Download CTC Union EcoZenith i250 Technical data

Transcript
162 105 45-1 2015-03-10
Providing sustainable energy solutions worldwide
Installation and Maintenance Manual
CTC EcoZenith i250
2
CTC EcoZenith i250
Installation and Maintenance Manual
CTC EcoZenith i250
162 105 45-1 2015-03-10
Table of Contents
GENERAL INFORMATION
Checklist______________________________________________________________________ 6
Important to remember!______________________________________________ 7
Safety Instructions______________________________________________________ 7
1. Your home’s heating installation__________________________ 8
2. Technical data_____________________________________________________ 11
2.1
Table 400V 3N~ _____________________________________________ 11
2.2
Table 230 V 1N~ ____________________________________________ 12
3.Measurements____________________________________________________ 13
4. CTC EcoZenith i250 design_______________________________ 14
5. Parameter list______________________________________________________ 15
6. Control system____________________________________________________ 16
7. Menu overview____________________________________________________ 17
8. Detail Description Menus___________________________________ 23
8.1
Start menu____________________________________________________ 23
8.2
Description of icons________________________________________ 23
8.3
Room temp.__________________________________________________ 24
8.3.1Setting a room temp. without a room sensor___ 24
8.3.2Outdoor Sensor/Room Sensor Faults__________ 25
8.3.3Night reduction temperature_________________ 25
8.4DHW____________________________________________________________ 26
8.3.4Holiday___________________________________ 26
8.4.1Weekly program DHW ______________________ 27
8.5
Operation data system____________________________________ 28
8.5.1Operation data EcoZenith___________________ 29
8.5.2Operation Heating circuit____________________ 30
8.5.3Stored operation data_______________________ 31
8.5.5Heat pump________________________________ 32
8.5.4Operation data heating______________________ 32
8.6Installer_________________________________________________________ 33
8.6.1Time/Language____________________________ 33
8.7Settings________________________________________________________ 34
8.7.1Heating circuit 1 or 2________________________ 34
8.7.2Set. heat pump____________________________ 37
8.7.3Electric heater_____________________________ 38
8.7.4Upper tank________________________________ 39
8.7.5Remote control____________________________ 40
8.7.6Communication____________________________ 40
8.7.7Solar panels (accessories)___________________ 40
8.7.8Sett. Diff termostat function__________________ 41
8.7.9Pool______________________________________ 41
8.7.10 Saving and loading settings_______________ 41
8.8
Define system________________________________________________ 42
8.8.1Def heating circuit 1 or 2____________________ 42
8.8.2Def Heat pump____________________________ 42
8.8.3Define CTC SMS (accessory)_________________ 43
8.8.4Define cooling (accessory)___________________ 43
8.8.5Def Solar panels___________________________ 44
8.8.6Define Differential thermostat function_________ 44
8.8.7Def. Pool__________________________________ 44
4
CTC EcoZenith i250
8.9Service__________________________________________________________ 45
8.10 Function test__________________________________________________ 45
8.11 Alarm log ______________________________________________________ 47
9. Operation and Maintenance______________________________ 49
10. Troubleshooting/appropriate measures____________ 50
10.1 Information messages_____________________________________ 53
10.2 Alarm texts____________________________________________________ 54
INSTALLATION
11.Installation___________________________________________________________ 57
11.1Transportation________________________________________________ 57
11.2Unpacking_____________________________________________________ 57
11.3 Standard delivery____________________________________________ 57
12. Pipe installation__________________________________________________ 58
12.1Filling____________________________________________________________ 58
12.1.1 Pressure drop in mixing valve______________ 58
12.1.2 Pump curve charge pump_________________ 59
12.2 Schematic diagram_________________________________________ 60
12.3 Connection to heat pump________________________________ 63
12.4 DHW system__________________________________________________ 65
13.Energyflex___________________________________________________________ 66
14. Electrical installation__________________________________________ 69
14.1 Electrical installation 400 V 3N~ _______________________ 69
14.2 Electrical installation 230V 1N~ ________________________ 69
14.3 Positioning of electrical components__________________ 70
14.4 Electrical connection to heat pump____________________ 71
14.4.1Communication_________________________ 71
14.4.2 Heat pump power supply 400 V 3N~_______ 72
14.4.3 Heat pump power supply 230V 1N~________ 72
14.4.4 Connecting the heat pump connector_______ 72
14.5 Extra low voltage protection_____________________________ 73
14.5.1 Remote-controlled temperature reduction___ 74
14.5.2 Current sensor connection________________ 74
14.5.3 Terminal boards_________________________ 75
14.6 Settings made by the installation electrician.________ 76
14.7 Installing a backup power supply_______________________ 76
14.8 Switching to 18 kW electric heater power.__________ 77
14.9 Connection of pump (G46) to Diff. therm. func.____ 79
14.10Connection of sensor (B46) to Diff. therm. func.___ 79
14.11Wiring diagram 3x400 V___________________________________ 80
14.12Wiring diagram 1x230 V___________________________________ 82
14.13Component list, wiring diagram_________________________ 84
14.14Resistances for sensors___________________________________ 85
15. Connection of CTC EcoAir 520M heat pump____ 86
15.1 Menu functions unique to the CTC EcoAir 520M__ 87
15.1.1 Operation data heat pump________________ 87
15.1.2 Heat pump Settings______________________ 88
15.1.3 Heat pump Settings continued_____________ 89
15.1.4 Set Schedule Noise reduction_____________ 90
16. First start_____________________________________________________________ 91
Declaration of Conformity_________________________________________ 93
General Information
General Information
Congratulations on your new product
You have just bought a CTC EcoZenith i250, which
we hope you will be very pleased with. In the following
pages you can read about how to operate and maintain
your boiler.
Keep this manual containing the installation and
maintenance instructions. If it is properly maintained,
you will be able to enjoy the use of your CTC EcoZenith
i250 for many years. This manual will provide all the
information you will need.
The complete system tank
The CTC EcoZenith i250 is a complete system tank
which meets your home’s heating and hot water
requirements. It has a built-in immersion heater giving a
total of 15 kW and is equipped with a motorised mixing
valve which ensures correct and even temperatures are
supplied to your heating system. The CTC EcoZenith
i250 has a built-in circulation pump for connection to a
heat pump.
The CTC EcoZenith i250 is fully ready for connection to
the following heat pumps:
• CTC EcoAir 406
• CTC EcoPart 406
• CTC EcoAir 408
• CTC EcoPart 408
• CTC EcoAir 410
• CTC EcoPart 410
• CTC EcoAir 520M*
• CTC EcoPart 412*
**Consider the flow requirements, particularly with the
CTC EcoAir 520M and CTC EcoPart 412 models. See
also the “Exact Primary Flow” function and use a larger
circulation pump if required.
All controls for the heat pump and charge pump are
built into the CTC EcoZenith i250. With this added
feature you achieve a very eco-friendly and energysaving heating system.
The CTC EcoZenith i250 has a control
system that:
• Monitors all system tank, heat pump and heating
system functions
• Permits individual settings
• Displays desired values, such as temperatures,
operation times, energy consumption and fault
signals
• Facilitates the setting of values and troubleshooting
in a simple and well-structured way
The built-in copper coil provides copious amounts of
hot water. The CTC EcoZenith i250 also has a socalled summer-time basement heating function and a
floor heating block, which maximises the temperature
supplied to the floor circuits. Using the integrated
night reduction function, you can set and change the
temperature in the house during the day, from one day
to the next.
Easily accessible electrical components, along with
effective troubleshooting functions in the control
program, make the CTC EcoZenith i250 easy to service.
It comes with a room sensor as standard, which is
equipped with an LED which flashes in the event of a
fault.
If you want to supplement your CTC EcoZenith i250
with other heating, you can do this easily thanks to two
unique connections. We have decided to call this option
Energyflex. With Energyflex you can, for example:
• Charge your heating system with solar energy
• Allow a water-jacketed stove to contribute heat
• Connect a pool exchanger to heat up a swimming
pool
For more information, please see the separate section in
this manual.
CTC EcoZenith i250
5
General Information
Checklist
The check list must be completed by the installer.
• In the event of a service, this information may be called for.
• Installation must always be done according to the installation and maintenance instructions.
• Installation must always be carried out in a professional manner.
• Following installation, the unit must be inspected, functional checks performed and the customer
informed.
The points below should be checked off.
Pipe installation
†† CTC EcoZenith i250 filled, positioned and adjusted in the correct manner according to the
instructions.
†† CTC EcoZenith i250 positioned so that it can be serviced.
†† Capacity of circulation pump(s) for required flow.
†† Open radiator valves and other relevant valves.
