SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SPLIT-TYPE, AIR CONDITIONERS
March 2009
No. OCS14
TECHNICAL DATA BOOK R410A INVERTER
<Indoor unit>
[Model names]
PLA-A·BA
PKA-A·HA
PKA-A·HAL
PKA-A·KA
PKA-A·KAL
PCA-A·KA
PEA-A·AA
<Outdoor unit>
PUZ-A18/24/30/36/42NHA3
PUZ-A18/24/30/36/42NHA3-BS
PUY-A12/18/24/30/36/42NHA3
PUY-A12/18/24/30/36/42NHA3-BS
[Model names]
CONTENTS
1. REFERENCE SERVICE MANUAL ............................................. 2
2. SPECIFICATIONS....................................................................... 3
3. OUTLINES AND DIMENSIONS ................................................ 10
4. WIRING DIAGRAM ................................................................... 21
5. REFRIGERANT SYSTEM DIAGRAM ...................................... 30
6. PERFORMANCE CURVES ...................................................... 33
7. CORRECTION FACTORS ........................................................ 35
8. AIR FLOW DATA ...................................................................... 36
9. NOISE CRITERION CURVES .................................................. 45
10. OPTIONAL PARTS .................................................... Back cover
1
REFERENCE SERVICE MANUAL
For information on service, please refer to the service manual as follows.
1-1. INDOOR UNIT
Service
Manual No.
Model name
Service Ref.
PLA-A12/18/24/30/36/42BA
PLA-A12/18/24/30/36/42BA1
OCH420
OCB420
PKA-A12/18HA
PKA-A12/18HAL
PKA-A12/18HA
PKA-A12/18HAL
OCH456
OCB456
PKA-A24/30/36KA
PKA-A24/30/36KAL
PKA-A24/30/36KA.TH
PKA-A24/30/36KAL.TH
OCH457
OCB457
PCA-A24/30/36/42KA
PCA-A24/30/36/42KA
OCH455
OCB455
PEA-A12/18AA
PEA-A12/18AA.TH
HWE08070
BWE0811A
1-2. OUTDOOR UNIT
Service
Manual No.
Model name
Service Ref.
PUZ-A18/24/30/36/42NHA3
PUZ-A18/24/30/36/42NHA3-BS
PUY-A12/18/24/30/36/42NHA3
PUY-A12/18/24/30/36/42NHA3-BS
PUZ-A18/24/30/36/42NHA3
PUZ-A18/24/30/36/42NHA3-BS
PUY-A12/18/24/30/36/42NHA3
PUY-A12/18/24/30/36/42NHA3-BS
2
OCH458
OCB458
2
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
Model name
Cooling
Heating
Heating
at low ambient
Power supply
Voltage
Indoor unit
Remote Controller
Outdoor unit
Indoor unit
Outdoor unit
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
EER
Btu/h/W
SEER
Btu/h/W
Moisture Removal
Pints/h
*1 SHF
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
COP
W/W
*1 HSPF (/)
Btu/h/W
Rated Capacity
Btu/h
Total Input
W
*2 COP
W/W
Phase, Cycle, Voltage
Breaker size
A
Indoor - Outdoor S1-S2
Indoor - Outdoor S2-S3
Indoor - Remote Controller
MCA
A
MOCP
A
Fan Motor
F.L.A.
Fan Motor Output
W
CMM
Air flow
DRY
(Lo-M2-M1-Hi) WET
CMM
Air flow
DRY
CFM
(Lo-M2-M1-Hi) WET
CFM
External pressure
Pa
Sound level
dB(A)
(Lo-M2-M1-Hi)
External finish (Panel)
Dimension
W : mm [inch]
Unit (Panel)
D : mm [inch]
H : mm [inch]
Weight
kg
Unit (Panel)
lbs
mm [inch]
Field drain pipe size O.D.
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Type
Charge
Oil
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length Height difference
Length
Refrigerant Piping
Connection Method
A
A
F.L.A.
W
R.L.A
L.R.A.
CMM [CFM]
dB(A)
dB(A)
W : mm [inch]
D : mm [inch]
H : mm [inch]
kg [lbs]
Refrigerant
kg [lbs, oz]
L [oz]
mm [inch]
mm [inch]
PLA-A12BA
PLA-A18BA
PLA-A24BA
PLA-A30BA
PLA-A36BA
PLA-A42BA
PUY-A12NHA3
PUY-A18NHA3
PUY-A24NHA3
PUY-A30NHA3
PUY-A36NHA3
PUY-A42NHA3
PUY-A12NHA3-BS PUY-A18NHA3-BS PUY-A24NHA3-BS PUY-A30NHA3-BS PUY-A36NHA3-BS PUY-A42NHA3-BS
12,000
18,000
24,000
30,000
35,000
42,000
12,000
18,000
24,000
30,000
35,000
42,000
6,000
8,000
12,000
12,000
12,000
18,000
1260
1940
2500
4100
4500
4600
9.5
9.3
9.6
7.3
7.8
9.1
13.5
14.2
13.6
13.6
14.2
14.4
1.7
3.0
5.1
7.2
8.1
10.9
0.84
0.81
0.76
0.73
0.74
0.71
1phase, 60Hz, 208/230V
15
25
30
AC 208 / 230V
DC24V
DC12V
1
2
15
0.51
1.00
50
120
11-12-13-15
12-14-16-18
14-16-18-21
20-23-26-30
22-25-28-31
10-11-12-14
11-13-15-17
13-15-17-20
19-22-25-29
21-24-27-30
390-420-460-530
420-490-570-640
490-570-640-740 710-810-920-1060 780-880-990-1090
350-390-420-490
390-460-530-600
460-530-600-710 670-770-880-1030 740-850-950-1060
0
27-28-29-31
28-29-31-32
28-30-32-34
32-34-37-40
34-36-39-41
White Munsell 6.4Y 8.9 / 0.4
840 (950) [ 33-1/16 (37-3/8) ]
840 (950) [ 33-1/16 (37-3/8) ]
258 (35) [ 10-3/16 (1-3/8) ]
298 (35) [ 11-3/4 (1-3/8) ]
22 (6)
23 (6)
25 (6)
49 (13)
51 (13)
55 (13)
32 [ 1-1/4 ]
Attached in Grille
13
18
25
26
15
20
30
40
0.35
0.75
0.4 + 0.4
40
75
86 + 86
SNB130FPBM1
TNB220FLHM
ANV33FDPMT
12
20
14
17.5
27.5
100 [3,530]
34 [1,200]
55 [1,940]
Linear Expansion Valve
46
48
51
Ivory Munsell 3Y 7.8/1.1
800 [31-1/2]
950 [37-3/8]
330+23 [13 + 7/8]
330+30 [13 + 1-3/16]
600 [23-5/8]
943 [37-1/8]
1350 [53-1/8]
117 [258]
41 [90]
44 [97]
74 [163]
R410A
4.5 [10 lbs]
1.3 [2 lbs 14 oz] 1.7 [3 lbs 12 oz]
3.0 [6 lbs 10 oz]
1.4 (FV50S) [45]
0.65 (MEL56) [20]
0.87 (FV50S) [28]
12.7 [1/2]
15.88 [5/8]
6.35 [1/4]
9.52 [3/8]
Max. 30m [Max.100ft]
Max. 30m [Max.100ft]
Max. 50 [Max.165ft]
Not Supplied
Flared
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
Operating range
Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Outdoor intake air temperature
Indoor intake air temperature
Maximum
D.B. 46(115°F)
D.B. 35(95°F), W.B. 21.7(71°F)
Minimum
D.B. -18(0°F)*
D.B. 19.4(67°F), W.B. 13.9(57°F)
Maximum
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. 26.7(80°F), W.B. 19.4(67°F)
Heating
Minimum
D.B. -11.1(12°F), W.B. -12.2(10°F)
D.B. 21.1(70°F), W.B. 15.6(60°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
Cooling
3
Model name
Cooling
Heating
Heating
at low ambient
Power supply
Voltage
Indoor unit
Remote Controller
Outdoor unit
Indoor unit
Outdoor unit
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
EER
Btu/h/W
SEER
Btu/h/W
Moisture Removal
Pints/h
*1 SHF
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
COP
W/W
*1 HSPF (/)
Btu/h/W
Rated Capacity
Btu/h
Total Input
W
*2 COP
W/W
Phase, Cycle, Voltage
Breaker size
A
Indoor - Outdoor S1-S2
Indoor - Outdoor S2-S3
Indoor - Remote Controller
MCA
A
MOCP
A
Fan Motor
F.L.A.
Fan Motor Output
W
Air flow
DRY
CMM
(Lo-M2-M1-Hi) WET
CMM
Air flow
DRY
CFM
(Lo-M2-M1-Hi) WET
CFM
External pressure
Pa
Sound level
dB(A)
(Lo-M2-M1-Hi)
External finish (Panel)
Dimension
W : mm [inch]
Unit (Panel)
D : mm [inch]
H : mm [inch]
Weight
kg
Unit (Panel)
lbs
mm [inch]
Field drain pipe size O.D.
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
A
A
F.L.A.
W
R.L.A
L.R.A.
CMM [CFM]
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
dB(A)
Sound level at heating
dB(A)
External finish
W : mm [inch]
Dimension
D : mm [inch]
H : mm [inch]
kg [lbs]
Weight
Refrigerant
Type
kg [lbs, oz]
Charge
L [oz]
Oil
Refrigerant pipe size Gas side O.D.
mm [inch]
Liquid side O.D.
mm [inch]
Refrigerant pipe length Height difference
Length
Refrigerant Piping
Connection Method
PLA-A18BA
PLA-A24BA
PLA-A30BA
PLA-A36BA
PLA-A42BA
PUZ-A18NHA3
PUZ-A24NHA3
PUZ-A30NHA3
PUZ-A36NHA3
PUZ-A42NHA3
PUZ-A18NHA3-BS PUZ-A24NHA3-BS PUZ-A30NHA3-BS PUZ-A36NHA3-BS PUZ-A42NHA3-BS
18,000
24,000
30,000
35,000
42,000
18,000
24,000
30,000
35,000
42,000
8,000
12,000
12,000
12,000
18,000
1940
2500
4100
4500
4600
9.3
9.6
7.3
7.8
9.1
14.2
13.6
13.6
14.2
14.4
3.0
5.1
7.2
8.1
10.9
0.81
0.76
0.73
0.74
0.71
20,000
28,000
34,000
38,000
48,000
19,000
26,000
32,000
37,000
45,000
8,000
12,000
12,000
12,000
18,000
1900
2570
3370
3300
4450
2.93
2.96
2.78
3.28
2.96
9.8 / 7.5
8.5 / 6.8
8.7 / 6.9
9.3 / 7.3
9.3 / 7.2
13,000
16,000
23,000
25,000
30,000
1590
2200
3050
3070
4300
2.40
2.14
2.20
2.37
2.05
1phase, 60Hz, 208/230V
15
25
30
AC 208 / 230V
DC24V
DC12V
1
2
15
0.51
1.00
50
120
12-14-16-18
14-16-18-21
20-23-26-30
22-25-28-31
11-13-15-17
13-15-17-20
19-22-25-29
21-24-27-30
420-490-570-640
490-570-640-740 710-810-920-1060 780-880-990-1090
390-460-530-600
460-530-600-710 670-770-880-1030 740-850-950-1060
0
28-29-31-32
28-30-32-34
32-34-37-40
34-36-39-41
White Munsell 6.4Y 8.9 / 0.4
840 (950) [ 33-1/16 (37-3/8) ]
840 (950) [ 33-1/16 (37-3/8) ]
258 (35) [ 10-3/16 (1-3/8) ]
298 (35) [ 11-3/4 (1-3/8) ]
22 (6)
23 (6)
25 (6)
49 (13)
51 (13)
55 (13)
32 [ 1-1/4 ]
Attached in Grille
13
18
25
26
15
30
40
0.35
0.75
0.4 + 0.4
40
75
86 + 86
SNB130FPBM1
TNB220FLHM
ANV33FDPMT
12
20
14
17.5
27.5
34 [1,200]
55 [1,940]
100 [3,530]
Linear Expansion Valve
Reverse Cycle
46
48
51
47
50
55
Ivory Munsell 3Y 7.8/1.1
800 [31-1/2]
950 [37-3/8]
330+23 [13 + 7/8]
330+30 [13 + 1-3/16]
600 [23-5/8]
943 [37-1/8]
1350 [53-1/8]
45 [99]
75 [165]
118 [260]
R410A
1.7 [3 lbs 12 oz]
3.0 [6 lbs 10 oz]
4.5 [10 lbs]
0.65 (MEL56) [20]
0.87 (FV50S) [28]
1.4 (FV50S) [45]
12.7 [1/2]
15.88 [5/8]
6.35 [1/4]
9.52 [3/8]
Max. 30m [Max.100ft]
Max. 30m [Max.100ft]
Max. 50 [Max.165ft]
Not Supplied
Flared
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
Operating range
Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Indoor intake air temperature
Outdoor intake air temperature
Maximum
D.B. 35(95°F), W.B. 21.7(71°F)
D.B. 46(115°F)
Minimum
D.B. 19.4(67°F), W.B. 13.9(57°F)
D.B. -18(0°F)*
Maximum
D.B. 26.7(80°F), W.B. 19.4(67°F)
D.B. 21.1(70°F), W.B. 15(59°F)
Heating
Minimum
D.B. 21.1(70°F), W.B. 15.6(60°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
Cooling
4
2-2. WALL-MOUNTED TYPE
Indoor unit
Model name
Cooling
Heating
Heating
at low ambient
Power supply
Voltage
Indoor unit
Outdoor unit
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
Sound level at heating
External finish
Dimension
Refrigerant
Refrigerant pipe size
Refrigerant pipe length
Weight
Type
Charge
Oil
Gas side O.D.
Liquid side O.D.
Height difference
Length
PKA-A18HA
PKA-A18HAL
PKA-A24KA
PKA-A24KAL
PKA-A30KA
PKA-A30KAL
PKA-A36KA
PKA-A36KAL
PUY-A12NHA3
PUY-A18NHA3
PUY-A24NHA3
PUY-A30NHA3
PUY-A36NHA3
PUY-A12NHA3-BS PUY-A18NHA3-BS PUY-A24NHA3-BS PUY-A30NHA3-BS PUY-A36NHA3-BS
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
EER
Btu/h/W
SEER
Btu/h/W
Moisture Removal
Pints/h
*1 SHF
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
COP
W/W
*1 HSPF (/)
Btu/h/W
Rated Capacity
Btu/h
Total Input
W
*2 COP
W/W
Phase, Cycle, Voltage
Breaker size
A
Indoor - Outdoor S1-S2
Indoor - Outdoor S2-S3
Indoor - Remote Controller
MCA
A
MOCP
A
Fan Motor
F.L.A.
Fan Motor Output
W
Air flow
DRY
CMM
(Lo-Mid-Hi) WET
CMM
Air flow
DRY
CFM
(Lo-Mid-Hi) WET
CFM
External pressure
Pa
Sound level
dB(A)
(Lo-Mid-Hi)
External finish (Panel)
Dimension
W : mm [inch]
Unit (Panel)
D : mm [inch]
H : mm [inch]
Weight
kg
Unit (Panel)
lbs
Field drain pipe size I.D.
mm [inch]
Remote Controller
Outdoor unit
Refrigerant Piping
Connection Method
PKA-A12HA
PKA-A12HAL
A
A
F.L.A.
W
R.L.A
L.R.A.
