VENT PIPE INSTALLATION TABLE 1 NON-DIRECT VENT INSTALLATION GUIDELINES UPFLOW UNITS FOR NON-DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION PROVIDED FROM INDOORS MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE IMPORTANT: Failure to correctly follow all venting guidelines may result in erratic furnace operation, freeze-up of combustion air or exhaust air piping or sooting of the furnace. All exhaust piping must be installed in compliance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code NPFA54/ ANSI Z223.1-, local codes or ordinances and these instructions. 1. Vertical piping is preferred. 2. All horizontal piping must slope upward a minimum of 1/4 inch per foot of run so that condensate drains toward the furnace. 3. All horizontal runs must be supported at least every 4 feet. No sags or dips are permitted. 4. IMPORTANT: Do not common vent with any other appliance. Do not install in the same chase or chimney with a metal or high temperature plastic pipe from another gas or fuelburning appliance unless the required minimum clearances to combustibles are maintained between the pvc pipe and other pipes. 5. All vent runs through unconditioned spaces where below-freezing temperatures are expected should be insulated with 1-in. thick, medium-density, foil-faced fiberglass. An equivalent “arm-aflex” or “rub-a-tex” insulation may also be used as long as there is no heat tape applied to the vent pipe. For horizontal runs where water may collect, wrap the vent pipe with selfregulating 3 or 5 watt heat tape. The heat tape must be U.L. listed and installed per the manufacturer’s instructions. 6. The minimum vent pipe length is 5 feet with 15” between elbows. 7. Extend the exhaust pipe a minimum of 18” from the cabinet before turning vent. 8. Vent cannot be run underground. FURNACE INPUT 45,000 PIPE SIZE 2” 2” 60,000 3” 75,000 90,000 3” 3” 105,000 3” 120,000 3” NUMBERS OF ELBOWS 45° OR 90° Medium / Long Radius ONLY TERMINATION 1-2 3-4 5-6 Standard 60 55 50 Alternate 55 50 45 Standard 30 25 20 Alternate 25 20 15 Standard 120 120 115 Alternate 120 120 110 Standard 45 40 NR Alternate NR NR NR Standard 90 85 75 Alternate 60 50 45 Standard 45 40 NR Standard 70 65 55 Alternate 40 30 25 NOTES: 1. *N.R. - NOT RECOMMENDED. 2. MAXIMUM OF 4 ELBOWS MAY BE USED. DO NOT COUNT ELBOWS REQUIRED FOR ALTERNATE TERMINATION. USE ONLY MEDIUM OR LONG SWEEP ELBOWS. 3. A 45 OR 22.5 DEGREE ELBOW IS CONSIDERED ONE ELBOW. 4. NO SCREENS MAY BE USED TO COVER EXHAUST. *A = 17-1/2” CABINET WIDTH B = 21) CABINET WIDTH TABLE 2 DOWNFLOW/HORIZONTAL UNITS FOR NON-DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION PROVIDED FROM INDOORS MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE FURNACE INPUT PIPE SIZE 2” 60,000 3” 75,000 90,000 105,000 3” 3” 3” TERMINATION NUMBERS OF ELBOWS 45° OR 90° Medium / Long Radius ONLY 1-2 3-4 Standard 50 40 Alternate 40 30 Standard 50 40 Alternate 50 40 Standard 50 40 Alternate 50 40 Standard 50 40 Alternate 50 40 Standard 50 40 Alternate 50 40 NOTES: 1. *N.A. - NOT APPLICABLE. 2. MAXIMUM OF 4 - 90 DEGREE ELBOWS MAY BE USED. DO NOT COUNT ELBOWS REQUIRED FOR ALTERNATE TERMINATION. USE ONLY MEDIUM OR LONG SWEEP ELBOWS. 3. A 45 OR 22.5 DEGREE ELBOW IS CONSIDERED ONE ELBOW. 4. NO SCREENS MAY BE USED TO COVER EXHAUST. *A = 17-1/2” CABINET WIDTH B = 21” CABINET WIDTH FIGURE 15 TEE TERMINAL – FOR STANDARD HORIZONTAL NON-DIRECT INSTALLATION VENT 12" 12" MIN. ABOVE GRADE OR SNOW LEVEL ELEVATED SINGLE PIPE ALTERNATE TEE TERMINATION See Figure 16. The tee termination may be elevated up to 24 inches above the wall penetration if required for anticipated snow levels. Use 2 long-sweep, 2-in. PVC elbows and 2-in. PVC pipe, attaching the tee so it is 12 inches from the wall. 21