Download Chloride Power Protection Active 1500 Technical data
Transcript
CHLORIDE POWER PROTECTION • REMAINING AUTONOMY This represents the remaining time to the battery cut off. Example: If LEARNT AUTONOMY is 15 minutes, AUTHORIZED AUTONOMY 10 minutes, after 3 minutes of discharging, the value of REMAINING AUTONOMY will be 10 minus 3 = 7 minutes. 5.0 MONITORING AND CONTROL 5.1 Introduction By employing microprocessor technology, the UPS shall provide an advanced and easy to use diagnostic system. 5.2 Control panel 1 3 4 8 7 9 10 2 6 1&2 3 4 5 6 7 8 9 10 - 5 Switch off buttons: both must be pushed simultaneously to prevent accidental shutdown. Start-up button. Alarm reset button: silences the audible alarm when pressed. Forced by-pass button: used to activate forced by-pass. By-pass LED: lit when unit is in by-pass mode. Battery LED: lit when batteries are charging. Mains LED: lit when the mains power is within limits. Output LED: lit when output voltage is sensed. Alarm LED: lit when a fault is detected. MKA4ST0UKPLAN5-7/Power Lan/ed.5/09-2003/UK 7