CMM [CFM]
dB(A)
dB(A)
W : mm [inch]
D : mm [inch]
H : mm [inch]
kg [lbs]
kg [lbs, oz]
L [oz]
mm [inch]
mm [inch]
12,000
12,000
6,000
1190
10.1
15.2
2.0
0.81
-
18,000
18,000
8,000
2240
8.0
15.3
5.2
0.68
15
0.33
30
9-10.5-12
8-9.5-11
320-370-425
290-335-380
24,000
24,000
12,000
2270
10.6
17.0
5.0
0.77
1phase , 60Hz , 208/230V
25
AC 208 / 230V
DC24V
DC12V : Wired type
1
15
0.36
30,000
30,000
12,000
4130
7.3
15.5
8.1
0.70
-
34,200
34,200
12,000
5030
6.8
14.0
9.2
0.70
30
0.57
56
18-20-22
16-18-20
635-705-775
570-635-700
20-23-26
18-21-23
705-810-920
635-730-830
39-42-45
43-46-49
0
36-40-43
White Munsell 1.0Y 9.2/0.2
1170 [46-1/16]
295 [11-5/8]
365 [14-3/8]
21
46
16 [5/8]
Attached in Indoor Unit
13
18
25
15
20
30
40
0.35
0.75
40
75
SNB130FPBM1
TNB220FLHM
12
14
17.5
34 [1,200]
55 [1,940]
Linear Expansion Valve
46
48
Ivory Munsell 3Y 7.8/1.1
800 [31-1/2]
950 [37-3/8]
330+23 [13 + 7/8]
330+30 [13 + 1-3/16]
600 [23-5/8]
943 [37-1/8]
41 [90]
44 [97]
74[163]
R410A
1.3 [2 lbs 14 oz] 1.7 [3 lbs 12 oz]
3.0 [6 lbs 10 oz]
0.65 (MEL56) [20]
0.87 (FV50S) [28]
12.7 [1/2]
15.88 [5/8]
6.35 [1/4]
9.52 [3/8]
Max. 30m [Max. 100ft]
Max. 30m [Max. 100ft]
Max. 50m [Max. 165ft]
Not Supplied
Flared
898 [35-3/8]
249 [9-13/16]
295 [11-5/8]
13
29
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
Operating range
Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Indoor intake air temperature
Outdoor intake air temperature
D.B. 35(95°F), W.B. 21.7(71°F)
D.B. 46(115°F)
Maximum
Cooling
D.B. 19.4(67°F), W.B. 13.9(57°F)
D.B. -18(0°F)*
Minimum
D.B. 26.7(80°F), W.B. 19.4(67°F)
D.B. 21.1(70°F), W.B. 15(59°F)
Maximum
Heating
D.B. 21.1(70°F), W.B. 15.6(60°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
Minimum
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
5
Indoor unit
Model name
Cooling
Heating
Heating
at low ambient
Power supply
Voltage
Indoor unit
Remote Controller
Outdoor unit
Outdoor unit
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
EER
Btu/h/W
SEER
Btu/h/W
Moisture Removal
Pints/h
*1 SHF
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
COP
W/W
*1 HSPF (/)
Btu/h/W
Rated Capacity
Btu/h
Total Input
W
*2 COP
W/W
Phase, Cycle, Voltage
Breaker size
A
Indoor - Outdoor S1-S2
Indoor - Outdoor S2-S3
Indoor - Remote Controller
MCA
A
MOCP
A
Fan Motor
F.L.A.
Fan Motor Output
W
Air flow
DRY
CMM
(Lo-Mid-Hi) WET
CMM
Air flow
DRY
CFM
(Lo-Mid-Hi) WET
CFM
External pressure
Pa
Sound level
dB(A)
(Lo-Mid-Hi)
External finish (Panel)
Dimension
W : mm [inch]
Unit (Panel)
D : mm [inch]
H : mm [inch]
Weight
kg
Unit (Panel)
lbs
Field drain pipe size I.D.
mm [inch]
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
Sound level at heating
External finish
Dimension
Refrigerant
Refrigerant pipe size
Refrigerant pipe length
Refrigerant Piping
Connection Method
Weight
Type
Charge
Oil
Gas side O.D.
Liquid side O.D.
Height difference
Length
A
A
F.L.A.
W
PKA-A18HA
PKA-A18HAL
PUZ-A18NHA3
PUZ-A18NHA3-BS
18,000
18,000
8,000
2240
8.0
15.3
5.2
0.68
20,000
19,000
8,000
1970
2.83
9.5 / 7.6
13,000
1670
2.28
PKA-A24KA
PKA-A30KA
PKA-A36KA
PKA-A24KAL
PKA-A30KAL
PKA-A36KAL
PUZ-A24NHA3
PUZ-A30NHA3
PUZ-A36NHA3
PUZ-A24NHA3-BS
PUZ-A30NHA3-BS
PUZ-A36NHA3-BS
24,000
30,000
34,200
24,000
30,000
34,200
12,000
12,000
12,000
2270
4130
5030
10.6
7.3
6.8
15.5
14.0
17.0
8.1
9.2
5.0
0.77
0.70
0.70
28,000
34,000
38,000
26,000
32,000
37,000
12,000
12,000
12,000
2330
3150
3610
3.27
2.98
3.00
10.8 / 8.6
8.9 / 7.1
9.3 / 7.5
18,000
23,000
25,000
2850
2200
3030
2.37
2.40
2.42
1phase , 60Hz , 208/230V
25
30
AC 208 / 230V
DC24V
DC12V : Wired type
1
15
0.36
0.57
56
18-20-22
20-23-26
16-18-20
18-21-23
635-705-775
705-810-920
635-730-830
570-635-700
0
15
0.33
30
9-10.5-12
8-9.5-11
320-370-425
290-335-380
36-40-43
39-42-45
43-46-49
White Munsell 1.0Y 9.2/0.2
1170 [46-1/16]
295 [11-5/8]
365 [14-3/8]
898 [35-3/8]
249 [9-13/16]
295 [11-5/8]
13
29
21
46
16 [5/8]
Attached in Indoor Unit
18
30
0.75
75
TNB220FLHM
12
13
20
0.35
40
SNB130FPBM1
R.L.A
L.R.A.
CMM [CFM]
34 [1,200]
dB(A)
dB(A)
46
47
W : mm [inch]
D : mm [inch]
H : mm [inch]
kg [lbs]
800 [31-1/2]
330+23 [13 + 7/8]
600 [23-5/8]
45 [99]
kg [lbs, oz]
L [oz]
mm [inch]
mm [inch]
1.7 [3 lbs 12 oz]
0.65 (MEL56) [20]
12.7 [1/2]
6.35 [1/4]
14
Max. 30m [Max. 100ft]
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
Operating range
25
40
17.5
55 [1,940]
Linear Expansion Valve
Reverse Cycle
48
50
Ivory Munsell 3Y 7.8/1.1
950 [37-3/8]
330+30 [13 + 1-3/16]
943 [37-1/8]
75 [165]
R410A
3.0 [6 lbs 10 oz]
0.87 (FV50S) [28]
15.88 [5/8]
9.52 [3/8]
Max. 30m [Max. 100ft]
Max. 50m [Max. 165ft]
Not Supplied
Flared
Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Indoor intake air temperature
Outdoor intake air temperature
Maximum
D.B. 35(95°F), W.B. 21.7(71°F)
D.B. 46(115°F)
Cooling
Minimum
D.B. 19.4(67°F), W.B. 13.9(57°F)
D.B. -18(0°F)*
Maximum
D.B. 26.7(80°F), W.B. 19.4(67°F)
D.B. 21.1(70°F), W.B. 15(59°F)
Heating
Minimum
D.B. 21.1(70°F), W.B. 15.6(60°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
6
2-3. CEILING-SUSPENDED TYPE
Model name
Cooling
Heating
Heating
at low ambient
Power supply
Voltage
Indoor unit
Remote Controller
Outdoor unit
Indoor unit
Outdoor unit
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
EER
Btu/h/W
SEER
Btu/h/W
Moisture Removal
Pints/h
*1 SHF
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
COP
W/W
*1 HSPF (/)
Btu/h/W
Rated Capacity
Btu/h
Total Input
W
*2 COP
W/W
Phase, Cycle, Voltage
Breaker size
A
Indoor - Outdoor S1-S2
Indoor - Outdoor S2-S3
Indoor - Remote Controller
MCA
A
MOCP
A
Fan Motor
F.L.A.
Fan Motor Output
W
Air flow
DRY
CMM
(Lo-M2-M1-Hi) WET
CMM
Air flow
DRY
CFM
(Lo-M2-M1-Hi) WET
CFM
External pressure
Pa
Sound level
dB(A)
(Lo-M2-M1-Hi)
External finish (Panel)
Dimension
W : mm [inch]
Unit (Panel)
D : mm [inch]
H : mm [inch]
Weight
kg
Unit (Panel)
lbs
mm [inch]
Field drain pipe size O.D.
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
A
A
F.L.A.
W
R.L.A
L.R.A.
CMM [CFM]
Refrigerant
Refrigerant pipe size
Refrigerant pipe length
PCA-A24KA
PUY-A24NHA3
PUY-A24NHA3-BS
24,000
24,000
12,000
2340
10.3
16.8
5.8
0.73
-
PCA-A30KA
PCA-A36KA
PUY-A30NHA3
PUY-A36NHA3
PUY-A30NHA3-BS
PUY-A36NHA3-BS
30,000
35,000
30,000
35,000
12,000
12,000
3760
4630
8.0
7.6
14.5
14.4
8.3
8.5
0.69
0.73
1phase , 60Hz , 208/230V
30
AC 208 / 230V
DC24V
DC12V
25
1
PCA-A42KA
PUY-A42NHA3
PUY-A42NHA3-BS
42,000
42,000
18,000
4110
10.2
15.8
11.7
0.69
-
2
15
0.54
95
0.97
160
15-16-17-19
14-15-16-18
530-565-600-670
495-530-565-635
16-17-18-20
15-16-17-19
565-600-635-705
530-565-600-670
33-35-37-40
35-37-39-41
22-24-26-28
20-22-24-26
775-850-920-990
705-775-850-920
23-25-27-29
21-23-25-27
810-885-955-1025
740-810-885-955
37-39-41-43
39-41-43-45
0
White Munsell 6.4Y 8.9/0.4
1280 [50-3/8]
1600 [63]
680 [26-3/4]
230 [9-1/16]
32
71
18
30
14
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
dB(A)
Sound level at heating
dB(A)
External finish
Dimension
W : mm [inch]
D : mm [inch]
H : mm [inch]
Weight
kg [lbs]
Type
kg [lbs]
Charge
Oil
L [oz]
Gas side O.D.
mm [inch]
Liquid side O.D.
mm [inch]
Height difference
Length
Refrigerant Piping
Connection Method
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
Operating range
36
79
26 [1-1/32]
Attached in Indoor Unit
25
40
0.75
75
TNB220FLHM
12
17.5
55 [1,940]
Linear Expansion Valve
48
Ivory Munsell 3Y 7.8/1.1
950 [37-3/8]
330+30 [13 + 1-3/16]
943 [37-1/8]
74[163]
R410A
3.0 [6 lbs 10 oz]
0.87 (FV50S) [28]
15.88 [5/8]
9.52 [3/8]
Max. 30m [Max. 100ft]
Max. 50m [Max. 165ft]
Not Supplied
Flared
Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Outdoor intake air temperature
Indoor intake air temperature
Maximum
D.B. 46(115°F)
D.B. 35(95°F), W.B. 21.7(71°F)
Cooling
Minimum
D.B. -18(0°F)*
D.B. 19.4(67°F), W.B. 13.9(57°F)
Maximum
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. 26.7(80°F), W.B. 19.4(67°F)
Heating
Minimum
D.B. -11.1(12°F), W.B. -12.2(10°F)
D.B. 21.1(70°F), W.B. 15.6(60°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
7
38
84
26
0.4 + 0.4
86 + 86
ANV33FDPMT
20
27.5
100 [3,530]
51
-
1350 [53-1/8]
117 [258]
4.5 [10 lbs]
1.4 (FV50S) [45]
Model name
Cooling
Heating
Heating
at low ambient
Power supply
Voltage
Indoor unit
Remote Controller
Outdoor unit
Indoor unit
Outdoor unit
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
EER
Btu/h/W
SEER
Btu/h/W
Moisture Removal
Pints/h
*1 SHF
Max. Capacity
Btu/h
Rated Capacity
Btu/h
Min. Capacity
Btu/h
Total Input
W
COP
W/W
*1 HSPF (/)
Btu/h/W
Rated Capacity
Btu/h
Total Input
W
*2 COP
W/W
Phase, Cycle, Voltage
Breaker size
A
Indoor - Outdoor S1-S2
Indoor - Outdoor S2-S3
Indoor - Remote Controller
MCA
A
MOCP
A
Fan Motor
F.L.A.
Fan Motor Output
W
Air flow
DRY
CMM
(Lo-M2-M1-Hi) WET
CMM
Air flow
DRY
CFM
(Lo-M2-M1-Hi) WET
CFM
External pressure
Pa
Sound level
dB(A)
(Lo-M2-M1-Hi)
External finish (Panel)
Dimension
W : mm [inch]
Unit (Panel)
D : mm [inch]
H : mm [inch]
Weight
kg
Unit (Panel)
lbs
Field drain pipe size O.D.
mm [inch]
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
A
A
F.L.A.
W
R.L.A
L.R.A.
CMM [CFM]
Refrigerant
Refrigerant pipe size
Refrigerant pipe length
PCA-A24KA
PUZ-A24NHA3
PUZ-A24NHA3-BS
24,000
24,000
12,000
2340
10.3
16.8
5.8
0.73
28,000
26,000
12,000
2310
3.30
10.9 / 8.9
18,000
2220
2.38
PCA-A30KA
PCA-A36KA
PUZ-A30NHA3
PUZ-A36NHA3
PUZ-A30NHA3-BS
PUZ-A36NHA3-BS
30,000
35,000
30,000
35,000
12,000
12,000
3760
4630
8.0
7.6
14.5
14.4
8.3
8.5
0.69
0.73
34,000
38,000
32,000
37,000
12,000
12,000
3210
3190
2.92
3.40
9.2 / 7.1
10.2 / 8.1
23,000
25,000
2940
2800
2.29
2.62
1phase , 60Hz , 208/230V
30
AC 208 / 230V
DC24V
DC12V
25
1
PCA-A42KA
PUZ-A42NHA3
PUZ-A42NHA3-BS
42,000
42,000
18,000
4110
10.2
15.8
11.7
0.69
48,000
45,000
18,000
3830
3.44
10.2 / 8.3
30,000
3820
2.30
2
15
0.54
95
0.97
160
15-16-17-19
14-15-16-18
530-565-600-670
495-530-565-635
16-17-18-20
15-16-17-19
565-600-635-705
530-565-600-670
33-35-37-40
35-37-39-41
22-24-26-28
20-22-24-26
775-850-920-990
705-775-850-920
23-25-27-29
21-23-25-27
810-885-955-1025
740-810-885-955
37-39-41-43
39-41-43-45
0
White Munsell 6.4Y 8.9/0.4
1280 [50-3/8]
1600 [63]
680 [26-3/4]
230 [9-1/16]
32
71
36
79
26 [1-1/32]
Attached in Indoor Unit
25
40
0.75
75
TNB220FLHM
12
17.5
55 [1,940]
Linear Expansion Valve
Reverse Cycle
48
50
Ivory Munsell 3Y 7.8/1.1
950 [37-3/8]
330+30 [13 + 1-3/16]
943 [37-1/8]
75 [165]
R410A
3.0 [6 lbs 10 oz]
0.87 (FV50S) [28]
15.88 [5/8]
9.52 [3/8]
Max. 30m [Max. 100ft]
Max. 50m [Max. 165ft]
Not Supplied
Flared
18
30
14
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
dB(A)
Sound level at heating
dB(A)
External finish
Dimension
W : mm [inch]
D : mm [inch]
H : mm [inch]
Weight
kg [lbs]
Type
kg [lbs]
Charge
Oil
L [oz]
Gas side O.D.
mm [inch]
Liquid side O.D.
mm [inch]
Height difference
Length
Refrigerant Piping
Connection Method
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
Operating range
Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Indoor intake air temperature
Outdoor intake air temperature
Maximum
D.B. 35(95°F), W.B. 21.7(71°F)
D.B. 46(115°F)
Minimum
D.B. -18(0°F)*
D.B. 19.4(67°F), W.B. 13.9(57°F)
Maximum
D.B. 26.7(80°F), W.B. 19.4(67°F)
D.B. 21.1(70°F), W.B. 15(59°F)
Heating
Minimum
D.B. 21.1(70°F), W.B. 15.6(60°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
Cooling
8
38
84
26
0.4 + 0.4
86 + 86
ANV33FDPMT
20
27.5
100 [3,530]
51
55
1350 [53-1/8]
118 [260]
4.5 [10 lbs]
1.4 (FV50S) [45]
2-4. CEILING CONCEALED TYPE
Model name
Cooling
Heating
Heating
at low ambient
Power supply
Voltage
Indoor unit
indoor unit
outdoor unit
Max. Capacity
Rated Capacity
Min. Capacity
Total input
EER
SEER
Moisture Removal
*1 SHF
Max. Capacity
Rated Capacity
Min. Capacity
Total input
COP
*1 HSPF(IV/V)
Rated Capacity
Total input
*2 COP
Phase,Cycle,Voltage
Breaker size
indoor - outdoor S1-S2
indoor - outdoor S2-S3
indoor - Remote controller
MCA
MOCP
Fan Motor
Fan Motor Output
Air flow
DRY
(Lo-Mid-Hi) WET
Air flow
DRY
(Lo-Mid-Hi) WET
External pressure
Sound level
(Lo-Mid-Hi)
External finish
Dimension
Unit (Panel)
Weight
Unit
Field Drain pipe seize O.D.
Remote Controller
Outdoor unit
MCA
MOCP
Fan Motor
Fan Motor Output
Compressor
Air flow
Refrigerant Control
Defrost Method
Sound level at cooling
Sound level at heating
External finish
Dimension
Refrigerant
Refrigerant pipe size
Refrigerant pipe length
Weignt
Type
Charge
Oil
Gas side O.D.
