SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS November 2008 TECHNICAL DATA BOOK <Indoor unit> [Model names] No. OCS12 REVISED EDITION-A HYPER HEATING INVERTER PLA-A·BA PKA-A·GA PKA-A·GAL PKA-A·FA PKA-A·FAL Revision : • PUZ-HA30NHA is added in REVISED EDITION-A. • Some descriptions have been modified. • Please void OCS12. <Outdoor unit> [Model name] PUZ-HA30NHA PUZ-HA36NHA CONTENTS 1. REFERENCE SERVICE MANUAL ············································· 2 2. SPECIFICATIONS ······································································ 3 3. OUTLINES AND DIMENSIONS ················································· 4 4. WIRING DIAGRAM····································································· 9 5. REFRIGERANT SYSTEM DIAGRAM ······································ 13 6. PERFORMANCE CURVES ······················································ 14 7. CORRECTION FACTORS ························································ 16 8. AIR FLOW DATA ······································································ 18 9. NOISE CRITERION CURVES ·················································· 24 10. OPTIONAL PARTS ···································································· 27 1 REFERENCE SERVICE MANUAL For information on service, please refer to the service manual as follows. 1-1. INDOOR UNIT Model name Service Ref. PLA-A18/30/36BA PLA-A18BA Service Manual No. PLA-A18BA1 OCH420 OCB420 PLA-A30BA1 PLA-A36BA PLA-A36BA1 PKA-A18GA PKA-A18GAL PKA-A18GA/GA1/GA2 PKA-A18GAL/GAL1/GAL2 PKA-A30/36FA PKA-A30/36FAL PKA-A36FA/FA1/FA2 PKA-A36FAL/FAL1/FAL2 OC369 PKA-A30FA2 PKA-A30FAL2 1-2. OUTDOOR UNIT Model name Service Ref. PUZ-HA30/36NHA PUZ-HA30/36NHA 2 Service Manual No. OCH426 OCB426 2 SPECIFICATIONS Model name Cooling *1 Heating *1 Heating at 17°F(-8.3°C) *2 Heating at 5°F(-15°C) *3 Power supply Voltage Indoor unit Indoor unit Outdoor unit Max. Capacity Rated Capacity Min. Capacity Total Input EER SEER Moisture Removal SHF Max. Capacity Rated Capacity Min. Capacity Total Input COP HSPF(4/5) Capacity Total Input COP Capacity Total Input COP Phase, Cycle, Voltage Breaker size Indoor - Outdoor S1 - S2 Indoor - Outdoor S2 - S3 Indoor - Remote Controller MCA MOCP Fan Motor Fan Motor Output Airflow (Lo-M2-M1-Hi) DRY Airflow (Lo-M2-M1-Hi) WET Airflow (Lo-M2-M1-Hi) DRY Airflow (Lo-M2-M1-Hi) WET External pressure Sound level (Lo-M2-M1-Hi) External finish (Grille) Dimension Unit (Grille) Weight Unit(Grille) Weight Unit(Grille) Field drain pipe size Remote Controller Outdoor unit MCA MOCP Fan Motor Fan Motor Output Compressor Air flow Refrigerant Control Defrost Method Sound level at cooling Sound level at heating External finish Dimension Refrigerant Refrigerant pipe size Refrigerant pipe length Weight Type Charge Oil Gas side O.D. Liquid side O.D. Height difference Length Refrigerant Piping Connection Method BTU/h BTU/h BTU/h W BTU/h/W BTU/h/W Pints/h BTU/h BTU/h BTU/h W W/W BTU/h/W BTU/h W W/W BTU/h W W/W A A A F.L.A. W CMM CMM CFM CFM Pa dB(A) W : mm[inch] D : mm[inch] H : mm[inch] kg lbs mm[inch] A A F.L.A. W Type R.L.A. L.R.A. CMM[CFM] dB(A) dB(A) W : mm[inch] D : mm[inch] H : mm[inch] kg[lbs] kg[lbs, oz] L[oz] mm[inch] mm[inch] PLA-A36BA PLA-A30BA PUZ-HA36NHA PUZ-HA30NHA 36,000 30,000 36,000 30,000 18,000 18,000 3,120 2,450 11.5 12.2 16.0 15.6 6.8 7.2 0.79 0.73 40,000 34,000 38,000 32,000 18,000 18,000 3,230 3,440 3.45 2.73 9.4 / 7.3 8.8 / 7.0 38,000 32,000 5,720 5,300 2.10 1.64 38,000 32,000 5,860 6,630 1.41 1.90 1phase, 60Hz, 208/230V 30 AC208/230V DC24V DC12V 2 1 15 1.00 0.51 120 50 20-23-26-30 14-16-18-21 19-22-25-29 13-15-17-20 710-810-920-1060 490-570-640-740 460-530-600-710 670-770-880-1030 0 28-30-32-34 32-34-37-40 White Munsell 6.4Y 8.9/0.4 840(950) [33-1/16(37-3/8)] 840(950) [33-1/16(37-3/8)] 258(35) [10-3/16(1-3/8)] 298(35) [11-3/4(1-3/8)] 23(6) 25(6) 55(13) O.D. 32 [1-1/4] Attached in Grille 28 40 0.4 + 0.4 60 + 60 ANB33FJEMT ANB33FJCMT 18 27.5 100[3,530] Electronic Expansion Valve Reverse Cycle 52 53 Ivory Munsell 3Y 7.8/1.1 950 [37-3/8] 330 + 30 [13 + 1-3/16] 1,350 [53-1/8] 121 [267] R410A 5.5 [12 lbs] 1.4(FV50S) [45] 15.88 [5/8] 9.52 [3/8] Max.30m [Max.100ft] Max.75m [Max.245ft] Not supplied Flared NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) *2.Rating conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) *3.Rating conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Operating range PKA-A36FA(L) PKA-A30FA(L) PUZ-HA36NHA PUZ-HA30NHA 34,200 30,000 34,200 30,000 18,000 18,000 2,950 2,730 11.6 11.0 16.0 14.5 7.1 7.9 0.77 0.70 40,000 34,000 38,000 32,000 18,000 18,000 3,100 3,460 3.59 2.71 9.4 / 7.3 8.9 / 7.2 38,000 32,000 5,300 5,600 2.10 1.67 38,000 32,000 5,860 6,370 1.47 1.90 1phase, 60Hz, 208/230V 30 AC208/230V DC24V DC12V : Wired type 1 15 0.43 0.52 45 70 15-20 (Lo-Hi) 22-28 (Lo-Hi) 14-18 (Lo-Hi) 20-25 (Lo-Hi) 530-705 (Lo-Hi) 780-990 (Lo-Hi) 480-635 (Lo-Hi) 700-890 (Lo-Hi) 0 39-45 (Lo-Hi) 46-49 (Lo-Hi) White Munsell 3.4Y 7.7/0.8 1400 [55-1/8] 1680 [66-1/8] 235 [9-1/4] 340 [13-3/8] 24 28 53 62 I.D. 20 [13/16] Attached in Indoor unit 28 40 0.4 + 0.4 60 + 60 ANB33FJCMT ANB33FJEMT 18 27.5 100[3,530] Electronic Expansion Valve Reverse Cycle 52 53 Ivory Munsell 3Y 7.8/1.1 950 [37-3/8] 330 + 30 [13 + 1-3/16] 1,350 [53-1/8] 121 [267] R410A 5.5 [12 lbs] 1.4(FV50S) [45] 15.88 [5/8] 9.52 [3/8] Max.30m [Max.100ft] Max.75m [Max.245ft] Not supplied Flared Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F) Outdoor : D.B. -15°C(5°F), W.B. -15°C(5°F) Indoor intake air temperature Outdoor intake air temperature Maximum D.B. 32°C(90°F), W.B. 23°C(73°F) D.B. 46°C(115°F) Minimum D.B. 19°C(66°F), W.B. 15°C(59°F) D.B. -18°C(0°F)* Maximum D.B. 28°C(83°F) D.B. 21.1°C(70°F), W.B. 15°C(59°F) Heating Minimum D.B. 17°C(63°F) D.B. -25°C(-13°F), W.B. -25°C(-13°F) * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5°C(23°F)DB.) Cooling 3 OUTLINES AND DIMENSIONS INDOOR UNIT PLA-A18BA PLA-A30BA PLA-A36BA Ceiling hole 33-27/32 to 35-13/16(860~910) 23-1/2 (597) Air intake hole 1-25/32 (20~45) Connected the attached flexible pipe or socket. 