls below the DHW Set Point and DHW Differential when using a DHW sensor. 7KH'+:3XPSRXWSXW relay is a Normally Open (N.O.) dry contact. It does not source any power. &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJHZLULQJ ,I6KXWGRZQZDVVHOHFWHGDVWKH([WHUQDO,QSXWSDJH18), The BCP-8W will ignore a DHW call when the Shutdown is active. L N DHW Pump :,5,1*7+(&20%867,21$,5'$03(57(50,1$/6 DHW COMB. EM PUMP AIR The BCP-8W can control the Combustion Air Damper when the Comb. Air Output option is activated in the Startup Menu (Page 18). In addition, the PROVE input will function as the Combustion Air Damper status checker. 7KH%&3:ZLOOHQHUJL]HWKH&RPEXVWLRQ$LU'DPSHUUHOD\ZKHQHYHUWKHUHLVDFDOOWRHQHUJL]HDQ\RIWKH boiler stages. 7KH&RPEXVWLRQ$LURXWSXW relay is a Normally Open (N.O.) dry contact. It does not source any power. &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJHZLULQJ 0 21 22 23 24 L N Comb. Air Damper :,5,1*7+(67$*(67(50,1$/672 7KH%&3:FDQEHFRQ¿JXUHGWRRSHUDWHWKHVWDJHVRIWKHERLOHUV0RUHRYHULWFDQEHFRQ¿JXUHGWR operate the boiler pumps or valves in addition to the boiler stages. 7KHUHOD\VDUHN.O. dry contacts only. They do not source any voltage. :LUHWKH12UHOD\FRQWDFWVLQVHULHVZLWKWKHERLOHU¶VOLPLWFLUFXLW &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWNQRFNRXWIURPDQ\&ODVVYROWDJH wiring. :,5,1*7+(67$*(2873876 (DFK6WDJHRXWSXW$WKURXJK+KDVRQH12UHOD\ :KHQZLULQJVHYHUDOPXOWLVWDJHERLOHUVVWDUWZLWKWKHORZHUVWDJHRIWKH¿UVWERLOHUDQGZLUHLWWR Output A, followed by the higher stage of the same boiler and wire it to Stage B. 12 Stage A Stage B Stage C Stage D Stage 3 4 5 6 7 8 9 10 11 1 Lo Hi Lo Hi Unit1 Unit2 Stages Stages %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO :,5,1*7+(3803259$/9(2873876 ,IWKH%&3:LVFRQ¿JXUHGWRRSHUDWH6WDJH3XPSVRU9DOYHV7KH\PXVWEHZLUHGWRWKHVWDJH RXWSXWDIWHUWKHKLJKHVWVWDJHIRUWKDWERLOHU7KDWLVWKHORZVWDJHIRUWKH¿UVWERLOHUPXVWEH connected to A and the higher stage of the same boiler must be connected to Stage B. The boiler valve or pump for the same boiler must be connected to Stage C. N Stage A Stage B Stage C Stage D Stage E Stage F 2 3 4 5 6 7 8 9 10 11 12 13 14 Lo Hi Unit1 Stages Lo Hi Unit2 Stages Unit1 Pump Unit2 Pump L N &211(&7,1*727+(%&3;3$1(/6$1'02',17(5)$&( KH%&3:LVHTXLSSHGZLWKDSKRQHVRFNHW56WRFRQQHFWWRWKH%&3;([WHQVLRQSDQHOVRUWKH02',QWHUIDFH 7 XVLQJWKHSURYLGHGSLQSKRQHFDEOH (DFK%&3;([WHQVLRQKDVWZR56FRPPXQLFDWLRQSRUWV8VHRQHWRFRQQHFWWRWKH%&3:8VHWKHRWKHUSRUWWR connect to the second extension or the 420MOD Interface. $GGLWLRQDOFRPSDWLEOHGHYLFHVFDQXWLOL]HWKHVHFRQG56FRQQHFWLRQRQWKHVHFRQG%&3;([WHQVLRQ$QH[DPSOHZRXOG EHWRXVHWKH02',QWHUIDFHWRSURYLGHDP$VHWSRLQWVLJQDOWRWKH%&3: 6(/(&7,1*7+(%&3;3$1(//(77(5 KH%&3:LVFDSDEOHRIFRPPXQLFDWLQJWRWZR%&3;([WHQVLRQV+RZHYHUHDFK 7 H[WHQVLRQPXVWEHLGHQWL¿HGDVHLWKHU$RU%XVLQJWKHVZLWFKRQHDFKH[WHQVLRQWRDYRLGKDYLQJ communication problem. ([WHQVLRQ$6ZLWFKLVVHWWR$ZLOORSHUDWHVWDJHV,WKURXJK3:KLOH([WHQVLRQ% (Switch is set to "B") will operate stages "Q" through "X". Ext A Ext B Connecting BCP-8 to Two Extension Panels and 420MOD Interface using RS485 BCP-8 BCP-8X A BCP-8W BCP-8X HYDRONIC SEQUENCING CONTROL SYS=144F Stage A Stage E SYSTEM Stage B Stage F DHW PUMP Stage C Stage G Stage D Stage H COMB. AIR ENCLOSED ENERGY MANAGEMENT EQUIPMENT INPUT RATINGS: 115VAC 60Hz, 12VA MAX LISTED 99RA C <AB > DE HI LO GH -- STAGE JK OFF L T O W J R MU P X K S N V MENU OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 115VAC 60Hz, 12VA MAX Comm DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS SENSORS MUST BE GOLD SERIES PROGRAM I Q Power US CAUTION: Risk of Electric Shock. Use Copper Conductors Only. SEQUENCING CONTROL EXTENSION OD=35F CAUTION: Risk of Electric Shock. Use Copper Conductors Only. RUN PWR SHUTDOWN /TSTAT PROVE /SETBACK L N Stage A Stage B Stage C Stage D Stage E Stage F DHW COMB. Stage G Stage H SYSTEM PUMP AIR PRESS + - 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 TEMP OUTDOOR RETURN TEMP TEMP DHW PWR RS485 Ext A Ext B EXTENSION MODULE I Q J R K S L T MU N V O W P X L N 1 2 RS-485 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 6 Pin Phone Cable (provided with Extension) BCP-8X B BCP-8X SEQUENCING CONTROL EXTENSION 420MOD EMS Interface I Q L T O W J R MU P X K S OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: N V Comm 115VAC 60Hz, 12VA MAX Power 4-20 mA EMS 4-20mA INPUT + 1 Signal GND 2 3 CAUTION: Risk of Electric Shock. RS485 EXTENSION CONNECTORS Use Copper Conductors Only. PWR Ext A Ext B I Q J R K S L T MU N V O W P X L N 1 2 4-20mA (+) EMS Signal (-) EXTENSION MODULE RS-485 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 6 Pin Phone Cable (provided with 420MOD EMS Interface) 13 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO S ,167$//(5 0(18 6(48(1&( 67$5783 SYS=168 F OD=45 F TGT=172 F ABC <EFG > ---LO BOILER MENU ------ SETTINGS -----Season Winter <Outdoor Rst> 135 F Set Point 135 F EMS Set Point135 F Min Return 110 F <System Settings> <Maintenance> <System Startup> BACK SELECT 0$,17(1$1&( & YOU SURE? SAVE --- SENSOR FAULT --Stages On Stages Off BACK SAVE --- CONTROL PID OSS BACK LOGIC--- ------ STAGING -----Multiple Outputs Single Output BACK SAVE Sys=120 F BACK SELECT 10:00AM NEXT --- SENSOR TRIM ---System Trim +0 F Outdoor Trim +0 F Return Trim +0 F DHW Trim +0 F BACK SELECT -- TOTAL ------- --- SAVE EMS [ BACK 4mA SET POINT 100 F ] SAVE [ BACK 20mA SET 170 F POINT ] SAVE SAVE BOILERS 8 -- -- BOILER None Pump Valve BACK OUTPUT -- --- BURNER On/Off 2-Stage 3-Stage 4-Stage BACK TYPE [ BACK UNIT (06 6(7 32,17 EMS BACK BACK ---- DISPLAY F C BACK SAVE ------ SEQUENCE Lo/Hi/Lo/Hi Lo/Lo/Hi/Hi BACK SELECT ---- CONTROL MODE --Outdoor Reset Set Point EMS 4-20mA BACK SAVE $/(57 7RDFFHVV,QVWDOOHU0HQXKROG down the Menu button for over three seconds. 7REHDEOHWRFKDQJHWKH%&3: settings the Program/Run Switch must be set to Program. ---- MAINTENANCE ---Unit F Present Time12:30P <Sensor Trim> <Histories> <Configuration> BCP-8W V1.00 Outdoor reset Day/Night Schedule DHW Parallel 14 ARE No Yes BACK ] SAVE SAVE ---- SAVE ---- DHW PIPING --Parallel Primary/Secondary BACK SAVE --DHW PUMP No Yes BACK --COMB. No Yes BACK AIR -- EXTERNAL Shutdown Tstat Setback BACK OUTPUT-SAVE OUTPUT-SAVE INPUT - SAVE %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO S 5(6(7 6 5$7,2 2 6(7 32,17 2 -- EMS SET POINT 140 F BACK ----[ BACK -- SAVE SET POINT 140 F ----] SAVE SYS=168 F OD=45 F TGT=172 F ABC <EFG > ---LO BOILER MENU ---- SEASON Winter Summer BACK BACK ---- [ BACK MIN [ BACK ---- [ BACK [ BACK ---- RETURN LAG 2min [ BACK - ---] SAVE SYSTEM SETTINGS <Stage Settings> <Setback Schedule> <DHW Settings> Setback 0 F Run-On 2min Pump Exercise Off BACK --- PUMP Off On BACK SELECT EXERCISE -- -- TARGET 140 F ---] SAVE ---] SAVE TARGET OFFSET +0 F --- ] SAVE '+: 6(77,1* *6 BACK -----[ BACK ------- BACK SELECT SETBACK 0 F RUN-ON 2min ---- RESET RATIO --Custom 1(8.00 OD:1.00 SYS) 2(4.00 OD:1.00 SYS) 3(3.00 OD:1.00 SYS) 4(2.00 OD:1.00 SYS) 5(1.50 OD:1.00 SYS) 6(1.25 OD:1.00 SYS) 7(1.00 OD:1.00 SYS) 8(1.00 OD:1.25 SYS) 9(1.00 OD:1.50 SYS) 10(1.00 OD:2.00 SYS) 11(1.00 OD:3.00 SYS) 12(1.00 OD:4.00 SYS) BACK -- SET [ ]BACK -- AT [ ]BACK -- [ BACK -- [ BACK -- - SAVE OD TEMP.1 70 F --- SYS TEMP.2 170 F - OD TEMP.2 0 F --- ] SAVE PRIORITY 2min DHW [ BACK SYS TEMP.1 100 F ] SAVE AT [ BACK SAVE SAVE SET DHW -- DHW SETTINGS --DHW Temp. 120 F DHW Prior Tmr 60min DHW Set Point120 F DHW Diff. 5 F [ SAVE TARGET 200 F -- OUTDOOR CUTOFF -60 F [ ] BACK SAVE ---] SAVE SELECT MAX ----- SETTINGS -----Season Winter <Outdoor Rst> 135 F Set Point 135 F EMS Set Point135 F Min Return 110 F <System Settings> <Maintenance> <System Startup> BACK SELECT RETURN 120 F SAVE -- OUTDOOR RESET Reset Ratio 7 Target Offset +0 F Outdoor Cutoff 65 F Min.Target 120 F Max.Target 120 F ---- MIN --- TIMER ] SAVE SET POINT 140 F -- ] SAVE ------] SAVE ------- DHW [ ]BACK DIFFERENTIAL 10 F SAVE ] SAVE 15 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO S 67$* *( 6(77,1* *6 - SYSTEM SETTINGS <Stage Settings> <Setback Schedule> <DHW Settings> Setback 0 F Run-On 2min Pump Exercise Off BACK SELECT ----- SETTINGS -----Season Winter <Outdoor Rst> 135 F Set Point 135 F EMS Set Point 135 F Min Return 110 F <System Settings> <Maintenance> <System Startup> BACK SELECT -- STAGE SETTINGS -Reaction Time 1min Purge Delay 0.0min Min Runtime 2min Standby Delay 10min Last Stage Hold 5 F Throttle 2 F <Lead Settings> BACK SELECT SETBACK SCHEDULE Setback 0 F Present Time **:** Day Schdul 7:00Am Night Schdul 7:00Pm BACK SELECT -- -- LEAD ROTATION Time Manual FOFO -- SCHEDULE 07:**Am BACK - SET SELECT BACK -----[ BACK 16 TIME SAVE SETBACK 0 F ---] SAVE MINIMUM RUNTIME 2min SAVE STANDBY DELAY 10min [ ]BACK LAST - -- SAVE STAGE 0 F HOLD ROTATE PERIOD 24hrs [ ] BACK SAVE [ BACK -- LEAD AB CD BACK -- THROTTLE RANGE -2 F [ ] BACK SAVE BOILER -- SELECT SYS=168 F OD=45 F TGT=172 F ABC <EFG > ---LO BOILER MENU ] SAVE 67$* *( 0(18 -- BOILER Auto Standby Off On BACK AB MODE - SAVE ---SAVE PRESENT **:** [ BACK -- -- SAVE PURGE DELAY 1.0min [ ]BACK SELECT SAVE DAY --- BACK -- NIGHT SCHEDULE -07:**Pm BACK [ ]BACK - AUTO 6& 6&+('8/(6 6 REACTION TIME 1min -- LEAD SETTINGS -Lead Boiler AB Rotate Mode Time BACK 1RW $YDLODEOH ZKHQ 6HWEDFN LV 6HOHFWHG IURP 6WDUWXS S 0HQX -- ------] SAVE -----[ ]BACK -------[ BACK BOOST PERIOD--30min SAVE BOOST 0 F --------] SAVE ----- BOILER AB ----Mode Auto Runtime 58Hrs <Prev Boiler> <Next Boiler> BACK SAVE BOILER BACK AB RUNTIME 58hrs CLEAR OK %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 67$57836(77,1*6 Can be accessed by holding down the Menu button for over three seconds. $/(57 $JRRGSUDFWLFHDIWHUSHUIRUPLQJDQ\6WDUWXSPHQXPRGL¿FDWLRQVLVWR check all operating settings and adjustments to match the new settings. 