†† Tightness test.
†† Bleeding and pressurising the system.
†† Safety valve function test.
†† The waste pipe is connected to the draining gutter.
Electrical installation
†† Power switch
†† Correct tight wiring
†† Primary flow sensor, return sensor + any required sensors for chosen system
†† Outdoor sensor
†† Room sensor (optional)
†† Accessories
†† Heat pump activated and started
Information for the customer (adapted to current installation)
†† Start-up with customer/installer.
†† Menus/controls for selected system
†† Installation and maintenance manual supplied to the customer
†† Check and filling, heating system
†† Trimming information, heat curve
†† Alarm information
†† Mixing valve
†† Safety valve function test
†† Information on procedures for fault registration
______________________________________
Date / Customer
6
CTC EcoZenith i250
______________________________________
Date / Installer
General Information
Important to remember!
Check the following in particular on delivery and installation:
• The product must be transported and stored in an upright position.
When moving the product, it can be placed temporarily on its back.
• Remove the packaging and check before installation that the product
has not been damaged in transit. Report any transport damage to the
carrier.
• Place the product on a solid foundation, preferably made of concrete.
If the product is to stand on a soft carpet, plates must be placed
under the feet.
• Remember to leave a service area of at least 1 m in front of the
product.
• The product must not be placed below floor level either.
Safety Instructions
The following safety instructions must be observed when handling, installing
and using the product:
• Close the safety switch before doing any work on the product.
• The product must not be flushed with water.
• When handling the product with a hoist ring or similar device, make
sure that the lifting equipment, eyebolts etc. are not damaged. Never
stand under the hoisted product.
!
• Never jeopardise safety by removing bolted covers, hoods or similar.
• Never jeopardise safety by deactivating safety equipment.
• Any work done on the product’s electrical system should be done by a
qualified professional.
If these instructions
are not followed when
installing, operating
and maintaining the
system, Enertech’s
commitment under the
applicable warranty
terms is not binding
• Safety valve check:
- The safety valve for the boiler/system and domestic hot water (DHW)
must be checked on a regular basis. See the chapter on Operation and
maintenance.
Information for the property owner to note
Complete the fields below. This information is useful if any servicing work is required
Product :
Manufacturing number:
Product :
Manufacturing number:
Installation company
Tel. no.
Date
Name
Electrical installation company
Tel. no.
Date
Name
No liability is accepted for any misprints or changes.
CTC EcoZenith i250
7
General Information
1.
Your
home’s
heating
installation
Your
home's
heating
installation
The House Heating Curve
The heating curve is the central part of the product’s control system. It is the heating
curve which determines the compensated flow temperature requirements for your
property dependent upon the outdoor temperatures. It is important that the heating
curve is correctly adjusted, so that you achieve the best operation and economy
possible.
One property requires a radiator temperature of 30 °C when the outdoor temperature
is 0 °C, whilst a different property requires 40 °C. The difference between different
properties is determined by the radiator surface area, the number of radiators and how
well insulated the house is.
!
The set heating curve is always given priority. The room sensor can only increase
or decrease the compensated flow temperature to a certain extent above the set
heating curve. Where operating without a room sensor, the selected heating curve
determines the flow temperature supplied to the radiators purely from the outside
temperature reading.
Adjustment of Default Values for the Heating Curve
You define the heating curve yourself for your property by setting two values in
the product control system. This is achieved by selecting the options Inclination or
Adjustment under the Installer/Settings/Radiator system menu. Ask your installer to
help you set these values.
It is extremely important to set the heating curve and, in some cases, unfortunately,
this process may take several weeks. The best way of doing this, upon the initial
start-up, is to select operation without any room sensor. The system then operates
using the outdoor temperature reading and the property’s heating curve only.
During the adjustment period it is important that:
• the night reduction function is not selected.
• all thermostat valves on the radiators be fully opened.
• the outdoor temperature is not higher than +5 °C. (If the outdoor temperature is
higher when the system is installed, use the factory set curve until the outdoor
temperature falls to a suitable level.)
• the radiator system is operational and correctly adjusted between different
circuits.
Appropriate Default Values
During installation you can seldom achieve a precise setting for the heating
curve instantly. In this case, the values given below may provide a good starting
point. Radiators with small heat-emission surfaces require a higher primary flow
temperature. You can adjust the gradient (heating curve gradient) for your heating
system under the Installer/Settings/Radiator system menu.
Recommended values are:
8
Floor heating only
Inclination 35
Low temperature system (well insulated houses)
Inclination 40
Normal temperature system (factory setting)
Inclination 50
High temperature system
(older houses, small radiators, poorly insulated)
Inclination 60
CTC EcoZenith i250
General Information
Adjusting the heating curve
The method described below can be used to adjust the heating curve correctly.
Adjustment if it is too cold indoors
• If the outdoor temperature is lower than 0 degrees:
Increase the Inclination value by a couple of degrees.
Wait 24 hours to see if any further adjustment is required.
• If the outdoor temperature is higher than 0 degrees:
Increase the Adjustment value by a couple of degrees.
Wait 24 hours to see if any further adjustment is required.
Adjustment if it is too warm indoors
• If the outdoor temperature is lower than 0 degrees:
Decrease the Inclination value by a couple of degrees.
Wait 24 hours to see if any further adjustment is required.
• If the outdoor temperature is higher than 0 degrees:
Decrease the Adjustment value by a couple of degrees.
Wait 24 hours to see if any further adjustment is required.
!
If the values set are too low, this may mean that the desired room temperature
is not being reached. You then need to adjust the heating curve, as necessary,
following the method shown above.
When the basic values have been set more or less correctly, the curve can be
finely adjusted directly using the Room temp. shown on the home menu screen.
Description of inclination and adjustment
Inclination 50:
The value set is the outgoing temperature of the water supplied to the radiators at an
outdoor temperature of –15 °C, e.g. 50 °C. A lower value is selected where a radiator
system has large radiator areas (a low temperature system). Floor heating systems
require low temperatures. A low value should therefore be selected. The value must be
increased for high temperature systems to achieve a high enough indoor temperature.
Adjustment 0:
The adjustment means that the flow temperature can be raised or lowered at a specific
outdoor temperature.
Adjustment 0 means 50 °C primary flow when the outside temperature is -15 °C.
Adjustment -5 means 45 °C primary flow when the outside temperature is -15 °C.
For example:
Inclination 50 means that the temperature of the water supplied to the radiators will
be 50 °C when the outdoor temperature is –15 °C (if adjustment is set to 0). If the
adjustment is set to +5, the temperature will be 55 °C instead. The curve is increased
by 5 °C at all temperatures, i.e. it is parallel displaced by 5 °C.
CTC EcoZenith i250
9
General Information
Examples of Heating Curves
You can see in the diagram below how the heating curve
changes with different Inclination settings. The gradient of
the curve shows the temperatures that the radiators require
at different outdoor temperatures.
Primary Flow Temperature
Curve Inclination
The inclination value which is set is the primary flow
temperature when the outside temperature is –15 °C.
Outside Temperature
Heating off, out
Adjustment
The curve can be parallel displaced (adjusted) by the
desired number of degrees to adapt to different systems/
houses.
Inclination 50 °C
Adjustment +5 °C
Primary Flow Temperature
Inclination 50 °C
Adjustment 0 °C
Outside Temperature
Heating off, out
An example
Inclination 60 °C
Adjustment 0 °C
Primary Flow Temperature
In this example, the maximum outgoing primary flow
temperature is set at 55 °C.
The minimum permitted primary flow temperature is 27 °C
(e.g. summer-time basement heating or the floor circuits in
a bathroom).
Outside Temperature
Summer-time operation
All properties have internal heat gains (lamps, oven,
personal heat etc.), which means that the heating can be
switched off when the outdoor temperature is lower than
the desired room temperature. The better insulated the
house is, the earlier the heating from the heat pump can be
switched off.
The example shows the product set at the default value of
18 °C. This Heating off value can be changed under the
Installer/Settings/Radiator system menu.
When the heat is switched off in this way, the radiator
pump stops and the mixing valve is shut down. The heating
starts up automatically when it is required again.
