Download Continental Fireplaces BCDV40-P Operating instructions
Transcript
31 8.2.1 HORIZONTAL AIR TERMINAL INSTALLATION A. B. Stretch the inner flex pipe to the required length taking into account the additional length needed for the finished wall surface. Apply a heavy bead of the high temperature sealant W573-0007 Mill Pac (not supplied) to the inner sleeve of the air terminal. Slip the vent pipe a minimum of 2” over the inner sleeve of the air terminal and secure with 3 #8 screws. Using the outer flex pipe, slide over the outer combustion air sleeve of the air terminal and secure with 3 #8 screws. Seal using high temperature sealant W573-0002 (not supplied). CAULKING EX ER FL INNP IPE 2" OVERLAP #10x2" SCREWS C. Insert the vent pipes through the firestop maintaining the required HI-TEMP clearance to combustibles. Holding the air terminal (lettering in SEALANT an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied). D. If more vent pipe needs to be used to reach the fireplace, couple them together as illustrated. The vent system must be OUTER supported approximately every 3 feet for both vertical and FLEX PIPE horizontal runs. Use noncombustible strapping to maintain the minimum clearance to combustibles. OUTER FLEX PIPE HIGH TEMPERATURE SEALANT #8 X 1/2” SELF DRILLING SCREWS & WASHERS INNER COUPLER OUTER COUPLER OUTER FLEX PIPE INNER FLEX PIPE The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its return flange. 23.1A W415-0812 / D / 08.16.12