Liquid side O.D.
Height difference
Length
Btu/h
Btu/h
Btu/h
W
Btu/h
Btu/h
Pints/h
Btu/h
Btu/h
Btu/h
W
W/W
Btu/h/W
Btu/h
W
W/W
PEA-A12AA
PUY-A12NHA3
PUY-A12NHA3-BS
12,000
12,000
6,000
1240
9.7
13.8
2.47
0.77
-
A
A
A
F.L.A
W
CMM
CMM
CFM
CFM
in.WG [Pa]
dB(A)
PEA-A18AA
PUY-A18NHA3
PUY-A18NHA3-BS
18,000
18,000
8,000
2150
8.4
14.3
3.26
0.80
1phase, 60Hz, 208/230V
15
AC208 / 230V
DC24V
DC12V
1
15
0.57
PEA-A18AA
PUZ-A18NHA3
PUZ-A18NHA3-BS
18,000
18,000
8,000
2150
8.4
14.3
3.26
0.80
20,000
19,000
8,000
1540
3.61
10.0 / 8.0
13,000
1520
2.51
2
15
0.74
96
7-9-11
6-8-10
247-317-388
222-285-349
12-15-18
11-14-17
423-529-635
381-476-572
0.02/0.06/0.14/0.20 [5/15/35/50]
23-28-33
30-34-38
Galvanized
W:mm[inch]
D:mm[inch]
H:mm[inch]
kg
lbs
mm[inch]
990[39]
700[27-9/16]
200[7-7/8]
21
48
32 [1-9/32]
Attached in indoor Unit
13
A
A
F.L.A.
W
15
R.L.A.
L.R.A.
CMM[CFM]
dB(A)
dB(A)
-
W:mm[inch]
D:mm[inch]
H:mm[inch]
kg[lbs]
41[90]
kg[lbs,oz]
L[oz]
mm[inch]
mm[inch]
1190[46-7/8]
700[27-9/16]
200[7-7/8]
27
60
1.3 [2lbs 14oz]
Refrigerant Piping
Connection Method
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F)
Operating range
20
0.35
40
SNB130FPBM1
12
14
34 [1,200]
Linear Expansion Valve
46
Ivory Munsell 3Y 7.8/1.1
800 [31-1/2]
330+23 [13+7/8]
600 [23-5/8]
44[97]
R410A
1.7 [3lbs 12oz]
0.65 (MEL 56) [20]
12.7 [1/2]
6.35 [1/4]
Max. 30m [Max.100ft]
Max. 30m [Max.100ft]
Not Supplied
Flared
Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Outdoor intake air temperature
Indoor intake air temperature
Maximum
D.B. 46(115°F)
D.B. 35(95°F), W.B. 21.7(71°F)
Cooling
Minimum
D.B. -18(0°F)*
D.B. 19.4(67°F), W.B. 13.9(57°F)
Maximum
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. 26.7(80°F), W.B. 19.4(67°F)
Heating
Minimum
D.B. -11.1(12°F), W.B. -12.2(10°F)
D.B. 21.1(70°F), W.B. 15.6(60°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
9
Reverse Cycle
47
45[99]
OUTLINES AND DIMENSIONS
Unit: inch (mm)
23-1/2 (597)
Air intake hole
(
Connected the attached
flexible pipe or socket.
)
(83)
(36)
Vane motor
Air outlet hole
37-3/8 (950)
1-27/64
3-17/64
(83)
Indoor unit
Ceiling
Grille
Min.94-1/2(2400)
from floor
Min.19-11/16(500)
Entire
periphery
Floor
(36)
6-9/16(167)
6-3/32 (155)
(:150)
Burring hole pitch
:4-29/32(:125)
120°
6-7/32
120°
Keep 25/64(10)to 19/32(15)
between unit ceiling
and ceiling slab.
+
Cut out hole
:3-15/16(:100)
++
(35)
1-3/8
Burring hole
3-:1/8(3-:2.8)
Ceiling
In case of standard grille
In case of wireless remote controller
Emergency operation switch<Cooling>
Emergency operation
switch<Heating>
23-1/2 (597)
Air intake hole
Air outlet hole
19-11/16 (500)
M
Corner pocket
Burring hole
Receiver
M
19-11/16 (500)
14-:1/8 (14-:2.8)
(350)
Auto vane
(Air outlet)
Air intake grille
1-27/64
13-25/32
Detail drawing of fresh air intake hole
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
M
3-15/16 (100)
5-1/8 (130)
25/32 to
(7.5)
1-25/32
(20~45)
Ceiling hole
Branch duct
hole
(:175) :6-7/8
Burring hole pitch
+3/16
0
(17+5
0 )
(50~70)
1-15/16~2-3/4
Ceiling
Grille
M
3-17/64
+ +
+
Suspension bolt
lower edge
37-3/8 (950)
24-13/32 (620)
25/32
(140)
+
+
7-15/32
+ +
5-1/2
(170)
6-11/16
2
A
(377)
14-27/32
(190)
11-3/16
Drain pipe
connected to VP-25
4-1/8 (105)
(284)
2-3/8
Cut out hole
6-9/64 (156)
(60)
1
3-17/32 (90)
Cut out hole
(160)
33-1/16 (840)
3-15/16 (100)
3-15/16 (100)
3-17/32 (90)
:5-29/32
6-5/16
7-3/8
(187.5)
Suspension bolt
M10 or W3/8
PLA-A42BA
Detail connecting of branch duct(Both aspects)
(7.5)
C
D
(5/16)
3-17/32 (90)
For wiring replacement kit
terminal block
+35
23-13/16 -3/16
+1-3/8 (605 -5 )
15/16 (24)
6-5/16 (160)
Indoor unit/Outdoor unit
connecting terminal block
Branch duct hole
5-29/32(150)
33-1/16(840)
For MA-Remote controller
terminal block
Suspension bolt pitch
(160)
(5/16)
(160)
to 1-25/32
(20~45)
6-5/16
PLA-A36BA
25/32 to 1-25/32(20~45)
31-7/8(810)
Suspension bolt pitch
B
Fresh air
intake hole
PLA-A30BA
33-27/32 to 35-13/16 (860~910)
25/32 to 1-25/32(20~45)
6-5/16
PLA-A24BA
Ceiling hole
33-27/32 to 35-13/16(860~910)
( 158)
INDOOR UNIT
PLA-A12BA PLA-A18BA
11/16
3
DEFROST/STAND BY lamp
Operation lamp
Note1. As for drain pipe, please use VP-25(O.D.1-1/4(32mm) PVC TUBE).
Drain pump is included.
Max. lifting height is 70-7/18(850mm) from the ceiling.
2. As for suspension bolt, please use M10 or W3/8.
(Procured at local site)
3. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for
control/power wires connection.
4. The height of the indoor unit can be adjusted
with the grille attached.
5. For the installation of the optional high efficiency filter
or optional multi-functional casement.
1) Add 5-5/16(135mm) to the dimensions + marked on the figure.
2) Optional high efficiency filter must be used jointly with optional
multi-functional casement.
6. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
7. As for necessary installation/service space, please refer to the
left figure.
Models
1
PLA-A12BA Refrigerant pipe
PLA-A18BA ····:6.35mm
Flared connection
····1/4
PLA-A24BA
PLA-A30BA
Refrigerant pipe
····:9.52mm
PLA-A36BA Flared connection
PLA-A42BA ····3/8
10
2
A
B
C
D
Refrigerant pipe
····:12.7mm
Flared connection 9-1/2 10-3/16 3-5/32 2-29/32
····1/2
(241) (258) (80) (74)
Refrigerant pipe
····:15.88mm
Flared connection
11-1/16 11-3/4 3-11/32 3-1/32
····5/8
(281) (298) (85)
(77)
PKA-A12HA
PKA-A12HAL
PKA-A18HA
PKA-A18HAL
15-3/16(387)
7-1/2(192)
Unit: inch (mm)
7-3/4(197)
Top side
Mount board
23-9/16(599)
Front side
11-5/8(295)
Right side
D
Left side
A
27-1/16(688)
2-1/8
(55)
Knockout hole
for left piping
9-13/16(249)
6-1/16(155)
35-3/8(898)
Front side(Grille open)
Sleeve
(purchased locally)
:2-1/2~:3-1/8
(:65~:80)
3/16(5)
Knock out hole
for right piping
Through hole
:2-1/2~:3-1/8
(:65~:80)
Terminal block for indoor/outdoor
connecting line
Terminal block for power supply (option)
Terminal block for
MA-remote controller
(only PKA-A·HA models)
17-15/16(457)Gas pipe
21-3/16(539)Liquid pipe
24(610)Drain hose
6-5/8(169)
6-3/16(158)
Under side
Vane(auto)
DEFROST/STAND BY lamp
Operation lamp
24-1/16(612)
5/16(8)
Emergency operation switch
(cooling/heating)
7-3/16(184)
Refrigerant Liquid pipe
Piping
Gas pipe
1/4F (:6.35)
Drain hose
:5/8 (:16) O.D
Knock out hole
for lower piping
Knock out hole
for lower piping
Louver(manual)
C
1/2F (:12.7)
Receiver
B
Center measurement hole :3/32(:2.5)
5/32(3.8)
12-7/8(237.5)
14(356.3)
14-5/8(372.3)
4-7/8(125)
Mount board
7-13/16(200)
8-13/16(225)
9-5/16(238)
10-3/8(265)
11-7/16(291.5)
2-1/4(58)
0
5/8(16)
1-1/16(28.5)
1-9/16(41)
3-1/16(78.5)
3-9/16(91)
4-1/16(103.5)
4-9/16(116)
6-1/2(166)
7(178.5)
8(203.5)
9-1/8(232.5)
9-15/16(253.5)
2-3/4(70)
0
2-3/4(70)
9/16(15)
0
9/16(15)
4-7/8(125)
8-13/16(225)
7-13/16(200)
77-:3/16(:5.1)
Tapping
screw hole
11-7/16(291.5)
10-3/8(265)
14-5/8(372.3)
14(356.3)
12-7/8(327.5)
4-:5/16(:9)
Bolt hole
Indoor unit outline
13/16(21.8)
0
3/4(20)
1-1/4(32.7)
2-1/16(53.5)
2-9/16(66)
5(128.5)
6(153.5)
11-1/16(281)
7-9/16(193.5)
Knockout hole for
rear piping
2-3/4×12-3/16(70×310)
4-1/2(115)
5-1/2(140)
6-9/16(167)
7-1/16(180.3)
10-15/16(278.3)
9-5/16(238)
8-3/8(213)
6-13/16(174)
15-1/2(394)
Wall hole
for
left rear
piping
17-5/8(449)
0
17-5/8(449)
9-1/16(231.5)
10-3/4(273.2)
Wall hole for
right rear piping
Required space(Indoor unit)
D
3/16(6)
1-3/4(46)
Min.1/4(7)
2-5/16(59)
1-11/16(43)
A
1-11/16(43)
1-11/16(43)
B
2-5/16(60)
11
Min.1-31/32(50)
250mm,9-13/16inch or greater with
optional drain pump installation.
2-3/16(56)
C
1-11/16(43)
2-3/16(56)
1-3/4(46)
2-3/16(56)
7/16(12.5)
Air inlet
3/16(6)
2-11/16(69)
(mm)
Air inlet
Air outlet
Min.1-31/32(50)
Min.8-5/8
(220)
Min.5-7/8(150)
Min.9-13/16(250)
Knockout hole for piping
PKA-A24KA
PKA-A36KA
PKA-A24KAL
PKA-A36KAL
PKA-A30KA
PKA-A30KAL
Unit: inch (mm)
5-17/132(140.3)
2-9/16(65.2)
Top side
17(431.7)
7/16(11)
16-11/16(423.7)
Left side
Right side
Front side
14-3/8(365)
Mount board
Knockout hole
for left piping
C
2-29/32(74)
9-1/2(241)
33-21/32(855)
46-1/16(1170)
A
3/16(5)
11-5/8(295)
Operation lamp
Front side(Grille open)
Knock out hole
for right piping
DEFROST/STAND BY lamp
Receiver
2-3/32(53)
1-1/4(32)
23/32(18)
Terminal block for Outdoor unit
Terminal block for power supply (option)
Terminal block for
MA-remote controller (only PKA-A·KA models)
Emergency operation switch
(cooling/heating)
Filter hook
1-3/16(30)
1-3/8(35)
17-15/32(444)Gas pipe
2-19/32(66)
4-27/32(123)
18-31/32(482)Liquid pipe
23-1/32(585)Drain hose
6-1/16(154)
5-9/32(134)
Under side
Piping connection department
Vane(auto)
Louver(manual)
B
Liquid pipe
B
Knock out hole
for lower piping
Sleeve
(purchased locally)
:2-15/16
(:75)
Through hole
Gas pipe
:2-15/16~:3-5/32
(:75~:80)
Drain hose
Refrigerant pipe: 3/8 O.D(:9.52)
Flared connection: 3/8F
Refrigerant pipe: 5/8 O.D(:15.88)
Flared connection: 5/8F
5/8(:16) O.D
Required space(Indoor unit)
Min.2-27/32(72.4)
13/32(10.7)
2-1/8(54)
1/8(3)
0
5/8(15.5)
31/32(25)
1-31/32(50)
2-15/16(75)
3-15/16(100)
4-19/32(117)
4-29/32(125)
5-19/32(142)
7-9/16(192)
9-17/32(242)
12-3/8(314)
14-11/32(364)
15-1/8(384.5)
16-3/32(408.5)
17-9/32(439)
17-7/8(454)
18-5/16(465.5)
4-11/32(110)
2-3/8(60)
13/32(10)
0
13/32(10)
2-3/8(60)
4-11/32(110)
12-3/8(314)
17-7/8(454)
17-9/32(439)
16-3/32(408.5)
15-1/8(384)
14-11/32(364)
20-3/8(517.4)
4-:11/32(:9) Bolt hole
Mount board
Indoor unit outline
2-1/8(54)
1-1/4(32)
31/32(25)
1/2(12.5)
0
1/2(12.5)
1-15/32(37.5)
2-15/32(62.5)
3-7/16(87.5)
4-1/8(104.5)
5-3/32(129.5)
0
6-9/16(167)
8-17/32(217)
9-1/32(229.5)
10-13/32(264)
11-1/2(292)
11(279.5)
11-1/2(292)
Wall hole for
right rear piping
12
23-1/32(585)
17-11/16(449.2)
13-11/32(339)
13-3/4(349.2)
15-1/8(384)
8-17/32(216.5)
0
7-7/16(189)
15-1/8(384)
13-11/32(339)
16-15/16(430.5)
Knockout hole for
rear piping
2-15/16×18-29/32(75×480)
37.5)
/32(R
R1-15
23-1/32(585)
12-5/32(308.5)
12-1/4(311)
Wall hole for
left rear piping
3-1/32(77)
2-5/8(67)
3-1/32(77)
3-7/16(87)
2-9/16(65)
Center measurement hole
:3/32(:2.5)
75-:3/16(:5.1)
Tapping
screw hole
B
A
5/16(7.8)
2-9/16(65)
2-5/8(67)
3-1/32(77)
C
5/16(7.8)
Min.9-27/32(250)
Min.2(50.5)
Min.1-7/8(48)
Knockout hole for piping
Air outlet
Min.8-21/32(220)
20-7/8(530.5)
Min.9/32(7)
Air inlet
2-9/16(65)
7-1/2(190)
1-13/16(46)
1
2
3
4
5
6
7
8
3(76)
4-7/8(124)
5/16(8)
2
8
120°
7
15-1/4(387)
1-1/2(38)
11/16(18)
10-1/4(260)
3-3/8(85)
1-7/8(48)
9-11/16(246)
9-3/16(233)
1/16(2)
1/16(1)
Air intake
5-7/16(138)
When drain socket
is installed
Drainage
4
3-3/8(86)
In case of the rear pipe arrangement, make sure to
remove the shaded portions from the independent piece.
Then put the independent piece back in initial
position.(The heat exchanger might be clogged because of dust)
18-1/8(461)
4-3/4(121)
Drainage pipe connection(1(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knockout hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knockout hole for upper drain pipe arrangement
Knockout hole for fresh air intake Φ3-15/16(Φ100)
Knockout hole for wiring arrangement Φ7/8(Φ22)
Accessory...Drain socket (1(26mm) I.D.)
