Download Manitowoc Q130 Specifications
Transcript
FLOODING EXPANSION VALVE A flooding expansion valve will have discharge and suction line temperatures 20°F (-7°C) lower than normal freeze cycle temperatures. Normal suction line temperature and low discharge line temperature DO NOT verify a flooding valve. Both discharge line temperature and suction line temperature must be low to verify a flooding expansion valve. Ice fill pattern is thin on the left hand side of the evaporator. STARVING EXPANSION VALVE/LOW REFRIGERANT CHARGE Important Confirm water float valve is set correctly . An overflowing st andpipe mimics these symptoms exactly. SYMPTOMS: • Ice Fill Pattern • Thin on top two rows of the evaporator • Thin on entire left side of the evaporator • Thick on the bottom of the evaporator • Freeze time longer than normal Diagnosis can be confirmed by adding 2 oz (56.7 g) of refrigerant: if the Suction line temperature drops or the ice fill pattern on the top two rows fills in, the ice machine is low on refrigerant. Refer to charging procedures for access valve installation procedure. OVERCHARGED SYSTEM Suction line temperature will be slightly low during freeze cycle 5°F (-15°C). Discharge line temperature is normal. Actual amperage readings will be higher than nameplate rating. Part Number 80-01111-9 7/10 143