6-9/16(167) 3-15/16 (100) 5-1/8 (130) Burring hole Burring hole 3-:1/8(3-:2.8) (:150) Burring hole pitch :4-29/32(:125) 120° 6-7/32 120° Keep 25/64(10)to 19/32(15) between unit ceiling and ceiling slab. + Cut out hole :3-15/16(:100) ++ (35) 1-3/8 ) ( 158) A 7-15/32 ( Ceiling In case of standard grille In case of wireless remote controller Emergency operation switch<Cooling> Auto vane (Air outlet) Emergency operation switch<Heating> Receiver 23-1/2 (597) Air intake hole Air outlet hole 19-11/16 (500) M 14-:1/8 (14-:2.8) (350) Detail drawing of fresh air intake hole Drain hole Drain pump clean hole and Drain emergency drainage hole M 13-25/32 (:175) :6-7/8 Burring hole pitch +3/16 0 (17+5 0 ) Ceiling Grille 11/16 Suspension bolt lower edge 37-3/8 (950) Branch duct hole + (50~70) + 1-15/16~2-3/4 5-1/2 + + (140) + (170) 6-11/16 2 (190) (377) 14-27/32 Ceiling hole 25/32 to 25/32 Drain pipe connected to VP-25 4-1/8 (105) 11-3/16 + + 6-9/64 (156) (284) 2-3/8 Cut out hole to 1-25/32 (20~45) (5/16) C D (60) 1 3-17/32 (90) Cut out hole (160) 33-1/16 (840) 3-15/16 (100) 3-15/16 (100) 3-17/32 (90) :5-29/32 6-5/16 7-3/8 (187.5) Suspension bolt M10 or W3/8 Detail connecting of branch duct(Both aspects) (7.5) For wiring replacement kit terminal block 24-13/32 (620) 15/16 (24) 6-5/16 (160) Suspension bolt pitch +35 23-13/16 -3/16 +1-3/8 (605 -5 ) Indoor unit/Outdoor unit connecting terminal block 3-17/32 (90) 5-29/32(150) 33-1/16(840) For MA-Remote controller terminal block Branch duct hole (7.5) (5/16) (160) B 6-5/16 25/32 to 1-25/32(20~45) 31-7/8(810) Suspension bolt pitch (160) 6-5/16 Fresh air intake hole 33-27/32 to 35-13/16 (860~910) 25/32 to 1-25/32(20~45) Unit : inch (mm) 6-3/32 (155) 3 Operation lamp DEFROST/STAND BY lamp (83) M M (36) Vane motor 1-27/64 3-17/64 Air intake grille 19-11/16 (500) Corner pocket Air outlet hole 37-3/8 (950) 1-27/64 3-17/64 (83) Indoor unit Ceiling Grille Min.94-1/2(2400) from floor Min.19-11/16(500) Entire periphery Floor (36) Note1. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE). Drain pump is included. Max. lifting height is 70-7/18(850mm) from the ceiling. 2. As for suspension bolt, please use M10 or W3/8. (Procured at local site) 3. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection. 4. The height of the indoor unit is able to be adjusted with the grille attached. 5. For the installation of the optional high efficiency filter or optional multi-functional casement. 1) Add 5-5/16(135mm) to the dimensions + marked on the figure. 2) The optional high efficiency filter becomes optional multi-functional casement and concomitant use. 6. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.) 7. As for necessary installation/service space, please refer to the left figure. 1 Models PLA-A12BA PLA-A18BA PLA-A24BA PLA-A30BA PLA-A36BA PLA-A42BA 2 Ref rigerant pipe ····: 6.35mm Flared connection ····1/4 Ref rigerant pipe ····: 12.7mm Flared connection ····1/2 Ref rigerant pipe ····: 9.52mm Flared connection ····3/8 Ref rigerant pipe ····: 15.88mm Flared connection ····5/8 4 A B C D 9-1/2 10-3/16 3-5/32 2-29/32 (241) (258) (80) (74) 11-1/16 11-3/4 3-11/32 3-1/32 (77) (281) (298) (85) PKA-A18GAL 8-27/32(225) 9-3/16(233) 9-21/32(245) 13/16(21) Less than 19/32(15) 7-25/32(198) Air intake 13-3/8(340) Air intake 13-3/8(340) 2-3/32(53) 9-21/32(245) Right side 2-3/8(60) 39(990) Lower side 2-3/8(60) Auto vane 9-1/4(235) 27-3/4(705) Air outlet 9-1/4(235) 6-5/16(160) 1-31/32(50) 15-3/4(400) Knockout hole for under piping Refrigerant piping.Drain pipe. Wiring hole 2-3/4(70) 1-3/8(35) 7-15/32(190) Service panel (Power supply access) 15-9/16(395) Front view (top open the grille) Wiring entrance holes Drain hose 22-7/8(581) 17-11/16(449) 27-9/16(700) (Flexible hose total length 31-1/2(800)) 11-1/32(280) 1-7/32(31) 1(25) 1-11/32(34) Filter grip 1-3/8(35) Field drain pipe size 13/ 16 (20=) I.D Liquid pipe Knockout hole for right piping Refrigerant pipe.Drain pipe. Wiring hole 1-9/16(40) 2-3/8(60) 3-1/8(79) 12-Louvers(manual) 2-3/4(70) 28-5/32(715) Air intake 3-5/32(80) 11-1/32(280) Air intake Front view 2-3/4(70) 13/16(21) Left side Knockout hole for left piping Refrigerant pipe.Drain pipe. Wiring hole. Unit : inch (mm) 3-1/8(80) PKA-A18GA 3/16(5) 1-5/16(33) 2-1/8(54) 3-3/8(86) 6-1/32(153) (Right side piping installation) Gas pipe Service space required around indoor unit 7-3/32(180) or more 1-13/16(30) or more Right side 18 1/4 Gas pipe 1/2 Sleeve *1 Through hole ø2-15/16(ø75) ø2-15/16~ø3-5/32 (ø75~ø80) Less than 5-1/8(130) 5-29/32(150) or more 1-31/32(50) or more MODEL Liquid pipe *1 Sleeves are available on the market. *2 This size shows the lower end of through hole. (Necessary clearance for Unit installation) Details of installation plate 19-1/2(495) 13-19/32(345) 10-1/4(260) 12-19/32(320) 8-1/16(205) 5-29/32(150) 3-3/4(95) 5-5/16(135) 2-15/16(75) 1-1/4(32) 25/32(20) 0 1-3/8(35) 