352*5$0&+$1*(6(77,1*6 PROGRAM To be able to change the BCP-8W settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. RUN 67$57836(48(1&( ARE YOU SURE? Hold Button: MENU/<System Startup> No :KHQSRZHUHGWKH%&3:SHUIRUPVDVHOIWHVWRQLWVFRPSRQHQWV$IWHUWKHVHOIWHVW Yes GLDJQRVWLFVKDYHEHHQVXFFHVVIXOO\FRPSOHWHGWKH%&3:ZLOOLQLWLDOL]HWKHSDQHO BACK SAVE 2QWKH¿UVWSRZHUXSWKH6\VWHP6WDUWXSVFUHHQZLOODSSHDUDIWHUWKHLQLWLDOL]DWLRQLV FRPSOHWH,ILWGRHVQ¶WWKH%&3:KDVDOUHDG\EHHQFRQ¿JXUHG 7KH6\VWHP6WDUWXSPHQXVHWVWKHPDLQSDUDPHWHUVDVWKHW\SHRIVHQVRUWKHVHTXHQFLQJPRGHDQGPDQ\RWKHUSDUDPHWHUV described in this section. %HIRUHHQWHULQJWKH6WDUWXSPHQXVHYHUDOZDUQLQJVZLOODOHUW\RXWRWKHFRQVHTXHQFHVRIPDNLQJ6WDUWXSFKDQJHV &21752/02'( ---- CONTROL MODE --2XWGRRU5HVHW6HW3RLQW(06P$ 'HIDXOW2XWGRRU5HVHW Outdoor Reset Hold Button: MENU/<System Startup>/..../Control Mode Set Point EMS 4-20mA 2XWGRRU5HVHWSURYLGHVDYDULDEOHVHWSRLQWEDVHGRQRXWGRRUWHPSHUDWXUH 2XWGRRU5HVHWPRGHUHTXLUHVWKHXVHRIDQRXWGRRUVHQVRU'2127VHOHFW2XWGRRU BACK SAVE Reset without an outdoor sensor. 6HW3RLQWPRGHGRHVQRWUHTXLUHDQRXWGRRUVHQVRU,IDQRXWGRRUVHQVRULVFRQQHFWHGLQ6HW3RLQWPRGHLWZLOOEHXVHGRQO\DV an Outdoor Cutoff point. That is, to turn the stages, system, and Comb. Air relays off. 7KH(06P$DOORZVWKH%&3:WRUHFHLYHDQH[WHUQDOVHWSRLQWIURPDQ(06%06V\VWHP7KLVRSWLRQUHTXLUHVWKHXVH RIWKH02',QWHUIDFH <RXPXVWVHOHFWWKHP$PLQDQGP$PD[6HW3RLQWYDOXHVLQWKHIROORZLQJVFUHHQV &RQQHFWWKH02',QWHUIDFHWRWKH%&3:56FRQQHFWLRQXVLQJWKHSKRQHFDEOHSURYLGHGZLWKWKH02'LQWHUIDFH ',63/$<81,7 º)º& 'HIDXOWºF Hold Button: MENU/<System Startup>/..../Display Unit 7KH%&3:FDQFRQWUROERLOHUVLQK\GURQLFHQYLURQPHQWZKHUHWKHWHPSHUDWXUHLV the critical factor. It allows the user to display temperature information and settings in either ºF (Fahrenheit) or ºC (Celsius). Select the display unit that is best suited for your application. ---- DISPLAY F C BACK UNIT --- SAVE 6(77,1*7+(0$$1'0$6(732,176$9$,/$%/(,10$(0621/< P$IURP)&WR)& 'HIDXOW)& P$IURP)&WR)& 'HIDXOW)& Hold Button: MENU/<System Startup>/..../EMS 4mA Set Point/EMS 20mA Set Point ,I(06P$LVVHOHFWHGIURPWKH&RQWURO0RGHPHQXDVWKHWHPSHUDWXUHVHWSRLQW VRXUFHWKHXVHUPXVWSXUFKDVHD:HLO0F/DLQ02',QWHUIDFHWR accept the 4-20mA signal and transmit it to the BCP-8W. ,QDGGLWLRQWKHXVHUZLOOQHHGWRVHWWKHWHPSHUDWXUHUDQJHSDUDPHWHUV)LUVWVHWWKHP$ temperature set point, then the 20mA temperature set point. 7RVKXWGRZQWKHFRQWUROXVLQJWKH(06VLJQDOVHQGDVLJQDOWKDWLVDERYHRUEHORZWKH 2-22mA range. The display will show the message "Shutdown by EMS" and all VWDJHVZLOOGHHQHUJL]H+RZHYHUWKH6\VWHP&RPE$LUDQGERLOHU3XPSVDQG9DOYHV ZLOOFRQWLQXHIRUWKH5XQ2QGHOD\SHULRGDQGWKHQGHHQHUJL]H EMS [ BACK EMS [ BACK 4mA SET POINT 100 F ] SAVE 20mA SET 170 F POINT ] SAVE 17 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO '+:3,3,1* ---- DHW PIPING --3DUDOOHO3ULPDU\6HFRQGDU\ 'HIDXOW3DUDOOHO Parallel Hold Button: MENU/<System Startup>/..../DHW Piping Primary/Secondary :KHQ3DUDOOHOLVVHOHFWHGWKH%&3:ZLOORIIHUD'+:3ULRULW\7LPHU7KH'+: BACK SAVE priority will only take place during heating periods. See the DHW Priority Timer on page 28. 7KHSULRULW\ZLOODOORZWKH'+:3XPSUHOD\WRHQHUJL]HZKLOHGHHQHUJL]LQJWKH6\VWHPUHOD\ZKHQWKHUHLVD'+:FDOOGXULQJ KHDWLQJ+RZHYHUGXULQJ6XPPHURQO\WKH'+:3XPSUHOD\ZLOOHQHUJL]HRQD'+:FDOO 6HOHFWLQJWKH3ULPDU\6HFRQGDU\RSWLRQZLOOHQHUJL]HWKH6\VWHPUHOD\ZLWKWKH'+:3XPSUHOD\ZKHQHYHUWKHUHLVDFDOOIRU DHW even during the Summer or when outdoor temperature is above the Outdoor Cutoff. No priority will be available. $/(57 A DHW call can be initiated by either a dry contact or using a Weil McLain Sensor (389-900-230) for immersion in a 3/8ID well (592-300-023). The use of a sensor will allow the adjustment of the DHW Set Point and DHW Differential. '+:3803287387 1R<HV 'HIDXOW<HV Hold Button: MENU/<System Startup>/..../DHW Pump Output 7KH%&3:FDQFRQWUROWKHRSHUDWLRQRIWKH'+:3XPS7KLVRSWLRQDOORZVWKHXVHU to select if the BCP-8W should be controlling the DHW Pump or not. --DHW PUMP No Yes BACK OUTPUT-SAVE &20%867,21$,5'$03(5287387 - COMB. AIR OUTPUT1R<HV 'HIDXOW<HV No Hold Button: MENU/<System Startup>/..../Comb. Air Output Yes 7KH%&3:FDQFRQWUROWKHRSHUDWLRQRIWKH&RPEXVWLRQ$LU'DPSHU7KLVRSWLRQ BACK SAVE allows the user to select if the BCP-8W should be controlling the Combustion Air Damper or not. ,I<HVLVVHOHFWHGWKH%&3:ZLOOHQHUJL]HWKH&RPE$LUUHOD\ZKHQHYHUWKHUHLVDFDOOIRUDERLOHUDQGZLOOXVHWKHPROVE LQSXWWRFKHFNRQWKHVWDWXVRIWKH&RPEXVWLRQ$LU'DPSHU:KHQWKHODVWVWDJHLVGHHQHUJL]HGWKH&RPE$LUUHOD\ZLOO UHPDLQHQHUJL]HGIRUWKH5XQ2QSHULRGDQGWKHQGHHQHUJL]H On a prove failure situation, the message "Wait for Comb. Prove". No boiler stages will be active until the Prove input is Shorted. ,I3URYHIDLOVDIWHUWKHERLOHUVWDJHVZKHUHHQHUJL]HGWKHVWDJHVZLOOGHHQHUJL]HDQGWKHPHVVDJHComb. Prove FailureZLOOGLVSOD\XQWLOWKHVLWXDWLRQLVUHFWL¿HG ,I1RLVVHOHFWHGWKHPROVE input will be used to check System status instead of the Combustion Air Damper. (;7(51$/,138702'( -- EXTERNAL INPUT 6KXWGRZQ7VWDW6HWEDFN 'HIDXOW7VWDW Shutdown Hold Button: MENU/<System Startup>/..../External Input Tstat Setback 7KH6KXWGRZQIXQFWLRQDOORZVWKH%&3:WRUHFHLYHDUHPRWH6KXWGRZQVLJQDOWR WHUPLQDOVDQGWRWXUQRIIDOOUHOD\VLQFOXGLQJDOOERLOHUVVWDJHV BACK SAVE :KHQ6KXWGRZQLVVHOHFWHG'+:FDOOVZLOOEHLJQRUHGXQOHVVWKHFRQWUROLVRXWRI Shutdown. 7KH7VWDWRSWLRQJLYHVWHUPLQDOV35 and 36 the capability of functioning as a heat-call. That is, when terminals 35 and 36 are shorted, the BCP-8W will sequence the stages. However, when they are opened, all stages will turn off. Thus, do not remove the factory installed jumper unless it was replaced with a Tstat signal. 6HWEDFNLVXVHGWRORZHUWKHVHWSRLQWZKHQOHVVORDGLVUHTXLUHGGXULQJQLJKWVDQGZHHNHQGV )RUVHWEDFNRSHUDWLRQWKH%&3:FDQHLWKHUXWLOL]HLWVEXLOWLQQLJKWVFKHGXOHDYDLODEOHZKHQ6KXWGRZQRU7VWDWLVVHOHFWHGDV the External Input, or an external dry contact signal to switch to setback by selecting Setback from this menu. 18 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO %851(57<3( 2Q2II6WDJH6WDJH6WDJH 'HIDXOW2Q2II Hold Button: MENU/<System Startup>/..../Burner Type 7KH%&3:FDQVHTXHQFHIURPDVLQJOHVWDJHDQGXSWRIRXUVWDJHVSHUERLOHU6HOHFW the option based on your boiler number of stages. --- BURNER On/Off 2-Stage 3-Stage 4-Stage BACK TYPE ---- SAVE %2,/(5287387 -- BOILER OUTPUT -1RQH3XPS9DOYH 'HIDXOW1RQH None Hold Button: MENU/<System Startup>/..../Boiler Output Pump Valve :KHQ1RQHLVVHOHFWHGWKH%&3:ZLOOVHTXHQFHPXOWLSOHERLOHUVZLWKRXWDQ\ additional boiler pumps or valves. BACK SAVE 7KH3XPSRSWLRQDOORZVWKH%&3:WRFRQWUROWKHERLOHUVWDJHVLQDGGLWLRQWRWKHERLOHU pumps. The pump stage will run for the Run-On delay after the lower stage of that boiler KDVGHHQHUJL]HG 7KH9DOYHRSWLRQIXQFWLRQVVLPLODUWRWKHSXPSRSWLRQH[FHSWWKDWZKHQDOOVWDJHVDUHRIIDQGDIWHUWKH5XQ2QGHOD\KDV HODSVHGWKH/HDGERLOHU VYDOYHUHOD\ZLOOUHPDLQHQHUJL]HGWRDOORZIRUÀRZDFURVVWKHV\VWHP7KHOHDGERLOHU VYDOYHZLOO UHPDLQHQHUJL]HGXQWLOWKHRXWGRRUWHPSHUDWXUHULVHVDERYHWKH2XWGRRU&XWRIIRUZKHQWKH6KXWGRZQRU6XPPHULVDFWLYDWHG 727$/%2,/(56 IURPWR 'HIDXOWYDULHVEDVHGRQ%XUQHU7\SHDQG%RLOHU2XWSXW Hold Button: MENU/<System Startup>/..../Boiler Output 7KLVRSWLRQLQFRPELQDWLRQZLWK%XUQHU7\SHDQG%RLOHU2XWSXW6WDUWXSRSWLRQVZLOO determine the total number of outputs the BCP-8W will need to control. ,IWKHWRWDOQXPEHURIVWDJHVVHOHFWHGLQFOXGLQJERLOHUSXPSVRUYDOYHVLVPRUHWKDQWKH control and extension stages, the additional boilers containing these stages will have CE DVWKHLUVWDWXVDQGZLOOVHL]HWRRSHUDWH 67$*,1* 0XOWLSOH2XWSXWV6LQJOH2XWSXW 'HIDXOW0XOWLSOH2XWSXWV Hold Button: MENU/<System Startup>/..../Staging 0RVWERLOHUVZLOOUHTXLUHWKDWWKHKLJKHURXWSXWVWDJHVEHHQHUJL]HGDIWHUWKHORZHURXWSXW stages. These boilers will need to select the Multiple Output option. That means, both /RZDQG+LJK2XWSXWVWDJHVPXVWEHHQHUJL]HGWRDFKLHYHWKHERLOHU VPD[LPXPRXWSXW 6RPHHTXLSPHQWUHTXLUHWKDWZKHQWKHKLJKHURXWSXWVWDJHVDUHUHTXLUHGWKHORZHUVWDJHV PXVWGHHQHUJL]H7RRSHUDWHWKHVHHTXLSPHQWWKHXVHUPXVWVHOHFWWKH6LQJOH2XWSXW option. -- TOTAL [ BACK BOILERS 8 -- ] SAVE ------ STAGING -----Multiple Outputs Single Output BACK SAVE 6(48(1&( ------ SEQUENCE ------/R+L/R+L/R/R+L+L 'HIDXOW/R+L/R+L Lo/Hi/Lo/Hi Hold Button: MENU/<System Startup>/..../Sequencing Lo/Lo/Hi/Hi 6RPHERLOHUVUXQPRUHHI¿FLHQWZKHQWKHORZHUVWDJHVDUHHQHUJL]HGDORQHWKDQZLWKWKH BACK SAVE KLJKHUVWDJHV7KHVHW\SHVRIERLOHUVVKRXOGVHOHFW/R/R+L+L7KHQWKH%&3:ZLOO sequence the lower stages of all Automatic boilers before sequencing the higher stages. )RUWKHUHVWRIWKHERLOHUW\SHVWKH/R+L/R+LVKRXOGDOORZWKHVWDJLQJRIWKHORZHUVWDJHRIWKHOHDGERLOHUIROORZHGE\WKH KLJKHUVWDJHRIWKHVDPHERLOHU7KHQZKHQPRUHVWDJHVDUHQHHGHGLWZLOO¿UHWKHORZHUVWDJHRIWKHODJERLOHUIROORZHGE\WKH higher stage of the lag boiler. &21752//2*,& 3,'2662YHU6L]HG6\VWHP 'HIDXOW3,' Hold Button: MENU/<System Startup>/..../Sequencing 7KH3,'RSWLRQDOORZVWKH%&3:WRVHTXHQFHVWDJHVEDVHGRQWKH5HDFWLRQ7LPH and the Boiler Minimum Run Time. The PID relies on the rate of change in the System Temperature. The PID logarithmic calculations foresee changes and sequence stages EDVHGRQWKRVHFKDQJHV,WLVWKHPRVWHI¿FLHQWRSHUDWLRQIRUPRVWKHDWLQJDSSOLFDWLRQV --- CONTROL PID OSS BACK LOGIC--SAVE 19 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO KH2YHUVL]HRSWLRQVHTXHQFHVWDJHVEDVHGRQKRZPDQ\7KURWWOLQJUDQJHVGLIIHUHQWLDOVLVWKHV\VWHPWHPSHUDWXUHDZD\IURP 7 the Target Temperature. At one Throttling range below the Set Point, only one stage will be on. For each additional Throttling range below the Set Point, an additional stage will be activated. The last stage on will be allowed to exceed the Set Point by one Throttling range before turning off that stage. This helps to prevent the last stage from short cycling. :KHQ3,'LV6HOHFWHGWKHIROORZLQJDUHWKHVHWWLQJVWKDWGLUHFWO\DIIHFWVWKLVPRGHVRSHUDWLRQ 5HDFWLRQ7LPHSJ24 6(/(&7Settings/System Settings/Stage Settings/Reaction Time 3XUJH'HOD\(pg 24) 6(/(&7Settings/System Settings/Stage Settings/Purge Delay 0LQLPXP5XQ7LPH(pg 24) 6(/(&7Settings/System Settings/Stage Settings/Min Runtime 6WDQGE\'HOD\(pg 25) 6(/(&7Settings/System Settings/Stage Settings/Standby Delay /DVW6WDJH+ROG(pg 25) 6(/(&7Settings/System Settings/Stage Settings/Last Stage Hold :KHQ2YHUVL]H266LV6HOHFWHGWKHIROORZLQJDUHWKHVHWWLQJVWKDWGLUHFWO\DIIHFWVWKLVPRGHVRSHUDWLRQ 7KURWWOH(pg 25) 6(/(&7Settings/System Settings/Stage Settings/Throttle 6(1625)$8/7 --- SENSOR FAULT --6WDJHV2Q6WDJHV2II 'HIDXOW6WDJHV2Q Stages On Hold Button: MENU/<System Startup>/..../Sensor Fault Stages Off The Sensor Fault will determine the operating status of all output stages set to Auto or BACK SAVE Standby when a sensor reads Short or Open. 7KH6KXWGRZQRU7VWDWDFWLYDWLRQZLOOWDNHSUHFHGHQFHRYHUWKH6HQVRU)DXOWVWDWXV7KDWPHDQVLI6WDJHV2QLVVHOHFWHGDQG the Shutdown was active, all stages will be Off on a sensor fault. 5(6(702'( :KHQ6WDJHV2QLVVHOHFWHGWKH%&3:ZLOOWXUQDOOERLOHUVWDJHV2QZKHQWKH6\VWHPUHDGVShort or Open and the outdoor is below the Outdoor Cutoff. When the Outdoor reads Short or Open, the BCP-8W will change the Target to the Maximum Target. :KHQ6WDJHV2IILVVHOHFWHGWKH%&3:ZLOOWXUQDOOVWDJHV2IIZKHQWKH6\VWHPUHDGVShort or Open. However, when the Outdoor reads Short or Open, the BCP-8W will change the Target to the Minimum Target. 6(732,1702'( :KHQ6WDJHV2QLVVHOHFWHGWKH%&3:ZLOOWXUQDOOVWDJHV2QZKHQWKH6\VWHPVHQVRUUHDGVShort or Open. :KHQ6WDJHV2IILVVHOHFWHGWKH%&3:ZLOOWXUQDOOVWDJHV2IIZKHQWKH6\VWHPVHQVRUUHDGV Short or Open. 7KH2XWGRRU6HQVRU6KRUWRU2SHQVWDWXVZLOOQRWDIIHFWWKHFRQWURORSHUDWLRQLQ6HW3RLQWPRGH 6(77,1*7+(&21752/72)$&725<'()$8/76 To Reset the BCP-8W control to its original factory defaults, power down the control. Hold down the two right most buttons while powering the control back up until the Total Clear Started screen appears. The Display will direct you to the Startup menu to program the control after the defaults are loaded. TOTAL CLEAR STARTED Release buttons and Please Wait 127(:KHQUHVHWWLQJWKHFRQWUROWRRULJLQDOIDFWRU\GHIDXOWVDOOFRQWUROVHWWLQJVZLOOEHRYHUZULWWHQDQGZLOOQRORQJHUH[LVW $/(57 Do not turn off power to control until all Startup settings have been made. Otherwise, the next SRZHUXSZLOOEHVHWWRPDQ\6WDUWXSIDFWRU\VHWWLQJVWKDWPLJKWQRW¿W\RXUDSSOLFDWLRQ 23(5$7,1*6(77,1*6 352*5$0&+$1*(6(77,1*6 To be able to change the BCP-8W settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. 20 PROGRAM RUN %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 6($621 5(6(75$7,2 &XVWRP2'6\VWR2'6\V'HIDXOW2'6\V Hold Button: MENU/<Outdoor Reset>/Reset Ratio ,Q2XWGRRU5HVHW2QO\ 7KH5HVHW5DWLRGHWHUPLQHVKRZWKHV\VWHP7DUJHWWHPSHUDWXUHZLOOYDU\EDVHGRQWKH outdoor temperature. With any of the ratios, the colder it becomes outside, the hotter the temperature of the system water. (See Understanding Operation Concept on page 5) :LWKD2'6<6UDWLRWKH6\VWHPZDWHUWHPSHUDWXUH6<6ZLOOLQFUHDVH UDSLGO\DVWKHRXWVLGHWHPSHUDWXUHIDOOVKLWWLQJWKH0D[LPXPRI)DW)RXWVLGH WHPSHUDWXUH:LWKD2'6<6UDWLRWKH6\VWHPWHPSHUDWXUH6<6ZLOO LQFUHDVHVORZO\DVWKHRXWVLGHWHPSHUDWXUHIDOOV(YHQDW)WKHV\VWHPZDWHUZLOO only be 125°F, and at 22°F outside, the system water will be 112°F. Such a low Reset 5DWLRPLJKWEHXVHGZLWKUDGLDQWÀRRUKHDWLQJDSSOLFDWLRQV :LWKPRVWEDVHERDUGKHDWLQJDSSOLFDWLRQVD2'6<6) setting is a good SODFHWRVWDUW:LWKD2'6<6) ratio, for every degree the outside temperature falls, the system water temperature is increased one degree. ,IUHTXLUHG$GMXVWWKH5(6(75$7,2LQFROGZHDWKHU If the ambient building temperature are cold in cold weather, move the ratio to a higher selection. That is, if 2'6<6ZDVLQLWLDOO\VHOHFWHGFKDQJHWKHVHOHFWLRQWR2' (6<6). If the building temperature are too warm in cold weather, move the ratio to a ORZHUVHOHFWLRQ7KDWLVLI2'6<6) was initially selected, change it to 1.25 2'6<6). $IWHUVHOHFWLQJWKH5HVHW5DWLRSUHVVLQJWKHSAVE button will switch to the Outdoor Cutoff setting option. $/(57 DO NOT turn power off to the BCP-8W when in off-season. If you do so, the battery will run down and have to be replaced. Instead, switch Season to Summer. ---- SEASON Winter Summer BACK --SAVE ---- RESET RATIO --Custom 1(8.00 OD:1.00 SYS) 2(4.00 OD:1.00 SYS) 3(3.00 OD:1.00 SYS) 4(2.00 OD:1.00 SYS) 5(1.50 OD:1.00 SYS) 6(1.25 OD:1.00 SYS) 7(1.00 OD:1.00 SYS) 8(1.00 OD:1.25 SYS) 9(1.00 OD:1.50 SYS) 10(1.00 OD:2.00 SYS) 11(1.00 OD:3.00 SYS) 12(1.00 OD:4.00 SYS) BACK SAVE Water Temperature :LQWHU6XPPHU 'HIDXOW:LQWHU Button: MENU/Season 7KH%&3:ZLOOWXUQDOOERLOHUUHOD\VRIIZKHQLWLVLQ6XPPHUVHWWLQJThe Message 'LVSOD\/LQHZLOOUHDGSummer to show status. However, a DHW call will bring the boilers back on if needed. When in Winter, the BCP-8W will activate the System relay whenever the Outdoor temperature falls to or below the Outdoor Cutoff setting. In addition, it will begin heating whenever the System temperature falls below the Set Point 7HPSHUDWXUH7KH0HVVDJH'LVSOD\/LQHZLOOQRWGLVSOD\DQ\VHDVRQLQIRUPDWLRQ :KHQWKHVHDVRQLVRYHULWLVDJRRGSUDFWLFHWRVZLWFKWKH%&3:6HDVRQVHWWLQJ7KLV will allow DHW calls to operate the boilers when needed. 130 1:4 1:1 Warmer 120 Colder 110 100 4:1 70 60 50 40 Outdoor Temperature &86720,=('5(6(75$7,2 Hold Button: MENU/<Outdoor Reset>/Reset Ratio/Custom )RUVLWXDWLRQVZKHUHWKHDYDLODEOHUHVHWUDWLRVGRQRWSURYLGHWKHSHUIHFWEXLOGLQJKHDWORVVHTXLOLEULXPWKHFXVWRPL]HGRSWLRQ can be used by selecting Custom from the Reset Ratio menu option. ,WSURYLGHVWKHXVHUZLWKWKHFDSDELOLW\RIDVVLJQLQJWZRSRLQWVRQWKHUHVHWUDWLRGLDJUDPDQGXVHWKHOLQHWKDWFRQQHFWVWKRVH WZRSRLQWVDVWKHFXVWRPL]HGUHVHWUDWLRFXUYH(DFKRIWKHWZRSRLQWVZLOOQHHGDVSHFL¿F6\VWHPDQG2XWGRRU7HPSHUDWXUHWR identify it on the diagram. 7R6HWWKH¿UVWSRLQWVSHFLI\6\V7HPSDQG2'7HPS7KHQVSHFLI\6\V7HPSDQG2'7HPSWRVHWWKHVHFRQGSRLQW on the curve. The two points can be anywhere on the line, not necessarily at the ends. 7KHFKDUWVKRZVDQH[DPSOHRIDFXVWRPL]HGFXUYH2'6<6WKDWGRHVQRWH[LVWLQWKHVWDQGDUGFXUYHRSWLRQV,IWKH RXWGRRUWHPSHUDWXUHUHDFKHV)WKHV\VWHPWDUJHWZLOOEH) 5HPHPEHUWKDWWKH2IIVHW0LQ7DUJHWDQG0D[7DUJHWDSSO\WRDOOUHVHWUDWLRVLQFOXGLQJWKHFXVWRPL]HGUHVHWUDWLRRQHV 21 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO -- SET [ BACK -- AT [ BACK SYS TEMP.1 120 F - ] SAVE OD TEMP.1 60 F --- ] SAVE -- SET [ BACK -- AT [ BACK SYS TEMP.2 170 F Water Temperature (in °F) Point1: System=120°F Oudoor=60°F 180 - ] SAVE OD TEMP.2 0 F --- Point2: System=170°F Oudoor=0°F Max Target tio 170 et 160 ed Ra Point2 s Re iz om st 150 Cu 140 130 Point1 120 Min Target 110 100 ] SAVE 70 60 50 40 30 20 10 0 -10 -20 Outdoor Temperature (in °F) Custom Reset Ratio 6(732,17127$'-867$%/(,1(0602'( ----- SET POINT ----$GMXVWDEOHIURPº)º&WRº)ºC 'HIDXOWº)º& 70 F Button: MENU/Set Point ,Q6HW3RLQWRU(06P$ [ ] 7KH6HWSRLQWLVWKHWHPSHUDWXUHYDOXHWKH%&3:ZLOOXVHWRFRQWUROWKHV\VWHP BACK SAVE 7KH%&3:ZLOODGGVXEWUDFWRUKROGWKHVWDJHVRIWKHKHDWLQJERLOHUVWRPDLQWDLQWKH system temperature around the Set point. 7KHV\VWHPFDQEHH[SHFWHGWRÀXFWXDWHDURXQGWKHVHWSRLQW7KHDPRXQWRIÀXFWXDWLRQGHSHQGVRQWKH6\VWHP6HWWLQJVDQG Stage Settings. ,IDQ2XWGRRU6HQVRUZDVFRQQHFWHGSUHVVLQJWKHSAVE button will continue to the Outdoor Cutoff setting option. ,IWKH(060RGHZDV(QDEOHGWKH6HW3RLQWZLOOEHVHWE\WKH(06%06V\VWHPDQGZLOOEHDYDLODEOHDVDUHDGRQO\ 7KHUDQJHRI6HW3RLQWLQWKH(06LVVHWLQWKH6WDUWXSPHQXDWP$DQGP$ $Q\UHDGLQJEHORZWKHP$RUDERYHP$ZLOOLQGLFDWHDShutdown by EMSPHVVDJHRQWKH0HVVDJH/LQH 287'225&872))7(03(5$785( -- OUTDOOR CUTOFF -$GMXVWDEOH2IIIURPº)º&WRº)º&2Q 'HIDXOW)& 70 F Hold Button: MENU/Set Point/Outdoor Cutoff LQ6HW3RLQW [ ] Hold Button: MENU/<Outdoor Reset>/Outdoor Cutoff LQ5HVHW BACK SAVE ,Q2XWGRRU5HVHWPRGH2XWGRRU&XWRIIZLOODOZD\VH[LVW+RZHYHULQ6HW3RLQWPRGH if the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear after the temperature Set Point has been selected. :KHQWKHRXWGRRUWHPSHUDWXUHIDOOVWRWKHDGMXVWDEOH2XWGRRU&XWRIIWHPSHUDWXUHWKH%&3:ZLOOFRQWURODQGVHTXHQFHWKH boiler stages to hold the calculated temperature. :KHQWKHRXWGRRUWHPSHUDWXUHULVHVWRWKH2XWGRRU&XWRIISOXVD)GLIIHUHQWLDOWKH%&3:ZLOOWXUQDOOERLOHUVRII7KH 6\VWHP&RPEXVWLRQ$LU'DPSHUDQGDQ\RWKHU3XPSRUYDOYHUHOD\VWKDWZHUHHQHUJL]HGZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2Q delayDQGWKHQGHHQHUJL]H. ,QDGGLWLRQWKH2XWGRRU&XWRIIFDQEHVHWWR21RU2)),QWKH21RSWLRQWKH6\VWHP5HOD\ZLOOUXQUHJDUGOHVVRIWKH2XWGRRU temperature and the burner stages will be active to hold the target water temperature. ,QWKH2))SRVLWLRQWKHV\VWHPSXPSZLOODOZD\VEHRIIDQGDOOVWDJHVZLOOEHRIIDVZHOO 7$5*(72))6(7 $GMXVWDEOHIURPº)º&WRº)º& 'HIDXOWº)º& Hold Button: MENU/<Outdoor Reset>/Offset LQ2XWGRRU5HVHWRQO\ 7KH2IIVHWVHWWLQJPRYHVWKH5HVHW5DWLRFXUYHYHUWLFDOO\7KLVPHDQVWKDWUHJDUGOHVV of the Outdoor temperature, or the Reset Ratio that has been selected, when the Offset setting is changed, that change is directly added to or subtracted from the calculated WHPSHUDWXUH)RUH[DPSOHLIWKH6HW3RLQWWHPSHUDWXUHZDV)DQGWKH2IIVHWZDV changed from 0° to 10° (an increase of 10°), the Set Point