Download AB Quality 1746-P3 Specifications

Transcript
116
Wiring Your I/O Modules
Features of an I/O Module
Below is an example of a combination I/O module.
OUTPUT
Color Band
INPUT
0
4
0
4
1
5
1
5
2
2
3
3
I/O Status
Indicators
Terminal Block Screw
(maximum torque: 0.6 Nm (5.3 lb-in))
Input and Output Terminals
Connected to Terminal Block
Terminal Block (may be color-coded
and removable on some modules)
Hinged Wiring Terminal
Door with Label
Terminal Wiring
• 2 wires per terminal maximum
• #14 AWG (2mm2) maximum
• Maximum torque: 0.9 Nm (8 lb-in)
Terminal Block Screw
(maximum torque: 0.6 Nm (5.3 lb-in))
Tie Wire
Wires Leading to Input and Output Devices
Wiring Your I/O Module
Terminals on the modules have self-lifting pressure plates that accept
two 2 mm2 (14 AWG) wires. Series B 12-point and 16-point and
analog modules are equipped with removable terminal blocks for
ease of wiring. The plug for the removable terminals is also color
coded:
•
•
•
•
red (ac)
blue (dc)
orange (relay)
green (specialty).
Status indicators on the front of each module display the status of
each I/O point. The status indicators illuminate when the proper
signal to an input terminal is applied or when the processor
commands an output to be energized.
To locate the I/O module wiring diagrams, contact your Rockwell
Automation sales office for the latest selection guide, publication
1747-SG001. Or, locate the installation instruction sheet that was sent
with your I/O module. It also includes I/O wiring diagrams.
Publication 1747-UM011G-EN-P - June 2008
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com