0 1-3/8(35) 2-5/32(55) 3-5/32(80) 5-1/8(130) 7-15/32(190) 9-1/16(230) 10-23/32(272) 12-7/32(310) R2-1/1 6(R52 .5) 5 16-23/32(425) Knockout hole for right-rear piping 6-11/16(170) 7-15/32(190) 0 9-1/16(230) 8-9/32(210) 12-11/16(322)+1 5) 2. R5 6( /1 -1 R2 Knockout hole for left-rear piping 16-17/32(420) 5) 2. R5 6( /1 -1 R2 Left-rear piping hole 7-15/32(190) 9-21/32(245) 49-:3/16(:5)holes for tapping screw Unit center R2 -1/ 16 (R 52 .5) 11-13/16(300) 14-3/16(360) 15-15/16(405) 14-:9/16(:14)holes for bolts 19-1/2(495) Installation plate balance point hole Right-rear piping hole PKA-A30FAL Unit : inch (mm) 2-15/32(62.5) 9-1/4(235) 1-25/32(45) 9-1/4(235) 1-25/32(45) Front view 9-1/4(235) 1/2(13) Top side 9-1/4(235) 1-25/32(45) Right side 55-1/8(1400) 9-1/4(235) 42-29/32(1090) Air intake 13-3/8(340) 7-3/4(197) Left side C Knockout hole for right piping Terminal block Knockout hole for left piping Less than 19/32(15) 1-5/16(34) 1-7/16(36) 1-21/32(42) 2-9/32(58) 2 Drain hose Field drain pipe size Drain hose 13/16 (20mm) I.D Wiring entrance holes 31/32(25) 15/16(24) 1 2-5/32(55) 4-23/32(120) 7-7/32(183) 43-11/16(1110) Drain hose Drain hose for left-hand side piping Louvers(Manual) Auto vanes 44-3/32(1120) 9-7/16(240) 21-23/32(552) Air outlet 21-23/32(552) Air outlet B Knockout hole for under-piping Refrigerant pipe /Drain pipe Knockout hole for wiring 1-9/16(39) 1-15/32(37) 2-29/32(74) 3-27/32(98) 1-3/16(30) 1-15/32(37) 1-1/4(32) 3/8 2 Gas pipe 5/8 Through hole ø3-17/32~ø3-15/16 (ø90~ø100) *1 Sleeves are available on the market. Less than 9-27/32(250) C 1-15/32(37) 2-9/16(65) B 1-3/16(30) 24/30 2-29/32(74) Details of installation plate Drainage range on left hand side Wall fixture Unit center 38-31/32(990) 17-29/32(455) 13/32*3-19/32=(35-13/16) (10*91=(910)) 35-7/16(900) 23/32(18) 3-19/32(91) 23/32(18) Drainage range on right-hand side 9-21/32(245) 11-7/32(285) 3/4(19) 66-ø1/4(ø6) holes for tapping screws 32-ø15/32(ø12) holes for bolts 8-27/32(225) 9-7/16(240) 7-3/32(180) 11-1/32(280) 12-ø1/4(ø6) holes for tapping screws 6 12-3/8(314) 24-1/32(610) 3-17/32(90) Range for left rear piping hole 2-3/8(60) 9-27/32(250) or more 1-17/32(39) 3-15/16(100) 1-31/32(50) or more 9-27/32(250) or more Air outlet MODEL 1 Liquid pipe Sleeve *1 ø3-17/32 (ø90) 1-3/16(30) or more Air intake 5/32(4) Service space required around indoor unit 3-15/16(100) 1-17/32(39) 5/32(4) 4-7/32(107) 4-3/8(111) Lower side Under panel(Removable at left-hand side piping) A Bolt 7-1/4(184) 13/32(10) 1-3/16(30) 1-3/16(30) 3-1/8(80) 1-5/32(29) 11-1/32(280) A 1-3/16(30) PKA-A30FA Rear piping hole PKA-A36FAL Unit : inch (mm) 2-15/32(62.5) PKA-A36FA 9-1/4(235) 1-25/32(45) 9-1/4(235) 1-25/32(45) 9-1/4(235) 1-25/32(45) 9-1/4(235) 1-25/32(45) 1/2(13) Top side 9-1/4(235) Knockout hole for right piping Front view Left side Right side 9-1/4(235) 13-3/8(340) 7-3/4(197) 66-1/8(1680) 53-15/16(1370) Air intake A Knockout hole for left piping C Terminal block Less than 9/16(15) 1-5/16(34) 1-7/16(36) 1-21/32(42) 2-9/32(58) 2 Field drain pipe size 13/16 (20mm) I.D Drain hose 43-11/16(1110) Drain hose 55-1/8(1400) 27-5/16(694) Air outlet 27-5/16(694) Air outlet 9-7/16(240) Louvers(Manual) B Under panel(Removable at left-hand side piping) Auto vanes Knockout hole for under-piping Refrigerant pipe /Drain pipe Service space required around indoor unit 1-17/32(39) 1-15/32(37) 3-27/32(98) 2-29/32(74) 5/8 Sleeve *1 ø3-17/32 (ø90) Through hole ø3-17/32~ø3-15/16 (ø90~ø100) *1 Sleeves are available on the market. Less than 5-29/32(150) C 1-3/16(30) Drainage range on left hand side 1-15/32(37) 2-29/32(74) Drainage range on right-hand side 23-7/16(595) 1/2*3-19/32=(46-9/16) (13*91=(1183)) 35-7/16(900) Wall fixture 84-ø1/4(ø6) holes for tapping screws 1-1/4(32) Unit center 50(1270) Unit out line 23/32(18) 23/32(18) 9-21/32(245) 11-7/32(285) 3/4(19) 3-19/32(91) 11-5/8(295) 8-27/32(225) 9-7/16(240) 7-3/32(180) 11-1/32(280) 41-ø15/32(ø12) holes for bolts 12-3/8(314) 29-17/32(750) 12-ø1/4(ø6) holes for tapping screws 3-9/16(90) Rear piping hole Range for left rear piping hole 7 2-3/8(60) 1-3/16(30) Gas pipe 1-3/16(30) 3-5/32(80) 11-1/32(280) B 1-15/32(37) 2-9/16(65) A Air outlet 36 3/8 1-17/32(39) 5/32(4) 5/32(4) 3-15/16(100) 1-17/32(39) Knockout hole for wiring 1-3/16(30) or more 1-31/32(50) or more 9-27/32(250) or more 3-15/16(100) 9-27/32(250) or more Air intake MODEL Liquid pipe 7-1/4(184) 13/32(10) 1-3/16(30) 1-5/32(29) Lower side 4-1/32(102) 4-3/8(111) 15/16(24) 1 2-5/32(55) 4-23/32(120) 7-7/32(183) Wiring entrance holes Drain hose for left-hand side piping 1-3/16(30) 31/32(25) Bolt Min. 150mm <5-29/32> Min. 10mm <3/8> Service space Min. 10mm<3/8> :92 8> <3-5/ 92<3-5/8> 65<2-9/16> Front piping hole (Knockout) 45<1-25/32> 55<2-3/16> 63 <2-1/2> 27<1-1/16> Front trunking hole 40<1-9/16> (Knockout) Conduit hole (2-:27<1-1/16>Knockout) Piping Knockout Hole Details 73<2-7/8> 23<29/32> Min. 500mm <19-11/16> 19<3/4> :92 <3-5/8 > 40<1-9/16> 92<3-5/8> 45<1-25/32> Conduit hole (2-:27<1-1/16>Knockout) 92<3-5/8> 65<2-9/16> : <3-5 92 /8> Rear piping hole (Knockout) 74<2-19/32> 40<1-9/16> 2-:22.2<7/8> Handle 1/2 Conduit attachment When installing the conduit. Set the attachment to the inner side of each panel. Handle Handle Side Air Intake Rear Air Intake Side Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. Rear trunking hole (Knockout) 40<1-9/16> Right trunking hole (Knockout) FOUNDATION <Foundation bolt height> Min. 30mm <1-3/16> Conduit hole (2-:27<1-1/16>Knockout) 