&\FOHDQGUHVSRQVHWLPHV
3K\VLFDOF\FOHWLPHGHSHQGLQJRQFRPPXQLFDWLRQORDG
The figure below describes the non-linear dependency of the physical cycle time
on communication load. In our sample we have chosen a cycle time of 10 ms.
Cycle time
30 ms
You can set the communication load here
25 ms
20 ms
15 ms
10 ms
5 ms
0%
5 % 10 %
20 %
30 %
40 %
50 %
60 %
Communication load
Figure 5-4 Cycle time depending on communication load
,QIOXHQFHRQWKHSK\VLFDOF\FOHWLPH
From the statistical viewpoint, asynchronous events - such as interrupts - occur
more frequently within the OB1 cycle when the cycle time is extended as a result of
communication load. This further extends the OB1 cycle. This extension depends
on the number of events that occur per OB1 cycle and the time required to process
these events.
1RWH
Change the value of the "communication load" parameter to check the effects on
the cycle time at system runtime. You must consider the communication load when
you set the maximum cycle time, otherwise timing errors can occur.
5-10
S7-300 Automation System CPU Specifications: CPU 31xC and CPU 31x