Electrical box
When electrical box
is pulled down
2
Ceiling
Φ
2-15/16(75)
3
12
5)
4-1
5/1
6(Φ
4-15/16(126)
1-7/16(37)
1
7-1/12(190)
1/16(2)
Air outlet
47-3/16(1198)
46-3/16(1173)
50-3/8(1280)
48-11/16(1237) (Suspension bolt pitch)
5-7/8(150)
Electrical box
5
7-3/16(182)
5-1/2(140)
2-7/16(62)
1/16(2)
12-5/8(320)
3-3/8(85)
3-5/16(84)
10(254)
[FRONT VIEW]
3-1/8(80)
3-7/16(88)
2-1/4(57)
26-3/4(680)
7-11/16(195)
26-3/4(680)
13
18-3/4(476)
6
2(51)
9/16
14
DEFROST/STAND BY lamp
Receiver
Operation lamp
Emergency operation
switch <Heating>
When drain socket
is installed
Drainage
9-3/16(233)
liquid Φ3/8(Φ9.52)
gas Φ5/8(Φ15.88)
9-11/16(246)
7-7/8(200)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain lift up
mechanism(option parts),refrigerant pipe will be only upward.
i-see sensor
Emergency operation
switch <Cooling>
9-5/16(236)
7-1/16(180)
In case of wireless remote controller
and i-see sensor(Optional Parts)
In case of wireless
remote controller
and i-see sensor
(Optional Parts)
3/16(5)
3/8(10)
PCA-A24KA
PCA-A30KA
Unit: inch (mm)
9-1/16(230)
11/16(18)
2
3
7-1/2(190)
1-13/16(46)
Ceiling
18-1/8(461)
4-3/4(121)
3(76)
4-7/8(124)
8
120°
5
7
15-1/4(387)
1-1/2(38)
11/16(18)
10-1/4(260)
3-3/8(85)
5-7/16(138)
1/16(2)
3-3/8(86)
6
7
8
5
1
2
3
4
1-7/8(48)
9-11/16(246)
9-3/16(233)
1/16(1)
Drainage
When drain socket
is installed
Electrical box
1/16(2)
7-1/2(190)
Drainage pipe connection(1(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knockout hole for left drain-piping arrangement
Refrigerant-pipe connection
(gas pipe side/flared connection)
Refrigerant-pipe connection
(liquid pipe side/flared connection)
Knockout hole for upper drain pipe arrangement
Knockout hole for fresh air intake Φ3-15/16(Φ100)
Knockout hole for wiring arrangement Φ7/8(Φ22)
Accessory...Drain socket (1(26mm)I.D.)
2
5/16(8)
Air outlet
59-3/4(1518)
58-3/4(1493)
63(1600)
61-5/16(1557) (Suspension bolt pitch)
11/16(18)
5-7/8(150)
4
In case of the rear pipe arrangement, make sure to
remove the shaded portions from the independent piece.
Then put the independent piece back in initial
position.(The heat exchanger might be clogged because of dust)
When electrical box
is pulled down
2-15/16(75)
Electrical box
12
5)
Φ4
-15
/16
(Φ
4-15/16(126)
1-7/16(37)
7-3/16
182
5-1/2
140
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain lift up
mechanism (option parts),refrigerant pipe will be only upward.
62
2-7/16
6
1/16(2)
3-3/8
85
3-5/16(84)
Air intake
10(254)
1
3-1/8
80
12-5/8(320)
3-7/16(88)
18-3/4(476)
[FRONT VIEW]
2(51)
9/16
14
liquid Φ3/8(Φ9.52)
gas Φ5/8(Φ15.88)
When drain socket
is installed
Drainage
9-3/16(233)
9-11/16(246)
7-7/8(200)
7-1/16(180)
9-5/16(236)
Emergency operation
switch <Heating>
DEFROST/STAND BY lamp
Receiver
Operation lamp
Emergency operation
switch <Cooling>
In case of wireless remote controller
and i-see sensor(Optional Parts)
In case of wireless
remote controller
and i-see sensor
(Optional Parts)
3/16(5)
3/8(10)
9-1/16(230)
26-3/4(680)
7-11/16(195)
2-1/4
57
14
26-3/4(680)
PCA-A36KA
PCA-A42KA
Unit: inch (mm)
PEA-A18AA
Unit: mm (inch)
Drain pipe(O.D.ø32(1-1/4))
(Emergency draining)
159(6-9/32)
345(13-19/32)
Suspension bolt hole
4-14X30(9/16X1-3/16) Slot
(24-5/8)
100
(3-15/16)
150(Duct)
(5-29/32)
23(29/32)
25(1)
Drain pipe(O.D.ø32(1-1/4))
700(27-9/16)
677(26-21/32)
23 (29/32)
10 (13/32)
Control box
116
(4-19/32)
2X2-ø2.9(1/8)
Refrigerant piping
flare connection (gas)
70
(2-25/32)
270(10-21/32)
88(3-15/32)
20(13/16)
23(29/32)
57(2-1/4)
(1-15/16)
102(4-1/32)
170(6-23/32)
90
(3-9/16)
200(7-7/8)
25 (1)
20(13/16)
30(1-3/16)
10 (13/32)
625 (Suspension bolt pitch)
49
Air filter
12(1/2)
A
Air
inlet
Air
outlet
N
B (Suspension bolt pitch)
C
M
L-ø2.9(1/8)
57(2-1/4)
D (Duct)
100(3-15/16)X(E-1)=F
100(3-15/16)
2XE-ø2.9(1/8)
20 (13/16)
12(1/2)
37(1-15/32)
100 (3-15/16)
157.5 (6-7/32)
37(1-15/32)
H
100(3-15/16)XJ=K
100(3-15/16)
15(19/32)
88(3-15/32)
PEA-A12AA
Knockout hole ø27(1-3/32)
(Indoor/outdoor connecting line)
Knockout hole ø27(1-3/32)
(Remote controller transmission line)
Terminal block (Indoor/outdoor connecting line)
Terminal block (Remote controller transmission line)
Refrigerant piping
flare connection (liquid)
Drain pipe(O.D.ø32(1-1/4))
(Spontaneous draining)
Note2
2)
7
77 19/3
- Access
(30
50
(131
G
/32
)
(131
/32 50 ~
~ 5 150
-29
/32
)
4
(17 50
-23
/32
)
175p5(6-29/32p7/32)
(Actual length)
Less than 550
(21-21/32)
)
/32
31
(150
door
0
0
45 2)
/3 n 30 16)
-23 tha
3/
(17 ore 11-1
(
M
More than 10
(13/32)
More than 20
(13/16)
Less than 300
(11-13/16)
Make the access door at the appointed position
properly for service maintenance.
Drain hose (I.D.ø32(1-1/4))
<accessory>
Required space for service and maintenance
mm(in.)
Model
PEA-A12AA
PEA-A18AA
A
B
C
D
E
900
952
998
860
9
(35-7/16) (37-1/2) (39-5/16) (33-7/8)
1100 1152 1198 1060
(43-5/16) (45-3/8) (47-3/16) (41-3/4)
11
F
G
800 1000
H
J
K
860
7
(27-9/16)
(31-1/2) (39-3/8) (33-7/8)
1000 1200 1060
(39-3/8) (47-1/4) (41-3/4)
9
700
900
(35-7/16)
L
M
1039 990
20 (40-29/32)
(39)
24 1239 1190
(48-25/32) (46-7/8)
Note1.Use M10 screw for the suspension bolt (field supply).
2.Keep the service space for the maintenance at the bottom.
3.This chart indicates for PEA-A12AA model,which has 2 fans.
PEA-A18AA models have 4 fans.
4.In case an inlet duct is used,remove the air filter(supply with
the unit), then install the filter(field supply) at suction side.
* PEA-A12AA Gas pipe: Connect the joint :12.7, 1/2” (supply with the unit).
15
N
1
Gas pipe
ø9.52(3/8) *
ø12.7(1/2)
Ceiling surface Access door
2
Liquid pipe
ø6.35(1/4)
OUTDOOR UNIT
PUY-A12NHA3(-BS)
Unit: mm (inch)
PUY-A18NHA3(-BS)
PUZ-A18NHA3(-BS)
347.5<13-11/16>
W33<1-5/16> drain hole
45.4<1-25/32>
4-oval hole
Air discharge
40<1-9/16>
18<23/32>
330<13>
Air intake
365<14-3/8>
300<11-13/16>
152<6>
155
Air intake
32.5<1-9/32>
43.6<1-23/32>
400<15-25/32>
23<29/32>
22<7/8>
Service panel
Service panel for charge plug
Connection for liquid pipe
FLARE W6.35<1/4>
90<3-17/32>
38<1-1/2>
241<9-1/2>
10<3/8>
300<11-13/16>
600<23-5/8>
Handle
155<6-3/32>
2-W22.2<7/8>
1/2 conduit hole
Connection for gas pipe
144<5-21/32>
FLARE W12.7<1/2>
183<7-7/32>
Service port
150<5-29/32>
287.5<11-11/32>
Installation bolt pitch
500<19-11/16>
69<2-23/32>
800<31-1/2>
FOUNDATION BOLTS
Basically
open
Free space around the outdoor unit
(basic example)
Please secure the unit firmly
with 4 foundation M10<W3/8> bolts.
(Bolts, washers and nut must
be purchased locally.)
Min.100mm<3-15/16> as long as
no obstacle is placed on the
rear and light-and-left sides
of the unit
Min.100mm<3-15/16>
Max.
18mm<23/32>
<Foundation bolt height>
Min.350mm<13-25/32>
*1
*2
*1
Min.500mm<19-11/16>
FOUNDATION
PIPING-WIRING DIRECTION
Min.100mm<3-15/16>
Piping and wiring connection can
be made from the rear direction only.
2 sides should be open in
the right, left and rear side.
Minimum installation space for outdoor unit
*1 In the place where short cycle tends to occur, cooling and heating capacity and power consumption might get lowered 10%.
Air outlet guide (optional PAC-SG58SG-E) will help them improve.
*2 If air discharges to the wall, the surface might get stained.
16
Min. 100mm
<3-15/16>
Service space
Front piping hole
(Knockout)
Front trunking hole
(Knockout)
45 <1-25/32>
19<3/4>
75
<2-31/32>
Right piping hole
(Knockout)
92<3-5/8>
55<2-3/16>
:92<3
-5/8>
40<1-9/16>
45<1-25/32>
Conduit hole
(2-:27<1-1/16>Knockout)
Right trunking hole
(Knockout)
Min.
500mm
<19-11/16>
65<2-9/16>
95<3-5/8>
40<1-9/16>
Rear piping hole
(Knockout)
:92<3
-5/8>
Rear trunking hole
(Knockout)
Conduit hole
(2-:27<1-1/16>Knockout)
40<1-9/16>
2-:22.2<7/8>
74<2-19/32>
1/2 Conduit attachment
When installing the conduit,
Set the attachment to the
inner side of each panel.
Handle
Side Air Intake
Handle
Rear Air Intake
FOUNDATION
Handle
30 <1-3/16>
220
145
145
145
<8-21/32> <5-23/32> <5-23/32> <5-23/32>
Earth terminal
2-U Shaped notched hole
(Foundfation Bolt M10<W3/8>)
66 <2-5/8>
175 <6-7/8>
417 <16-13/32>
2
1
Handle
Service panel
Terminal Block
Left···Power supply wiring
Reight···Indoor/Outdoor wiring
2-12%36 Oval hole
(Foundation Bolt M10<W3/8>)
42 <1-21/32>
Drain hole
(5-:33<1-5/16>)
71 <2-13/16>
Air Discharge
600 <23-5/8>
950 <37-13/32>
322 <12-11/16>
175 <6-7/8>
Rear Air Intake
Bottom piping hole
(Knockout)
Rear piping cover
Front piping cover
PUY-A24NHA3(-BS)
PUY-A30NHA3(-BS)
PUY-A36NHA3(-BS)
65<2-9/16>
92<3-5/8>
:92 >
<3-5/8
40 <1-9/16>
Conduit hole
(2-:27<1-1/16>Knockout)
Piping Knockout Hole Details
Air Intake
Handle
····Refrigerant GAS pipe connction (FLARE):15.88<5/8>
····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8>
*1 ····Indication of STOP VALVE connection location.
Example of Notes
Min. 500mm
<19-11/16>
Min.
10mm
<3/8>
<Foundation bolt height>
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
23<29/32>
FREE
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
be purchased locally.)
73<2-7/8>
63<2-1/2>
Min. 10mm
<3/8>
55<2-3/16>
27<1-1/16>
Min.
500mm
<191/16>
55<2-3/16>
27<1-1/16>
Min. 10mm
<3/8>
63<2-1/2>
73<2-7/8>
23<29/32>
4 PIPING-WIRING DIRECTIONS
Max.
300mm<1-3/16>
Min.
100mm
<3-15/16>
3 FOUNDATION BOLTS
943 <37-1/8>
330 <13>
30 <1-3/16>
23<29/32>
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
27<1-1/16>
92<3-5/8>
63<2-1/2>
73<2-7/8>
23<29/32>
71 <2-13/16>
Dimensions of space needed
for service access are
shown in the below diagram.
*1 443<17-7/16>
1 FREE SPACE (Around the unit) 2 SERVICE SPACE
31<1-7/32>
473 <18-5/8>
219 <8-5/8>
45 <1-25/32>
*1 447<17-19/32>
17
81<3-3/16>
56 <2-7/32>
53 <2-3/32>
19 <3/4>
370 <14-9/16>
28 <1-3/32>
670 <26-3/8>
PUZ-A24NHA3(-BS)
PUZ-A30NHA3(-BS)
PUZ-A36NHA3(-BS)
Unit: mm (inch)
Min. 150mm
<5-29/32>
Min. 10mm
<3/8>
Service space
Min.
10mm<3/8>
Min.
500mm
<19-11/16>
:92
8>
<3-5/
92<3-5/8>
65<2-9/16>
Front piping hole
(Knockout)
45<1-25/32>
55<2-3/16>
63
27<1-1/16>
Front trunking hole 40<1-9/16>
(Knockout)
Conduit hole
(2-:27<1-1/16>Knockout)
Piping Knockout Hole Details
<2-1/2>
73<2-7/8>
23<29/32>
Handle
19<3/4>
:92
92<3-5/8>
55<2-3/16>
>
<3-5/8
45<1-25/32>
92<3-5/8>
65<2-9/16>
40<1-9/16>
74<2-19/32>
Rear piping hole
(Knockout)
:
<3-592
/8>
Handle
1/2 Conduit attachment
When installing the conduit.
Set the attachment to the
inner side of each panel.
Handle
Handle
Side Air Intake
Rear Air Intake
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
Conduit hole
(2-:27<1-1/16>Knockout) 2-:22.2<7/8>
Rear trunking hole
(Knockout)
40<1-9/16>
Right trunking hole
(Knockout)
FOUNDATION
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
be purchased locally.)
Conduit hole
(2-:27<1-1/16>Knockout)
75
<2-31/32> 40<1-9/16>
Right piping hole
(Knockout)
Air intake
*1 ····Indication of STOP VALVE connection location.
····Refrigerant GAS pipe connction (FLARE):15.88<5/8>
····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8>
Example of Notes
Min. 1000mm
<39-3/8>
Min. 10mm
<3/8>
FREE
27<1-1/16>
92<3-5/8>
63<2-1/2>
73<2-7/8>
Min.
30mm
<1-3/16>
Min.
150mm
<5-29/32>
Min.
500mm
<19-11/16>
73<2-7/8>
63<2-1/2>
23<29/32>
1350<53-5/32>
Rear Air Intake
30<1-3/16>
66<2-5/8>
42<1-21/32>
175<6-7/8>
2-U Shaped notched hole
(Foundation Bolt M10<W3/8>)
950<37-13/32>
220
145 145
145
<8-21/32> <5-23/32> <5-23/32> <5-23/32>
Drain hole
5-:33<1-5/16>
71<2-13/16>
2
1
Handle
Service panel
Terminal Block
Left···Power supply wiring
Right····Indoor/Outdoor wiring
2-12%36 Oval hole
(Foundation Bolt M10<W3/8>)
600<23-5/8>
322<12-11/16>Earth terminal
Air Discharge
175<6-7/8>
330<13>
30<1-3/16>
23<29/32>
3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS
* 1 443<17-7/16>
Dimensions of space needed
for service access are
shown in the below diagram.
