Download Siemens LFL Series Technical data

Transcript
GAS PRESSURE
The adjacent diagram shows minimum pressure losses
along the gas supply line depending on the maximum
burner output operation with natural gas.
Δp [“WC]
Column 1
Gas manifold pressure measured at test point 1)(B),
with:
• Combustion chamber at 0” WC;
• Burner operating at maximum output;
• Combustion head adjusted as indicated in diagram
(C)p. 8.
(A)
D3188
Calculate the approximate maximum output of the
burner as follows:
- subtract the combustion chamber pressure from the
gas pressure measured at test point 1)(B).
- Find the nearest pressure value to your result in
diaram (A).
- Read off the corresponding output on the left.
Example
• Maximum output operation
• Natural gas
• Gas pressure at test point 1)(B)
= 4.09“ WC
• Pressure in combustion chamber = 1.18“ WC
4.09 - 1.18 = 2.91“ WC
A maximum output of 4094 MBtu/hr shown in diagram
(A) corresponds to 2.91” WC pressure.
This value serves as a rough guide, the effective delivery must be measured at the gas meter.
1
2
(B)
D2441
6