55<2-3/16> 75 <2-31/32> Right piping hole (Knockout) Air intake Handle ····Refrigerant GAS pipe connction (FLARE):15.88<5/8> ····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8> *1 ····Indication of STOP VALVE connection location. Example of Notes Min. 1000mm <39-3/8> Min. 10mm <3/8> FREE 27<1-1/16> 92<3-5/8> 63<2-1/2> 73<2-7/8> 30<1-3/16> 220 <8-21/32> 66<2-5/8> 42<1-21/32> Earth terminal 950<37-13/32> Drain hole 5-:33<1-5/16> 71<2-13/16> 2 1 Handle Service panel Terminal Block Left···Power supply wiring Right····Indoor/Outdoor wiring 2-12%36 Oval hole (Foundation Bolt M10<W3/8>) 145 145 145 <5-23/32> <5-23/32> <5-23/32> 322<12-11/16> Air Discharge 175<6-7/8> 175<6-7/8> 600<23-5/8> 2-U Shaped notched hole (Foundation Bolt M10<W3/8>) Rear Air Intake Front piping cover Bottom piping hole (Knockout) Rear piping cover PUZ-HA36NHA 23<29/32> Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.) 55<2-3/16> 27<1-1/16> 1350<53-5/32> Min. 150mm <5-29/32> Min. 500mm <19-11/16> 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS * 1 443<17-7/16> 330<13> 30<1-3/16> 23<29/32> 45<1-25/32> Dimensions of space needed for service access are shown in the below diagram. 31<1-7/32> * 1 447<17-19/32> The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc. 73<2-7/8> 63<2-1/2> 23<29/32> 635<25> 371<14-19/32> 219<8-5/8> 417<16-13/32> 1 FREE SPACE (Around the unit) 2 SERVICE SPACE 71<2-13/16> 8 81<3-3/16> 56<2-7/32> 19<3/4> 370<14-9/16> 28<1-3/32> 53<2-3/32> 1076<42-3/8> PUZ-HA30NHA Unit : mm<inch> 4 WIRING DIAGRAM PLA-A18BA PLA-A30BA PLA-A36BA [LEGEND] SYMBOL I.B CN2L CN24 CN30 CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 ZNR01, 02 DP FS NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR<BACK-UP HEATING> CONNECTOR<LLC> CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1. SWITCH (CAPACITY CODE) +See table 2. CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) VARISTOR DRAIN-UP MACHINE DRAIN FLOAT SWITCH SYMBOL MF MV TB4 TB5, TB6 NAME FAN MOTOR VANE MOTOR TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (32˚F/15kΩ, 77˚F/5.4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (32˚F/15kΩ, 77˚F/5.4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (32˚F/15kΩ, 77˚F/5.4kΩ DETECT) TH1 TH2 TH5 OPTION PART W.B BZ LED1 LED2 RU SW1 SW2 PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION: GREEN) LED (PREPARATION FOR HEATING: ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT/DOWN) EMERGENCY OPERATION (COOL/UP) TB5 2 1 TRANSMISSION WIRES DC12V 2 1 TB6 Refer to tables 1 and 2. R.B I.B VANE CNV(WHT) 20 18 16 14 12 10 8 6 4 2 SW1 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 Pair No. 5 CN2L LED3 LED2 LED1 OUTDOOR 1 3 5 CN01 CN32 (WHT) 1 3 CN51(WHT) CN24(YLW) CN41(WHT) 2 1 4 SWE (BLU) 12 REMOCON CN22 1 DSA INDOOR/OUTDOOR COMMUNICATION CN3C 2 1 1 (BLK) 1 3 FUSE ZNR02 U DC280V U ZNR01 RECTIFICATION (BLU) ON OFF 1 3 CN3G (BLK) 1 WIRELESS CN90 (WHT) 9 I-SEE SENSOR CN4Y 1 (WHT) 4 I-SEE SENSOR MOTOR CN6Y 1 (RED) 6 CNAC (WHT) 3 1 FLOAT SW LIQUID/PIPE INTAKE CN4F CN44 CN20 CN30 (WHT) (WHT) (RED) (GRN) 1 4 1 4 1 2 1 3 7 FAN CNMF (WHT) 4 X1 1 3 1 D.U.M CNP (BLU) 5 5 5 5 M M M M MV MV MV MV GRILLE CNB BZ LED2 SW1 LED1 SW2 ON OFF I-SEE SENSOR FS M t˚ t˚ TH2 TH5 t˚ TH1 MS 3~ MF TB4 YLW S1 ORN S2 S3 +1 TO OUTDOOR UNIT ORN BRN M 1~ DP +Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor.) MT I-SEE SENSOR CORNER PANEL (OPTIONAL PART) RU W.B <Table 1>SW1(MODEL SELECTION) SW1 Service 1 2 3 4 5 5 4 9 YLW ORN <Table 2>SW2(CAPACITY CODE) SW2 MODELS Service MODELS PLA-A12BA PLA-A18BA PLA-A24BA 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON PLA-A30BA OFF ON PLA-A36BA OFF ON PLA-A42BA OFF Service 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON OFF ON OFF ON OFF Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal block. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. +1. Use copper supply wires. [Self-diagnosis] 1. For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc. 2. For the wired remote control: When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis, and Check Codes generated in the past appear on the display. 9 PKA-A18GA SYMBOL P.B I.B FUSE ZNR CN2L CN24 CN30 CN32 CN41 CN51 SW1 SW2 SWE X4 BCR LED1 PKA-A18GAL SYMBOL NAME LED2 POWER SUPPLY <R.B> LED3 TRANSMISSION <INDOOR-OUTDOOR> C CAPACITOR <FAN MOTOR> FAN MOTOR MF MV VANE MOTOR TB4 TERMINAL BLOCK <INDOOR/OUTDOOR CONNECTING LINE> TB5, TB6 TERMINAL BLOCK <REMOTE CONTROLLER TRANSMISSION LINE > TH1 ROOM TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> TH2 PIPE TEMP.THERMISTOR/LIQUID <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> TH5 COND./EVA.TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> R.B WIRED REMOTE CONTROLLER BOARD NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (6.3A/250V) VARISTOR CONNECTOR <LOSSNAY> CONNECTOR <BACK-UP HEATING> CONNECTOR <LLC> CONNECTOR <REMOTE SWITCH> CONNECTOR <HA TERMINAL-A> CONNECTOR <CENTRALLY CONTROL> SWITCH <MODEL SELECTION>+See Table 1. SWITCH <CAPACITY CODE>+See Table 2. SWITCH <EMERGENCY OPERATION> RELAY <FAN MOTOR> FAN CONTROL ELEMENT POWER SUPPLY <I.B> P.B CNSK (RED) 1 DC13.1V 3 Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. CN2S (WHT) 1 2 SYMBOL W.B RU BZ LED1 LED2 SW1 SW2 NAME WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED<RUN INDICATOR > LED<HOT ADJUST> SWITCH<HEATING ON/OFF> SWITCH<COOLING ON/OFF> Table 1 SW1 Service board 1 2 3 4 5 ON OFF Table 2 MODELS PKAA12GA(L) YLW ORN TB4 MF M 1~ Service board 1 2 3 4 5 1 2 3 4 5 PKAON OFF A18GA(L) ON OFF +1 TO OUTDOOR UNIT S1 S2 S3 YLW ORN BRN SW2 Service board MODELS POWER POWER CNDK CND 3 1 (RED) (ORN) 1 3 FUSE FAN (WHT) 1 3 5 BCR X4 U ZNR LED3 LED2 LED1 6 1 3 2 1 POWER A-CONTROL CN3C CN2D (BLU) (WHT) CN2L(RED) 4 1 CN51(WHT) 2 1 CN32(WHT) SW2 SW1 CN24 (YLW) 2 1 1 1 INTAKE LIQUID PIPE REMOCON CN20 CN21 CN29 CN22 (RED) (WHT) (BLK) (BLU) 2 1 2 1 2 1 2 1 Refer to tables 1 and 2 for service PCB. 6 VANE CN6V (GRN) CN41(WHT) 5 SWE ON OFF BRN ORN BLK WHT YLW ORN RED WHT I.B RED WHT BLK 1 2 3 C 3 1 1 WIRELESS CN90 (WHT) CN30 (BLK) 3 1 9 M MV For A12/18GAL 9 9 BZ CNB RU RECEIVER LED1 LED2 SW2 SW1 W.B R.B t˚ t˚ t˚ TH1 TH2 TH5 1 TRANSMISSION WIRES DC12V 2 TB5 NOTES: 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. 