Primary Flow Temperature
Outside Temperature
Heating off, out
10
CTC EcoZenith i250
General Information
2. Technical data
2.1 Table 400V 3N~
CTC EcoZenith i250 H
Electrical Data
CTC EcoZenith i250 L
400V 3N~ 50Hz
Electrical data
Rated power
kW
15.04
15.04
Immersion heater (steps of 0,3 kW)
kW
0 - 15.0
Max immersion heater output
@ fuse size 16 / 20 / 25 A
kW
3+6/6+6/9+6
IPX1
IP class
CTC EcoZenith i250 H
Heating system
Water volume. thermal store (V)
Max. operating pressure. thermal store (PS)
Max. temperature. thermal store (TS)
l
223
bar
2,5
°C
110
Pressure drop for mixing valve heating
See pressure drop diagram in the Pipe installation chapter
Hot water system
Water volume, hot water coil (V)
Max. operating pressure, hot water coil (PS)
Max. temperature, hot water coil (TS)
CTC EcoZenith i250 H
CTC EcoZenith i250 L
l
5,7
bar
10
°C
110
Other data
Weight
CTC EcoZenith i250 L
kg
CTC EcoZenith i250 H
CTC EcoZenith i250 L
182
167
Width x Height x Depth
mm
595x1904x672
595x1654x672
Minimum ceiling height
mm
1925
1696
CTC EcoZenith i250
11
General Information
2.2 Table 230 V 1N~
CTC EcoZenith i250 H
Electrical Data
230V 1N~ 50 Hz
Electrical data
Rated power
kW
Immersion heater (steps: 3, 5, 7, 9, 12 kW)
kW
12,04
IPX1
CTC EcoZenith i250 H
Heating system
Max. operating pressure. thermal store (PS)
Max. temperature. thermal store (TS)
l
Max. temperature, hot water coil (TS)
2,5
110
See pressure drop diagram in the Pipe installation chapter
CTC EcoZenith i250 H
12
CTC EcoZenith i250 L
l
5,7
bar
10
°C
110
Other data
Weight
223
°C
Hot water system
Max. operating pressure, hot water coil (PS)
CTC EcoZenith i250 L
bar
Pressure drop for mixing valve heating
Water volume, hot water coil (V)
12,04
0-12
IP class
Water volume. thermal store (V)
CTC EcoZenith i250 L
kg
CTC EcoZenith i250 H
CTC EcoZenith i250 L
182
167
Width x Height x Depth
mm
595x1904x672
595x1654x672
Minimum ceiling height
mm
1925
1696
CTC EcoZenith i250
General Information
1748 / 1497
1904 / 1654
3. Measurements
10
Sockets (3/4) for
energyflex
(Behind front plate)
192
83
618 / 366
10
595
672
595
1. Bleeding
7. From heat pump Ø22 (CTC EcoZenith i250L)
5
6
2
3
423
9
423
6. Radiator return Ø22 mm/expansion connection
4
344
5. Radiator primary flow 22 compression
190
4. Hot water Ø22
1
344
3. Cold water connection Ø22
114
190
2. Safety/connection waste pipe 3/4” 22
8
7
114
10
8. To heat pump Ø22 (CTC EcoZenith i250L)
9. Lifting sleeve 3/4” BSP
10.Sockets for connection of external systems/
Energyflex
133
69
55
221
133
69
55
221
CTC EcoZenith i250
13
General Information
4. CTC EcoZenith i250 design
The picture below shows the basic construction of CTC EcoZenith i250.
If a heat pump is connected, the energy in the air or bedrock/ground is drawn
up by the cooling system. The compressor then increases the temperature
to a usable level. Afterwards it releases the energy for the heating system
and hot water. The built-in immersion heaters help when additional heat is
needed or when a heat pump is not connected.
Fresh Water Connections
Here you connect the
property’s fresh water
connections. The cold water
is fed down and heated in
the lower part of the coiling.
Bivalent Mixing Valve
The automated mixing valve
ensures that an even heat is
continuously supplied to the
radiator system.
Upper part
In the upper part of the coil
the hot water is then heated
to the desired temperature.
Insulation
The heat pump’s tank is
insulated with die-cast
polyurethane foam for minimal
heat loss.
Finned Coil for Hot Water
The EcoZenith i250 is
equipped with a welldimensioned finned coil made
of copper. Since hot water is
not stored, there is no risk of
legionella bacteria.
Upper immersion heater
Built-in upper immersion
heater. When connected to
a heat pump, the immersion
heater acts as additional heat.
Lower immersion heater
Built-in lower immersion
heater. Not used in normal
operation when the heat
pump is connected.
Draining/expansion vessel
connection
Two connections in the
lower part of the product
where water from the boiler
and radiator system can be
drained and an expansion
vessel connected.
14
Heat pump pipes
The CTC EcoZenith i250 L
is equipped with connection
pipes for top connection
CTC EcoZenith i250
Lower part
In the lower part of the coil
the hot water is pre-heated by
the water heated by the heat
pump. The major section of
the coil is located in this part.
Expansion connection
15 mm.
Diverting valve
The heated water from the
heat pump heats up the
upper or lower part of the
tank alternately.
Heat medium pump
The adjustable-speed charge
pump transports the cold
water from the boiler to the
heat pump where the energy
from the air or bedrock/ground
is drawn up and taken back to
the boiler.
The boiler is supplied with a
circulation pump for a heat
pump of up to 12 kW!
General Information
5. Parameter list
Radiator system
Factory
value
Max. primary flow ºC
55
Min. primary flow ºC
Off
Heating off, out ºC
18
Heating off, time
120
Inclination ºC
50
Adjustment ºC
0
Room temp. reduced
-2
Primary flow reduced
-3
Anti Water Hammer
No
DHW increase
Yes
CTC EcoPart heat pump
Compressor
Brine pump on
Tariff HP
Minimum run time
CTC EcoAir heat pump
Compressor
Factory
setting
Auto
Off
6
Factory
setting
Tariff HP
Off
6
Factory
value
Boiler upper ºC
50
Boiler upper add ºC
57
Boiler upper extra DHW ºC
60
Boiler upper max kW
5.5
Boiler lower ºC
55
Boiler lower kW
6.0
Delay mixing valve
180
Main fuse A
20
Input voltage
3x400 V
Tariff EL
Upper tank
Stop temp. HP ºC
User (set) value
Blocked
-15
Immersion heaters
User (set) value
Blocked
Min. outdoor temp ºC
Minimum run time
User (set) value
User (set) value
Off
Factory
value
User (set) value
Max.
Start/stop diff. upper ºC
7
Max. time upper tank
20
Max. time lower tank
40
CTC EcoZenith i250
15
General Information
1
2
Room temperature settings
Room temp.
Def heating circuit 1
6. Control system
The CTC EcoZenith i250 has an advanced yet
straightforward control system with a touchscreen on
which all settings are entered directly.
The CTC EcoZenith i250 control system:
• monitors all functions in the system tank, heat
pump and heating system.
Heating
Heatingcircuit
circuit11
Room sensor 1
Type
Action circuit 2 (50)
Heating
Disconnect
Status
Start
menu
Start
menu
1
2
Associated
Level
of signal
CTC EcoZenith
Battery
Night reduction
Version
• Facilitates the setting of values and troubleshooting
1
in a simple and well-structured way.
Yes
Yes
Wireless
Monday 09:35
85%Holiday
x0102
Selecting DHW comfort
Room temp.
DHW
DHW
• Permits individual settings
• Displays desired values, such as temperatures,
operation times, energy consumption and fault
signals.
Sett. D
Charge sta
Charge sto
Charge tem
Operation
Installer
Test D
1
2
1
2
Extra
Hot water 22,2 ºC
0.0 hours58 ºC
21,2 ºC
On
Pump H-ta
Temperatu
H-tank (B6)
-5 ºC
Temperature
Define Cooling
Normal
2
Room
temperature settings
Cooling
Factory values
The CTC EcoZenith i250 is delivered with set factory
values which are suitable for a standard house with
a standard radiator system. The CTC EcoZenith i250
automatically adjusts the water temperature to the
primary flow’s current heating requirement. This is
monitored by the control system, which continuously
ensures that you are provided with optimum function
and economy. These values are easy to change as and
when required. Ask your installer to help you determine
the correct values.
Heat pump
On delivery the CTC EcoZenith i250 is ready for
connection to a CTC heat pump – either the CTC EcoAir
400 outdoor air heat pump, the CTC EcoAir 520M or
the CTC EcoPart 400 bedrock/ground source heat
pump.
NB: Note that the connection of the CTC EcoAir 520M
inverter is dealt with in a separate section!
This means that the control system already contains all
the controls for the heat pump. When the heat pump
has been defined (On) the CTC EcoZenith i250 senses
which heat pump has been connected
Installer/Define/Heat pump
Once this has taken place the menus for the heat pump
are displayed. On delivery the compressor is blocked
and must be set to permitted. This is done under the
Installer/Settings/Heat pump menu.
Menu structure
The product’s menus are described on the following
pages. First there is an overview and then each menu is
described in detail.
No
Common heating/cooling
No
Condense
secured
No
Roompipe
temp.