31<1-7/32>
28<1-3/32>
Bottom piping hole
(Knockout)
Rear piping cover
Front piping cover
1076<42-3/8>
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
55<2-3/16>
27<1-1/16>
635<25>
371<14-19/32>
81<3-3/16> 219<8-5/8>
19<3/4>
45<1-25/32>
56<2-7/32>
370<14-9/16>
417<16-13/32>
53<2-3/32>
* 1 447<17-19/32>
1 FREE SPACE (Around the unit) 2 SERVICE SPACE
71<2-13/16>
18
23<29/32>
PUZ-A42NHA3(-BS)
PUY-A42NHA3(-BS)
Unit: mm (inch)
Unit: mm (inch)
WIRED REMOTE CONTROLLER
48.5<1-15/16>
120<4-3/4>
130<5-1/8>
19
<3/4>
19
Unit: mm (inch)
WIRELESS REMOTE CONTROLLER
58<2-9/32>
CHECK TEST
MODEL RUN
SELECT
FAN
SWING
°F
°C
STOP AMPM
START AMPM
NOT AVAILABLE
159.3<6-3/8>
COOL
DRY
AUTO
FAN
HEAT
19<3/4>
55<2-5/32>
20
4
WIRING DIAGRAM
PLA-A12BA
[LEGEND]
SYMBOL
I.B
CN2L
CN24
CN30
CN32
CN41
CN51
DSA
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
X1
ZNR01,02
DP
FS
PLA-A18BA
PLA-A24BA
NAME
INDOOR CONTROLLER BOARD
CONNECTOR (LOSSNAY)
CONNECTOR<BACK-UP HEATING>
CONNECTOR<LLC>
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
SURGE ABSORBER
FUSE (T6.3AL250V)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
SWITCH (MODEL SELECTION) +See table 1.
SWITCH (CAPACITY CODE) +See table 2.
CONNECTOR (EMERGENCY OPERATION)
RELAY (DRAIN PUMP)
VARISTOR
DRAIN-UP MACHINE
DRAIN FLOAT SWITCH
PLA-A30BA
SYMBOL
MF
MV
TB4
TB5,TB6
PLA-A36BA
PLA-A42BA
NAME
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP. THERMISTOR
(32˚F/ 15kΩ, 77˚F / 5.4kΩ DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(32˚F/ 15kΩ, 77˚F/ 5.4kΩ DETECT)
COND. / EVA. TEMP. THERMISTOR
(32˚F/ 15kΩ, 77˚F/ 5.4kΩ DETECT)
TH1
TH2
TH5
OPTION PART
W.B
BZ
LED1
LED2
RU
SW1
SW2
PCB FOR WIRELESS REMOTE CONTROLLER
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
EMERGENCY OPERATION (HEAT / DOWN)
EMERGENCY OPERATION (COOL / UP)
TB5
2
1
TRANSMISSION
WIRES
DC12V
2 1
TB6
Refer to tables 1 and 2.
R.B
I.B
VANE CNV(WHT)
20 18 16 14 12 10 8 6 4 2
SW1
J41 J42
SW2
19 17 15 13 11 9 7 5 3 1
Pair No.
CN32
(WHT) 1
CN51(WHT)
5
CN2L
LED3
LED2
LED1
4
SWE
DSA
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
12
REMOCON
CN22
1
(BLK)
1 3
2 1
1
CN41(WHT)
2 1
OUTDOOR 1 3 5
CN01
3
CN24(YLW)
FUSE
ZNR02 U
DC280V
U
ZNR01
RECTIFICATION
(BLU)
ON OFF
1
3
CN3G
(BLK)
1
WIRELESS
CN90
(WHT)
9
I-SEE
SENSOR
CN4Y
1 (WHT) 4
I-SEE
SENSOR MOTOR
CN6Y
1 (RED) 6
CNAC
(WHT)
3 1
FLOAT SW LIQUID/PIPE INTAKE
CN4F
CN44
CN20 CN30
(WHT)
(WHT)
(RED) (GRN)
1
4
1
4
1 2
1
3
7
FAN
CNMF
(WHT)
4
X1
1
3
1 D.U.M
CNP
(BLU)
5
5
5
5
M
M
M
M
MV
MV
MV
MV
GRILLE
CNB
BZ
LED2
SW1
LED1
SW2
ON
OFF
I-SEE
SENSOR
FS
M
t˚
t˚
TH2 TH5
t˚
TH1
MS
3~
MF
TB4
YLW S1
ORN S2
S3
+1
TO
OUTDOOR
UNIT
ORN
BRN
M
1~
DP
+Be sure to turn off the power source
and then disconnect fan motor connector.
(Failure to do so will cause trouble in fan motor.)
MT
I-SEE SENSOR
CORNER PANEL
(OPTIONAL PART)
RU
W.B
<Table 1>SW1(MODEL SELECTION)
SW1
Service
1 2 3 4 5
5
4
9
YLW
ORN
<Table 2>SW2(CAPACITY CODE)
SW2
MODELS
Service
MODELS
PLA-A12BA
PLA-A18BA
PLA-A24BA
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON PLA-A30BA
OFF
ON PLA-A36BA
OFF
ON PLA-A42BA
OFF
Service
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
Notes: 1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal block.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
+1.Use copper supply wires.
[Self-diagnosis]
1.For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis,
and Check Codes generated in the past appear on the display.
21
PKA-A12HA PKA-A18HA PKA-A12HAL
PKA-A18HAL
[Explanation of symbols]
Symbol
I.B
CN2L
CN30
CN32
CN41
CN51
CN90
CN152
DSA
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
ZNR01,02
R.B
TB6
Symbol
Name
M
Indoor controller board
MS
Connector (LOSSNAY)
S.W
Connector (LLC)
Connector ( Remote switch)
SWE2
Connector (HA terminal-A)
TB2
Connector (Centrally control)
TB4
Connector (Remote operation adapter)
TB5
Connector (Back-up heating)
TH1
Surge absorber
FUSE(T3.15AL250V)
TH2
Power supply (I.B)
Power supply (R.B)
TH5
Transmission (Indoor-outdoor)
W.B
Switch (Model selection) +See table 1
LED1
Switch (Capacity code) +See table 2
LED2
Connector (Emergency operation)
Varistor
REC1
Wired remote controller
Terminal block (Remote controller transmission line)
Name
Vane motor
Fan motor
Switch board
Emergency operation
Terminal block(Indoor unit Power (option))
Terminal block (Indoor/outdoor connecting line)
Terminal block (Remote controller transmission line)
Room temp. Thermistor
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
Pipe temp. Thermistor/liquid
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
Cond./eva. temp. Thermistor
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
Pcb for wireless remote controller
LED (Operation indication: Green)
LED (Preparation for heating: Orange)
Receiving unit
MS
3~
<Table 1>
SW1
(MODEL SELECTION)
I.B
CNMF
6
(WHT) FUSE
1
T11
DB1
ZNR01
U
SWE
ON
OFF
LED2
Refer to
tables
1and 2
1 2
CN2L
(RED)
1
1
CN151
(WHT)
5
1
X1
9
CN90
(WHT)
CN41
(WHT)
4
BLK
1 CN32 3
(WHT)
1
CN51
(WHT)
1 CN30 3
(BLK)
CN44
CN4F
(WHT)
(WHT)
1
4
1
4
5
MODELS
3
1
CNP(BLU)
CN3C 3
(BLU) 1
ORN
BRN
CNRU
(WHT)
2
1 2 3 4 5
A18
W.B
6
RU
LD101(B) REC1
LED1
ON
OFF
ON
OFF
R.B
BLU
CN22 1
(BLU) 2
SETTING
1 2 3 4 5
A12
S.W
LDSWE(B) SWE2
LDSWE(A)
(BLU)
ON
OFF
<Table 2>
SW2(CAPACITY CODE)
10
CN152
(WHT)
CN20
(RED)
1 2
1 2 3 4 5
DSA
LED3
1
SETTING
TB4 <+3>
YLW
TO
S1
ORN
OUTDOOR
S2
UNIT
S3
YLW
ORN
CN01
(BLK)
ZNR02
U
LED1
1
3
5
BLU
LED2
1
2
TB6
1
2
TB5
For PKA-A.HA
M
t
○
t
○
TH1
+1(Fig. 1)
CN01
I.B
(BLK)
YLW
1
ORN
3
5
t
TH2 TH5
○
Notes:
1.SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3)for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of
230V), adopting superimposed system for power and signal.
+1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+2: For power supply system of this unit, refer to the caution label located near this diagram.
+3: Use copper supply wires.
22
I.B
RED
BLU
GRN/YLW
YLW
ORN
ORN
BRN
TB2
L1
L2
GR
POWER SUPPLY
208/230V 60Hz
TB4
S1
S2
S3
INDOOR/OUTDOOR
1 3
COMMUNICATION
CN3C(BLU)
TO OUTDOOR
UNIT
PKA-A24KA
PKA-A24KAL
PKA-A30KA
PKA-A30KAL
Notes:
1.SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3)for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of
230V), adopting superimposed system for power and signal.
+1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+2: For power supply system of this unit, refer to the caution label located near this diagram.
+3: Use copper supply wires.
23
PKA-A36KA
PKA-A36KAL
PCA-A24KA
PCA-A30KA
PCA-A36KA
PCA-A42KA
[LEGEND]
SYMBOL
I.B
CN2L
CN24
CN30
CN32
CN41
CN51
DSA
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
X1
ZNR01,02
R.B
MF
MV
NAME
INDOOR CONTROLLER BOARD
CONNECTOR (LOSSNAY)
CONNECTOR (BACK-UP HEATING)
CONNECTOR (LLC)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
SURGE ABSORBER
FUSE (T6.3AL250V)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
SWITCH (MODEL SELECTION) +See table 1
SWITCH (CAPACITY CODE) +See table 2
CONNECTOR (EMERGENCY OPERATION)
RELAY (DRAIN LIFT UP MECHANISM)
VARISTOR
WIRED REMOTE CONTROLLER BOARD
FAN MOTOR
VANE MOTOR
SYMBOL
TB4
TB5,TB6
TH1
TH2
TH5
OPTIONAL PARTS
W.B
BZ
LED1
LED2
RU
SW1
SW2
DP
FS
NAME
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP. THERMISTOR
(32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT)
COND. / EVA. TEMP. THERMISTOR
(32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT)
PCB FOR WIRELESS REMOTE CONTROLLER
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
EMERGENCY OPERATION (HEAT / DOWN)
EMERGENCY OPERATION (COOL / UP)
DRAIN LIFT UP MECHANISM
DRAIN FLOAT SWITCH
<Table 1>SW1(MODEL SELECTION)
SW1
Service
Refer to tables 1 and 2
TB5
2
1
TRANSMISSION
WIRES
DC12V
2 1
TB6
VANE CNV(WHT)
SW1
20 18 16 14 12 10 8 6 4 2
CN32
(WHT) 1
J41 J42
SW2
19 17 15 13 11 9 7 5 3 1
Pair No.
CN2L
LED3
LED2
2 1
LED1
4
WIRELESS
CN90
(WHT)
9
I-SEE
SENSOR
CN4Y
(WHT)
1
4
CNB
BZ
SW1
M
LED2
SW2
MV
1
6
2 1
I-SEE
SENSOR
DSA
ZNR02
(BLU)
ON OFF
1
LIQUID/PIPE INTAKE
CN44
CN20 CN30
(WHT)
(RED) (GRN)
4
4
1 2
t°
t°
TH2 TH5
t°
TH1
1
1
3
7
FAN
CNMF
(WHT)
4
MS
MT
I-SEE SENSOR
(OPTIONAL PARTS)
LED1
RU
ZNR01
DC294~325V
RECTIFICATION
(BLU)
FLOAT SW
CN4F
(WHT)
FUSE
U
REMOCON
CN22
1
When attaching
When attaching
drain lift up
drain lift up
mechanism
mechanism
(optional parts),
(optional parts)
remove the jumper
1
connector CN4F FLOAT SW
CN4F
and fit the drain
FS
(WHT)
float switch (FS).
M
U
1 2
5
4
9
I-SEE
SENSOR MOTOR
CN6Y
(RED)
(BLK)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(YLW)
CN41(WHT)
OUTDOOR 1 3 5
CN01
1 3
CN24
1
SWE
(RED)
3
CN51(WHT)
5
5
ON
OFF
R.B
I.B
1
1 2 3 4 5
3~
MF
X1
1 D.U.M
1 3
CNP
(BLU)
YLW
ORN
PCA-A24KA
PCA-A30KA
1 2 3 4 5
1 2 3 4 5
ON PCA-A36KA
OFF
ON PCA-A42KA
OFF
1 2 3 4 5
M
DP
(OPTIONAL PARTS)
+Be sure to turn off the source power
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor)
4
ON
OFF
ON
OFF
Notes: 1.SymboIs used in wiring diagram above are,
: Connector,
: Terminal block.
2. Indoor and outdoor connecting wires have poIarities, make sure
to match terminal numbers (S1, S2, S3) for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to
check the outdoor unit electric wiring for servicing.
+1: Use copper supply wire.
TO OUTDOOR
UNIT
1~
Service
1 2 3 4 5
+1
ORN
BRN
W.B
(OPTIONAL PARTS)
<Table 2>SW2(CAPACITY CODE)
SW2
MODELS
Service
MODELS
TB4
YLW S1
ORN S2
S3
[Self-diagnosis]
1.For details on how to operate self-diagnosis with the wireless
remote control,refer to the technical manuals etc.
2.For the wired remote control:When you quickly press twice the
CHECK switch on the remote control, the unit begins selfdiagnosis, and Check Codes generated in the past appear on
the display.
For Check Codes and Symptoms refer to the table below.
24
PEA-A12AA
PEA-A18AA
INSIDE SECTION OF CONTROL BOX
TO MA REMOTE
CONTROLLER
TB15
1
2
I. B.
SW1
SW2
CN2L
CN24
(Yellow)
CN51
1
CN32
12
CN22 (Blue)
ON OFF
1
3
5
3
1 CNP
(Blue)
DSA
CN41
SWE
ZNR02
U
DC310~340V
Rectify circuit
ZNR01
FUSE
U
LED2
LED3
CN90
CN01
(Black)
3
CN3C (Blue)
LED1
CN4F
1234
CN44
1234
CN20 (Red)
12
CNMF
7654
X1
1
TB4
S1
S2
TO
OUTDOOR
UNIT
S3
to
FS
to
to
TH2 TH5
M
TH1
Fan motor
M
1~
Drainpump
SYMBOL EXPLANATION
SYMBOL
NAME
INDOOR CONTROLLER BOARD
FUSE
FUSE AC250V 6.3A
LED3
TRANSMISSION(INDOOR-OUTDOOR)
ZNR01,02
VARISTOR
SW1
SWITCH (FOR MODE SELECTION)
DSA
ARRESTER
SW2
SWITCH (FOR CAPACITY CODE)
X1
AUX. RELAY
SWE
CN2L
CONNECTOR (LOSSNAY)
TH1
INTAKE AIR TEMP. THERMISTOR
CN24
CONNECTOR (BACK-UP HEATING)
TH2
PIPE TEMP. THERMISTOR/LIQUID
CN32
CONNECTOR (REMOTE SWITCH)
TH5
COND./EVA. TEMP. THERMISTOR
CN41
CONNECTOR (HA TERMINAL-A)
FS
CN51
CONNECTOR (CENTRALLY CONTROL)
TB4
CN90
CONNECTOR (WIRELESS)
LED1
POWER SUPPLY(I.B.)
FLOAT SWITCH
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK
(REMOTE CONTROLLER TRANSMISSION LINE)
I. B.
SYMBOL
LED2
TB15
NAME
POWER SUPPLY(I.B.)
CONTROL BOX
I. B.
CONNECTOR (EMERGENCY OPERATION)
Note1.Since the outdoor side electric wiring may change be sure
to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3)for correct wirings.
3.Symbols used in wiring diagram above are, :Connector, :Terminal.
4.Use copper supply wire.
25
TB15
TB4
PARTS LOCATION
SYMBOL
PFC
IPM
CB1~CB3
N.F.
LI/LO
NI/NO
EI,E2,E3
52C
C.B.
SW1
NAME
Converter
Power Module
Main Smoothing Capacitor
Noise Filter Circuit Board
Connection Terminal<L1-Phase>
Connection Terminal<L2-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Switch<Forced Defrost, Defect History
Record Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
Switch<Function Setup>
Switch<Function Setup>
SW4
SW5
SW6
SW7
SW8
5
5
6
1
1
3
1
TRANS
1
5
1
4
X51
3
X55
F1
1
2
5
F3
CNAC
(WHT)
1
X52
F2
3
2
2
1 3
1 SV2 3
1 SS
21S4 3
(GRN)
F4
(BLU)
21S4
RED
RED
WHT
WHT
CND
(WHT)
3 1
3
1 2
1 2
CNDC
(PNK)
M-NET ADAPTER
2
1
CN31
CN52C
(RED)
CN4
(WHT)
7
14
CNM
(WHT)
63H
(YLW)
CN2
(WHT)
3
3
CNVMNT CNMNT
(WHT) (WHT)
LED5 CN2M
(WHT)
LED1
LED2
LEV-A
(WHT)
SW6
1
1 2
TH3
(WHT)
SW1
4
LED4
CNDM
(WHT)
1
+1
CN51
(WHT)
1 2
SW12
LED3
1
CNS
(WHT)
LED2
+1
TH32 TH7/6
(BLK) (RED)
SW11
SW1
1
t°
LED1
1
MF1
MS
3~
t°
When M-NET adapter is connected
5
3
C. B.
t°
NAME
Switch
LED<Operation Inspection Indicators>
Fuse<T6.3AL250V>
Switch<Pump Down>
Connector<Emergency Operation>
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
CNVMNT Connector
<Connected to Optional M-NET Adapter Board>
Connector <Connected for Option (Contact Input)>
CNDM
Connector <Connected for Option (Signal output)>
CN51
X51, X52, X55 Relay
M
TH32 TH7 TH6 TH3
t°
SYMBOL
SW9
LED1,LED2
F1~F4
SWP
CN31
SS
CNM
CNMNT
LEV-A
63H
CNF1
7 (WHT)
PUY-A12/18NHA3-BS
CN5
(WHT)
NAME
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heatsink>
Thermistor<Shell>
Electronic Expansion Valve
Reactor
Capacitor
Power Circuit Board
Connection Terminal<L1/L2-Phase>
Connection Terminal<U/V/W-Phase>
PUY-A12/18NHA3
SW4 SWP SW8 SW5
[LEGEND]
SYMBOL
TB1
MC
MF1
21S4
63H
TH3
TH6
TH7
TH8
TH32
LEV-A
ACL
CY1,CY2
P.B.