2. Indoor and outdoor connecting wires have polarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring. 3. Symbols used in wiring diagram above are, : Connector, : Terminal (block). 4. This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. +1. Use copper supply wires. [Self-diagnosis] Please refer to technical manuals etc. 10 1 2 TB6 For A12/18GA PKA-A30FA PKA-A30FAL PKA-A36FA PKA-A36FAL [LEGEND] SYMBOL NAME LED2 POWER SUPPLY <R.B> LED3 TRANSMISSION <INDOOR-OUTDOOR> C CAPACITOR <FAN MOTOR> FAN MOTOR MF MV VANE MOTOR TB4 TERMINAL BLOCK <INDOOR/OUTDOOR CONNECTING LINE> TB5,TB6 TERMINAL BLOCK <REMOTE CONTROLLER TRANSMISSION LINE > TH1 ROOM TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> TH2 PIPE TEMP.THERMISTOR/LIQUID <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> TH5 COND./EVA.TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> R.B WIRED REMOTE CONTROLLER BOARD NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (6.3A/250V) VARISTOR CONNECTOR <LOSSNAY> CONNECTOR <BACK-UP HEATING> CONNECTOR <LLC> CONNECTOR <REMOTE SWITCH> CONNECTOR <HA TERMINAL-A> CONNECTOR <CENTRALLY CONTROL> SWITCH <MODEL SELECTION>+See Table 1. SWITCH <CAPACITY CODE>+See Table 2. SWITCH <EMERGENCY OPERATION> RELAY <FAN MOTOR> FAN CONTROL ELEMENT POWER SUPPLY <I.B> P.B I.B FUSE ZNR CN2L CN24 CN30 CN32 CN41 CN51 SW1 SW2 SWE X4 BCR LED1 P.B CNSK (RED) 1 CN2S (WHT) 1 DC13.1V 3 SYMBOL W.B RU BZ LED1 LED2 SW1 SW2 NAME WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED <RUN INDICATOR > LED <HOT ADJUST> SWITCH <HEATING ON/OFF> SWITCH <COOLING ON/OFF> Table 1 SW1 Service board 1 2 3 4 5 Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. 2 ON OFF Table 2 MODELS PKAA24FA(L) YLW ORN TB4 YLW ORN BRN MF M 1~ +1 TO OUTDOOR UNIT S1 S2 S3 SW2 Service board 1 2 3 4 5 ON OFF MODELS Service board PKAA30FA(L) 1 2 3 4 5 ON OFF MODELS Service board PKAA36FA(L) 1 2 3 4 5 ON OFF POWER POWER CND CNDK (RED) 1 3 (ORN) 1 3 FUSE FAN (WHT) 1 3 5 BCR X4 U ZNR LED3 LED2 LED1 SW2 SW1 CN24 (YLW) 2 1 6 1 3 2 1 POWER A-CONTROL CN3C CN2D (BLU) (WHT) CN2L(RED) 4 1 CN51(WHT) 2 1 CN32(WHT) 1 1 INTAKE LIQUID PIPE REMOCON CN20 CN21 CN29 CN22 (RED) (WHT) (BLK) (BLU) 2 1 2 1 2 1 2 1 6 VANE CN6V (GRN) CN41(WHT) 5 SWE ON OFF BRN ORN BLK WHT YLW ORN RED WHT I.B RED WHT BLK 1 2 3 C 3 WIRELESS CN90 (WHT) CN30 (BLK) 3 1 Refer to tables 1 and 2 for service PCB. 1 1 9 M MV For A24/30/36FAL 9 9 BZ CNB RU RECEIVER LED1 LED2 SW2 SW1 W.B R.B tº tº tº TH1 TH2 TH5 1 TRANSMISSION WIRES DC12V 2 TB5 1 2 TB6 For A24/30/36FA Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal block. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. 4. This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. +1. Use copper supply wires. [Self-diagnosis] Please refer to technical manuals etc. 11 PUZ-HA36NHA NAME Terminal Block<Power Supply, Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch Solenoid Valve (Bypass Valve) Thermistor <Outdoor Pipe> Thermistor <Discharge> Thermistor <Outdoor 2-Phase Pipe> Thermistor <Outdoor> Thermistor <Heatsink> Electronic Expansion Valve Reactor Active Filter Module Main Smoothing Capacitor Capacitor SYMBOL P.B. TABU/V/W TABS/T TABP1/P2/P TABN1/N2/N DS2, DS3 IPM N.F. LI/LO NI/NO EI, E2 52C C.B. SW1 NAME Power Circuit Board Connection Terminal <U/V/W-Phase> Connection Terminal <L/N-Phase> Connection Terminal <DC Voltage> Connection Terminal <DC Voltage> Diode Bridge Power Module Noise Filter Circuit Board Connection Terminal <L-Phase> Connection Terminal <N-Phase> Connection Terminal <Ground> 52C Relay Controller Circuit Board Switch <Forced Defrost, Defect History Record Reset, Refrigerant Address> Switch <Test Operation> Switch <Function Switch> SW4 SW5 SYMBOL SW6 SW7 SW8 SW9 SWP CN31 SS CNM CNMNT NAME Switch <Model Select> Switch <Function Setup> Switch <Function Setup> Switch Switch <Pump Down> Connector <Emergency Operation> Connector <Connection for Option> Connector <A-Control Service Inspection Kit> Connector <Connected to Optional M-NET Adapter Board> Connector CNVMNT <Connected to Optional M-NET Adapter Board> Connector CNDM < Connected for Option (Contact Input)> LED1, LED2 LED <Operation Inspection Indicators> Fuse < T6.3AL250V> F1~F4 X51,X52,X55 Relay When M-NET adapter is connected LEV-C 63L LEV-A LEV-B M M TH33 TH32 TH7 TH6 TH3 TH4 M 5 C. B. t° t° t° t° 12 1 2 1 1 1 63L (RED) 3 63H (YLW) 3 TRANS 2 1 3 1 6 LEV-B (RED) 1 CN2 (WHT) 1 F1 3 1 21S4 3 (GRN) F4 4 14 LEV-C (BLU) 6 1 2 3 1 SV2 3 (BLU) 21S4 1 SW12 LED4 2 1 M-NET SUBSTRATE CN2M (WHT) CND (WHT) 3 1 CN31 1 2 X52 2 3 1 5 CN52C (RED) 2 1 7 1 7 F3 CNAC (WHT) 3 CNM (WHT) 5 2 F2 1 CNVMNT CNMNT (WHT) (WHT) CN4 (WHT) CNDC 1 (PNK) CNS (WHT) 6 X55 MF2 1 MS 3~ CNF2 (WHT) LEV-A (WHT) SW1 SW6 4 SW1 