Room temp. cooling Weekly schedule
25.0
Heating circuit 1
Heating system data
Heating circuit 2
(50)
Operation data system
1
Night reduction
Activate
Level of signal
Phone Number
1
Selecting
DHW
Phone Number 2
DHW
Hardware
Version
Software Version
Yes
comfort
Cooling
Temperature
Installer
Normal
Operation data system
Weekly schedule
Settings
Define system
Service
Heating system data
Software
displaydata
PCB: system
20120205
Operation
Software HP PCB:
01234
The screen shows operating information with the
CTC EcoPart heat pump connected.
Installer
CTC EcoZenith i250
Heating cir
+46712345678
----------------1
1
1
9
Extra
The
screen shows operating information with the
0.0 hours
Hot water
CTC
heat pump connected.
On EcoAir
Installer
settings menu
Time/Language
2
Room
Holiday
Def CTC SMS
Installer settings menu
16
1
2
Nigh
CTC EcoZenith
Monday 09:35
General Information
Room temp.
DHW
Operation
Installer
Room temp.
Room temp.
DHW
DHW
Operation
Operation
Installer
Installer
DHW
21,2 ºC
Operation
58 ºC
Installer
-5 ºC
21,2 ºC
21,2 ºC
58 ºC
58 ºC
-5 ºC
-5 ºC
21,2 ºC
58 ºC
-5 ºC
1
2 1
Room
temp.
22,2
1
2 1 ºC
7. Menu overview
1
1
1
1
1
1
2 1 ºC
22,2
22,2
2 1ºC
2
2
2
2
22,2 ºC
2
Heating circuit
2
1
Room temp.
1
2
DHW
1
Installer
2
22,2 ºC
1
Operation
21,2 ºC
58 ºC
-5 ºC
1
2
(50)
2
2
Night reduction
Holiday
2
Night reduction
Night reduction
Holiday
Holiday
Night reduction
Holiday
1
1
1
1
1
(50)
Heating circuit 2 (50)
Heating circuit
2 (50)
1
Monday 09:35
1
2
Room
temperature
Room
temperature settings
settings
2
Room temperature settings
2
Room
temperature
Room
temp. settings
RoomRoom
temperature
temp. settings
Room temp.
Heating
circuit
1
Room
temp.
Heating circuit 1
Heating circuit 1
Heating
Heating circuit
circuit 2
1
Start menu
CTC EcoZenith
1
1
1
Selecting DHW comfort
SelectingDHW
DHW comfort
comfort
Selecting
DHW
Selecting
DHW comfort
DHW
Selecting
DHW comfort
DHW
Extra
DHW
0.0 hours
Hot water
Extra
2
On water1
Extra
0.0 hours
Hot
0.0 hours
Hot
water
Temperature
Extra
On
On
0.0 hours
Hot
water
Normal
Temperature
Night
reduction
heat circ. 1
Temperature
On
Normal
Normal
Temperature
Weekly program
Day by day
Normal
Monday
00 - 06
22
TuesdayWeekly schedule 00
Wednesday
Weekly schedule 00
Thursday
Weekly schedule 00
Friday
00
Weekly schedule 00
Saturday
system Sunday
data
00
-
06
06
06
06
08
08
22
22
22
23
23
22
Block
Sunday
Friday
---------------
NR
22:00
14:00
00:00
00:00
Heating
Heating system
data
1
2
Operation
data system
Heating
system
Heating
systemdata
data
Operation
data system
Heating
system data
Operation data system
Night reduction heat circ.
Operation data system
Weekly program
Decrease
Increase
Decrease
Increase
2
Room temperature settings
NR
-
24
24
24
24
24
24
24
Room temp.
1
2
Heating circuit 1
Heating circuit 2
1
(50)
2
Night reduction
Holiday
Selecting DHW comfort
DHW
Extra
Hot water
On
0.0 hours
Temperature
Normal
Weekly schedule
Installer settings menu
Holiday
Installer settings menu
Installer
settings menu
Installer
Installer
settings
menu
Installer
Installer
settings
menuperiod
Holiday
Installer
Installer
3 days
Time/Language
Settings
Define system
Service
Time/Language
Time/Language
Settings
Settings
Define system
Define system
Service
Service
Time/Language
Settings
Define system
Service
Software display PCB:
20120205
Software HP PCB: Weekly program
01234
Software display PCB:
20120205DHW
Software
PCB:
20120205
Software display
HP PCB:
01234
Weekly program01234 Day by day
Software
PCB:
Software HP
display
PCB:
20120205
Monday
06 - 09
Software HP PCB:
01234
Tuesday
07 - 09
Wednesday
08 - 09
Thursday
08 - -Friday
08 - -Saturday
10 - 12
Sunday
10 - 12
18
----20
20
DHW
- 21
- -- -- 21
- 21
- 23
- 23
CTC EcoZenith i250
17
Room temp.
DHW
Operation
Installer
General Information
1
1
2
1
21,2 ºC
58 ºC
Night reduction heat circ.
-5 ºC
2
1
Room temp.
Start menu
CTC EcoZenith
1
Weekly program
Decrease
Increase
Decrease
Increase
2
art menu
CTC EcoZenith
Heating circuit 2
1
Room temp.
DHW
2
Start menu
CTC EcoZenith
Night reduction
1
Installer
Monday
Holiday
1
09:35
2
22,2 ºC
DHW
Room temp.
Operation
21,2 ºC
Operation
58 ºC
Installer
-5 ºC
1
Weekly
program
Day by day
NR
2
Monday
00 - 06
22 - 24
Tuesday
00 -circ.
06 1 22 - 24
Night
reduction heat
Wednesday
00 - 06
22 - 24
- 06
22 - 24
1 Thursday
2
HolidayDay00
Weekly
program
by
day
NR
Friday
00 - 06
23 - 24
Monday
00 -0006- 08 2223
- 24
Saturday
- 24
Tuesday
00 -0006- 08 2222
- 24
Sunday
- 24
Holiday
period
days
Wednesday
00 - 06 heat
22circ.
-324
Night
reduction
1
2
Thursday
00 - 06
22 - 24
Weekly program
NR
Friday
00 - 06 Day by
23day
- 24
Saturday Monday
00 - 08 00 - 06
23 - 2422 - 24
- 06
Night reduction
Sunday Tuesday
00 - heat
08 00circ.
22 - 2422 - 24
2
Selecting DHW comfort
2 21
1 1
2
Room temp.
DHW
Operation
DHW
22,2
ºC temperature
21,2 ºC settings
58 ºC
Room
Room
temp.
Extra
1
2 1
Hot water 22,2 ºC
-5 ºC
0.0 hours
58 ºC
2
21,2 ºC
On
Installer
1
Wednesday
Thursday
Weekly
program
Friday
Decrease
Saturday
Increase
Sunday
Decrease
Night
reduction
2
Increase
-5 ºC
Normal
Friday
Increase
Holiday
Saturday
Decrease
Sunday
Increase
(50)
Room temperature settings
1
Room temp. 2
Heating circuit 1
1
1
Weekly schedule
Night reduction
Heating circuit 2
Holiday
2
1
(50)
Heating system data
Selecting DHW comfort
1
Night
reduction
DHW
Night reduction
Holiday
DHW comfort
Selecting DHW
comfort
DHW Normal
DHW
Extra
Hot water
On
Temperature
Normal
0.0 hours
0.0 hours
Temperature
Installer
Heating
system
data
Normal
Operation data system
Weekly schedule Weekly schedule
Time/Language
Settings
eating system Heating
data system data
Define system
Software display PCB:
20120205
Operation
data system
Software
HP PCB:
01234
Operation data system
-- - 21
14:00
20 - 23
00:00
20 - 23
00:00
3 days
2
Holiday Operation data EcoZenith
Heating circuit
60 Weekly program DHW
Weekly program
Day by day
DHW
40
program
Monday Weekly
06 - 09 Day by
18day
- 21 DHW
Tuesday Monday
07 - 09 06 - 09
-- - --18 - 21
20
Tuesday
Wednesday
08 - EcoZenith
09 07 - 09
-- - ---- - -Operation data
08 - 09
Thursday Wednesday
08
--- 21-- - -0
Thursday
08 - --- - 21
FridayStatus
08
--- 21
HP
Friday
08upper
- -- tank-- - 21
Saturday
10
12
20
23
Tank-20
upper °C
49 (58)20 - 23
Saturday
10 - 12
16
Sunday
10 20
- 12 10 - 012
20
23204 - 23
TankSunday
lower °C
42 -(45)
Weekly schedule
Installer
settings menu
On
24
24
24
24
24
Weekly program
Day by day
DHW
Monday
06 - 09
18 - 21
Tuesday
07 - 09
-- - -Wednesday
08 - 09
-- - -Thursday
08 - --- - 21
Friday
08 - --- - 21
heating
Saturday Operation data
10 - 12
20 - 23
Weekly
program DHW
Sunday
10 - 12
20 - 23
T ºC
electing DHW
comfort
Temperature
Extra
Hot water
-
3
0.0 hours
On
22
22
23
23
22
Status
HP upper tank
Tank Holiday
upper °C
49 (58)
Holiday period
days 42 (45)
Tank lower °C
Electric power kW
0.0+2.5 Stored oper data
Current period
L1/L2/L3
0.0
0.0 0.0
Holiday
3 days
Diff func. Pump / ºC
On 32
Weekly
Pool
ºC program DHW
Off 22(20)
system
2 Holiday
Extra
Hot water
08 - -Friday
10 - 12
-------10 - 12
--------
Holiday period
Heating circuit 1
Heating
circuit 2 data
(50)
2
Operation
00 - 06
Block00 - 06
NR
00 - 06
Sunday
22:00
00 - 08
Friday
14:00
00 - 08
-------heat
circ. 00:00
-------00:00
Weekly program DHW
Weekly program
Block
NR
by day
DHW
Decrease Weekly program
Sunday Day
22:00
Night reduction06heat
Monday
- 09circ. 18 - 21
Increase
Friday
14:00
1
2
Tuesday
07 - 09
-- - -Decrease Weekly
-------- Block
program
Wednesday
0800:00
- 09 NR-- - -Increase Decrease
-------- Sunday
Thursday
0800:00
- -- 22:00
-- - 21
Heating
circuit 1
Temperature
oom temperature
settings
1
2
Room
temp.