would increase to 140°F. 22 -- TARGET OFFSET +0 F [ BACK --- ] SAVE %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO KH2IIVHWVHWWLQJGRHVQRWFKDQJHWKHUDWLRVHOHFWLRQ)RULQVWDQFHZLWK2' 7 6<65HVHW5DWLRWKH6\VWHPZDWHUWHPSHUDWXUHZLOODOZD\VLQFUHDVHRQHGHJUHHIRU every 1.5 degree change in the Outdoor temperature. What the Offset does is add or subtract a constant temperature value. (See Understanding Operation Concept on page 5) 7KH0LQLPXPDQG0D[LPXP7DUJHWZLOOWDNHSUHFHGHQFHRYHUWKH2IIVHW7KDWLVLIWKH 0D[7DUJHWZDVVHWWR)DQGWKH2IIVHWZDVVHWWR),IWKHVHWSRLQWZDV) the new calculated set point based with the Offset should be 175°F. However, it will not exceed 170°F due to the Maximum Target setting. ,IUHTXLUHG$GMXVWWKH:DWHU2IIVHWLQPLOGZHDWKHU. If the ambient building temperatures are too warm in the mild weather, decrease the Target Offset. If the ambient building temperatures are too cold in the mild weather, increase the Target Offset. The rule of thumb for baseboard radiation is to change the Offset 4°F for every 1°F you wish to change the building temperatures. In radiant heat applications, change the Offset 1°F or 2°F for every 1°F you wish to change the building temperature. Offset=10°F Reset Ratio=1.5 : 1.0 Min Target=120°F Max Target=170°F 180 Water Temperature (in °F) 170 Max Target t fse 160 0F Of 1 o+ 150 io ati at tR tR se 140 se Re Re 130 Min Target 120 110 100 70 60 50 40 30 20 10 0 -10 -20 Outdoor Temperature (in °F) Target Offset 0,1,0807$5*(7 ---- MIN TARGET ---$GMXVWDEOHIURPº)º&WRº)º& 'HIDXOWº)º& 140 F Hold Button: MENU/<Outdoor Reset>/Min. Target LQ2XWGRRU5HVHWRQO\ [ ] 7KH0LQLPXP7DUJHWPXVWEHVHWWRWKHERLOHUPDQXIDFWXUHU¶VVSHFL¿FDWLRQ7KH%&3 BACK SAVE 8W will calculate the Set Point based on the Outdoor temperature, the Reset Ratio, and the Offset value. The BCP-8W will control all boilers to hold either the Set Point temperature, or the Minimum Target, whichever is higher. 7KH0LQLPXP7DUJHWPXVWEHDWOHDVW)ORZHUWKDQWKH0D[LPXP7DUJHW6HHQH[WVHWWLQJ 0$;,0807$5*(7 $GMXVWDEOHIURPº)º&WRº)º& 'HIDXOWº)º& Hold Button: MENU/<Outdoor Reset>/Max. Target LQ2XWGRRU5HVHWRQO\ 7KLVLVWKHKLJKHVW7DUJHWWHPSHUDWXUHWKH%&3:ZLOOFDOFXODWHIRUWKHKHDWLQJV\VWHP :KHQXVLQJLQÀRRUUDGLDQWV\VWHPLWVKRXOGEHVHWDFFRUGLQJWRWKHWXELQJRUÀRRU PDQXIDFWXUHU¶VVSHFL¿FDWLRQ 7KH0D[LPXP7DUJHWPXVWEHDWOHDVW)KLJKHUWKDQWKH0LQLPXP7DUJHW6HH previous setting).. ---- MAX [ BACK TARGET 200 F ---] SAVE %2,/(50,1,0805(7851 When a return sensor is connected to the BCP-8W, it will monitor and control the boiler return. It does that by monitoring the Target WHPSHUDWXUH7*76\VWHPWHPSHUDWXUH6<60LQLPXP5HWXUQDQGDFWXDOUHWXUQ571:KHQWKH%&3:IRUHVHHVWKDWDORZ return will occur, it will increase the Target automatically as an effort to increase the return temperature. See Return Sensor Wiring on page 10. 0,1,0805(7851 ---- MIN RETURN ---$GMXVWDEOH2IIIURPº)º&WRº)º& 'HIDXOW2II OFF Hold Button: MENU/Min. Return [ ] 7KH0LQLPXP5HWXUQLVWKHFULWLFDOWHPSHUDWXUHDWZKLFKWKHUHWXUQVKRXOGEHDERYH BACK SAVE Normally, this setting is provided by the boiler manufacturer or the system engineer. 7KH%&3:ZLOOXVHWKDWYDOXHDVDJXLGH,WZLOOVWDUWWRDGGDGGLWLRQDOVWDJHVLILWIRUHVHHVWKDWWKH571WHPSHUDWXUHZLOO drop below the Min. Return. During that period, it will display "Hold Return at 120 F" in the Display Message /LQHWRLQGLFDWHWKDWWKH%&3:LVVHTXHQFLQJERLOHUVWRSURWHFWWKHUHWXUQIURPGURSSLQJEHORZWKH0LQLPXP5HWXUQ 0RVWFRQGHQVLQJERLOHUVZLOOUXQPRUHHI¿FLHQWZLWK&RROHUUHWXUQWHPSHUDWXUHV,QWKLVFDVHVHOHFWWKH2IIRSWLRQRQWKH Minimum Return to allow the monitoring of the return on the display without sequencing the boiler stages. 23 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 5(7851/$* $GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV Hold Button: MENU/Min. Return/Return Lag ,WLVWKHWLPHLWWDNHVIRUWKHV\VWHPUHWXUQWRFKDQJHDIWHUVHTXHQFLQJWKHVWDJHV ,QLWLDOO\DGMXVWWKLVYDOXHWRHTXDOWKH5HDFWLRQ7LPH7KHQLQH[WUHPHFROGZHDWKHU monitor the return making sure it is about 10°F above the Minimum Return setting and adjust it if needed. 6<67(06(77,1*6 ---- To be able to change the BCP-8W settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. 67$*(6(77,1*6 Button: MENU/<System Settings>/<Stage Settings> 5($&7,217,0( $GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV Hold Button: MENU/<System Settings>/<Stage Settings>/Reaction TimeLQ3,'/RJLFRQO\ ,WLVWKHDPRXQWRIWLPHLWWDNHVDVLQJOHVWDJHWRDIIHFWWKHV\VWHP $IWHUWKH%&3:WXUQVRQDVWDJHWU\LQJWRPHHWDVHWSRLQWLWZLOOQRWWXUQRQDQRWKHU stage until the Reaction Time has elapsed. 7RGHWHUPLQHWKHRSWLPXPWLPHLQDKHDWLQJV\VWHPVWDUWZLWKDKRWV\VWHP7XUQRQ a single stage and calculate how long it takes until the system begins to respond to that stage. That period should be set as the Reaction Time (See PID operation ). ---- [ BACK - Hold Button: MENU/<System Settings> 7KH6\VWHP6HWWLQJVPHQXSURYLGHVDFFHVVWRDGMXVWLQJDQG¿QHWXQLQJWKHV\VWHPIRUHQKDQFHG comfort and better fuel savings. The BCP-8W behaves differently based on the selected Control Modes (see Startup Settings 17). 352*5$0&+$1*(6(77,1*6 RETURN LAG 2min ] SAVE SYSTEM SETTINGS <Stage Settings> <Setback Schedule> <DHW Settings> Setback 0 F Run-On 2min Pump Exercise Off BACK SELECT PROGRAM RUN -- STAGE SETTINGS -Reaction Time 1min Purge Delay 0.0min Min Runtime 2min Standby Delay 10min Last Stage Hold5 F Throttle 2 F <Lead Settings> BACK -- SELECT REACTION TIME 2min [ BACK -- ] SAVE 385*('(/$< --- PURGE DELAY ---$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV 1.0min Hold Button: MENU/<System Settings>/<Stage Settings>/Purge DelayLQ3,'/RJLFRQO\ [ ] 0RVWODUJHERLOHUVPXVWJRWKURXJKDSXUJHF\FOHEHIRUHWKH\DUHEURXJKWRQOLQH BACK SAVE :KHQWKH%&3:DFWLYDWHVDERLOHUWKHORZHVWVWDJHRQDERLOHULWGRHVQRWVWDUWWR calculate its output until the Purge Delay is over. This allows the boiler to fully come on line and to begin producing output. 7KH3XUJH'HOD\KHOSVSUHYHQWVKRUWF\FOLQJRIDQHZO\DFWLYDWHGERLOHU2QFHWKHORZHVWERLOHUVWDJHLVDFWLYDWHGLW0867UXQ through the entire Purge Delay period (See PID operation on page ). 7KHPLQLPXP3XUJH'HOD\VHWWLQJ0867EHVHWWRWKHWLPHUHTXLUHGE\WKHERLOHUVPDQXIDFWXUHUVSHFL¿FDWLRQ 0,1,0805817,0( - MINIMUM RUNTIME $GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV 1min Hold Button: MENU/<System Settings>/<Stage Settings>/Min RuntimeLQ3,'/RJLFRQO\ [ ] 7KLVLVWKHPLQLPXPDPRXQWRIWLPHDQ\VWDJHZLOOUXQ (See PID operation on page ). BACK SAVE )RUWKHORZHVWVWDJHRIDERLOHUWKH0LQLPXP5XQWLPHVWDUWVDIWHUWKHSXUJHF\FOH 7KLVWLPHUGRHVQRWDSSO\WRWKHODVWVWDJHRQOLQH7KH/DVW6WDJH+ROGDSSOLHVLQWKDWFDVH ,QLWLDOO\VHWWKHMinimum Runtime to half the Reaction Time. ,I6\VWHPWHQGVWRRYHUVKRRWUHGXFHWKHMinimum Runtime. If boilers tend to short cycle, increase Minimum Runtime. 24 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 67$1'%<'(/$< -- STANDBY DELAY -$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV 10min Hold Button: MENU/<System Settings>/<Stage Settings>/Standby DelayLQ3,'/RJLFRQO\ [ ] 7KH6WDQGE\'HOD\RQO\DSSOLHVWRERLOHUVLQ6WDQGE\0RGH6HH0RGHRQSDJH2. BACK SAVE $6WDQGE\ERLOHUFDQRQO\EHDFWLYDWHGDIWHUDOOWKHERLOHUVLQ$XWR0RGHKDYHKDGDOO their stages on running for the full Standby Time. 6WDQGE\ERLOHUVDUHXVHGDVDEDFNXSLQH[WUHPHORDGFRQGLWLRQV$6WDQGE\ERLOHUFDQQHYHUEHD/HDGERLOHU 7KHIXOO6WDQGE\'HOD\PXVWDOZD\VHODSVHUHJDUGOHVVRIZKDWKDSSHQVWRWKHV\VWHPWHPSHUDWXUH7KHUHIRUHVKRUWHU6WDQGE\ WLPHVZLOOUHVXOWLQVPRRWKHUVHWSRLQWRSHUDWLRQLQH[WUHPHFRQGLWLRQV/RQJHU6WDQGE\WLPHVPD\SUHYHQWD6WDQGE\ERLOHU from starting if the other boilers can eventually meet the load or if the load decreases. :KHQVHWWLQJWKH6WDQGE\'HOD\UHPHPEHUWKDWLWZLOOEHDGGHGWRWKH5HDFWLRQ7LPHIRUWKH¿UVWVWDJHRQWKH¿UVWVWDQGE\ boiler. The following stages start time will rely on Pre-Purge and Reaction Time only. /$6767$*(+2/' LAST STAGE HOLD $GMXVWDEOHIURP)º&ºWR)º&º 'HIDXOW)º&º 5 F Hold Button: MENU/<System Settings>/<Stage Settings>/Lst Stg Hld LQ3,'/RJLFRQO\ [ ] 7KH/DVW6WDJH+ROGSUHYHQWVVKRUWF\FOLQJRIWKH/HDG6WDJHGXULQJORZORDGFRQGLWLRQV BACK SAVE ZKHUHWKHV\VWHPPLJKWKDYHDORDGWKDWLVVLJQL¿FDQWO\OHVVWKDQWKHRXWSXWRIRQHVWDJH :KHQWKH%&3:EULQJVRQWKH/HDG6WDJHWKH6HW3RLQWLVTXLFNO\H[FHHGHGDQGWKH/HDG6WDJHLVWXUQHGRII7RSURORQJ WKHUXQWLPHGXULQJWKLVW\SHRIFRQGLWLRQXVHWKH/DVW6WDJH+ROGVHWWLQJ 7KH%&3:ZLOODOORZWKHV\VWHPWHPSHUDWXUHWRH[FHHGWKH6HW3RLQWE\WKHQXPEHURIGHJUHHVVHOHFWHGEHIRUHWKH/HDG Stage is turned off. (See PID operation ). )RUH[DPSOHZLWKD6HW3RLQWRI)DQGD/DVW6WDJH+ROGVHWWLQJRI)WKH/HDG6WDJHERLOHUZLOOUHPDLQRQXQWLOWKH6HW Point reaches 170°F. During that period, the display will show "Hold Until 170F" then, the lead stage will turn off 7+5277/(5$1*( -- THROTTLE RANGE -$GMXVWDEOHIURP)º&ºWR)º&º 'HIDXOW)º&º 2 F Hold Button: MENU/<System Settings>/<Stage Settings>/Throttle LQ266/RJLFRQO\ [ ] 7KH7KURWWOLQJ5DQJHVHWVDWHPSHUDWXUHEDQGDURXQGWKH6HW3RLQWWKDWFRQWUROVZKHQ BACK SAVE stages will be turned on or off. )RUH[DPSOHLQWKH266&RQWURO0RGHQRVWDJHVZLOOEHDFWLYDWHGXQWLOWKHWHPSHUDWXUHIDOOVRQHIXOO7KURWWOLQJ5DQJHEHORZWKH Set Point. A second stage will be activated when the temperature falls to two full Throttling Ranges below the Set Point, and so on, with one extra stage being turned on for every throttling range below the Set Point the System temperature reaches. 6WDJHVZLOOEHWXUQHGRIIDVWKHWHPSHUDWXUHULVHVWRZDUGWKH6HW3RLQWXVLQJRQHIXOOWKURWWOLQJUDQJHDVDGLIIHUHQWLDOEHWZHHQ stages. 7KHODVWVWDJHWREHWXUQHGRIIZLOOEHDOORZHGWRH[FHHGWKH6HW3RLQWE\DIXOOWKURWWOLQJUDQJHEHIRUHLWLVWXUQHGRII7KLVKHOSV WRSUHYHQWWKHODVWVWDJHIURPVKRUWF\FOLQJZKHQWKHORDGLVORZRUZKHQWKHVWDJHLVRYHUVL]HG (See OSS operation ). 