TABR/S
TABU/V/W
PUZ-A18NHA3-BS
SW9 SW7
PUZ-A18NHA3
3
A B S
1
TB7
5
M-NET
1
(WHT)
PUZ only
RED
WHT
N. F.
ACL
LO
MS MC
3~
U
PFC
CN4 1
(WHT) 2
2
2
CN52C
(BLK)
CN5 1
(RED) 2
2
2
1
52C
RED
BLK
P. B.
WHT
W V
M-NET ADAPTER
NO
E3
IPM
TABU
1
3
t°
TH8
1
5
CN5
(RED)
CN3 1
(WHT) 2
TABV
TABW
CNAC2
(RED)
TABR
RED
TABS WHT
CN2
(WHT)
CB2
CB3
1
2
2
7
E2
CB1
1
+1 MODEL SELECT
1 2 3 4 5 6 7 8
+2. SW5-1 to 4 : Function switch
CNAC1
(WHT)
U
1 2 3 4 5 6
LI
BRN
ON
OFF
1 2 3 4 5 6
ORN
ON
OFF
YLW
ON
PUY-A18N OFF
1 2 3 4 5 6 7 8
ON
OFF
+2
U
EI
1 2 3 4 5 6
L1
CY1
CY2
GRN
ON
PUY-A12N OFF
1 2 3 4 5 6 7 8
SW5-5.6
BLU
ON
PUZ-A18N OFF
3
SW6
RED
MODEL
L2 GR
POWER SUPPLY
208 / 230V 60Hz
S1
S2
S3 TB1
INDOOR
UNIT
+Use copper supply wires.
26
NI
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
NAME
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1s digit>
Switch<Address setting : 10s digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Recelving>
LED<Power Supply : DC12V>
PUY-A24NHA3
NAME
Converter
Power Module
Main Smoothing Capacitor
Noise Filter Circuit Board
Connection Terminal<L1-Phase>
Connection Terminal<L2-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Switch<Forced Defrost, Defect History
Record Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
Switch<Function Setup>
Switch<Function Setup>
Switch
SW4
SW5
SW6
SW7
SW8
SW9
5
5
CN2
(WHT)
3
1
TRANS
1
1
3
1 2
1 2
CNDC
(PNK)
3
2
2
3
1
21S4 3
(GRN)
F4
4
PUZ only
1
3
1 SV2
3
3
3
A B S
1
TB7
5
M-NET
1
1 SS
(WHT)
(BLU)
21S4
CND
(WHT)
3 1
X51
X52
2
X55
5
F3
CNAC
(WHT)
1
F1
M-NET ADAPTER
2
1
CN31
CN52C
(RED)
CN4
(WHT)
7
14
CNM
(WHT)
1
F2
5
LED5 CN2M
(WHT)
LED1
3
SW7
1
CNVMNT CNMNT
(WHT) (WHT)
CNDM
(WHT)
LED2
1
6
SW6
LEV-A
(WHT)
LED4
SW1
1
1 2
TH3
(WHT)
SW12
LED3
+1
CN51
(WHT)
4
SW4 SWP SW8 SW5
1
63H
(YLW)
CNS
(WHT)
LED2
LED1
1 2
TH32 TH7/6
(BLK) (RED)
SW11
SW1
1
t°
+1
CNF1
7 (WHT)
1
5
3
C. B.
MF1
MS
3~
When M-NET adapter is connected
M
TH32 TH7 TH6 TH3
t° t°
NAME
LED<Operation Inspection Indicators>
Fuse<T6.3AL250V>
Switch<Pump Down>
Connector<Emergency Operation>
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
CNVMNT
<Connected to Optional M-NET Adapter Board>
Connector
<Connected for Option (Contact Input)>
CNDM
Connector <Connected for Option (Signal output)>
CN51
X51,X52,X55 Relay
LEV-A
63H
t°
SYMBOL
LED1,LED2
F1~F4
SWP
CN31
SS
CNM
CNMNT
CN5
(WHT)
SYMBOL
PFC
IPM
CB1~CB3
N.F.
LI/LO
NI/NO
EI,E2,E3
52C
C.B.
SW1
PUY-A24NHA3-BS
SW9
NAME
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heatsink>
Thermistor<Shell>
Electronic Expansion Valve
Reactor
Capacitor
Power Circuit Board
Connection Terminal<L1/L2-Phase>
Connection Terminal<U/V/W-Phase>
SV
RED
RED
WHT
WHT
RED
WHT
N. F.
ACL
LO
MS MC
3~
NO
U
PFC
2
CN4 1
(WHT) 2
2
CN3 1
(WHT) 2
TH8
2
CN52C
(BLK)
CN5 1
(RED) 2
2
1
52C
P. B.
RED
W V
BLK
E3
IPM
1
TABV
TABW
3
t°
5
1
CN5
(RED)
TABR
RED
TABS WHT
CNAC2
(RED)
TABU
1
CN2
(WHT)
CB2
CB3
2
2
7
E2
CB1
+1 MODEL SELECT
1 2 3 4 5 6 7 8
1
3
1 2 3 4 5 6
CNAC1
(WHT)
ON
OFF
+2
1 2 3 4 5 6
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
NAME
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1s digit>
Switch<Address setting : 10s digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Recelving>
LED<Power Supply : DC12V>
L1
CY1
CY2
GRN
M-NET ADAPTER
BLU
+2. SW5-1 to 4 : Function switch
L2 GR S1
POWER SUPPLY
208 / 230V 60Hz
S2
S3
INDOOR
UNIT
+Use copper supply wires.
27
U
U
LI
BRN
ON
PUY-A24N OFF
1 2 3 4 5 6 7 8
SW5-5.6
ON
OFF
YLW
SW6
ORN
MODEL
ON
PUZ-A24N OFF
RED
[LEGEND]
SYMBOL
TB1
MC
MF1
21S4
63H
SV
TH3
TH6
TH7
TH8
TH32
LEV-A
ACL
CY1,CY2
P.B.
TABR/S
TABU/V/W
PUZ-A24NHA3-BS
WHT
PUZ-A24NHA3
TB1
NI
EI
PUZ-A30/36NHA3
[LEGEND]
SYMBOL
TB1
MC
MF1
21S4
SV
63H
TH3
TH6
TH7
TH8
TH32
LEV-A
DCL
CY1, CY2
ACTM
PUZ-A30/36NHA3-BS
NAME
Terminal Block<Power Supply, Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
Solenoid Valve (Bypass Valve)
High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heatsink>
Thermistor<Shell>
Electronic Expansion Valve
Reactor
Capacitor
Active Filter Module
SYMBOL
P.B.
TABU/V/W
TABS/T
TABP1/P2
TABN1/N2
DS2, DS3
IPM
N.F.
LI/LO
NI/NO
EI, E2
52C
C.B.
F1~F4
SW1
PUY-A30/36NHA3
NAME
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal<L1/L2-Phase>
Connection Terminal<DC Voltage>
Connection Terminal<DC Voltage>
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Lead<L1-Phase>
Connection Lead<L2-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Fuse<T6.3AL250V>
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Address>
SYMBOL
SW4
SW5
SW6
SW7
SW8
SW9
SWP
CN31
LED1,LED2
SS
CNM
CNMNT
CNVMNT
CNDM
CN51
X51,X52,X55
PUY-A30/36NHA3-BS
NAME
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
Switch<Function Setup>
Switch<Function Setup>
Switch
Switch<Pump Down>
Connector<Emergency Operation>
LED<Operation Inspection Indicators>
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector<Connected to Optional M-NET Adapter Board>
Connector<Connected to Optional M-NET Adapter Board>
Connector< Connected for Option (Contact Input)>
Connector< Connected for Option (Signal output)>
Relay
When M-NET adapter is connected
LEV-A
5
M
TH32 TH7TH6 TH3
3
C. B.
t°
1
TRANS
CN52C
(RED)
12
SW6
SW1
LED1
LED2
2
3
X51
4
1 21S4 3
(GRN)
1 SV2 3
(BLU)
1 SS
(WHT)
21S4
CND
(WHT)
3 1
3
X55
3
F4
2
1
CN31
7
F3
CNAC
(WHT)
1
2
F1
14
CNM
(WHT)
2
F2
1
1
CN4
(WHT)
12
7
CNDC
(PNK)
CNS
(WHT)
3
1 3 1
5
CNVMNT CNMNT
(WHT) (WHT)
X52
1
CN2
(WHT)
6
+1
CN51 CNDM
(WHT) (WHT)
1
5 1 3
3
LEV-A
(WHT)
SW4SWPSW8 SW5
1
1 3
63H
(YLW)
2
LED2
SW12
LED3
LED4
M-NET ADAPTER
t°
12 1
4 12
TH32 TH7/6 TH3
(BLK) (RED) (WHT)
SW11
SW1
1
LED5 CN2M
(WHT)
LED1
t°
+1
CNF1
7 (WHT)
1
5
5
SW9 SW7
t°
MF1
MS
3~
CN5
(WHT)
63H
A B S
TB7
M-NET
SV
BLU
WHT
PUZ only
2
CN52C
(BLK)
1
CNAF
(WHT)
ON
PUZ-A36N OFF
ON
PUY-A30N OFF
ON
PUY-A36N OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
TABN1
BLK
ON
OFF
ON
OFF
ON
OFF
1 2 3 4 5 6
RED
BLK
P
N1
N2
6
RED
CNAC2
(RED)
L1
L2 GR S1
S2
CN5
(RED)
BRN
1
ORN
L2
YLW
WHT
L1
S3
WHT
Io
1 2 3 4 5 6
ACTM
INDOOR
UNIT
1 2 3 4 5 6
POWER SUPPLY
208 / 230V 60Hz
1 2 3 4 5 6
+Use copper supply wires.
+2. SW5-1 to 4 : Function switch
M-NET ADAPTER
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
U
4
BLK
+2
GRN
ON
OFF
CNAC1
(WHT)
LI
BLU
ON
PUZ-A30N OFF
1
V
W
MS
3~ MC
DCL
SW5-5.6
1
2
+1 MODEL SELECT
SW6
E2
U
3
U
MODEL
3
1
RED
TABP
TABS WHT
TABP1 RED
TABP2
RED
TABN
DS2
WHT TABN2
2
TABT BLU
TABW
2
7
1 CN3
2(WHT)
1 CN5
2 (RED)
1 CN4
2(WHT)
RED TABU
WHT
TABV
BLK
TH8
DS3
3
IPM
CN2
(WHT)
t°
CNDC
(PNK) 2
1
6
1
7
2
1
P. B.
4
N. F.
NO
52C
LO
NAME
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1s digit>
Switch<Address setting : 10s digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Recelving>
LED<Power Supply : DC12V>
28
CY1
CY2
TB1
NI
U
EI
2
PUZ-A42NHA3
[LEGEND]
SYMBOL
TB1
MC
MF1,MF2
21S4
63H
63L
TH3
TH4
TH6
TH7
TH8
LEV-A
DCL
CY1, CY2
ACTM
CB
PUZ-A42NHA3-BS
NAME
Terminal Block<Power Supply, Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Low Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heatsink>
Electronic Expansion Valve
Reactor
Capacitor
Active Filter Module
Main Smoothing Capacitor
PUY-A42NHA3
SYMBOL
P.B.
TABU/V/W
TABS/T
TABP1/P2/P
TABN1/N2/N
DS2, DS3
IPM
N.F.
LI/LO
NI/NO
EI, E2
52C
C.B.
F1~F4
SW1
PUY-A42NHA3-BS
NAME
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal<L1/L2-Phase>
Connection Terminal<DC Voltage>
Connection Terminal<DC Voltage>
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Lead<L1-Phase>
Connection Lead<L2-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Fuse<T6.3AL250V>
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Address>
SYMBOL
SW4
SW5
SW6
SW7
SW8
SW9
SWP
CN31
LED1,LED2
SS
CNM
CNMNT
CNVMNT
CNDM
CN51
X51,X52
NAME
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
Switch<Function Setup>
Switch<Function Setup>
Switch
Switch<Pump Down>
Connector<Emergency Operation>
LED<Operation Inspection Indicators>
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector<Connected to Optional M-NET Adapter Board>
Connector<Connected to Optional M-NET Adapter Board>
Connector< Connected for Option (Contact Input)>
Connector< Connected for Option (Signal output)>
Relay
When M-NET adapter is connected
63H
LEV-A
5
M
3
C. B.
1
CNDC
(PNK)
14
CNM
(WHT)
SW6
5
1 3 1
CNVMNT CNMNT
(WHT) (WHT)
6
2
2
3
1
F3
CNAC
(WHT)
1
2
F1
3
X52
F2
3
F4
4
CND
(WHT)
3 1
3
A B S
TB7
M-NET
X51
7
CNS
(WHT)
2
1
CN31
CN52C
(RED)
12
CN4
(WHT)
12
CN2
1 (WHT) 7
TRANS
LEV-A
(WHT)
LED5 CN2M
(WHT)
LED1
1 3
63H
(YLW)
1 3
63L
(RED)
2
1
1
SW1
CNF2
7 (WHT)
3
LED2
SW12
LED3
LED4
M-NET ADAPTER
+1
CN51 CNDM
(WHT) (WHT)
1
5 1 3
1
4 12 21
TH7/6 TH3 TH4
(RED) (WHT)(WHT)
SW11
SW1
1
t°
SW4SWPSW8 SW5
1
t°
LED1
MF2
MS
3~
t°
+1
CNF1
7 (WHT)
LED2
1
5
5
SW9 SW7
t°
MF1
MS
3~
CN5
(WHT)
63L
TH7TH6 TH3 TH4
1 21S4
(GRN)
3
1 SS
(WHT)
21S4
BLU
WHT
+2 PUZ only
1
CN52C
(BLK)
1
CNAF
(WHT)
TABN1
ON
PUY-A42N OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BLK
ON
OFF
1 2 3 4 5 6
RED
BLK
6
CN5
(RED)
CNAC1
(WHT)
L1
YLW
GRN
L2 GR S1
S2
S3
RED
WHT
INDOOR
UNIT
ACTM
POWER SUPPLY
208 / 230V 60Hz
M-NET ADAPTER
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
P
N1
N2
Io
1 2 3 4 5 6
+2. SW5-1 to 4 : Function switch
1
BRN
L2
ORN
L1
BLU
WHT
+2
RED
4
BLK
SW5-5.6
ON
OFF
1
LI
DCL
SW6
1
3
V
W
M
3~
MC
+1 MODEL SELECT
MODEL
CNAC2
(RED)
TABP2
RED
U
ON
PUZ-A42N OFF
E2
U
WHT TABN2
RED
TABP
3
1
2
TABV
WHT
CB
TABS WHT
TABW
2
DS2
BLU
TABP1 RED
TABU
2
TABT
RED
WHT
BLK
TH8
7
1 CN3
2(WHT)
1 CN5
2 (RED)
1 CN4
2(WHT)
TABN
DS3
3
IPM
CN2
(WHT)
t°
CNDC
(PNK) 2
1
6
1
7
2
2
P. B.
4
N. F.
NO
52C
LO
+Use copper supply wires.