LED3 +1 CN51 CNDM (WHT) (WHT) 1 SW4 SWP SW8 SW5 1 2 3 X51 1 TH33 TH32 TH7/6 TH3 TH4 (YLW) (BLK) (RED) (WHT) (WHT) 7 5 5 t° LED1 MS 3~ t° +1 CNF1 (WHT) LED2 7 MF1 1 SW11 CN5 (WHT) 1 LED2 5 3 SW9 SW7 63H LED1 [LEGEND] SYMBOL TB1 MC MF1, MF2 21S4 63H 63L SV TH3,TH32,TH33 TH4 TH6 TH7 TH8 LEV-A, LEV-B,LEV-C DCL ACTM CB CY1, CY2 LED5 PUZ-HA30NHA 3 1 3 A B S TB7 1 M-NET 5 SS (WHT) SV BLU WHT N. F. LO NO 2 52C 1 2 CN52C (BLK) P. B. 1 CNAF (WHT) CNDC (PNK) 2 6 1 TABN1 BLK 2 1 W BLK U L2 1 P N1 N2 BLK 6 RED L1 L2 GR ON OFF SW5-6 +2 36N ON OFF 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 ON OFF ON OFF S2 S3 CY1 CY2 TB1 INDOOR UNIT +1MODEL SELECT 30N U WHT Io ACTM SW6 S1 BRN RED L1 RED 4 ORN DCL GRN YLW MC MODEL NI BLU LI BLU MS 3~ CN5 (RED) 1 CNAC1 (WHT) WHT V TABN2 2 M-NET ADAPTER NAME Terminal Block <M-net connection> Connector <Transmission> Connector <Power Supply> Connector <M-NET communication> Switch <Status of communication> Switch <Address setting: 1s digit> Switch <Address setting: 10ths digit> LED <Power Supply: DC5V> LED <Connection to Outdoor Unit> LED <Transmission: Sending> LED <Transmission: Recelving> LED <Power Supply: DC12V> BLK E2 U 3 U SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 CNAC2 (RED) WHT RED 1 2 1 2 TABP WHT BLK WHT CB CN5 (RED) CN4 (WHT) TABN TABS 1 TABW 2 DS2 TABP1 RED RED TABU t° 2 7 1 CN3 2 (WHT) BLU 3 IPM WHT TABV BLK TH8 TABP2 CN2 (WHT) TABT 3 1 RED 7 DS3 RED 4 POWER SUPPLY ~/N 208/230V 60Hz +Use copper supply wires. 1 2 3 4 5 6 1 2 3 4 5 6 12 +2. SW5 -1 to 5: Function Switch EI 5 REFRIGERANT SYSTEM DIAGRAM 5-1. INDOOR UNIT PLA-A·BA PKA-A·GA PKA-A·GAL PKA-A·FA PKA-A·FAL Strainer(#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH5 (Cond./Eva. temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Distributor with strainer(#50) Thermistor TH2 Pipe temperature (Liquid) Thermistor TH1 (Room temperature) Strainer(#50) 5-2. OUTDOOR UNIT PUZ-HA30NHA PUZ-HA36NHA unit : mm (inch) Heat exchanger Refrigerant GAS pipe connection :15.88 (5/8) Thermistor TH6 (Outdoor 2-phase pipe) Solenoid valve (Four-way valve) Ball valve Strainer #50 Charge plug (High pressure) Charge plug (Low pressure) Muffler Low pressure switch 63L Thermistor TH3 (Outdoor pipe) High pressure switch 63H Thermistor TH32 (Outdoor pipe) Strainer #100 Strainer #100 Electronic expansion valve B Refrigerant LIQUID pipe connection :9.52 Strainer (3/8) #100 Stop valve (with service port) Thermistor TH7 (Outdoor) Distributor Thermistor TH33 (Outdoor pipe) Strainer #100 Thermistor TH4 (Discharge) Electronic expansion valve A Strainer #100 Compressor Power receiver Electronic expansion valve C Bypass valve Injection port Heat inter change circuit Replace filter Restrictor Strainer valve #100 Refrigerant flow in cooling Refrigerant flow in heating 13 6 PERFORMANCE CURVES FOR THE COMBINATION OF OUTDOOR UNIT PUZ-HA·NHA Cooling performance curve CAPACITY (RATIO) 1.4 1.2 INDOOR W.B. 72°F (22°C) 1.0 68°F (20°C) 64°F (18°C) 61°F (16°C) 0.8 INDOOR W.B. 72°F (22°C) 68°F (20°C) 64°F (18°C) 61°F (16°C) 1.2 TOTAL INPUT (RATIO) 1.0 0.8 0.6 0.4 23 30 (-5°C) (-1°C) 50 (10°C) 70 (21°C) 90 (32°C) 110 (43°C) OUTDOOR D.B.(°F) Note : This diagram shows the case where the operation frequency of a compressor is fixed. 14 Rated heating performance curve Rated heating capacity 1.40 60˚F (16˚C) 70˚F (21˚C) CAPACITY (RATIO) 1.20 80˚F (27˚C) 1.00 0.80 Indoor intake air dry-bulb temperature (˚F DB) 0.60 -15 -10 -5 0 5 -26 -23 -21 -18 -15 10 15 20 25 30 35 40 45 50 55 -12 -9 -7 -4 -1 2 4 7 10 13 (˚FWB) 16 (˚CWB) 60 Outdoor ambient temp. Heating input 2.00 INPUT (RATIO) 1.50 80˚F (27˚C) 70˚F (21˚C) 60˚F (16˚C) 1.00 Indoor intake air dry-bulb temperature (˚F DB) 0.50 -15 -10 -5 0 5 -26 -23 -21 -18 -15 10 15 20 25 30 35 40 45 50 55 60 -12 -9 -7 -4 -1 2 4 7 10 13 16 Outdoor ambient temp. 15 (˚FWB) (˚CWB) CORRECTION FACTORS 7 7-1. COOLING CAPACITY CORRECTION FACTORS Refrigerant piping length (one way) Outdoor unit 5m (16ft) PUZ-HA30NHA PUZ-HA36NHA 1.00 10m (33ft) 20m (70ft) 30m (100ft) 40m (130ft) 50m (165ft) 55m (180ft) 60m (195ft) 70m (230ft) 80m (260ft) 0.985 0.957 0.931 0.908 0.886 0.876 0.865 0.846 0.829 7-2. HEATING CAPACITY CORRECTION FACTORS Refrigerant piping length (one way) Outdoor unit 5m (16ft) PUZ-HA30NHA PUZ-HA36NHA 1.00 10m (33ft) 20m (70ft) 30m (100ft) 40m (130ft) 50m (165ft) 55m (180ft) 60m (195ft) 70m (230ft) 80m (260ft) 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955 7-3. CAPACITY CORRECTION Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m) Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft) 100 Heating HA30,36 Capacity ratio [%] 95 90 85 Cooling HA30,36 model 80 Cooling 75 Heating Note: The permitted pipe length is up to 80m<260ft>. 70 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 m <16> <33> <50> <70> <80> <100> <115> <130><150><165><180><195><215><230><245><260> <ft> Corrected pipe length [m] When gas pipe is one size larger than standard size, capacity can be obtained by referring to capacity curves of standard size. 16 7-4. ADDITION OF REFRIGERANT • Additional charging is not necessary if the pipe length does not exceed 30 m (100 ft). • If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the permitted pipe lengths in the chart below. * When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe extensions and indoor unit have been vacuumized. * When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant directly to the check valve. * After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit). • Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have a serious effect on operation performance. Model Max. pipe Max. height 30 m length difference 100 ft 0 oz 75 m 30 m HA30,36 0 kg 245 ft 100 ft Additional refrigerant charging amount 33 m 37 m 40 m 43 m 46 m 49 m 52 m 55 m 58 m 61 m 64 m 67 m 70 m 73 m 75 m 110 ft 120 ft 130 ft 140 ft 150 ft 160 ft 170 ft 180 ft 190 ft 200 ft 210 ft 220 ft 230 ft 240 ft 245 ft 6 oz 12 oz 18 oz 24 oz 30 oz 36 oz 42 oz 48 oz 54 oz 60 oz 66 oz 72 oz 78 oz 84 oz 86 oz 0.2 kg 0.4 kg 0.5 kg 0.7 kg 0.9 kg 1.0 kg 1.2 kg 1.4 kg 1.5 kg 1.7 kg 1.9 kg 2.0 kg 2.2 kg 2.3 kg 2.4 kg 17 8 AIR FLOW DATA 8-1. OUTLET AIR SPEED AND COVERAGE RANGE Airflow CFM Air speed ft/sec.