Heating circuit 2
NR
22:00
14:00
00:00
00:00
1
Monday 09:35
(50)
Block
Sunday
Friday
---------------
Night reduction heat circ. 1
2
Monday 09:35
Heating circuit 1
2
23 - 24
23 - 24
22 - 24
2
Room temperature
temperature settings
settings
1
00 - 06
00 - 08
00 - 08
2
22,2 ºC
1
Friday
Saturday
Sunday
OutkW Room1
Electric power
Current L1/L2/L3
Diff func. Pump / ºC
Pool ºC
Service
12
Return
Room2
Prim2
0.0+2.5
Stored oper data
0.0 0.0 0.0
On 32
Off 22(20)
Operation
data EcoZenith Heating circuit
Operation
data EcoZenith
Status
HP upper tank
Status
HP upper tank
Tank upper °C
49 (58)
Tank upper °C
49 (58) 42 (45)
Tank lower °C
Tank lower °C
42
(45)
Electric power kW
0.0+2.5 Stored oper data
Electric power
kWL1/L2/L3
Operation
data heating0.0+2.5
Stored
Current
0.0 0.0
0.0 oper data
Current
Diff func. Pump / ºC 0.0 0.0 0.0On 32
T ºC L1/L2/L3
Diff func.
On Off
32 22(20)
60 Pump
Pool ºC/ ºC
Pool ºC
Off 22(20)
40
Installer settings menu
Heating circuit
Heating circuit
20
Installer
0
-20
18
8
Prim1
CTC EcoZenith i250
16
Operation data heating
20
0
T ºC
Out data
Room1
Prim1
Operation
heating
60
T ºC
4
Return
8
Room2
12
Prim2
Weekly program
Decrease
ating system data
Normal
Increase
Decrease
Operation data system
Increase
Block
Sunday
Friday
---------------
Temperature
07 - 09
-- - -OperationTuesday
data EcoZenithCompressor
NR
22:00
14:00
00:00
00:00
Current
L1 oper data 4.0
0.0+2.5
Stored
0.0 0.0 0.0
On 32
Off 22(20)
Electric power kW
Current L1/L2/L3
Diff func. Pump / ºC
Pool ºC
Weekly schedule
1
2
Operation data EcoZenith
Heating circuit
Heating system data
data
Installer
HP
upper tank
Holiday
Operation
data system
3 days
Holiday period
i
T ºC
60
Status
Tank upper °C
Tank lower °C
Electric power kW Time
L1/L2/L3
OperationCurrent
data heating
Diff func. Pump / ºC Date
Pool ºC
49 (58)
42 (45)
0.0+2.5 Stored oper
21:34
data
0.0 0.0 0.0
On 32
2012-02-05
Off 22(20)
Heating circuit
40
taller settings menu
20
Installer
0
-20
i
i
Time/Language
Settings
Total Operation time
Block Heating
NR circuit 1
Sunday Room
22:00sensor 1
Friday Type
14:00
-------00:00
-------00:00
oliday
-20
-20
3 days
period
16
Out1
Heating circuit
Room sensor 1
Type
Action
Disconnect
Installer
Status
Associated
Level of signal
Time
Battery
Version
20
Room1
Heating circuit
Date
0
Compressor
Primary flow1 ºC
Return pump
flow ºC
Charge
Radiator
pump
Brine
pump
Mixing
valve
HP
in/out °C
4
21:34 85%
x0102
2012-02-05
8
Room2
12
Prim2
On
33(34)
31
On 47%
Till
On
Open
35.5 / 42.3
180
33(34)
4.0
Från
DHW
18 - 21
-- - --- - --- - 21
-- - 21
20 - 23
20 - Installer
23
Define Cooling
Settings language
Cooling
12
Return
8
Room2
Prim2
Dansk
Heating circuit 1
Heating circuit 2
1540pump
Heat
Electric heater
Upper tank
Remote control
None
Communication
Solar panels
Diff thermostat function
Pool
Save settings
Load settings
Load factory settings
Define system
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
Diff thermostat function
Pool (G50, G51, B50)
Charge start diff temp ºC
Charge stop diff temp ºC
Charge temperature °C
No
No
Installer
7
3
60 Service
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
Svenska
Nederlands
English
Test Diff thermostat function
Pump H-tank (G46)
Temperatures
H-tank
Suomi(B6) ºC Française
No
English
4
Time
21:34
Sett. Diff termostat function
Date
2012-02-05
Settings language
Day by day
06 - 09
07 - 09
08 - 09
08 - -08 - -10 - 12
10 - 12
Prim1
Nederlands
Suomi
Française
14196
51
20
Settings
Heat
pump Circuit
Op. Heating
Installer
Yes
Wireless
eekly program DHW
12
Prim2
0
Room1
Total Operation time
Delay mixing valve
Primary flow 2ºC
Radiator pump 2
Mixing valve 2
Return
Yes
20
Total operation time h:
Max primary flow °C:
Consumtion kWh
Compressor:
Current L1
4.0
Prim1
Room2
Svenska
16
Stored oper data
On
On 47%
On
35.5 / 42.3
0
8
Installer
4
Return
Settings language
Out
Heat pump
Current
L1 circuit 1
Def
heating
Prim1
0
1540
Yes
Yes
Wire
Compressor
40
Charge
pump
Brine pump
20
HP in/out °C
0
Room1
20
Operation data heating
T ºC
60
T ºC
6020
40
Service
Day by day
DHW
06 - 09
18 - 21
07 - 09
-- - -08 - 09
-- - -08 - --- - 21
08 - --- - 21
10 - 12
20 - 23
Define
Service
10
- 12system20 - 23
Day by day
NR
00 - 06
22 - 24
00 - 06
22 - 24
PCB:
20120205
00 - 06 Software
22 -display
24
Operation
data01234
EcoZenith
PCB:
00 - 06 Software
22 -HP
24
Stored
oper data
00 - 06
23 - 24
ay
Status
HP upper tank
00 - 08
23
- 24
Tank
upper °C
49 (58)
00 - 08
22
- 24
Total
operation
time
h:
14196
Tank lower °C
42
(45)
Max primary
flow °C:
51
Electric
power
kW
0.0+2.5
Stored oper data
Consumtion
kWh
20
Current
L1/L2/L3
0.0 0.0 0.0
Compressor:
Diff func. Pump / ºC
On 32
ºC
Off 22(20)
Def heating
circuit 1
ght reduction heat circ. Pool
ay
16
Out
program
y
y
sday
ay
program
y
y
sday
ay
Operation data heating
Weekly program DHW
Installer settings menu
Define system
Weekly program
Installer
Monday
Tuesday
Wednesday
Thursday
Software display PCB:
20120205
Friday
Software HP PCB:
01234
Saturday
ght reduction heatTime/Language
circ. Sunday
1
Settings
program
se
e
se
e
On
Wednesday
08 - 09 pump
-- - -Charge
On 47%
Thursday
08 - --- - 21
On
Status
HP upper Brine
tank pump
Friday
08 in/out °C
- --- - 21
35.5 / 42.3
Tank upper °C Saturday
49HP
(58)
General
Information
10 - 12
20 - 23
Tank lower °C Sunday
42 (45)
10 - 12
20 - 23
Settings
Heating circuit 1
Deutsch
Off
Dansk 32
Norsk
CTC EcoZenith i250
19
Consumtion kWh
Compressor:
20
Total Operation time
1540
General Information
Heat pump
Installer settings menu
Installer settings menu
Compressor
Charge pump
Brine pump
HP in/out °C
On
On 47%
On
35.5 / 42.3
Current L1
4.0
Installer
Time/Language
Settings
Define system
Service
Installer
Software display PCB:
Software HP PCB:
Time
21:34
Date
2012-02-05
20120205
01234
Installer
Settings language
Svenska
Nederlands
English
Deutsch
Suomi
Française
Dansk
Norsk
Settings
Heating circuit 1
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
Upper tank
Remote control
None
Communication
Solar panels
Diff thermostat function
Pool
Save settings
Load settings
Load factory settings
Max primary flow °C
Min primary flow °C
Heating off, out °C
Heating off
Inclination °C
Adjustment °C
Room temp reduced °C
or
Primary flow reduced °C
>>
Service
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
20
CTC EcoZenith i250
-3
Def heating circuit 1
Define system
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
Diff thermostat function
Pool (G50, G51, B50)
55
Off
18
120
50
0
-2
Heating circuit 1
Room sensor 1
Type
No
No
Function test
Heating circuit
Heat pump
Valves
Electric heater
Solar
Diff thermostat function
Pool
Yes
Yes
Wire
ettings language
Sto
Pa
Sto
Sto
Settings language
General Information
venska
Nederlands
English
Deutsch
Svenska
Nederlands
English
Suomi
Française
Dansk
Norsk
Suomi
Française
Dansk
Settings
Deutsch
Norsk
Settings menu
Settings
ating circuit 1
Heating circuit 1
ating circuit 2
Heating circuit 2
at pump
Heat pump
ectric heater
Electric heater
pper tank
Upper
mote control
Nonetank
Remote control
None
ommunication
Communication
lar panels
Solar panels
f thermostat function
Diff thermostat function
ol
Pool
ve settings
Save settings
ad settings
ad factory settings Load settings
Load factory settings
Define system
Service
Room temp.