7KURWWOLQJ([DPSOH 6HW3RLQW °) 7KURWWOLQJ )° %RLOHU6WDJHV$%&DQG' )DOOLQJ7HPSHUDWXUH 5LVLQJ7HPSHUDWXUH 7HPSHUDWXUH &DOFXODWLRQ 6WDJH7XUQHG2Q 6WDJHV2Q 6WDJH7XUQHG2II 6WDJHV2Q 185°F 180 + (1)THR --- None A None 180°F 180 - (0)THR --- None --- A 175°F 180 - (1)THR A A B A 171 to 174°F --- --- A --- A,B 170°F 180 - (2)THR B A,B C A,B 166 to 169°F --- --- A,B --- A,B,C 165°F 180 - (3)THR C A,B,C D A,B,C 161 to 165°F --- --- A,B,C --- A,B,C,D 160°F 180 - (4)THR D A,B,C,D --- A,B,C,D /($'6(77,1*6 Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Settings> 7KHOHDGPHQXLVWRKHOSLQVHOHFWLQJWKH/HDGERLOHUDQGWKHW\SHRIURWDWLRQDSSURSULDWHIRU the system. -- LEAD SETTINGS -Lead Boiler AB Rotate Mode Time BACK SELECT 25 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO /($'%2,/(5 'HSHQGLQJRQWKHQXPEHURIVWDJHV 'HIDXOW7KH¿UVWVHWRIVWDJHV Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Setting>/Rotate Mode 7KH/HDG%RLOHU¶VORZHVWVWDJHZLOODOZD\VEHWKHILUVWVWDJHEURXJKWRQZKHQWKHUHLVD call for output. As more output is needed, additional stages are added. 7KH/HDG%RLOHULVDOZD\VVKRZQRQWKHPDLQGLVSOD\LQEUDFNHWV ,QD6WDJHV\VWHPVHH%XUQHU7\SHLQWKH6WDUWXSVHFWLRQRQSDJH19), the display will show the WZR/HDG%RLOHUVWDJHVEUDFNHWHG$%!,QD6WDJHV\VWHPWKHGLVSOD\ZLOO VKRZWKHWKUHH/HDG%RLOHUVWDJHVEUDFNHWHG$%&!DQGVRRQ ,IDSXPSRUDYDOYHLVVHOHFWHGDVWKH%RLOHU2XWSXWLQWKH6WDUWXSPHQXVHHSDJH19), the pump or valve letter will be skipped from the number os stages. See example to the ULJKW7KHPLVVLQJVWDJH&DQG)UHSUHVHQWWKH%RLOHU9DOYHRU3XPS 7KH/HDG%RLOHUFDQEHURWDWHGEDVHGRQWKH5RWDWLRQ0RGHVHOHFWHG6HHQH[WVHWWLQJ 527$7(02'( $GMXVWDEOH7LPHIURPKUWRKUV0DQXDO)2)2 'HIDXOW7LPH+RXUV Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Setting>/Rotate Mode 7KH/HDG%RLOHULVWKH¿UVWERLOHUEURXJKWRQZKHQRXWSXWLVUHTXLUHG 7KH/HDG%RLOHUFDQEHURWDWHGDXWRPDWLFDOO\PDQXDOO\RUEDVHGRQ)LUVW2Q)LUVW2II (FOFO). The automatic rotation is recommended for most applications. 7KHFXUUHQW/HDG%RLOHULVVKRZQLQEUDFNHWVRQWKHPDLQGLVSOD\ 2QO\ERLOHUVWKDWDUHVHWWR$XWR0RGHFDQEH/HDG7KHUHIRUHQRWDOOWKHERLOHUVPD\ EHDYDLODEOHZKHQPDQXDOO\VHOHFWLQJDQHZ/HDG%RLOHU ,I7LPHLVVHOHFWHGDVHFRQGVFUHHQZLOODOORZWKHDGMXVWPHQWRIWKH$XWR5RWDWH3HULRG ,I+RXUVGHIDXOWVHWWLQJZDVVHOHFWHGWKH¿UVWURWDWLRQZLOOWDNHHIIHFWDIWHUKRXUV if the Time was not set. However, if the Time was set, the rotation will always take SODFHDW$07KHIROORZLQJURWDWLRQVZLOOWDNHSODFHHYHU\KRXUVWKHUHDIWHU ,I7LPH5RWDWLRQZDVVHWWRRWKHUWKDQKRXUVWKHURWDWLRQWLPHUZLOOVWDUWIURPWKH moment the setting is changed. ,I)LUVW2Q)LUVW2II)2)2LVVHOHFWHGWKHFRQFHSWZLOOIROORZWKLVH[DPSOHLI$LVWKH OHDGWKHVWDUWLQJVHTXHQFHRIWKHERLOHUVZLOOEH$%WKHQ&:KHQWKHGHHQHUJL]LQJ of the stages starts, it will turn off A, B, Then C. Then, stage D will be the new lead for the next load. No Pump or Valve stages -- LEAD BOILER -AB CD EF BACK SELECT With Pump or Valve stages -- LEAD BOILER -AB DE BACK SELECT -- LEAD ROTATION Time Manual FOFO BACK -- SELECT If Time Rotation is selected AUTO ROTATE PERIOD 24hrs [ ] BACK SAVE SETBACK SCHEDULE Setback 0 F Present Time **:** Day Schdule 7:00Am Night Schdul 7:00Pm BACK SELECT 6(7%$&.6&+('8/( Hold Button: MENU/<System Settings>/<Stage Settings>/<Setback Schedule> This menu provides the Setback and Boost based on Day/Night Schedule. It will only be available when Shutdown or Tstat are selected as the Startup External Input option. 6(7%$&. ------ SETBACK ------$GMXVWDEOHIURP°)°&WR)& 'HIDXOW°)°& 0 F Hold Button: MENU/<System Settings>/<Stbck Schdle>/Setback LQ'D\1LJKW6FKHGXOH [ ] Hold Button: MENU/<System Settings>/Setback LQ([WHUQDO6LJQDO BACK SAVE 7KH6HWEDFNIHDWXUHFDQEHXVHGWRSURYLGHWKH%&3:ZLWKDORZHUWHPSHUDWXUH6HW Point when less load is required during the night or on the weekends when the building is not occupied, but heat is still required. 7KHQHZ6HW3RLQWZLOODSSHDURQWKHPDLQGLVSOD\LQGLFDWLQJWKLVFRQGLWLRQSetback to 160 F". )RUH[DPSOHLIWKHFDOFXODWHGWHPSHUDWXUHLV)DQGWKH6HWEDFNLV)WKHQZKHQLQ6HWEDFNWKH%&3:ZLOOKROGD6HW 3RLQWRI)180°F - 20°F). $IWHUVHOHFWLQJDYDOXHLQ6HWEDFN\RXZLOOEHGLUHFWHGWRWKH%RRVWPHQX %2267 $GMXVWDEOHIURP)&WR)& 'HIDXOW°)°& Hold Button: MENU/<System Settings>/Setback/Boost 7KLVIHDWXUHVDOORZVDEXLOGLQJWRZDUPXSGRZQTXLFNO\DIWHUD6HWEDFNSHULRGWREULQJ the building to the desired temperature faster. 26 -------[ BACK BOOST 0 F --------] SAVE %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO KH%RRVWWHPSHUDWXUHZLOOEHWKHQXPEHURIGHJUHHVWREHDGGHGWRWKH7DUJHW 7 7KHQHZ6HW3RLQWZLOODSSHDURQWKHPDLQGLVSOD\LQGLFDWLQJWKLVFRQGLWLRQBoost to 190 F". 8VLQJWKHSUHYLRXVH[DPSOHLIWKH7DUJHWZDV)DQGWKH6HWEDFNZDV)DQGWKH%RRVWZDV)IRUPLQXWHVDIWHUWKH VHWEDFNSHULRGWKH%RRVWZLOOFKDQJHWKHWDUJHWWR)IRUDSHULRGRIPLQXWHV %22673(5,2' ------ BOOST PERIOD--$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV 30min Hold Button: MENU/<System Settings>/Setback/Boost/Boost Period [ ] 7KLVZLOOGHWHUPLQHWKHOHQJWKRIWLPHWKHV\VWHPZLOOUHFHLYH%RRVW BACK SAVE ,I([WHUQDO6LJQDOZDVVHOHFWHGDVWKH6HWEDFN0RGHWKH%RRVWZLOOVWDUWZKHQWKH switch from Setback to normal operation takes place and will continue for the full Boost Period. An example would be if WKH%RRVW3HULRGZDVVHWWRPLQXWHVDQGWKHVKRUWLQJRIWKH6HWEDFNWHUPLQDOVKDVHQGHGDW$PWKH%RRVWZLOOVWDUWDW $PDQGZLOOWHUPLQDWHDW$PZKHUHWKHFRQWUROZLOOUHVXPHQRUPDORSHUDWLRQ ,I'D\1LJKW6FKHGXOHVZHUHDYDLODEOHWKH%RRVWZLOOVWDUWDIXOO%RRVW3HULRGSULRUWRWKHVZLWFKIURP1LJKWVHWEDFNWR'D\ QRUPDORSHUDWLRQ,IWKH'D\ZDVVHWWRVWDUWDW$PWKH%RRVW3HULRGZDVVHWWRPLQXWHVWKH%RRVWZLOOVWDUWDW$P DQGWHUPLQDWHDW$P $YRLGLQJ&RQÀLFWLQJ%RLOHU/LPLWV :$51,1* 7KHWHPSHUDWXUHOLPLWVVHWRQWKHERLOHUV0867EHVHWFRQVLGHUDEO\KLJKHUWKDQWKH The temperature limits set on BCP-8W’s Set Point for the reasons detailed below. the boilers must be higher than 7KH%&3:VHQVRULVORFDWHGLQDFRPPRQKHDGHUVRPHGLVWDQFHIURPWKHERLOHUV$V the BCP-8W Set Point. Read the temperature rises in the header and before reaching the sensor location, energy is the section at left for details dissipated. Therefore, the temperature in the header could be lower than that registered that will prevent erratic system by boiler sensors. operation. ,QDGGLWLRQWRWKHQRUPDOGURSH[SHULHQFHGEHWZHHQWKHERLOHU¶VWHPSHUDWXUHDQGWKDW UHDGE\WKH%&3:VHQVRUWKH/DVW6WDJH+ROGVHWWLQJPXVWEHDFFRXQWHGIRU7KHERLOHUOLPLWPXVWEHVHWDERYHWKH6HW3RLQW 3/86WKH/DVW6WDJH+ROG3/86WKHQRUPDOGURSH[SHULHQFHGLQWKHSLSLQJ 8VLQJWKHSUHYLRXVH[DPSOHRID)/DVW6WDJH+ROGZLWKD)6HW3RLQWWKHERLOHUV¶OLPLWVPXVWEHVHWHQRXJKRYHU) to prevent the boilers’ internal limits being reached. In this situation, the boiler high limit should be set at approximately 180°F to prevent the difference in boiler temperature vs. header temperature from causing erratic operation. '$<1,*+76&+('8/(6 -- DAY SCHEDULE ---Hold Button: MENU/<System Settings>/<Setback Schedule>/Day Schedules 07:**Am 7KH%&3:KDVWZROHYHOVRIKHDW7KH'D\OHYHOLVXVHGZKHQDEXLOGLQJLVRFFXSLHG BACK SAVE and people are active. -- NIGHT SCHEDULE - 7KH1LJKW6HWEDFNOHYHOLVXVHGZKHQDEXLOGLQJLVQRWRFFXSLHGRUZKHQSHRSOHDUH 10:**Pm sleeping. This setting reduces the calculated temperature by the Setback setting based RQWKHSURYLGHGVFKHGXOH,IWKH'D\FDOFXODWHGZDWHUWHPSHUDWXUHZDVÛ)DQGWKH BACK SAVE 6HWEDFNZDVÛ)WKH1LJKW6FKHGXOHZLOOUXQDWÛ)Û) Û) ,IWKH%RRVWIHDWXUHLVEHLQJXVHGLWXVHVWKH'D\6FKHGXOHDVD%RRVWHQGLQJSRLQW7KDWLVLIWKH'D\6FKHGXOHLVVHWWRVWDUW DW$0WKH%RRVWZDVVHWWR)DQGWKH%RRVW3HULRGZDVPLQXWHVWKH%RRVWZLOOVWDUWDW$07KHQZKHQLQ %RRVW%&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWHPSHUDWXUHE\WKH%RRVWDPRXQW8VLQJWKHSUHYLRXVH[DPSOHDW$0WKH %&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWRÛ)Û)Û)XQWLO$0ZKHUHLWZLOOGURSEDFNWRWKHQRUPDOFDOFXODWHG temperature of 150ÛF. 6(735(6(177,0( Hold Button: MENU/<System Settings>/<Setback Schedule>/Present Time Hold Button: MENU/<Maintenance>/Present Time 7KH7LPHLVXVHGIRU'D\1LJKW6FKHGXOHDQG+LVWRU\JUDSK $GMXVWWKHWLPHE\VHOHFWLQJ7LPHIURPWKHPHQXDQGWKHQVFUROOLQJWKURXJKWKHKRXUV followed by the minutes. If hours are to be set to PM, scroll through the AM hours to reach the PM hours. - SET BACK PRESENT **:** TIME SAVE $/(57 Remember that the battery is used as a time backup. If no power is supplied to the BCP-8W, the battery will die in three months and time clock values will be lost. Thus, DO NOT power down the control during off-season. 