NAME
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1s digit>
Switch<Address setting : 10s digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Recelving>
LED<Power Supply : DC12V>
29
U
CY1
CY2
TB1
NI
U
EI
2
5
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
PLA-A·BA
PCA-A·KA
PEA-A·AA
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH5
(Cond./Eva. temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Distributor
with strainer(#50)
Thermistor TH2
Pipe temperature (Liquid)
Thermistor TH1
(Room temperature)
PKA-A·HA
Strainer(#50)
PKA-A·HAL
PKA-A·KA
PKA-A·KAL
Strainer (#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH2
Pipe temperature(Liquid)
Thermistor TH5
(Cond./ Eva.temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Thermistor TH1
(Room temperature)
Strainer (#50)
Distributor
with strainer
(#50/#50 : HA(L))
(#50/#100 : KA(L))
30
5-2. OUTDOOR UNIT
PUZ-A18NHA3(-BS)
Unit: mm (inch)
4-way valve
(#50)
Strainer
Refrigerant GAS pipe
12.7 (W1/2)
<4-way valve solenoid coil>
Heating : ON
Cooling : OFF
Service
port(check)
High pressure
protect switch
Stop valve
(with service port)
Outdoor heat exchanger
Thermistor
(TH6)
Muffler
Thermistor
(TH3)
Thermistor
(TH32)
Distributor
Accumulator
Compressor
Refrigerant LIQUID pipe
6.35 (W1/4)
Stop valve
Refrigerant flow in cooling
Refrigerant flow in heating
(#100)
Strainer
(#100)
Strainer
Linear expansion valve
PUZ-A24NHA3(-BS) PUZ-A30NHA3(-BS) PUZ-A36NHA3(-BS)
Bypass valve
Ball valve 4-way valve
(#50)
Refrigerant GAS pipe
Strainer
15.88 (W5/8)
Service
port
(check)
Service
port
(check)
High pressure
protect switch
Outdoor heat exchanger
Thermistor
(TH6)
Muffler
Thermistor
(TH3)
Thermistor
(TH32)
Distributor
Accumulator
Refrigerant LIQUID pipe
9.52 (W3/8)
Compressor
Stop valve
(with service port)
Refrigerant flow in cooling
Refrigerant flow in heating
(#100)
Strainer
(#100)
Strainer
Linear expansion valve
PUZ-A42NHA3(-BS)
Low pressure protect
switch
4-way
Ball valve
valve
(#50)
Strainer
Refrigerant GAS pipe
15.88 (W5/8)
Service
port
(check)
Service port
(check)
High pressure protect switch
Outdoor heat exchanger
Thermistor
(TH6)
Muffler
Thermistor
(TH4)
Strainer
(#100)
Accumulator
Refrigerant LIQUID pipe
9.52 (W3/8)
Stop valve
(with service port)
Distributor
Refrigerant flow in cooling
Refrigerant flow in heating
Compressor
Strainer
(#100)
Thermistor
(TH3)
Strainer
(#100)
Linear expansion valve
31
PUY-A12NHA3(-BS) PUY-A18NHA3(-BS)
Stop valve
(with service port)
(#50)
Strainer
Refrigerant GAS pipe
12.7 (W1/2)
Unit: mm (inch)
Service port
(Check)
Outdoor heat exchanger
High pressure
protect switch
Thermistor
(TH6)
Thermistor
(TH3)
Thermistor
(TH32)
Distributor
Accumulator
Compressor
Refrigerant LIQUID pipe
6.35 (W1/4)
Stop valve
Refrigerant flow in cooling
(#100)
Strainer
(#100)
Strainer
Linear expansion valve
PUY-A24NHA3(-BS) PUY-A30NHA3(-BS) PUY-A36NHA3(-BS)
Refrigerant GAS pipe
15.88 (W5/8)
Ball valve
(#50)
Strainer
Bypass valve
Service
port
(check)
Outdoor heat exchanger
Thermistor
(TH6)
High pressure
protect switch
Thermistor
(TH32)
Service
port
(check)
Thermistor
(TH3)
Distributor
Accumulator
Refrigerant LIQUID pipe
9.52 (W3/8)
Compressor (#100)
Strainer
Stop valve
(with service port)
Refrigerant flow in cooling
(#100)
Strainer
Linear expansion valve
PUY-A42NHA3(-BS)
Low pressure protect
switch
Service
port
(#50) Strainer
(check)
Strainer (#100)
Ball valve
Refrigerant GAS pipe
15.88 (W5/8)
Outdoor heat exchanger
Thermistor
(TH6)
Thermistor
(TH3)
High pressure
protect switch
Service
port
(check)
Thermistor
(TH4)
Accumulator
Distributor
Refrigerant flow in cooling
Compressor
Refrigerant LIQUID pipe
9.52 (W3/8)
Strainer
(#100)
Stop valve
(with service port)
Strainer
(#100)
Linear expansion valve
32
6
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT PUZ-A·NHA3(-BS), PUY-A·NHA3(-BS)
Cooling performance curve
CAPACITY (RATIO)
1.4
1.2
INDOOR
W.B.(˚C)
22 (72˚F)
1.0
20 (68˚F)
18 (64˚F)
0.8
16 (61˚F)
INDOOR
W.B.(˚C)
22 (72˚F)
20 (68˚F)
18 (64˚F)
16 (61˚F)
1.2
TOTAL INPUT (RATIO)
1.0
0.8
0.6
0.4
-5
0
(23˚F) (32˚F)
10
(50˚F)
20
(68˚F)
30
(86˚F)
40
46
(104˚F) (115˚F)
OUTDOOR D.B.(˚C)
Note : This diagram shows the case where the operation frequency of a compressor is fixed.
33
Heating performance curve
Correcting the capacity line influenced by frosting
Not correcting the capacity line influenced by frosting
INDOOR
1.4
CAPACITY (RATIO)
1.2
D.B.(˚C)
In some cases, heating operation cannot be
conducted with the maximum frequency in the
area below the slanting line.
15 (59˚F)
20 (68˚F)
25 (77˚F)
1.0
0.8
0.6
0.4
1.4
1.2
INDOOR
In some cases, heating operation cannot be
conducted with the maximum frequency in the
area above the slanting line.
D.B.(˚C)
25 (77˚F)
20 (68˚F)
TOTAL INPUT (RATIO)
15 (59˚F)
1.0
0.8
0.6
0.4
-12 -10
(10˚F) (14˚F)
-5
(23˚F)
0
(32˚F)
5
(41˚F)
10
(50˚F)
OUTDOOR W.B.(˚C)
Note : This diagram shows the case where the operation frequency of a compressor is fixed.
34
15
(59˚F)
CORRECTION FACTORS
7
7-1. COOLING CAPACITY CORRECTION FACTORS
Outdoor unit
PUY-A12/18
PUZ-A18
PUY-A24/30/36
PUZ-A24/30/36
PUY-A42
PUZ-A42
Refrigerant piping length (one way)
30m (100ft)
20m (70ft)
5m (16ft)
10m (33ft)
40m (130ft)
50m (165ft)
1.00
0.985
0.957
0.931
–
–
1.00
0.988
0.966
0.946
0.929
0.913
1.00
0.985
0.957
0.931
0.908
0.886
40m (130ft)
50m (165ft)
7-2. HEATING CAPACITY CORRECTION FACTORS
Outdoor unit
Refrigerant piping length (one way)
30m (100ft)
20m (70ft)
5m (16ft)
10m (33ft)
PUZ-A18
1.00
0.997
0.991
0.985
–
–
PUZ-A24/30/36
1.00
0.997
0.991
0.985
0.979
0.973
PUZ-A42
1.00
0.997
0.991
0.985
0.979
0.973
7-3. CAPACITY CORRECTION
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
Cooling
Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft)
Heating
100
Heating A18,24,30,36,42
models
(Up to 30m(100ft) for
A18 model)
95
Capacity ratio [%]
Cooling A24,30,36 model
90
Cooling A12,18,42 models
(Up to 30m (100ft) for
A12/18 models)
85
80
75
70
5
10
15
20
25
30
35
40
45
<16>
<33>
<50>
<70>
<80>
<100>
<115>
<130>
<150>
Corrected pipe length
35
50 m
<165> ft
7-4. ADDITION OF REFRIGERANT
• Additional charging is not necessary if the pipe length does not exceed 20 m(70 ft) for A12-A36 or 30 m(100 ft) for A42.
• If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the
permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe
extensions and indoor unit have been vacuumized.
* When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit).
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have
a serious effect on operation performance.
Model
Max. pipe
length
Max. height
difference
A12, A18
30 m, 100 ft
30 m, 100 ft
0
A24, A30, A36
50 m, 165 ft
30 m, 100 ft
0
A42
50 m, 16 5 ft
30 m, 100 ft
0
8
20 m
70 ft
25 m
80 ft
0.06 kg
2 oz
0.17 kg
6 oz
27 m
90 ft
0.11 kg
4 oz
0.34 kg
12 oz
0
0
Additional refrigerant charging amount (kg/oz)
30 m
33.5 m 36.6 m
40 m
43 m
45.5 m
100 ft
110 ft
120 ft
130 ft
140 ft
150 ft
0.17 kg
–
–
–
–
–
6 oz
0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg 1.36 kg
18 oz
24 oz
30 oz
36 oz
42 oz
48 oz
0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg
0
6 oz
12 oz
18 oz
24 oz
30 oz
48.8 m
160 ft
50 m
165 ft
–
–
1.53 kg
54 oz
1.02 kg
36 oz
1.70 kg
60 oz
1.19 kg
42 oz
AIR FLOW DATA
8-1. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow
CFM
Air speed
ft/sec.(m/sec.)
Coverage range
ft(m)
Air flow
CFM
Air speed
ft/sec.(m/sec.)
Coverage range
ft(m)
PLA-A12BA
530
8.5(2.6)
13(4.1)
PLA-A18BA
640
10.5(3.2)
15(4.8)
PLA-A24BA
640
10.5(3.2)
15(4.8)
PKA-A12HA
PKA-A12HAL
PKA-A18HA
PKA-A18HAL
425
20.0(6.1)
35(10.8)
425
20.0(6.1)
35(10.8)
PLA-A30BA
740
12.1(3.7)
18(5.6)
PLA-A36BA
1060
17.4(5.3)
26(8.0)
PLA-A42BA
1090
17.7(5.4)
26(8.2)
Air flow
CFM
Air speed
ft/sec.(m/sec.)
Coverage range
ft(m)
PKA-A24KA
PKA-A24KAL
775
19.7(6.0)
47(14.3)
PKA-A30KA
PKA-A30KAL
775
19.7(6.0)
47(14.3)
PKA-A36KA
PKA-A36KAL
920
22.3(6.8)
53(16.1)
PCA-A24KA
670
10.2(3.1)
32(9.6)
PCA-A30KA
PCA-A36KA
PCA-A42KA
Air flow
CFM
Air speed
ft/sec.(m/sec.)
Coverage range
ft(m)
705
10.5(3.2)
33(10.1)
990
11.8(3.6)
41(12.5)
1025
12.1(3.7)
42(12.9)
The air coverage range is the distance to which the 0.8 ft/sec. air can reach, when air is blown out horizontally from the unit at
the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
36
8-2. PLA-A·BA
8-2-1 FRESH AIR INTAKE AND BRANCH DUCT
1. Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 5-5/16 to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
Unit : inch(mm)
[Fig. 1]
Fresh air intake hole diagram
Fresh air intake hole
3-:1/8(:2.8) burring hole
Indoor unit
6-7/32
(*158)
120
:4-29/32(:125) burring hole pitch
120
Branch duct hole
3-:15/16(:100) cut out hole
Ceiling
*6-3/32(155)
70
:6-7/8(:175) burring hole pitch
13-25/32(350)
*6-9/16(167)
3-17/32 3-15/16 3-15/16 3-17/32
(90) (100) (90) (90)
5-1/8(130)
Refrigerant pipe
Branch duct hole diagram
(view from either side)
3-15/16(100)
Drain pipe
14-:1/8(:2.8) burring hole
:5-29/32(:150) cut out hole
2. Fresh air intake (Installation at site)
By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct flange (option) onto it
further, fresh exterior air intake can be accomplished.
(The mounting of the multi-function casement increases the height of the ceiling plenum by 5-5/16(135mm).)
37
3. Fresh air intake amount & static pressure characteristics
1 PLA-A12 · A18 · A24 · A30BA
Multifunction casement + Standard filter
50(20)
Static pressure [Pa(in.W.G.%10-2)]
Static pressure [Pa(in.W.G.%10-2)]
Multifunction casement + High efficiency filter
0
-50(-20)
2 - inlet
-100(-40)
-150(-60)
1 - inlet
-200(-80)
0
1
2
50
3
4
100
6[CMM]
5
150
200
50(20)
0
-50(-20)
2 - inlet
-100(-40)
-150(-60)
1 - inlet
-200(-80)
0
1
2
[CFM]
3
50
4
100
6[CMM]
5
150
200
[CFM]
Air flow rate
How to read curves
1
A
2
E
C
A
-100(-40)
-150(-60)
0
1
2
3
4
100
Air flow rate
5
3
6[CMM]
150
200
D
-200(-80)
Q
[CFM]
Q
Qa
2 PLA-A36 · A42BA
Multifunction casement + Standard filter
Multifunction casement + High efficiency filter
50(20)
Static pressure [Pa(in.W.G.%10-2)]
Static pressure [Pa(in.W.G.%10-2)]
B
Q
-50(-20)
Q…Designed amount of fresh air intake
<CMM(CFM)>
A…Static pressure loss of fresh air
intake duct system with air flow
<Pa(in.W.G.o10-2)>
amount Q
B…Forced static pressure at air conditioner inlet with air flow amount Q
<Pa(in.W.G.o10-2)>
C…Static pressure of booster fan with
air flow amount Q <Pa(in.W.G.o10-2)>
D…Static pressure loss increase amount
of fresh air intake dust system for air
<Pa(in.W.G.o10-2)>
flow amount Q
E…Static pressure of indoor unit with air
<Pa(in.W.G.o10-2)>
flow amount Q
Qa … Estimated amount of fresh air
<CMM(CFM)>
intake without D
Duct characteristics
at site
0
0
50
0
-50(-20)
2 - inlet
-100(-40)
-150(-60)
1 - inlet
-200(-80)
0
2
50
4
100
150
6
200
8
[CMM]
50(20)
0
-50(-20)
-100(-40)
2 - inlet
-150(-60)
-200(-80)
[CFM]
250
50(20)
0
-50(-20)
-100(-40)
-150(-60)
0
2
50
4
100
150
2
4
100
150
Air flow rate
Taking air into the unit
-200(-80)
1 - inlet
0
50
Air flow rate
Static pressure [Pa(in.W.G.%10-2)]
Curve in the
graphs
C
50(20)
A
Static pressure [Pa(in.W.G.%10-2)]
Taking air into the unit
6
200
8
250
[CMM]
[CFM]
Air flow rate
38
6
200
8
250
[CMM]
[CFM]
4. Change of outlet numbers
The optional air outlet is necessary.
To change the air outlet number to 3-, or 2-way outlet, the
outlet number should be closed with the operational air
outlet shutter.
Indoor unit
When the air outlets are closed, close the vane by
removing the vane connector.
Outlet concave
portion
Button
Vane motor
Up/down vanes
Connector
Air outlet shutter plate
(Option)
Vane motor
Connector
Button
5. Branch duct and change of outlet numbers
+ Branch duct should be connected to one of the branch duct holes on the main unit.
<4- way air flow and branch duct>
Branch
duct
Air intake
Air
outlet
+ Close the outlet on the side of branch duct and air flows in 3 directions.
<3- way air flow and branch duct>
Branch
duct
Air intake
Air
outlet
Air
outlet
closed
position
+ The outlet on the side of branch duct and one of the other outlets are closed.
Air flows in 2 directions.
<2- way air flow and branch duct>
Branch
duct
Air
Air
outlet
outlet
closed
closed
position
position
Air intake
Air
outlet
closed
position
39
PLA-A30BA
4-way air flow (horizontal vane) Round duct
4-way air flow (horizontal vane) Rectangular duct
30(12)
Static pressure [Pa(in.W.G%10-2)]
Static pressure [Pa(in.W.G%10-2)]
30(12)
Duct
20(8)
10(4)
High
Low
0
0
2
0
50
4
100
6
150
200
Air flow rate
Low
0
0
[CFM]
0
250
3-way air flow (horizontal vane) Round duct
High
2
50
4
100
250
[CFM]
70(28)
Static pressure [Pa(in.W.G%10-2)]
60(24)
Close
50(20)
40(16)
30(12)
20(8)
High
Low
10(4)
0
0
2
50
4
100
6
150
8
200
250
Close
50(20)
40(16)
30(12)
High
20(8)
Low
10(4)
0
10[CMM]
300
Duct
60(24)
[CFM]
0
0
2
50
4
100
6
150
Air flow rate
8
200
250
10[CMM]
300
[CFM]
Air flow rate
2-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct
80(32)
Static pressure [Pa(in.W.G%10-2)]
80(32)
Static pressure [Pa(in.W.G%10-2)]
Air flow rate
8[CMM]
200
3-way air flow (horizontal vane) Rectangular duct
Duct
70(28)
Duct
60(24)
Close
Close
50(20)
40(16)
30(12)
High
20(8)
Low
10(4)
0
6
150
80(32)
70(28)
Static pressure [Pa(in.W.G%10-2)]
10(4)
8[CMM]
80(32)
0
Duct
20(8)
70(28)
Duct
60(24)
Close
Close
50(20)
40(16)
30(12)
20(8)
High
Low
10(4)
0
0
0
2
50
4
100
150
6
200
8
250
Air flow rate
10
300
350
400
12[CMM]
0
[CFM]
0
2
50
4
100
150
6
200
8
250
10
300
350
12[CMM]
400
[CFM]
Air flow rate
• Use 1 of the 2 duct holes on the indoor unit.
