32a Service parameter(s) 22-30 22 Pump exercise Circuit Setting range Factory setting I ON / OFF ON Exercises the pump to avoid blocking in periods without cooling demand. ON:The pump is switched ON for 1 minute every third day around noon. OFF:The pump exercise is not active. 23 Valve exercise Circuit Setting range Factory setting I ON / OFF ON Exercises the valve to avoid blocking in periods without heat demand. ON:The valve receives a signal to open and close every third day around noon. OFF:The valve exercise is not active. 24 Gear motor / thermo actuator Circuit Setting range Factory setting I ON / OFF ON Choose the actuator type for your valve. ON:Gear motor OFF:Thermo actuator (ABV type) 30 Return temperature limitation, sensor S4 Circuit Setting range Factory setting I 10 ... 110 °C 60 °C Set the limitation temperature at S4. Set the limitation temperature. When the temperature at S4 falls below or gets higher than the set value, the desired DHW charging temperature is changed. The influence is set in lines 35 and 36. The grey side of the ECL Card Extended service Control parameters (lines 4-7) are overruled if thermo actuator is chosen (OFF).