27 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO '+:6(77,1*6 -- DHW SETTINGS --DHW Temp. 140 F DHW Prior Tmr 60min DHW Set Point120 F DHW Diff. 5 F Hold Button: MENU/<System Settings>/<DHW Settings> $'+:FDOOFDQEHLQLWLDWHGE\VKRUWLQJWKH'+:LQSXWWHUPLQDOV33 and 34. In DGGLWLRQXVLQJD:HLO0F/DLQWHPSHUDWXUHVHQVRURQWKHVDPHWHUPLQDOVLQVWHDGRID dry-contact input will add the DHW Set Point and Differential control capability. BACK SELECT On a DHW call, the BCP-8W will raise the Target to either 200ºF or the Maximum Target, which ever is lower. The BCP-8W provides three levels of DHW pump operation. The ¿UVWLVZKHQ3ULPDU\ Secondary is selected as the DHW Piping from the Startup Menu on page 18. This option will provide no DHW Priority. And, if there was a DHW call during the Summer or when the outdoor temperature is above the Outdoor Cutoff, both the DHW Pump and WKH6\VWHPUHOD\VZLOOHQHUJL]H8SRQWKHWHUPLQDWLRQRIWKH'+:FDOOWKH'+:3XPS UHOD\ZLOOGHHQHUJL]HOHDYLQJWKH6\VWHPUHOD\HQHUJL]HGIRUWKH5XQ2QGHOD\ ,I3DUDOOHOZDVVHOHFWHGDVWKH'+:3LSLQJIURPWKH6WDUWXSPHQXRQSDJH18 and the Season was set to Winter while the DHW 3ULRULW\7LPHUZDVVHWWR12D'+:FDOOZLOONHHSWKH6\VWHPUHOD\HQHUJL]HGLQDGGLWLRQWRHQHUJL]LQJWKH'+:3XPSUHOD\ 8SRQWHUPLQDWLRQRIWKH'+:FDOOWKH'+:3XPSUHOD\ZLOOGHHQHUJL]HOHDYLQJWKH6\VWHPUHOD\RQ +RZHYHULQ:LQWHULIWKH'+:3ULRULW\7LPHUZDVVHWWRDYDOXHRWKHUWKDQ12D'+:FDOOZLOOGHHQHUJL]HWKH6\VWHPUHOD\ DQGHQHUJL]HWKH'+:3XPSUHOD\7KLVZLOOUHPDLQIRUWKHSHULRGRIWKH'+:3ULRULW\7LPHUVHWWLQJRUXQWLOWKH'+:FDOO terminates, whichever is sooner. If the DHW call was still active after the DHW Priority Timer elapses, the System relay will HQHUJL]HIRUWKHUHPDLQLQJRIWKH'+:FDOOSHULRG '+:35,25,7<7,0(5$9$,/$%/(:,7+3$5$//(/'+:3,3,1* $GMXVWDEOH12WRPLQXWHV 'HIDXOWPLQXWHV DHW PRIORITY TIMER Hold Button: MENU/<System Settings>/<DHW Settings>/DHW Prior. Timer LQ3DUDOOHO 2min 7KH'+:3ULRULW\7LPHULVRQO\DYDLODEOHZKHQ'+:3LSLQJLVVHWWR3DUDOOHO6HHSDJH [ ] 18). It provides the user with the capability of selecting the DHW Priority period. If BACK SAVE 12ZDVVHOHFWHGD'+:FDOOZLOOHQHUJL]HWKH'+:SXPSUHOD\ZLWKRXWDIIHFWLQJWKH System Pump operation. That is, when in Summer or Outdoor Cutoff, a DHW call will HQHUJL]HRQO\WKH'+:3XPSUHOD\OHDYLQJWKH6\VWHPUHOD\RII ,Q:LQWHULIWKH'+:3ULRULW\7LPHUZDVVHWWRDYDOXHRWKHUWKDQ12D'+:FDOOZKHQWKHRXWGRRUWHPSHUDWXUHLVEHORZWKH 2XWGRRU&XWRIIZLOOFDXVHWKH6\VWHPUHOD\WRGHHQHUJL]HDQGWKH'+:3XPSUHOD\WRHQHUJL]HIRUWKHSHULRGRIWKH'+: Priority Timer or until the DHW call expertise, whichever happens sooner. If the DHW call did not expire within the Priority SHULRGWKHQWKH6\VWHPUHOD\ZLOOHQHUJL]H '+:6(732,175(48,5(6$1237,21$/'+:7(03(5$785(6(1625 $GMXVWDEOH°)°&WR)& 'HIDXOW°)°& -- DHW SET POINT -Hold Button: MENU/<System Settings>/<DHW Settings>/DHW Set Point 140 F 7KLVLVWKHGHVLUHG'+:WHPSHUDWXUHVHWWLQJDWZKLFKWKH'+:3XPSUHOD\ZLOOGH [ ] HQHUJL]HZKHQUHDFKHG BACK SAVE 7KH%&3:FDQDFFHSWD'+:FDOOLQWZRZD\V$QDTXDVWDWFDQSURYLGHDGU\ FRQWDFWFORVXUHWRWHUPLQDOVDQGLVWKH¿UVWRSWLRQ 7KHVHFRQGRSWLRQZLOOEHFRQQHFWLQJD:HLO0F/DLQWHPSHUDWXUHVHQVRUIRULPPHUVLRQLQD,'ZHOO ZLOORIIHUWKHFDSDELOLW\RIDGMXVWLQJWKH'+:6HW3RLQWDQG'LIIHUHQWLDOWKURXJKWKH%&3:HDV\WRIROORZPHQX (See page 28). In addition to being able to view and log DHW temperature history. '+:',))(5(17,$/ $GMXVWDEOH°)°&WR)& 'HIDXOW°)°& Hold Button: MENU/<System Settings>/<DHW Settings>/DHW Diff. 7KLVUHSUHVHQWVWKHQXPEHURIGHJUHHVWKH'+:WHPSHUDWXUHFDQGURSIURPWKH'+: 6HW3RLQWEHIRUHD'+:FDOOFDQEHUHFRJQL]HGDQGWKH'+:3XPSUHOD\HQHUJL]HG $ODUJH'+:'LIIHUHQWLDOZLOOUHVXOWLQRVFLOODWLRQLQWKH'+:WHPSHUDWXUH+RZHYHUD small DHW Differential will have a tighter control over the DHW temperature but might result in boilers coming on frequently for short periods to satisfy the DHW Set Point and Differential settings. 28 DHW [ BACK DIFFERENTIAL 10 F ] SAVE %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 38039$/9($1'&20%867,21$,5'$03(523(5$7,21 KH%&3:FRQWUROVPXOWLSOHUHOD\VHDFKFRQWUROOLQJGLIIHUHQWW\SHVRIHTXLSPHQW,QDGGLWLRQWRWKHFRQWURORIWKHERLOHUVLW 7 can control the primary system pump, boiler pumps or valves, a DHW pump, and a combustion air damper. The operation of those relays depends on the Startup and System Settings. 58121 ------- RUN-ON ------$GMXVWDEOHWRPLQXWHV 'HIDXOWPLQXWHV 2min Hold Button: MENU/<System Settings>/Run-On [ ] 7KH5XQ2QDSSOLHVWRDOOSXPSVYDOYHVDQGGDPSHUV,WLVWKHDGGLWLRQDOWLPHDSXPS BACK SAVE valve, or a combustion air damper relay will run after the output boiler relays has deHQHUJL]HG)RUSXPSVDQGYDOYHVLWLVXVHGWRGLVVLSDWHWKHH[FHVVHQHUJ\IURPWKH heating system into the building. For a combustion air damper, it brings in enough fresh DLUIRUWKHQH[WERLOHU¿UHXS 7KH5XQ2QWLPHVKRXOGEHVHWEDVHGRQWKHVL]HDQGW\SHRIWKHHTXLSPHQW$ERLOHUZLWKORZZDWHUFRQWHQWZLOOQHHGDORQJHU Run-On than a boiler with more water content. 3803(;(5&,6( $GMXVWDEOH2II2Q 'HIDXOW2II Hold Button: MENU/<System Settings>/Pump Exercise 7KH%&3:SURYLGHVDQRSWLRQWRH[HUFLVHSXPSVIRUVHFRQGVZKHQQRWXVHGIRU seven days. This option reduces pumps' impellers locking after a long off-season period. --- PUMP Off On BACK EXERCISE -- SAVE 29 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 0$,17(1$1&( Hold Button: MENU/<Maintenance> The Maintenance menu gives access to sensor and output trimmings in addition to viewing WKH6WDUWXSFRQ¿JXUDWLRQVHWWLQJVDVZHOODVVHQVRU+LVWRU\ $/(57 To be able to change the BCP-8W settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. 6<67(0287'2256(162575,0 $GMXVWDEOH°)°&WR°)°& 'HIDXOW°F Hold Button: MENU/<Maintenance>/System Trim Hold Button: MENU/<Maintenance>/Outdoor Trim Hold Button: MENU/<Maintenance>/Return Trim Hold Button: MENU/<Maintenance>/DHW Trim 7KH:HLO0F/DLQWKHUPLVWRUW\SHVHQVRUVDUHYHU\DFFXUDWHDQGQRUPDOO\UHTXLUHQR calibration. However, sometimes it may be desirable to make small adjustments to the displayed value. 'RQRWXVHWKH7ULPVHWWLQJWRPDNHWKH2XWGRRUVHQVRUPDWFKWKHRQHUHSRUWHGRQWKH UDGLRRU792XWGRRUWHPSHUDWXUHFDQYDU\ZLGHO\RYHUDEURDGFDVWUDQJH +,6725< Hold Button: MENU/<Histories> The BCP-8W provides users with a graphical history of the System, Outdoor, DHW, and Return sensors for the previous 24 hours. The temperatures are sampled every 12 minutes. That is, readings of temperatures are recorded and stored every 12 minutes for the last 24 hours. 7RYLHZWKHYDOXHVRIDVSHFL¿FSHULRGXVHWKHWZRPLGGOHEXWWRQVWRVFUROOWRWKDWWLPH and read the upper left temperature. 7KH¿UVWVFUHHQZLOOEHWKH6\VWHP7HPSHUDWXUH+LVWRU\%\FOLFNLQJRQWKH1H[WEXWWRQ you will be able to view the Outdoor Temperature History, then, the Return History followed by the DHW History. &21),*85$7,21 Hold Button: 0(180DLQWHQDQFH!&RQ¿JXUDWLRQ! 7KLVPHQXSURYLGHVDFRQVROLGDWHGYLHZRIWKH6WDUWXSVHWWLQJV $GGLWLRQDOFRQWUROVHWWLQJVZLOOEHDYDLODEOHE\VHOHFWLQJWKH1(;7RSWLRQ ---- MAINTENANCE ---Unit F Present Time12:30P <Sensor Trim> <Histories> <Configuration> BACK SELECT --- SENSOR TRIM ---System Trim +0 F Outdoor Trim +0 F Return Trim +0 F DHW Trim +0 F BACK SELECT Sys=120 F 10:00AM BACK NEXT BCP-8W V1.00 Outdoor reset Heating-BreakOnRise Day/Night Schedule DHW Parallel BACK 8 X On/Off PID,Fault Stgs NEXT Off ',63/$<$1'%877216 The BCP-8W display layout provides a variety of information that gives an immediate picture of the operation status. The display shows four heating boilers at a time. The two middle buttons scrolls the screen to view any additional boilers. Moreover, all the information is brightly displayed. It can be viewed in brightly or dimly lit rooms. 7KHEXWWRQV IXQFWLRQDOLW\FKDQJHVEDVHGRQWKHVFUHHQDQGPHQXOHYHO7KHEXWWRQV functionality is displayed on a dark background on the screen's bottom line. 7KHVHFRQGOLQHIURPWKHWRSLVWKH0HVVDJH'LVSOD\/LQH,QQRUPDORSHUDWLRQLW displays the Target Set Point. If a Return sensor was connected, the Target display will be alternating its value with the Return temperature. When the control is to display a status message, the message will replace Target and Return temperatures. See Display Messages on page 1. 30 BACK NEXT %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 7KHWZRPLGGOHEXWWRQVIXQFWLRQVDUHDVIROORZV 7KH+RUL]RQWDODUURZVDUHWRVFUROOWKURXJKWKHDYDLODEOHVWDJHV 7KH9HUWLFDODUURZVDUHWRVFUROOWKURXJKWKHPHQXIXQFWLRQVZKHQLQ PHQXVRUWRFKDQJHYDOXHVRIVHWWLQJVZKHQLQLWVVSHFL¿FVFUHHQ System Temp Outdoor Temp Sys=155 F OD=58 F DHW all (200 F) <AB > DE GH JK HI HI LO ---BOILER MENU Message Display Line Units and their Status Button functions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tandby. 0/2 %RLOHU0LGGOH/RZVWDJHLVDFWLYH$YDLODEOHLQ)RXUVWDJHERLOHUVRQO\7KHERLOHU0RGHLVVHWWRHLWKHU$XWRRU Standby. /2 %RLOHU/RZHVWVWDJHLVDFWLYH7KHERLOHU0RGHLVVHWWRHLWKHU$XWRRU6WDQGE\ 21 $OO%RLOHU6WDJHVDUHVHWWR21 2)) $OO%RLOHU6WDJHVDUHVHWWR2))RUWKHERLOHUGRHVQRWH[LVW &( %RLOHURQ([WHQVLRQSDQHOLVQRWFRPPXQLFDWLQJEDFNWRWKH%&3: Boiler Pumps are being controlled by the BCP-8W. %RLOHU9DOYHVDUHEHLQJFRQWUROOHGE\WKH%&3: ',63/$<0(66$*(6 The BCP-8W normal display layout reserved the second line for message indications. The following is a list of the most common 0HVVDJH'LVSOD\/LQHLQIRUPDWLRQ 6XPPHU 7KHFRQWUROLVVHWWR6XPPHU1RKHDWLVDFWLYH 2XWGRRU&XWRII 7KH2XWGRRUWHPSHUDWXUHLVDERYHWKH2XWGRRU&XWRII 6KXWGRZQ$FWLYH 7KH6KXWGRZQ7HUPLQDOVDUH6KRUWHG1RKHDWLQJERLOHUVZLOOEHDFWLYH 6KXWGRZQE\(06 7KH(06LVEHORZP$RUDERYHP$ '+:&DOOÛ) 7KHUHLVD'+:'RPHVWLF+RW:DWHUFDOO7KH%&3:ZLOO5DLVHV\VWHP6HW3RLQWWRWKH LQGLFDWHGWHPSHUDWXUH'+:LQFUHDVHVFDOFXODWHGWHPSHUDWXUHWRÛ)RU0D[:DWHU7HPSHUDWXUH whichever is lower. +ROGLQJ5HWXUQDWÛ) 5HWXUQVHQVRULVUHDGLQJOHVVWKDQWKH0LQLPXP5HWXUQ%&3:LVWU\LQJWRUDLVHUHWXUQWRÛ) +ROGLQJ8QWLOÛ) 7KH/HDGERLOHULVLQ/DVW6WDJH+ROG7KLVH[DPSOHVKRZVWKDWWKHOHDGVWDJHZLOOWXUQRIIZKHQ V\VWHPWHPSHUDWXUHUHDFKHVÛ) :DLWLQJIRU&RPE3URYH 7KH6\VWHPRU&RPEXVWLRQ$LU'DPSHUUHOD\LV21DQGWKHSURYHWHUPLQDOVDUHRSHQEHIRUHWKHOHDG ERLOHUUHOD\FDQHQHUJL]H 6<63URYH)DLOXUH $IWHUERLOHUVKDYHUXQIRUDZKLOH3URYHVLJQDOZDVRSHQHG7KHERLOHUUHOD\VZLOOGHHQHUJL]H +RZHYHUWKH6\VWHPUHOD\ZLOOUHPDLQHQHUJL]HG 31 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO %2,/(56(77,1*6 ----- BOILER AB ----Mode Auto Runtime 58Hrs <Prev Boiler> <Next Boiler> BACK SAVE 0DNHDOOWKHDSSURSULDWHVHWWLQJVIRU%RLOHU$%LI6WDJHZDVVHOHFWHGDVWKH%XUQHU7\SHIURPWKH6WDUWXSRQSDJH19). 7KHQVHOHFWWKH1H[W6WDJHRSWLRQIURPWKHPHQXWREULQJXSWKH%RLOHU&'6HWWLQJVPHQXDQGPDNHDOOWKHVHWWLQJV&RQWLQXH until all boilers have been set. ,ID%&3;LVFRQQHFWHGWRWKH%&3:VFUROOLQJWKURXJKVWDJHVXVLQJWKH1H[WDQG3UHYPHQXRSWLRQVZLOOVFUROOWKURXJKWKH BCP-8X stages as well. Button: BOILER/ ,QPRVWLQVWDOODWLRQVDOODFWLYHERLOHUDGMXVWPHQWVDUHWKHVDPHEXWHDFKFDQEH FRQ¿JXUHGGLIIHUHQWO\LIGHVLUHG :KHQWKH%2,/(5EXWWRQLVGHSUHVVHGWKH%RLOHU$6HWWLQJVPHQXZLOOEHVKRZQ $/(57 To be able to change the BCP-8W settings, the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. 