(m/sec.) Coverage range ft (m) Airflow CFM Air speed ft/sec.(m/sec.) Coverage range ft (m) Airflow CFM Air speed ft/sec.(m/sec.) Coverage range ft (m) PLA-A18BA PLA-A30BA PLA-A36BA 640 10.5 (3.2) 15 (4.8) 740 12.1 (3.7) 18 (5.6) 1060 17.4 (5.3) 26 (8.0) PKA-A18GA PKA-A18GAL 425 17.4 (5.3) 33 (10) PKA-A30FA PKA-A30FAL 705 16.1 (4.9) 41 (12.4) PKA-A36FA PKA-A36FAL 990 17.7 (5.4) 50 (15.3) The air coverage range is the distance to which the 0.8 ft/sec. air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room. 18 8-2. PLA-A·BA 8-2-1 FRESH AIR INTAKE AND BRANCH DUCT 1. Branch duct hole and fresh air intake hole (Fig. 1) At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 5-5/16 to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. Unit : inch(mm) [Fig. 1] Fresh air intake hole diagram 3-:1/8(:2.8) burring hole 120 Indoor unit 6-7/32 (*158) Branch duct hole :4-29/32(:125) burring hole pitch 120 Fresh air intake hole 3-:15/16(:100) cut out hole Ceiling 13-25/32(350) *6-9/16(167) *6-3/32(155) 70 :6-7/8(:175) burring hole pitch 5-1/8(130) 3-17/32 3-15/16 3-15/16 3-17/32 (90) (100) (90) (90) Refrigerant pipe 3-15/16(100) Drain pipe Branch duct hole diagram (view from either side) 14-:1/8(:2.8) burring hole :5-29/32(:150) cut out hole 2. Fresh air intake (Installation at site) By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct flange (option) onto it further, fresh exterior air intake can be accomplished. (The mounting of the multi-function casement increases the height of the ceiling plenum by 5-5/16 (135mm).) 19 3. Fresh air intake amount & static pressure characteristics 1 PLA-A18BA PLA-A30BA 50(20) 0 -50(-20) 2 - inlet -100(-40) -150(-60) 1 - inlet 0 1 2 Taking air into the unit 3 4 100 Airflow rate 6[CMM] 5 150 200 50(20) 0 -50(-20) -100(-40) -150(-60) 0 1 2 Curve in the graphs 1 Duct characteristics at site A 0 B Q -50(-20) C A 2 E -100(-40) Q -150(-60) D 3 1 2 3 4 100 Airflow rate 5 6[CMM] 150 200 [CFM] A 0 Q Qa Multifunction casement + Standard filter Static pressure [Pa(in.W.G.%10-2)] 0 -50(-20) 2 - inlet -100(-40) -150(-60) 1 - inlet 0 2 50 4 100 Taking air into the unit 6 150 200 Airflow rate 8 250 [CMM] -100(-40) 2 - inlet -150(-60) -200(-80) -150(-60) 4 100 150 200 Airflow rate 6 8 250 1 - inlet 0 2 50 [CFM] -100(-40) 2 Q…Designed amount of fresh air intake <CMM(CFM)> A…Static pressure loss of fresh air intake duct system with airflow amount Q <Pa(in.W.G.o10-2)> B…Forced static pressure at air conditioner inlet with airflow amount Q <Pa(in.W.G.o10-2)> C…Static pressure of booster fan with airflow amount Q <Pa(in.W.G.o10-2)> D…Static pressure loss increase amount of fresh air intake duct system for airflow amount Q <Pa(in.W.G.o10-2)> E…Static pressure of indoor unit with airflow amount Q <Pa(in.W.G.o10-2)> Qa…Estimated amount of fresh air intake without D <CMM(CFM)> -50(-20) -50(-20) 50 [CFM] 0 0 0 200 50(20) 50(20) -200(-80) 6[CMM] 5 150 Multifunction casement + High efficiency filter 50(20) -200(-80) 4 100 Airflow rate How to read curves 0 -200(-80) 3 50 [CFM] 2 PLA-A36BA Static pressure [Pa(in.W.G.%10-2)] 1 - inlet -200(-80) 50(20) 50 Static pressure [Pa(in.W.G.%10-2)] 2 - inlet C -200(-80) 50 Static pressure [Pa(in.W.G.%10-2)] Multifunction casement + Standard filter Static pressure [Pa(in.W.G.%10-2)] Static pressure [Pa(in.W.G.%10-2)] Multifunction casement + High efficiency filter [CMM] [CFM] 20 4 100 150 200 Airflow rate 6 8 250 [CMM] [CFM] 4. Change of outlet numbers The optional air outlet is necessary. To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter. Indoor unit When the air outlets are closed, close the vane by removing the vane connector. Outlet concave portion Button Vane motor Up/down vanes Connector Air outlet shutter plate (Option) Vane motor Connector Button 5. Branch duct and change of outlet numbers + Branch duct should be connected to one of the branch duct holes on the main unit. <4- way air flow and branch duct> Branch duct Air intake Air outlet + Close the outlet on the side of branch duct and air flows in 3 directions. <3- way air flow and branch duct> Branch duct Air intake Air outlet Air outlet closed position + The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions. <2- way air flow and branch duct> Branch duct Air Air outlet outlet closed closed position position Air intake Air outlet closed position 21 • Airflow rate of PLA-A18BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-A30BA. PLA-A30BA 4-way airflow (horizontal vane) Rectangular duct 4-way airflow (horizontal vane) Round duct 30(12) Static pressure [Pa(in.W.G%10-2)] Static pressure [Pa(in.W.G%10-2)] 30(12) Duct 20(8) 10(4) High Low 0 0 2 0 50 4 100 6 150 200 Airflow rate [CFM] 0 250 High 2 50 4 100 Airflow rate 250 [CFM] 70(28) 