• Air flow rate of PLA-A12~24BA can be calculated from the air flow rate based on the characteristic of the duct for PLA-A30BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow.
40
PLA-A42BA
Duct
20(8)
10(4)
0
2
0
50
30(12)
Duct
20(8)
10(4)
High
Low
0
4-way air flow (horizontal vane) Rectangular duct
Static pressure [Pa(in.W.G%10-2)]
Static pressure [Pa(in.W.G%10-2)]
4-way air flow (horizontal vane) Round duct
30(12)
4
100
6
150
8[CMM]
0
0
[CFM]
0
250
200
Air flow rate
3-way air flow (horizontal vane) Round duct
4
100
8[CMM]
250
200
Air flow rate
[CFM]
70(28)
Duct
Duct
Static pressure [Pa(in.W.G%10-2)]
Close
60(24)
50(20)
40(16)
High
30(12)
20(8)
Low
10(4)
0
0
0
2
50
4
100
6
150
8
200
250
Air flow rate
Close
60(24)
50(20)
40(16)
High
30(12)
20(8)
Low
10(4)
10[CMM]
0
0
[CFM]
0
300
2
50
4
100
8
200
10[CMM]
250
300
Air flow rate
[CFM]
100(40)
90(36)
90(36)
Duct
Duct
80(32)
80(32)
Close
Close
Close
Close
70(28)
Static pressure [Pa(in.W.G%10-2)]
70(28)
60(24)
50(20)
40(16)
High
30(12)
Low
20(8)
10(4)
0
0
6
150
2-way air flow (horizontal vane) Rectangular duct
2-way air flow (horizontal vane) Round duct
100(40)
Static pressure [Pa(in.W.G%10-2)]
6
150
80(32)
70(28)
Static pressure [Pa(in.W.G%10-2)]
2
50
3-way air flow (horizontal vane) Rectangular duct
80(32)
0
High
Low
2
50
4
100
150
6
200
8
250
300
10
350
12[CMM]
400
[CFM]
60(24)
50(20)
High
40(16)
Low
30(12)
20(8)
10(4)
0
0
0
2
50
4
100
150
6
200
8
250
300
10
350
Air flow rate
Air flow rate
• Use 1 of the 2 duct holes on the indoor unit.
• Air flow rate of PLA-A36BA can be calculated from the air flow rate based on the characteristic of the duct for PLA-A42BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow.
41
12[CMM]
400
[CFM]
8-3. PCA-A·KA
FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS
Fresh air intake hole
At the time of installation, use the duct holes (knock out)
located at the positions shown in the left diagram, as and
when required.
A Indoor unit
B Fresh air intake hole (knock out hole)
C Filter
in. (mm)
A
C
B
A
B
C
10-3/16
(259.5)
ø 3-15/16
(ø 100)
4-5/16
(109)
How to read curves
Curve in the
graphs
1
A
0
-100(-40)
Duct characteristics
at site
-150(-60)
Q
-200(-80)
B
0
-50(-20)
-250(-100)
2
1
2
50
3
100
4 [CMM]
C
A
-300(-120)
0
[CFM]
Airflow rate
Q
D
3
Static pressure[Pa(in.W.G.×10ˉ²]
A
■ PCA-A36, 42KA
Q
Qa
50(20)
0
-50(-20)
-100(-40)
-150(-60)
-200(-80)
-250(-100)
-300(-120)
0
1
2
50
3
100
4 [CMM]
[CFM]
Airflow rate
42
C
50(20)
E
Static pressure[Pa(in.W.G.×10ˉ²]
■ PCA-A24, 30KA
Q…Designed amount of fresh air intake
<CMM(CFM)>
A…Static pressure loss of fresh air
intake duct system with airflow
amount Q
<Pa(in.W.G.x10-2)>
B … Forced static pressure at air conditioner inlet with airflow amount Q
<Pa(in.W.G.x10-2)>
C…Static pressure of booster fan with
airflow amount Q <Pa(in.W.G.x10-2)>
D…Static pressure loss increase amount
of fresh air intake duct system for
airflow amount Q <Pa(in.W.G.x10-2)>
E…Static pressure of indoor unit with
airflow amount Q <Pa(in.W.G.x10-2)>
Qa … Estimated amount of fresh air
intake without D
<CMM(CFM)>
8-4. PEA-A·AA
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
PEA-A12AA
PEA-A12AA
(External static pressure 0.020[in.WG](5Pa) 208/230V 60Hz
(External static pressure 0.060[in.WG](15Pa) 208/230V 60Hz
50
[0.20]
External static pressure [in.WG](Pa)
External static pressure [in.WG](Pa)
40
[0.16]
30
[0.12]
Limit
20
[0.08]
High
10
[0.04]
40
[0.16]
Limit
30
[0.12]
High
20
[0.08]
Middle
Rated point
10
[0.04]
Middle
Rated point
Low
Low
0
6
[212]
7
[247]
8
[282]
9
[318]
10
[353]
11
[388]
0
12
[424]
6
[212]
7
[247]
Airflow rate(m3/min)[CFM]
11
[388]
12
[424]
(External static pressure 0.200[in.WG](50Pa) 208/230V 60Hz
80
[0.32]
80
[0.32]
70
[0.28]
70
[0.28]
60
[0.24]
External static pressure [in.WG](Pa)
External static pressure [in.WG](Pa)
10
[353]
PEA-A12AA
(External static pressure 0.140[in.WG](35Pa) 208/230V 60Hz
Limit
50
[0.20]
40
[0.16]
Rated point
30
[0.12]
High
Middle
20
[0.08]
Low
Limit
60
[0.24]
50
[0.20]
Rated point
High
40
[0.16]
Middle
30
[0.12]
20
[0.08]
Low
10
[0.04]
0
6
[212]
9
[318]
Airflow rate(m3/min)[CFM]
PEA-A12AA
10
[0.04]
8
[282]
0
7
[247]
8
9
10
[282]
[318]
[353]
3
Airflow rate(m /min)[CFM]
11
[388]
12
[424]
6
[212]
7
[247]
8
[282]
9
[318]
3
10
[353]
Airflow rate(m /min)[CFM]
43
11
[388]
12
[424]
PEA-A18AA
PEA-A18AA
(External static pressure 0.020[in.WG](5Pa) 208/230V 60Hz
(External static pressure 0.060[in.WG](15Pa) 208/230V 60Hz
50
[0.20]
40
[0.16]
Limit
External static pressure [in.WG](Pa)
External static pressure [in.WG](Pa)
Limit
30
[0.12]
20
[0.08]
High
Middle
10
[0.04]
High
30
[0.12]
Middle
20
[0.08]
Low
Rated point
10
[0.04]
Low
Rated point
0
9
[318]
40
[0.16]
0
10
11
[353] [388]
12
[424]
13
14
15
16
17
18
19
[459] [494] [530] [565] [600] [636] [671]
9
[318]
10
11
[353] [388]
3
Airflow rate(m /min)[CFM]
PEA-A18AA
PEA-A18AA
(External static pressure 0.140[in.WG](35Pa) 208/230V 60Hz
(External static pressure 0.200[in.WG](50Pa) 208/230V 60Hz
80
[0.32]
80
[0.32]
Limit
60
[0.24]
High
50
[0.20]
40
[0.16]
Middle
Rated point
30
[0.12]
Low
20
[0.08]
Limit
70
[0.28]
External static pressure [in.WG](Pa)
External static pressure [in.WG](Pa)
70
[0.28]
High
60
[0.24]
50
[0.20]
Middle
40
[0.16]
Rated point
30
[0.12]
Low
20
[0.08]
10
[0.04]
10
[0.04]
0
9
[318]
12
13
14
15
16
17
18
19
[424] [459] [494] [530] [565] [600] [636] [671]
3
Airflow rate(m /min)[CFM]
0
10
11
[353] [388]
12
13
14
15
16
17
18
19
[424] [459] [494] [530] [565] [600] [636] [671]
Airflow rate(m3/min)[CFM]
9
[318]
44
10
11
[353] [388]
12
13
14
15
16
17
18
19
[424] [459] [494] [530] [565] [600] [636] [671]
Airflow rate(m3/min)[CFM]
9
NOISE CRITERION CURVES
PLA-A12BA
NOTCH SPL(dB)
High
31
Medium1
29
Medium2
28
Low
27
LINE
PLA-A18BA
90
bar)
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
70
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
250
500
1000
2000
4000
10
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
BAND CENTER FREQUENCIES, Hz
PLA-A24BA
NOTCH SPL(dB)
High
32
Medium1
31
Medium2
29
Low
28
LINE
500
PLA-A30BA
bar)
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
70
10
250
1000
2000
4000
8000
NOTCH SPL(dB)
High
34
Medium1
32
Medium2
30
Low
28
LINE
90
80
20
NC-20
BAND CENTER FREQUENCIES, Hz
90
bar)
LINE
90
80
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
NOTCH SPL(dB)
High
32
Medium1
31
Medium2
29
Low
28
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
45
4000
8000
PLA-A36BA
NOTCH SPL(dB)
High
40
Medium1
37
Medium2
34
Low
32
LINE
PLA-A42BA
bar)
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
LINE
90
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
bar)
90
NOTCH SPL(dB)
High
41
Medium1
39
Medium2
36
Low
34
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
UNIT
CEILING
5ft
MICROPHONE
46
4000
8000
PKA-A12HA
PKA-A18HA
PKA-A12HAL
PKA-A18HAL
NOTCH SPL(dB)
High
43
36
Low
LINE
PKA-A24KA
PKA-A30KA
PKA-A24KAL
PKA-A30KAL
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 μbar)
70
80
70
125
250
500
1000
2000
4000
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
63
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)
High
49
Low
43
PKA-A36KA
PKA-A36KAL
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 μbar)
80
10
LINE
90
90
20
NOTCH SPL(dB)
High
45
Low
39
UNIT
WALL
3.3ft
3.3ft
MICROPHONE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
47
125
250
500
1000
2000
4000
8000
NOTCH SPL(dB)
High
40
Medium1
37
Medium2
35
Low
33
PCA-A30KA
LINE
90
90
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
PCA-A24KA
63
125
70
500
1000
2000
4000
50
NC-50
40
NC-40
30
NC-30
10
8000
NC-70
NC-60
20
250
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
90
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
1000
2000
2000
4000
8000
4000
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
ceiling
3.3ft
unit
about 4.62ft
MICROPHONE
48
LINE
NC-60
10
8000
NOTCH SPL(dB)
High
45
Medium1
43
Medium2
41
Low
39
NC-70
BAND CENTER FREQUENCIES, Hz
3.3ft
1000
60
20
500
500
70
NC-20
250
250
PCA-A42KA
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
NOTCH SPL(dB)
High
43
Medium1
41
Medium2
39
Low
37
90
20
NC-20
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
PCA-A36KA
LINE
60
NC-20
10
NOTCH SPL(dB)
High
41
Medium1
39
Medium2
37
Low
35
4000
8000
<60Hz>
PEA-A12AA
NOTCH SPL(dB)
High
33
Middle
28
Low
23
External static pressure :
0.020[in.WG](5Pa)
LINE
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
20
10
8000
63
NOTCH SPL(dB)
High
34
Middle
29
Low
24
External static pressure :
0.140[in.WG](35Pa)
LINE
1000
2000
4000
8000
<60Hz>
NOTCH SPL(dB)
High
35
Middle
31
Low
25
External static pressure :
0.200[in.WG](50Pa)
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
500
PEA-A12AA
90
10
250
BAND CENTER FREQUENCIES, Hz
<60Hz>
PEA-A12AA
NC-20
125
BAND CENTER FREQUENCIES, Hz
20
LINE
90
80
10
NOTCH SPL(dB)
High
33
Middle
28
Low
23
External static pressure :
0.060[in.WG](15Pa)
90
20
<60Hz>
PEA-A12AA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
20
10
8000
63
BAND CENTER FREQUENCIES, Hz
NC-20
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level
can be higher by about 2 dB than the displayed level during cooling and heating operation.
Aux. duct
test unit
3.3ft
5ft
6.6ft
Measurement location
49
<60Hz>
PEA-A18AA
NOTCH SPL(dB)
High
37
Middle
33
Low
29
External static pressure :
0.020[in.WG](5Pa)
LINE
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)
High
39
Middle
35
Low
31
External static pressure :
0.140[in.WG](35Pa)
LINE
500
1000
2000
4000
8000
<60Hz>
NOTCH SPL(dB)
High
39
Middle
36
Low
32
External static pressure :
0.200[in.WG](50Pa)
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
250
PEA-A18AA
90
10
NC-20
BAND CENTER FREQUENCIES, Hz
<60Hz>
PEA-A18AA
20
LINE
90
80
10
NOTCH SPL(dB)
High
38
Middle
34
Low
30
External static pressure :
0.060[in.WG](15Pa)
90
20
<60Hz>
PEA-A18AA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level
can be higher by about 2 dB than the displayed level during cooling and heating operation.
50
MICROPHONE
3.3ft
UNIT
5ft
GROUND
PUY-A12NHA3 (-BS)
PUY-A18NHA3 (-BS)
PUZ-A18NHA3 (-BS)
MODE SPL(dB)
COOLING
46
HEATING
47
PUY-A24/30/36NHA3(-BS)
PUZ-A24/30/36NHA3(-BS)
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
MODE SPL(dB)
COOLING
51
HEATING
55
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
PUY-A42NHA3(-BS)
PUZ-A42NHA3(-BS)
LINE
90
90
20
MODE SPL(dB)
COOLING
48
HEATING
50
8000
BAND CENTER FREQUENCIES, Hz
51
8000
10
OPTIONAL PARTS
10-1. INDOOR UNIT
Part Name
Model Name
Remote sensor (extensible)
PAC-SE41TS-E
PAC-88HA-E (1pc.)
PAC-725AD (10pcs.)
PAC-SE55RA-E
PAC-SE57RA-E
PAC-SE56RA-E
PAC-SE59RA-E
PAC-SH55HR-E
PAC-SG95HR-E
PAC-SH98HR-E
PLP-42BAMD
PLP-40BAU
PAC-SH53TM-E
PAC-SH65OF-E
Connector for CN51
(output for remote display + pulse12V input)
Connector for CN32 (remote ON/OFF)
Connector for CN30 (LLC)
Connector for CN24 (Back up heating)
Connector for CN152 (Back up heating)
Power supply terminal kit
Decoration panel with wired remote controller
Decoration panel
Multi-function casement
Flange for fresh air intake
High-efficiency filter element
(PAC-SH53TM-E is needed.)
i-see sensor corner panel
Wireless signal receiver
Wireless remote controller kit
Space panel
Air outlet shutter plate
High efficiency filter
Drain lift up mechanism
i-see Sensor
Wireless remote controller kit
with i-see Sensor
Wireless remote controller kit
Wireless remote controller
PAC-SH59KF-E
PAC-SA1ME-E
PAR-SA9FA-E
PAR-SW96U-E
PAC-SH48AS-E
PAC-SH51SP-E
PAC-SH89KF-E
PAC-SH90KF-E
PAC-SH84DM-E
PAC-SH91MK-E
PAR-SA92MW-E
Applicable model
All models
PLA-A·BA, PKA-A·HA(L)/KA(L), PCA-A·KA
PLA-A·BA, PCA-A·KA, PEA-A·AA
PKA-A·HA(L)/KA(L)
PLA-A·BA
PKA-A·HA(L)/KA(L)
PCA-A·KA
PLA-A·BA
PCA-A24/30KA
PCA-A36/42KA
PCA-A·KA
PAR-SL93B-E
PAR-FL32MA-E
PEA-A·AA
Part Name
Model Name
Applicable model
M-NET adapter
A-control service tool
Drain socket
PAC-SF80MA-E
PAC-SK52ST
PAC-SG61DS-E
PAC-SG58SG-E
PAC-SG59SG-E
PAC-SG56AG-E
PAC-SH63AG-E
PAC-SG63DP-E
PAC-SG64DP-E
MSDD-50SR-E
10-2. OUTDOOR UNIT
Air outlet guide
(A42 needs 2 pieces.)
Air protect guide
(A42 needs 2 pieces.)
Drain pan
Distribution pipe for twin use
All models
A12,18
A24-42
A12,18
A24-42
A12,18
A24-42
A24,36
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Mar. 2009 No.OCS14 PDF6
Made in Japan
New publication, effective Mar. 2009
Specifications subject to change without notice