Download Daikin FTXR42EV1B9 Specifications
Transcript
Control Specification 2.2 SiBE04-624_B Controls at Mode Changing / Start-up 2.2.1 Preheating Operation Outline The inverter operation in open phase starts with the conditions of the preheating command from the indoor unit, the outdoor temperature, and the discharge pipe temperature. Detail Outdoor temperature ≥ 7°C Preheating OFF 12˚C Discharge pipe temperature 10˚C Preheating ON (R5922) Outdoor temperature < 7°C Preheating OFF 22˚C Discharge pipe temperature 20˚C Preheating ON (R5923) 2.2.2 Four Way Valve Switching Outline In heating operation, current is conducted, and in cooling and defrost operation, current is not conducted. In order to eliminate the switching sound, as the four way valve coil switches from ON to OFF when the heating is stopped, the OFF delay switch of the four way valve is carried out. Detail OFF delay switch of four way valve: The four way valve coil is energized for 160 seconds after the operation is stopped. 2.2.3 Four Way Valve Operation Compensation Outline At the beginning of the operation as the four way valve is switched, the differential pressure to activate the four way valve is acquired by having output frequency which is more than a certain fixed frequency, for a certain fixed time. Detail Starting Conditions 1. When the compressor starts and the four way valve switches from OFF to ON 2. When the four way valve switches from ON to OFF during operation 3. When the compressor starts after resetting 4. When the compressor starts after the fault of four way valve switching The lower limit of frequency keeps A Hz for B seconds with any conditions 1 through 4 above. Condition Cooling Heating 56 outdoor temperature < 16°C outdoor temperature ≥ 16°C A (Hz) 52 B (seconds) 52 – 0.9 × outdoor temperature + 68 60 Function and Control