60(24) Close 50(20) 40(16) 30(12) 20(8) High Low 10(4) 0 0 2 50 4 100 6 150 8 200 250 Close 50(20) 40(16) 30(12) High 20(8) Low 10(4) 0 10[CMM] 300 Duct 60(24) [CFM] 0 0 2 4 50 100 6 150 Airflow rate 8 200 250 10[CMM] 300 [CFM] Airflow rate 2-way airflow (horizontal vane) Rectangular duct 2-way airflow (horizontal vane) Round duct 80(32) Static pressure [Pa(in.W.G%10-2)] 80(32) Static pressure [Pa(in.W.G%10-2)] 8[CMM] 200 3-way airflow (horizontal vane) Rectangular duct Duct 70(28) Duct Close 60(24) Close 50(20) 40(16) 30(12) High 20(8) Low 10(4) 0 6 150 80(32) Static pressure [Pa(in.W.G%10-2)] Static pressure [Pa(in.W.G%10-2)] Low 0 0 70(28) 0 10(4) 8[CMM] 3-way airflow (horizontal vane) Round duct 80(32) Duct 20(8) 70(28) Duct 60(24) Close Close 50(20) 40(16) 30(12) 20(8) High Low 10(4) 0 0 0 2 50 4 100 150 6 200 8 250 Airflow rate 10 300 350 400 12[CMM] 0 [CFM] 0 2 50 4 100 150 6 200 8 250 Airflow rate • Use 1 of the 2 duct holes on the indoor unit. • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow. 22 10 300 350 12[CMM] 400 [CFM] • Airflow rate of PLA-A36BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-A42BA. PLA-A42BA 4-way airflow (horizontal vane) Rectangular duct Static pressure [Pa(in.W.G%10-2)] Static pressure [Pa(in.W.G%10-2)] 4-way airflow (horizontal vane) Round duct 30(12) Duct 20(8) 10(4) 30(12) Duct 20(8) 10(4) High High Low 0 0 2 0 50 Low 4 100 6 150 Airflow rate 8[CMM] 0 0 [CFM] 0 250 200 3-way airflow (horizontal vane) Round duct 4 100 Airflow rate [CFM] 70(28) Duct Duct Static pressure [Pa(in.W.G%10-2)] Close 60(24) 50(20) 40(16) High 30(12) 20(8) Low 10(4) 0 0 0 2 50 4 100 6 150 8 200 250 Airflow rate Close 60(24) 50(20) 40(16) High 30(12) 20(8) Low 10(4) 10[CMM] 0 0 [CFM] 0 300 2 50 4 100 100(40) 8 200 250 Airflow rate 10[CMM] 300 [CFM] 100(40) 90(36) 90(36) Duct Duct 80(32) 80(32) Close Close 70(28) Close Close Static pressure [Pa(in.W.G%10-2)] 70(28) 60(24) 50(20) 40(16) High 30(12) Low 20(8) 10(4) 0 0 6 150 2-way airflow (horizontal vane) Rectangular duct 2-way airflow (horizontal vane) Round duct Static pressure [Pa(in.W.G%10-2)] 8[CMM] 250 200 80(32) 70(28) 0 6 150 3-way airflow (horizontal vane) Rectangular duct 80(32) Static pressure [Pa(in.W.G%10-2)] 2 50 2 50 4 100 150 6 200 8 250 300 10 350 50(20) [CFM] Low 30(12) 20(8) 10(4) 0 0 Airflow rate • Use 1 of the 2 duct holes on the indoor unit. • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow. 23 High 40(16) 0 12[CMM] 400 60(24) 2 50 4 100 150 6 200 8 250 Airflow rate 300 10 350 12[CMM] 400 [CFM] 9 NOISE CRITERION CURVES 9-1. INDOOR UNIT PLA-A18BA NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 LINE PLA-A30BA 90 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 70 10 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 BAND CENTER FREQUENCIES, Hz PLA-A36BA 125 NC-20 250 500 1000 NOTCH SPL(dB) High 40 Medium1 37 Medium2 34 Low 32 CEILING bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 5ft NC-70 MICROPHONE 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 125 NC-20 250 500 1000 2000 8000 UNIT 70 63 4000 LINE 80 10 2000 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 80 20 NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 4000 8000 BAND CENTER FREQUENCIES, Hz 24 PKA-A18GA PKA-A18GAL NOTCH SPL(dB) High 43 Medium1 41 38 Medium2 Low 36 LINE PKA-A30FA PKA-A30FAL bar) NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 70 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz NOTCH High Low PKA-A36FA PKA-A36FAL SPL(dB) 49 46 LINE bar) 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002 80 10 LINE 90 90 20 NOTCH SPL(dB) High 45 Low 39 UNIT WALL 3.3ft 3.3ft MICROPHONE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 25 4000 8000 9-2. OUTDOOR UNIT MODE SPL(dB) COOLING 52 HEATING 53 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) PUHZ-HA30NHA PUHZ-HA36NHA LINE 90 80 MICROPHONE 70 3.3 ft NC-70 UNIT 60 NC-60 5 ft 50 NC-50 40 NC-40 30 GROUND NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz 26 10 OPTIONAL PARTS 10-1. INDOOR UNIT Part Name Remote sensor (extensible) Connector for CN51 (output for remote display + pulse12V input) Connector for CN32 (remote ON/OFF) Model Name PAC-SE41TS-E PAC-88HA-E(1pc.) PAC-725AD(10pcs.) Connector for CN24 (Back up heating) Connector for CN30 (LLC) PAC-SE56RA-E PAC-SE57RA-E Power supply terminal kit PAC-SH55HR-E PAC-SH98HR-E Decoration panel with Wired remote controller Decoration panel Multi-function casement Flange for fresh air intake PLP-42BAMD PLP-40BAU PAC-SH53TM-E PAC-SH65OF-E PAC-SH59KF-E Applicable model All models PAC-SE55RA-E High-efficiency filter element (PAC-SH53TM-E is needed.) i-see sensor corner panel Wireless signal receiver Wireless remote controller kit PAC-SA1ME-E PAR-SA9FA-E PAR-SW96U-E Space panel Air outlet shutter plate L shape connection pipe PAC-SH48AS-E PAC-SH51SP-E PAC-SC84PI-E 27 PLA-A·BA PKA-A·GA(L)/FA(L) PLA-A·BA PKA-A30/36FA(L) 10-2. OUTDOOR UNIT FOR PUZ-HA30/36NHA Part Name Model Name M-NET adapter PAC-SF80MA-E A-control service tool PAC-SK52ST Drain socket PAC-SG61DS-E Air outlet guide(HA30/36 needs 2 pieces.) Air protect guide(HA30/36 needs 2 pieces.) PAC-SG59SG-E Drain pan PAC-SH63AG-E PAC-SG64DP-E Distribution pipe for twin use MSDD-50SR-E HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Nov. 2008 No.OCS12 REVISED EDITION-A PDF 6 Distributed in Oct. 2007 No.OCS12 PDF 7 Made in Japan New publication, effective Nov. 2008 Specifications subject to change without notice.