MCQUAY Service Guide Book Diagnosis Wall Mounted G Series Inverter-X Model Model MWMX 10/15/20/25G/GR SLEEP Board VA2.0 POWER TIMER (Green/Red) (Orange) Handset G17 / SLM3 IONIZER (Green) Error Code (SLM3) / / - Cooling mode - / / - Heating mode / Standby mode (only for heat pump model) - / / - Auto mode in operation - - Timer On - - Sleep mode On - - Ionizer On - / - Fan mode On - / - Dry mode On - - Defrost mode - (Red) Red E1 Green Green E2 Outdoor temperature sensor loose / short E3 Communication error between indoor and outdoor E4 Compressor overload protection E6 Compressor overheat / gas leak E7 IPM / PFC error E8 E9 Green ON / ON or OFF Indoor temperature sensor loose / short Coil temperature sensor loose / short - Green Operation / Faulty Indication Outdoor total current trip / DC peak Indoor fan feedback error BLINKING 55 Action Check indoor coil sensor connection / change indoor coil sensor Check coil sensor connection / change coil sensor Check outdoor coil sensor connection / change outdoor coil sensor Check the connection wires between indoor and outdoor If running ampere highly increase, change the compressor Check for leakage & repair / Top up refrigerant Check supply voltage and compressor phase Check the input current and discharge pressure Check indoor fan motor / fan motor wiring