3200 Series 11.5 Engineering Handbook Example: To Configure Heating and Cooling Enter configuration level as described. Then:Do This The Display You Should See Additional Notes 1. Press as many times as necessary to select ‘C T R L ’ 2. Press 3. Press V or Heating Type 4. Press 5. Press V or Cooling Type 6. Press to select ‘C T R L . A ’ 7. Press V or 8. Press to scroll to ‘P B . U N T ’ 9. Press V or to scroll to ‘C T R L H ’ W to select the to select ‘C T R L . C ’ W W W to select the to ‘rev’ to choose units 10. Continue to select parameters using for example ‘O P . H I ’ 11. Press values V or Part No HA028651 W to change their Heating Type choices are:Pid PID (3 term) control on.of On/Off control oFF No heating output configured Cooling Type choices are:oFF No cooling output configured PId PID (3 term) control on.of On/Off control Control Action choices are:rev Reverse - heating control Dir Direct - cooling only control Proportional Band Units choices are:EnG Engineering units Perc Percentage When PID control is selected, this places a limit on the output demand from the PID which can be applied to the heating circuit. ‘O P.LO ’ can be set up in the same way if required. If on/off control is selected these parameters do not apply. They are replaced by ‘HYST.H’ and ‘HYST.L’ to set the difference between the output switching off to switching on. Issue 10.0 Dec -10 69