02'( PROGRAM RUN -- BOILER AB MODE Auto Standby Off On BACK SAVE The BCP-8W will control the boiler’s operation to maintain the desired Set Point. Only boilers set to Auto can be lead boiler. These boilers can only be activated when all boilers in Auto have been at HI for an adjustable Standby delay period. Standby boilers are generally used as a backup in extreme load conditions. Note that, a Standby boiler cannot be a lead boiler. Standby Delay is only available in PID mode. Any output boiler not connected to a physical boiler should be set to Off. The Off Mode can also be used to disable boilers that are being serviced. The On Mode should only be used when testing a boiler. The On Mode overrides the PROVE and SHUTDOWN inputs. Once set to On the boiler will immediately start all of its stages. $XWR6WDQGE\2II2Q 'HIDXOW$XWR Button: BOILER/Mode 7KH%&3:RQO\FRQWUROVDQ\ERLOHUVHWWR$XWRRUDIWHUDGHOD\WKRVHVHWWR6WDQGE\ $Q\RXWSXWZLWKRXWDQDFWLYHERLOHUFRQQHFWHGPXVWEHVHWWR2II 7KHIROORZLQJOLVWGHVFULEHVWKH02'(RSWLRQV $XWR 6WDQGE\ 2II 2Q 5817,0( &OHDU Button: BOILER/RunTime 7KH5XQ7LPHSURYLGHVDQDFFXPXODWLYHKRXUO\UXQIRUWKHVHOHFWHGERLOHU 7KH5XQ7LPHIRUDVSHFL¿FERLOHUFDQEHUHVHWWR]HURE\SUHVVLQJWKHPLGGOHWZR buttons. 32 BOILER BACK AB RUNTIME 58hrs CLEAR OK %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 7528%/(6+227,1* 7(03(5$785(,13876 'LVSOD\VKRZV6HQVRU23(1 Check the sensor is connected and the wires are continuous to the BCP-8W. Finally follow the procedure for Incorrect Temperature Display. 'LVSOD\VKRZV6HQVRU6+257 The BCP-8W sees a short across the input terminals. Remove the wires from the the sensor terminals. The display should change to read OPEN. If it doesn’t, the BCP-8W may be damaged. 'LVSOD\VKRZVDQ,QFRUUHFW7HPSHUDWXUH'LVSOD\ Remove the wires from the sensor terminals. The display should change to read OPEN. If it doesn’t, the BCP-8W may be damaged. Take an ohm reading across the detached sensor wires. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the Temperature sensor Table. If it does not, the sensor may be damaged. 5HWXUQ6HQVRUGRHVQRW'LVSOD\7HPSHUDWXUH 7HPSHUDWXUH6HQVRU&KDUW Check the sensor is connected and the wires are continuous to the BCP-8W. Finally follow the 7(03(5$785( 9DOXH procedure for Incorrect temperature display. LQ'HJUHHV°) LQ2KPV &21752/23(5$7,21 7RR0XFK+HDW &KHFNLIWKHFRQWUROKDVDQ\RIWKHIROORZLQJFRQGLWLRQV 'RPHVWLF+RW:DWHUFDOO- The BCP-8W will raise the temperature of the system to either Û)RU0D[LPXP7DUJHWRQD'+:FDOO 5HVHW5DWLRDQG2IIVHW- If excessive heat occurs only in certain weather conditions, adjust the Reset Ratio and Offset (See Understanding Operating Concept on page 5). If excessive heat occurs year round, reduce the Offset. %RLOHU0RGH6HWWLQJV- The BCP-8W will only sequence boilers with a Mode set to Auto or Standby. Check to if any boiler stage is set to On. &RQWURO6HWWLQJV7KH/DVW6WDJH+ROGZLOODOORZRQO\WKH/HDGERLOHUWRH[FHHGWKHVHWSRLQW ,IWKHVHWWLQJLVWRRKLJKDQGRQO\WKH/HDGERLOHULVRQWKHV\VWHPFDQRYHUKHDW5HGXFHWKH /DVW6WDJH+ROGVHWWLQJ7KLVZLOOPRVWO\RFFXULQPLOGZHDWKHU 7RR/LWWOH+HDW &KHFNLIWKHFRQWUROKDVDQ\RIWKHIROORZLQJFRQGLWLRQV 5HVHW5DWLRDQG2IIVHW- If reduced heat occurs only in certain weather conditions, adjust the Reset Ratio and Offset (See Understanding Operating Concept on page 5). If reduced heat occurs year round, increase the Offset. 6HWEDFNDQG'D\1LJKW6FKHGXOH,IUHGXFHGKHDWRFFXUVRQO\GXULQJVSHFL¿FKRXUVFKHFN the Day/Night Schedule and the Setback, Boost, and Boost Period values. Either reduce the Setback or Boost settings or change the Day and Night Schedules. %RLOHU0RGH6HWWLQJV- The BCP-8W will only modulate boilers their mode is set to Auto or Standby. Check if any boiler stage is set to Manual, Off, or Standby. %RLOHUVDUH6KRUW&\FOLQJ 0LQLPXP5XQWLPH- Increase the Minimum Runtime only if all boilers tend to short-cycle. /DVW6WDJH+ROG,QFUHDVHWKH/DVW6WDJH+ROGRQO\LIWKHOHDGERLOHUWHQGVWRVKRUWF\FOH 6\VWHPLV2YHUVKRRWLQJRU8QGHUVKRRWLQJ 5HDFWLRQ7LPHDQG0LQLPXP5XQWLPH- If the system is overshooting or undershooting, adjust Minimum Runtime or the Reaction Time. That depends on if the stages are brought on fast and were not allowed to turn off until the Minimum Runtime elapsed. Or, the stages were brought on slowly, however, were allowed to turn off quickly. 3,'YV266- If the application the system is used on requires fast response that the normal PID mode cannot provide, try using the OSS mode and adjust the Throttle Range according to the system requirements. -30 117720 -20 82823 -10 59076 0 42683 10 31215 20 23089 25 19939 30 17264 35 14985 40 13040 45 11374 50 9944 55 8714 60 7653 70 5941 80 4649 90 3667 100 2914 110 2332 120 1879 130 1524 140 1243 150 1021 160 842 170 699 180 583 190 489 200 412 210 349 220 297 230 253 240 217 250 187 33 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 08/7,3/(%2,/(56:,7+380363,3,1*:,5,1*',$*5$06 Otdoor u Sensor SQ-Elite The BCP-8W sequencing 4 singlestage boilers and their boiler pumps. The boilers are piped in Reverse Return on the primary loop. The System output is controlling the System Pump. SQ-Elite-8 SEQUENCING CONTROL Stage A Stage E SYSTEM Stage B Stage F DHW PUMP Stage C Stage G COMB. AIR Stage D Stage H ENCLOSED ENERGY MANAGEMENT EQUIPMENT INPUT RATINGS: 115VAC 60Hz, 12VA MAX LISTED 99RA C SYS=144F OD=35F <A > HI E -- C HI STAGE DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS SENSORS MUST BE GOLD SERIES CAUTION: Risk of Electric Shock. Use Copper Conductors Only. G OFF MENU US PROGRAM RUN PWR SYSTEM L N Stage A Stage B Stage C Stage D Stage E Stage F DHW COMB. Stage G Stage H SYSTEM PUMP AIR PRESS + - 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 SHUTDOWN TEMP OUTDOORRETURN DHW PROVE /SETBACK TEMP TEMP RS485 C A V 0 2 1 Boiler 1 Boiler 2 Boiler 3 Boiler 4 ySstem Sensor ySstem Pum p Building Heating o L op SQ-Elite-8 SEQUENCING CONTROL Stage A Stage E SYSTEM Stage B Stage F DHW PUMP Stage C Stage G COMB. AIR Stage D Stage H ENCLOSED ENERGY MANAGEMENT EQUIPMENT INPUT RATINGS: 115VAC 60Hz, 12VA MAX LISTED 99RA C SYS=144F OD=35F > C <A HI LO E -- STAGE DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS SENSORS MUST BE GOLD SERIES PROGRAM RUN PWR L N 34 SYSTEM RS485 PRESS + - 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 PROVE Prove Dry Contact n Uit4 SHUTDOWN /TSTAT /SETBACK Shutdown Dry Contact n Uit3 Sensor Shiled n Uit2 TEMP OUTDOORRETURN DHW TEMP TEMP System Sensor n Uit1 Pum p4 DHW COMB. Stage G Stage H SYSTEM PUMP AIR Pum p3 Stage A Stage B Stage C Stage D Stage E Stage F Pum p2 L N Pum p1 L N MENU US CAUTION: Risk of Electric Shock. Use Copper Conductors Only. G OFF :HLO0F/DLQLVDZDUHWKDWHDFK LQVWDOODWLRQLVXQLTXH7KXV:HLO 0F/DLQLVQRWUHVSRQVLEOHIRUDQ\ LQVWDOODWLRQUHODWHGWRDQ\HOHFWULFDORU SOXPELQJGLDJUDPJHQHUDWHGE\:HLO 0F/DLQ7KHSURYLGHGLOOXVWUDWLRQVDUH WRGHPRQVWUDWH:HLO0F/DLQ¶VFRQWURO RSHUDWLQJFRQFHSWRQO\ %&3:8VHU2SHUDWLRQ0DQXDO S 86(50(186(48(1&( SYS=168 F OD=45 F TGT=172 F ABC <EFG > ---LO BOILER MENU ---- SEASON Winter Summer BACK --- ---- SAVE TARGET OFFSET +0 F -- ] SAVE SELECT $/(57 DO NOT turn power off to the BCP-8W when in off-season If you do so, the battery will run down and will have to be replaced. Instead, switch Season to Summer. SETBACK ------20 F [ BACK -- ------ SETTINGS -----Season Winter Set Point 170 F EMS StPont 170 F Outdoor Reset 170 F Target Offset +0 F Outdoor Cutoff 70 F Setback 20 F BACK --- [ BACK ----- DAY ] SAVE SCHEDULE 07:**Am BACK ---SAVE [ BACK -- SET POINT 140 F EMS BACK SCHEDULE 07:**Pm -- SAVE ] SAVE SET POINT 170 F BACK -- SAVE ---- RESET RATIO --Custom 1(8.00 OD:1.00 SYS) 2(4.00 OD:1.00 SYS) 3(3.00 OD:1.00 SYS) 4(2.00 OD:1.00 SYS) 5(1.50 OD:1.00 SYS) 6(1.25 OD:1.00 SYS) 7(1.00 OD:1.00 SYS) 8(1.00 OD:1.25 SYS) 9(1.00 OD:1.50 SYS) 10(1.00 OD:2.00 SYS) 11(1.00 OD:3.00 SYS) 12(1.00 OD:4.00 SYS) BACK - NIGHT ----- SAVE - OUTDOOR CUTOFF 70 F [ ] BACK SAVE 2SHUDWLQJXVHUVKDYHDVLPSOL¿HGPHQXWKDWFDQEHDFFHVVHGE\FOLFNLQJWKH0HQXEXWWRQ,QVWDOOHUPHQXZLOOKDYHWKHVDPH settings in addition to Startup and more advanced operation settings. The installer menu can be access by holding down the Menu button for three seconds or more. 352*5$0 &+$1*( 6(77,1*6 To be able to change the BCP-8W settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. PROGRAM RUN 6($621 ---- SEASON --Button: MENU/Season Winter :LQWHU 6XPPHU 'HIDXOW :LQWHU Summer 7KH%&3:ZLOOWXUQDOOERLOHUUHOD\VRIIZKHQLWLVLQ6XPPHUVHWWLQJ7KH0HVVDJH BACK SAVE 'LVSOD\/LQHZLOOUHDGSummer to show status. :KHQLQ:LQWHUWKH%&3:ZLOODFWLYDWHWKH6\VUHOD\ZKHQHYHUWKH2XWGRRUWHPSHUDWXUHIDOOVWRRUEHORZWKH2XWGRRU&XWRII setting. In addition, it will begin heating whenever the System temperature falls below the Set Point. The Message Display /LQHZLOOQRWGLVSOD\DQ\VHDVRQLQIRUPDWLRQ 35 %&3:8VHU2SHUDWLRQ0DQXDO 6(732,17127$'-867$%/(,1(0602'( ----- SET POINT ----$GMXVWDEOHº)º&º)ºC 'HIDXOWº)º& 140 F Button: MENU/Set Point ,Q6HW3RLQWRU(06P$ [ ] 7KH6HWSRLQWLVWKHWHPSHUDWXUHYDOXHWKH%&3:ZLOOXVHWRFRQWUROWKHV\VWHP BACK SAVE 7KH%&3:ZLOODGGVXEWUDFWRUKROGWKHVWDJHVRIWKHERLOHUVWRPDLQWDLQWKHV\VWHP temperature around the Set point. 