HARVEST CYCLE OPERATION During the Harvest cycle, the cool vapor valve opens and allows refrigerant from the top of the receiver tank to enter the evaporator. The refrigerants change of state (from vapor to liquid) releases the heat necessary for the Harvest cycle. Opening the cool vapor valve causes a drop in discharge pressure. Air-Cooled Models The discharge pressure will drop below the condenser fan cycling control setpoint and the condenser fan motor cycles off (at ambient temperatures above 110°F (43°C) the condenser fan motor remains energized). Water-Cooled Models The head pressure control valve cycles into a complete bypass position (stopping all refrigerant flow through the condenser). All CVD Models The warm discharge gas adds heat to the receiver in the harvest cycle. Without this additional heat the head pressure would continue to drop as liquid refrigerant boils off in the receiver. Example: A service technician removes refrigerant vapor from a cylinder by boiling off the liquid refrigerant. A refrigeration effect is created as the refrigerant changes state from a liquid to a vapor. The cylinder cools and the refrigerant pressure drops. To maximize flow and maintain pressure the technician places the cylinder in warm water. A head pressure control valve that will not completely bypass in the harvest cycle will result in longer harvest cycles with lower that normal suction pressure and safety limit #2 trips. (Refer to the “Cycle Times/24 Hr Ice Production/ Refrigerant Pressure Charts” for the model being worked on, to obtain the correct harvest cycle pressure range). –161–