Room temp.
Room temp.
Heating circuit 1
Sav
Sav
Sav
Sav
Sav
Loa
Sav
Loa
Loa
1
Min primary flow °C
Off
flow °C
Heating off, out °C Min primary18
Heating off,120
out °C
Heating off
Heating off 50
Inclination °C
Inclination °C
Adjustment °C
0
Adjustment °C
Room temp reduced °C
-2
Holiday
orNight reduction Room temp reduced °C
Night reduction
Holiday
PrimaryNight
flowreduction
reduced °C or
-3
Holiday
Primary flow reduced °C
>>
>>
55
Off
18
120
50
0
-2
-3
Set. heat pump
Def
circuit 1
Set.heating
heat pump
Set. heat pump Def heating circuit 1
Compressor
Permitted
Heating
circuit
1 °C
1
Compressor
Permitted
Min outdoor
temp
-15Yes
circuit
12
Compressor
Room
sensor
1 °C Heating Permitted
Yes 1
Min
outdoor
temp
-15
Brine
pump
on
Auto
12
1
Min
temp °C Room sensor
-15
Brineoutdoor
pump on
Auto
Type
Wire
Tariff
HP
Off
2
BrineHP
pump
Auto
Type
Tariff
Off
Minimum
runon
time
6
Tariff
HP run time
Minimum
Minimum run time
Off
6
6
Hea
Hea
Flow
Hea
Flow
Flow
Yes
Yes
Wire
No
No
Function test
Electric heater Function test
Heating
circuit heater
Electric
Electric heaterHeating circuit
Heat pump
Service
nction test
Function test
arm log
Alarm log
ctory settings coded
Factory settings coded
uick start compressor.
ftware update, USBQuick start compressor.
Software update, USB
rite log to USB
Write log to USB
ontrol current sensors
Control current sensors
-installation
Re-installation
Heat pump
Boiler upper °C
50
Valves
Boiler
Boiler upper °C
upper
add °C
57
Valves 50
Electric
heater
Boiler
upper °C
50
Boiler
57
Boiler upper
upper add °C
extra DHW °C
60
Electric heater
Solar
Boiler
upper
add °C
57
Boiler
DHW °C
60
Boiler upper
upper extra
max kW
5.5
Solar
Diff
thermostat
Boiler
extra
DHW °C
60
Boiler
upper
maxfunction
kW
5.5
Boiler upper
lower °C
55
Diff
thermostat
function
Pool
Boiler
upper
max
kW
5.5
Boiler
55
Boiler lower
lower °C
max kW Pool
6.0
Boiler
lower
°C
55
Boiler lower max kW
6.0
Delay mixing valve
Boiler
lower
kW
Delay
mixing
valve
Main fuse
A max
Delay
mixing
Main
A valve
Input fuse
voltage
Main
Input
voltage
Tariff fuse
EL A
Input
Tariff voltage
EL
Tariff EL
Mix
Mix
Rad
Mix
Rad
Mix
Rad
Mix
Rad
Mix
Rad
LED
Rad
LED
LED
180
6.0
180
25
180
25
3x400 V
25
3x400
V
Off
3x400
V
Off
Off
Op. Heating Circuit
Def heating circuit 1
Heating circuit 1
Room sensor 1
Type
2
2
2
Holiday
Holiday
Holiday
Heating circuit
Heating circuit 1
(50)
Heating
circuitflow °C
1
(50)
Max
primary
55
Heating circuit 1
(50)Max primary flow °C
Define system
ating circuit 1
Heating circuit 1
ating circuit 2
Heating circuit 2
at pump
Heat pump
C SMS
CTC SMS
oling
Cooling
lar panels
Solar panels
f thermostat function
No
ol (G50, G51, B50) Diff thermostat
No function
Pool (G50, G51, B50)
1
1
1
Night reduction
Night reduction
Night reduction
Upper
Primary
flow1tank
ºC
Upper
tank
Return
flow ºC
Upper
tank
Radiator
pump
Stop
temp
HP °C
Mixing
valve
Stop
temp
HP °C
Start/stop
diff upper
Delay
mixing
valve ºC
Stop
temp
HP °C
Start/stop
diff
upper
Max
time
upper
tank ºC
Primary
flow
2ºC
Start/stop
diff
upper
ºC
Max
time
upper
tank
Max
time lower
tank
Radiator
pump
2
Max
time
upper
tank
Max
timevalve
lower2tank
Mixing
Max time lower tank
Yes
Yes
Wire
33(34)
31
Till
Open
180
33(34)
Från
S
Max
Max
7
Max
7
20
7
20
40
20
40
40
S
Def heating circuit 1
Heating circuit 1
Room sensor 1
Type
Action
Disconnect
Status
Associated
Level of signal
Battery
Version
Sett. Diff termostat function
Yes
Yes
Wireless
Charge start diff temp ºC
Charge stop diff temp ºC
Charge temperature °C
7
3
60
85%
x0102
CTC EcoZenith i250
Test Diff thermostat function
21
Current L1 Current L1 4.0
Svenska
4.0
Nederlands
English
Night reduction
General Information
1
2
Suomi
Installer Installer
Française
Dansk
Deutsch
Holiday
Norsk
Room temp.
Time
Time
Settings21:34
21:34
Heating circuit 1
Heating circuit 1
(50)
Date
2012-02-05
Date
2012-02-05
Heating circuit
2
Heat pump
Electric heater
Upper tank
Remote control
None
Communication
Solar panels Night reduction
Diff thermostat function
Pool
InstallerSave
Installer
settings
Loadtosettings
Set.the
heat
pump
Menu
define
system
Load factory
settings
Settings language
Settings
language
Svenska
Compressor
1
Min outdoor temp °C
2
Brine pump on
Define
system
Tariff HP
Nederlands
English
Svenska
Nederlands
Minimum
run
time
Permitted
-15
Auto
Off
Deutsch
English
Deutsch
6
Heating circuit 1
Heating circuit 2
Heat pump
Suomi
Française
Dansk
Norsk
Suomi
Dansk
CTC
SMS Française
Cooling
Solar panels
Settings
DiffSettings
thermostat function
No
Heating circuit
1 (G50,
Heating
circuit
1 B50)
Electric
heater
Pool
G51,
No
Heating circuit
2 circuit 2
Heating
Heat pump Heat pump
Boiler upper °C
Electric heater
Electric heater
Boiler upper add °C
Upper tank Upper tank
Boiler upper extra DHW °C
Boiler
upper max None
kW
Remote control
None
Remote control
Boiler lower °C
Communication
Communication
Service
Boiler lower max kW
Solar panels
Solar panels
Delay mixing valve
Diff thermostat
function
Diff thermostat
function
Main
fuse
A
Function
test
Pool
Pool
Input voltage
Alarm
log
Tariff EL
Save settings
Save settings
Load settings
Load
settings
Factory
settings coded
Load factory
settings
Load
factory
Quick
start settings
compressor.