7KHV\VWHPWHPSHUDWXUHFDQEHH[SHFWHGWRÀXFWXDWHDURXQGWKHVHWSRLQW7KHDPRXQWRIÀXFWXDWLRQGHSHQGVRQWKH6\VWHP Settings and Stage Settings. ,IWKH(060RGHZDV(QDEOHGWKH6HW3RLQWZLOOEHVHWE\WKH(06%06V\VWHPDQGZLOOEHDYDLODEOHWREHRQO\UHDG 7KHUDQJHRI6HW3RLQWLQWKH(06LVVHWLQWKH6WDUWXSPHQXDWP$DQGP$ $Q\UHDGLQJEHORZWKHP$RUDERYHP$ZLOOLQGLFDWHDShutdown by EMSPHVVDJHRQWKH0HVVDJH/LQH &XVWRP2'6\VWR2'6\V'HIDXOW2'6\V Button: MENU/Outdoor Reset/Reset Ratio ,Q2XWGRRU5HVHW2QO\ 7KH5HVHW5DWLRGHWHUPLQHVKRZWKH6\VWHPZDWHUWHPSHUDWXUHZLOOYDU\ZLWKWKH outside temperature. With any of the ratios, the colder it becomes outside, the hotter the temperature of the system water. (See Understanding Operation Concept on page 5) :LWKD2'6<6UDWLRWKH6\VWHPZDWHUWHPSHUDWXUH6<6ZLOOLQFUHDVH UDSLGO\DVWKHRXWVLGHWHPSHUDWXUHIDOOVKLWWLQJWKH0D[LPXPRI)DW)RXWVLGH WHPSHUDWXUH:LWKD2'6<6UDWLRWKH6\VWHPZDWHUWHPSHUDWXUH6<6 ZLOOLQFUHDVHVORZO\DVWKHRXWVLGHWHPSHUDWXUHIDOOV(YHQDW)WKHV\VWHPZDWHU will only be 125°F, and at 22°F outside, the system water will be 112°F. Such a low 5HVHW5DWLRPLJKWEHXVHGZLWKUDGLDQWÀRRUKHDWLQJDSSOLFDWLRQV :LWKPRVWEDVHERDUGKHDWLQJDSSOLFDWLRQVD2'6<6VHWWLQJLVDJRRG SODFHWRVWDUW:LWKD2'6<6UDWLRIRUHYHU\GHJUHHWKHRXWVLGH temperature falls, the system water temperature is increased one degree. ,IUHTXLUHG$GMXVWWKH5(6(75$7,2LQFROGZHDWKHU If the ambient building temperatures are too cold in cold weather, move the ratio to a higher selection. That is, LI2'6<6ZDVLQLWLDOO\VHOHFWHGFKDQJHWKHVHOHFWLRQWR2' 6<6,IWKHEXLOGLQJWHPSHUDWXUHVDUHWRRZDUPLQFROGZHDWKHUPRYHWKHUDWLRWR DORZHUVHOHFWLRQ7KDWLVLI2'6<6ZDVLQLWLDOO\VHOHFWHGFKDQJHWKH VHOHFWLRQWR2'6<6 ---- RESET RATIO --Custom 1(8.00 OD:1.00 SYS) 2(4.00 OD:1.00 SYS) 3(3.00 OD:1.00 SYS) 4(2.00 OD:1.00 SYS) 5(1.50 OD:1.00 SYS) 6(1.25 OD:1.00 SYS) 7(1.00 OD:1.00 SYS) 8(1.00 OD:1.25 SYS) 9(1.00 OD:1.50 SYS) 10(1.00 OD:2.00 SYS) 11(1.00 OD:3.00 SYS) 12(1.00 OD:4.00 SYS) BACK SAVE Water Temperature 5(6(75$7,2 130 1:4 1:1 Warmer 120 Colder 110 100 4:1 70 60 50 40 Outdoor Temperature &86720,=('5(6(75$7,2 Button: MENU/Outdoor Reset/Reset Ratio/Custom )RUVLWXDWLRQVZKHUHWKHDYDLODEOHUHVHWUDWLRVGRQRWSURYLGHWKHSHUIHFWEXLOGLQJKHDWORVVHTXLOLEULXPWKHFXVWRPL]HGRSWLRQ can be used by selecting Custom from the Reset Ratio menu option. ,WSURYLGHVWKHXVHUZLWKWKHFDSDELOLW\RIDVVLJQLQJWZRSRLQWVRQWKHUHVHWUDWLRGLDJUDPDQGXVHWKHOLQHWKDWFRQQHFWVWKRVH WZRSRLQWVDVWKHFXVWRPL]HGUHVHWUDWLRFXUYH(DFKRIWKHWZRSRLQWVZLOOQHHGDVSHFL¿F6\VWHPDQG2XWGRRU7HPSHUDWXUHWR identify it on the diagram. 7R6HWWKH¿UVWSRLQWVSHFLI\6\V7HPSDQG2'7HPS7KHQVSHFLI\6\V7HPSDQG2'7HPSWRVHWWKHVHFRQGSRLQW on the curve. The two points can be anywhere on the line, not necessarily at the ends. 7KHFKDUWVKRZVDQH[DPSOHRIDFXVWRPL]HGFXUYH2'6<6WKDWGRHVQRWH[LVWLQWKHVWDQGDUGFXUYHRSWLRQV,IWKH RXWGRRUWHPSHUDWXUHUHDFKHV)WKHV\VWHPWDUJHWZLOOEH) 5HPHPEHUWKDWWKH2IIVHW0LQ7DUJHWDQG0D[7DUJHWDSSO\WRDOOUHVHWUDWLRVLQFOXGLQJWKHFXVWRPL]HGUHVHWUDWLRRQHV 36 %&3:8VHU2SHUDWLRQ0DQXDO -- AT [ ]BACK OD TEMP.1 60 F --- SAVE -- SET SYS TEMP.2 170 F [ ]BACK SAVE -- AT [ BACK OD TEMP.2 0 F --- ] SAVE Point1: System=120°F Oudoor=60°F 180 Water Temperature (in °F) -- SET SYS TEMP.1 120 F [ ]BACK SAVE Point2: System=170°F Oudoor=0°F Max Target io at 170 Point2 tR se 160 ed Re iz om st 150 Cu 140 130 Point1 120 Min Target 110 100 70 60 50 40 30 20 10 0 -10 -20 Outdoor Temperature (in °F) Custom Reset Ratio 287'225&872))7(03(5$785( - OUTDOOR CUTOFF $GMXVWDEOH2IIº)º&º)º&2Q 'HIDXOW)& 70 F Button: MENU/Outdoor Cutoff LQ6HW3RLQW [ ] ,Q2XWGRRU5HVHWPRGH2XWGRRU&XWRIIZLOODOZD\VH[LVW+RZHYHULQ6HW3RLQWPRGH BACK SAVE if the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear after the temperature Set Point has been selected. :KHQWKHRXWGRRUWHPSHUDWXUHULVHVWRWKH2XWGRRU&XWRIISOXVD)GLIIHUHQWLDOWKH%&3:ZLOOWXUQDOOERLOHUVRII7KH 6\VWHPDQG&RPE$LUUHOD\VWKDWZHUHHQHUJL]HGZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2QGHOD\ 7KH2XWGRRU&XWRIIFDQEHVHWWR21RU2)),QWKH21SRVLWLRQWKH6\VWHP5HOD\ZLOOUXQUHJDUGOHVVRIWKH2XWGRRU temperature and the burner stages will be active to hold the set point. ,QWKH2))SRVLWLRQWKH6\VWHP5HOD\ZLOODOZD\VEHRIIDQGDOOVWDJHVZLOOEHRIIDVZHOO 6(7%$&. ---- SETBACK ------$GMXVWDEOH°)°&WR)& 'HIDXOW°)°& 0 F Button: MENU/Setback [ ] 7KH6HWEDFNIHDWXUHFDQEHXVHGWRSURYLGHWKH%&3:ZLWKDORZHU6HW3RLQWZKHQ BACK SAVE less load is required. :KHQWKHRXWGRRUWHPSHUDWXUHIDOOVWRWKHDGMXVWDEOH2XWGRRU&XWRIIWHPSHUDWXUHWKH%&3:ZLOOFRQWURODQGVHTXHQFHWKH boiler stages to hold the calculated temperature. :KHQWKHRXWGRRUWHPSHUDWXUHULVHVWRWKH2XWGRRU&XWRIISOXVD)GLIIHUHQWLDOWKH%&3:ZLOOWXUQDOOERLOHUVRII7KH 6\VWHP&RPEXVWLRQ$LU'DPSHUDQGDQ\RWKHU3XPSRUYDOYHUHOD\VWKDWZHUHHQHUJL]HGZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2Q GHOD\DQGWKHQGHHQHUJL]H ,QDGGLWLRQWKH2XWGRRU&XWRIIFDQEHVHWWR21RU2)),QWKH21RSWLRQWKH6\VWHP5HOD\ZLOOUXQUHJDUGOHVVRIWKH2XWGRRU temperature and the burner stages will be active to hold the target water temperature. ,QWKH2))SRVLWLRQWKHV\VWHPSXPSZLOODOZD\VEHRIIDQGDOOVWDJHVZLOOEHRIIDVZHOO '$<1,*+76&+('8/(6 -- DAY SCHEDULE ---Button: MENU/Setback/Day Schedules/Night Schedule 07:**Am 7KH%&3:KDVWZROHYHOVRIKHDW7KH'D\OHYHOLVXVHGZKHQDEXLOGLQJLVRFFXSLHG BACK SAVE and people are active. -- NIGHT SCHEDULE 7KH1LJKW6HWEDFNOHYHOLVXVHGZKHQDEXLOGLQJLVQRWRFFXSLHGRUZKHQSHRSOHDUH 10:**Pm sleeping. This setting reduces the calculated temperature by the Setback setting based RQWKHSURYLGHGVFKHGXOH,IWKH'D\FDOFXODWHGZDWHUWHPSHUDWXUHZDVÛ)DQGWKH BACK SAVE 6HWEDFNZDVÛ)WKH1LJKW6FKHGXOHZLOOUXQDWÛ)Û) Û) ,IWKH%RRVWIHDWXUHLVEHLQJXVHGLWXVHVWKH'D\6FKHGXOHDVD%RRVWHQGLQJSRLQW7KDWLVLIWKH'D\6FKHGXOHLVVHWWRVWDUW DW$0WKH%RRVWZDVVHWWR)DQGWKH%RRVW3HULRGZDVPLQXWHVWKH%RRVWZLOOVWDUWDW$07KHQZKHQLQ %RRVW%&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWHPSHUDWXUHE\WKH%RRVWDPRXQW8VLQJWKHSUHYLRXVH[DPSOHDW$0WKH %&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWRÛ)Û)Û)XQWLO$0ZKHUHLWZLOOGURSEDFNWRWKHQRUPDOFDOFXODWHG WHPSHUDWXUHRIÛ) 37 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 38 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 39 %&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO 9ROWDJH,QSXW . . . . . . 3RZHU&RQVXPSWLRQ . . 2SHUDWLQJ7HPSHUDWXUH 2SHUDWLQJ+XPLGLW\ . . 'LPHQVLRQV . . . . . . . . :HLJKW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63(&,),&$7,216 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9$&+] . . . . . . . . 9$0D[ 20qF/-7qC to 120qF/49qC . . . . . . . 20% to 80% . . . :[+[ô . . . . . . . . 2.5 pounds %&3:63(&,),&$7,216 /HDG6WDJH5RWDWLRQ . . . . . . . . . . . . . . . . . . . . . . . Time ( 1 to 999 Hours (41 days)), Manual, First-On/First-Off %&3:2XWSXWVDQG/('V . . . . . . . . . . 11 N.O. S.P.S.T (8 Stages, 1 System, 1 DHW Pump, 1 Combustion Air) %&3:,QSXWV . . . . . . . . . . . . 1 Sys(Temp), 1 Outdoor, Return Temp, DHW Temp, Ext Setback/Shutdown, Prove 6WDJH0RGHV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auto, Standby, Off, On 6WDQGE\7LPH3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WRPLQXWHV 2XWSXW%XLOWLQ5HOD\5DWLQJV . . . . . . . . . . . . . . . . . 2 Amp inductive (Maximum of 1/4 HP) DW9$&+] $GG2Q%&3;3DQHOV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up two BCP-8X Panels using RS485 7HPSHUDWXUH'LVSOD\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fahrenheit or Celsius. 'LVSOD\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Graphical Alphanumeric (7 rows x 21 char. each) 7HPSHUDWXUH6HQVRU5DQJHV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . qF to 250qF 2XWGRRU&XWRII5DQJH . . . . . . . . . . . . . . . . . . . . . . . . . . . )&WR)&21DQG2)) 6HW3RLQW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . )&WR)& ([WHUQDO6HW3RLQW . . . . . . . . . . . . . . . . . . )&WR)& using 420MOD Interface (optional) 5HVHW5DWLR5DQJH2XWGRRU5HVHW2QO\ . . . . . . (WR2XWGRRU6\VWHP:DWHUDQG&XVWRP5HVHW5DWLR 2IIVHW$GMXVWPHQW2XWGRRU5HVHW2QO\ . . . . . . . . . . . . . . . . . . . . . .minus -40°F/-22°C to plus 40°F/22°C 0LQLPXP7DUJHW2XWGRRU5HVHW2QO\ . . . . . . . . . . . . . . . . . . . . . . . . 70qF/21qC to 170qF/77qC 0D[LPXP7DUJHW2XWGRRU5HVHW2QO\ . . . . . . . . . . . . . . . . . . . . . . . 90q)qC to 240q)& 5HDFWLRQ7LPH3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 10 minutes 0LQLPXP5XQ7LPH3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WRPLQXWHV 3XUJH'HOD\3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.0 to 10.0 minutes /DVW6WDJH+ROG3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . )&WR)& 7KURWWOH5DQJH266RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2°F/1°C to 20°F/11°C 'RPHVWLF+RW:DWHU3ULRULW\2SWLRQV . . . . . . Parallel Piping with Priority or without Priority and Primary Secondary 3XPS5XQ2Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WRPLQXWHV 3XPS([HUFLVH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <HVRU1R 6FKHGXOHV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Day and 1 Night (Setback) settings per day 1LJKW6HWEDFN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°F/0°C to 80°F/44°C 3RZHU%DFNXS . . . . . . . ./LWKLXPFRLQEDWWHU\GD\VPLQLPXP\HDUUHSODFHPHQW0DLQWDLQV&ORFNLQSRZHURXWDJHV ([WHUQDO,QSXWV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shutdown Input, and Prove Input. (Dry Contacts Only) 6HDVRQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Winter and Summer. %&3;63(&,),&$7,216 HT #059072-00 A ([WHQVLRQ1XPEHULQJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Toggle Switch A or B /(' . . . 1 Power (Dual Color Green (A)/Red (B)), 1 Communication, 8 Stage Output relays (Dual Color Green (A)/Red (B)) 6WDJH2XWSXWV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 N.O. S.P.S.T. 2XWSXW%XLOWLQ5HOD\5DWLQJV . . . . . . . . . . . . . . . . . 2 Amp inductive (Maximum of 1/4 HP) DW9$&+] &RQQHFWLRQWR%&3:DQGDQRWKHU%&3; . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two RS485 500 Blaine Street Michigan City, Indiana 46360 219-879-6561 http://www.weil-mclain.com 40 Part Number 550-100-071/0408