50
57
60
5.5
55
6.0
180
25
3x400 V
Off
No
No
No
25.0
Heating circuit 1
Service
Function test
Function test
Alarm log Alarm log
Factory settings
coded
Factory
settings coded
Quick start Quick
compressor.
start compressor.
Software update,
USB
Software
update, USB
Write log toWrite
USB log to USB
Control current
sensors
Control
current sensors
Re-installation
Re-installation
22
CTC EcoZenith i250
3-way valve
Max primary flow °C
Min primary flow °C
Heating off, out °C
Heating off
Inclination °C
Define Cooling
Adjustment °C
Room temp reduced °C
Cooling
No
Def CTC SMS
or
Common heating/cooling
No
Primary flow No
reduced °C
Condense pipe secured
Activate
Yes
Room temp. cooling
25.0
Def Heat pump >>
Level of signal
Phone Number 1
Heat
pump
Phone
Number 2
Flow/level switch
Hardware Version
Software Version
+46712345678
Off----------------None
Def
circuit
1 heating
1
1
9
Heating circuit 1
Room sensor 1
Type
55
Off
18
120
50
0
-2
Tes
1
2
Pump H
Temper
H-tank (
Roo
-3
Heating c
Test Ele
1
Yes
Yes
Wire
Electric heater
Cooling
Electric heater
Electric heater
Electric heater
Electric heater
1 Electric
2 heater
Electric heater
Nig
Ro
Def CTC SMS
Activate
Yes
Level ofOperation
signal
data
system
Heating circuit
1 circuit 1
Heating
Test Heating
Phone
Number 1circuit
+46712345678
Number
2
MaxPhone
primary
flow °C
55
Max
primary
flow °C----------------55
Mixing
valve1 Version
Open1 Off1
MinHardware
primary
flow °C
Min
primary flow °C
Off
Rad Software
pump1 Version
On 1
Heating
off,Heating
out °C off, out °C
189
18
Mixing
valve2
Off
Heating
120
120
Rad
pump2off Heating off
Off
Function
test
LED
room sensor
Inclination °C
50
Inclination °C On
50
Adjustment °C
0
Adjustment °C
Heating circuit
Room tempRoom
reduced °C
-2
temp reduced °C
Heat pump
or
or
Valves
Primary flow
reduced °C
-3
Primary
flow reduced °C
Electric heater
>>
>>
0
-2
Heating
Alarm lo
Cooling
Latest alarm:
Low brine flow
Stored alarms:
Wrong phase o
Com. err m. pro
N
-3
Solar
Max
7
20
40
Heating circuit
1 circuit 1
Heating
Room sensor
1 sensor 1
Room
Type
Type
Yes
Yes
Wire
No
No
Service menu
Service
Test val
Diffdata
thermostat
Operation
systemfunction
Pool1 circuit 1
Def heating
circuit
Def
heating
Software update, USB
Write
log to
USB tank
Upper
Define system
Define
system
Control current sensors
Stop temp
Re-installation
Heating circuit
1 circuit
Heating
1 HP °C
Start/stop diff upper ºC
Heating circuit
2 circuit
Heating
2
Max time upper tank
Heat pump Heat pump
Max time lower tank
CTC SMS CTC SMS
Cooling
Cooling
Solar panels
Solar panels
Diff thermostat
function function
No
Diff thermostat
Pool (G50, G51,
Pool B50)
(G50, G51, B50) No
Norsk
H-tank (B6
85%
x0102
Cooling
Common heating/cooling
Condense
Installer pipe secured
Room temp. cooling
Save settings
Save settings
Load factory settings
Holiday
Heating
Cable
Pump
H-ta
4-way
valve(Y1
Temperatu
Status
Associated
Level of signal
Battery
Define Cooling
Version
Function test
Function test
Heating circuit
Heating circuit
Heat pump Heat pump
Valves
Valves
Electric heater
Electric heater
Solar
Solar
Diff thermostat
function function
Diff thermostat
Pool
Pool
Yes
Yes
Wire
Factory
Code
Upper tank
Lower tank
Compressor op
Expansion valv
Log compresso
Cooling
General Information
8. Detail Description Menus
Start menu
CTC EcoZenith
All the settings can be configured directly on screen
using the well-structured control panel. The large icons
operate as buttons on the touch display.
Operational and temperature information is also
displayed here. You can easily enter the different menus
to find information on the operation or to set your own
values.
Room temp.
1
8.1 Start menu
This menu is the system’s start menu. This provides an
overview of the current operation data.
Monday 09:35
2
1
DHW
Installer
2
22,2 ºC
1
Operation
21,2 ºC
58 ºC
-5 ºC
2
Room temperature settings
The system returns to this menu if no buttons are
pressed within 10 minutes. All other menus can be
accessed from this menu. NB: Some menus are only
shown if a heat pump is installed.
Room temp.
8.2 Description
of icons
Settings for raising or lowering
the
temperature indoors and also for scheduling
temperature changes.
DHW
Settings for DHW production.
Operation
This displays current operational data for
both your heating system and heat pump.
Historical operational data is also available.
Installer
This option is used by the installer to
configure the settings and servicing for your
heating system.
1
Room
temp. Radiator system 1
2
If radiator system 1 is defined, the current
room temperature is displayed here.
Room temp.
Return
The Return button takes you back to the
previous
level.
Heating circuit
1
OK
(50)
The OK button is used to mark and confirm
text and options
in the menus.
1
2
Heating circuit 2
NightNight
reduction
reduction
Holiday
This schedules a temperature reduction at
night if selected.
Holiday
Selecting DHW
comfort
You can use this to reduce the room
temperature permanently, e.g. during holidays
DHW
when the house is unoccupied.
Extra
Weekly
Hot water
program
0.0 the
hours
This is used to reduce
temperature for a
On
few days, for instance if you commute every
Temperature
week.
Normal
Stored operation data
This displays historical data.
Weekly schedule
1
2
Room temp. Radiator system 2
If radiator system 2 is defined, the current
room temperature is displayed here.
Tank temperature
This displays the current temperature in the
upper part of the tank.
Outdoor temperature
This displays the current outdoor
temperature.
Home
The Home button takes you back to the Start
menu.
Time/Language
This is used to set the date, time and the
language
Heating system
datayou want the menu to be displayed
in.
Operation
data system
Settings
The settings for operation of EcoZenith and
the system are usually configured by the
installer.
Define system
The heating system’s structure can be
adjusted/modified using this option.
Service
Advanced settings are configured by the
appropriate technical person.
Installer settings menu
Installer
CTC EcoZenith i250
23
General Information
1
2
Start menu
CTC EcoZenith
Room temp.
8.3 Room temp.
Heating circuit 1
This is used to set the desired
room temperature. Use
Yes
Yes
minus buttons
to set the temperature
Wire
you want, which gives you the “setpoint” temperature,
shown in brackets. You can see the current value next
to the brackets.
Primary flow1 ºC
33(34)
Return flow ºC
31
Room
temp.
DHW
Radiator pump
Till
Mixing valve
Open
Delay mixing valve
180
Primary
flow
2ºC 2 33(34)
1
2 1
Night
reduction
Radiator pump 2
Från
22,2
ºC
21,2 ºC
reduction
MixingNight
valve
2
Heating circuit 1
Room
sensor
1
the plus
and
Type
If two radiator systems are installed, the values for both 1
are displayed.
1
Def heating circuit 1
You can select Room sensor No under the Installer/
Define system/Radiator system menu. This can be
Heating circuit 1
Yes
donesensor
if the1room sensor is awkwardly
positioned, if the
Room
Yes
Type
floor heating control has its ownWireless
room sensors or if you
Action
Disconnect
use a fire place or open stove. The alarm LED on the
Status
room sensor still functions as normal.
Associated
1
Define Cooling
8.3.1 Setting a room temp. without a
(this can be
selected from the Installer/Define/Radiator system
menu), the room temperature is adjusted using
this option, which displays the setting range as a
percentage. (50) denotes default setting; the heat can
be increased or decreased in variable adjustments from 1
this value. If this range is not sufficient, the basic setting
must be adjusted under the Installer/Settings/Radiator
system
menu.
Def CTC
SMS
Activate
Yes
Change
Level
of signalthe value in small steps each time (approx. 2
Phone
to 3Number
steps)1and wait for+46712345678
the result (approx. one day), as
Phone Number 2
----------------there is a delay in the system responding.
Hardware Version
1
1
Software Version
1
9
Several adjustments may be necessary at different
outdoor temperatures, but you will gradually achieve the
right setting that will not need to be changed.
24
CTC EcoZenith i250
Holiday
Installer
58 ºC
Holiday
-5 ºC
The
example above shows that the room temperature is 22.4
2
°C and the desired value (setpoint) is 23.5 °C.
D
2
S
Sav
Sav
Loa
Room temp.
fire or open stove 85%
only occasionally, the
x0102
can affect the room
sensor and reduce
the temperature supplied to the radiators. It can then
get cold in the rooms in other parts of the house. The
room sensor can temporarily be deselected during
1
the firing process. The EcoZenith i250 then provides
heating to the radiators using the set heating curve. The
radiator thermostats reduce the heating supplied to the
section of the house where a fire is burning.
Cooling
No
room sensor
Common heating/cooling
No
Condense
secured
No installed
If a roompipe
sensor
has not been
Room temp. cooling
25.0
Operation
Room Room
temperature
temp.settings
Level of signal
If you use the
Battery
Version
firing process
Operation data system
MB
Ba
Pa
S
St
Op. Heating Circuit
Def heating circuit 1
If you want to schedule a temperature reduction,
you can continue to the Night reduction or Holiday
submenus.
Monday 09:35
1
(50)
2Heating
Sett.circuit
Diff termostat
function
Heatingstart
circuit
Charge
diff1 temp ºC
Charge stop diff temp ºC
Room
temp.°C
Charge
temperature
Heating circuit 2 (50)
1
Heating circuit
1
7
3
60
2
Night reduction
MB
Ba
Pa
Sto
Holiday
Night reduction
Holiday
The example above shows how it operates with two radiator
systems.
Radiator
Set.
heat system
pump 1 with a room sensor and radiator
system 2 without one.
Selecting
DHW
comfort
Night
reduction
Compressor
Permitted
1
Min DHW
outdoor temp °C
-15
22
Brine pump on
Auto
Tariff HP
Off
Test run
Difftime
thermostat function
Minimum
6
Extra
hours
Hot
water
Room
temp.
Pump H-tank (G46)
Off
On
Temperatures
H-tank (B6) ºC
32
Temperature
Holiday
Hea
Flo
0.0
Heating circuit 1
Normal
Sav
Sav
Loa
(50)
Weekly schedule
Electric heater
Night reduction
Boiler upper °C
Holiday
50
57
The
example
shows how it60operates with a radiator
Boiler
upper above
extra DHW °C
Boiler upper
maxsystem
kW
5.5a room sensor.
system.
Radiator
1 without
Operation
data
system
Boiler lower °C
55
2
Boiler lower max kW
6.0
Set.
heat
pump
Delay mixing valve
180
Main fuse A
25
Input
voltage
3x400 V
Compressor
Permitted
Room
temp.
1
Tariff
EL
Off
Min outdoor
temp °C
-15
2
Brine pump on
Auto
Tariff HP
Off
Heating
circuit
1
Minimum run time
620.2 (20.0)
Boiler upper
add °C
Heating
system
data
Upper
Cooling
tank
Stop temp HP °C
Start/stop diff upper ºC
Max time upper tank
Night reduction
Max time
lower tank
Installer
settings
menu
Hea
Flow
20.2 (20.0)
Max
7
20
40
Holiday
Electric
heater
Installer
The example
above
shows how it operates with a radiator
system and cooling.
Boiler upper °C
Boiler upper add °C
Boiler upper extra DHW °C
Boiler upper max kW
Boiler
lower °C
Time/Language
Settings
Boiler lower max kW
Delay mixing valve
Main fuse A
Mix
Rad
Mix
Rad
LED
50
57
60
5.5
55
Define
system
6.0
180
25
Service
Mix
Rad
Mix
Rad
LED
General Information
8.3.2 Outdoor Sensor/Room Sensor
Faults
!
If a fault occurs with an outdoor sensor, the product
triggers an alarm and an outdoor temperature of -5 °C is
simulated so that the house does not get cold.
The thermostats of the radiators
must be fully open and well
operating when the system is
tuned.
If a fault occurs with a room sensor, the product triggers
an alarm and automatically switches to operating
according to the set curve.
1
8.3.3 Night reduction temperature
enu
coZenith
Night reduction heat circ. 1
Monday 09:35
m temp.
DHW
enu
2 1
coZenith
You use this menu to activate and set a reduction in
the temperature at night. A night reduction means that
you reduce the temperature indoors during scheduled
periods, for example at night.
Operation
1
Installer
The value by which the temperature is reduced, -Room1
temp. red./Prim. flow red., is set under Installer/
Settings/RadiatorMonday
system/ 09:35
21,2 ºC
58 ºC
-5 ºC
Factory setting: -2/-5 °C.
2
22,2 ºC
The options in the night reduction menu are: Off, Day
by Day or Block. If you select Off, no reduction is made
at all.
emperature settings
m temp.
DHW
oom temp.
2
1
2
2
22,2 ºC
circuit
1
Operation
Installer
Day by day menu
1
You use this menu to schedule a reduction on the days
of the week. This schedule is repeated every week.
1
21,2 ºC
58 ºC
-5 ºC
Block
This menu allows you to set a reduction for a few
circuit 2 (50)
days during the week, for example, if you are working
elsewhere on weekdays and at home at weekends.
mperature settings
1
2
Day by day
00 - 06
00 - 06
00 - 06
00 - 06
00 - 06
00 - 08
00 - 08
NR
22
22
22
22
23
23
22
-
24
24
24
24
24
24
24
Night reduction heat circ. 1
e.g.
to activate
night reduction
the temperature
Weekly
program
byofday
NR Mondays
Night
reductionDay
heat
circ.
Monday
00:00–06:00
and 22:00–24:00
00 - 06etc. 22 - 24
Tuesday
06
22 on
- 24
When
the clock is within 00
the-range,
e.g.
a Monday at 03:00,
Weekly
program
Block
NR
Wednesday
00 - 06
22 - 24
“NR”
is
displayed
Decrease
Sunday
Thursday
00
06 22:00
22 the
- 24time on the right for
The
time on the left mustFriday
be- lower
than
Increase
Friday
00 - 06 14:00
23 - 24
the
interval to be valid. -------Decrease
Saturday
00 - 08 00:00
23 - 24
Sunday
00 - 08 00:00
22 - 24
Increase
-------2
2
Night reduction heat circ.
Weekly program
Holiday
Decrease
Increase
Decrease
Increase
Holiday period
2
oom temp.
Night reduction
Weekly program
Monday
Tuesday
Wednesday
Thursday
Friday
2Saturday
Sunday
Block
Sunday
Friday
---------------
NR
22:00
14:00
00:00
300:00
days
Holiday
1
2
circuit 1
On Sunday at 10 pm, the temperature is lowered by the set
value inHoliday
the Room temp. reduced menu (in the Installer/Settings
menu). On Friday at 2 pm the temperature is increased to the
set value again.
g DHW comfort
circuit 2
HW
(50)
1
er
Weekly
Holiday
periodprogram DHW 3 days
2
Night reduction
0.0 hours Holiday
ature
al
g DHW comfort
HW
er
!
When both are in use, Holiday Reduction overrides Night
Weekly schedule
0.0 hours
system data
ature
l
peration
data system
Weekly program
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Day by day
DHW
06 - 09
18 - 21
07 - 09
-- - -08 - 09
-- - -08 - --- - 21
08 - --- - 21
10 - 12
20 - 23
10 - 12
20 - 23
Reduction.
Weekly program DHW
Weekly program
Day by day
DHW
Operation data06
EcoZenith
Monday
- 09
18 - 21
Tuesday
07 - 09
-- - -Wednesday
08 -HP
09upper--tank
- -Status
Thursday
08 - -- 21
Tank upper °C
49--(58)
Friday
08 - --CTC
21 EcoZenith i250
Tank lower °C
42--(45)
Saturday
10 - 12
20 - 23Stored oper data
Electric power kW
0.0+2.5
Sunday
10 - 12 0.0 0.0
20 0.0
- 23
Current L1/L2/L3
25
Weekly program
Block
Sunday
Friday
---------------
Decrease
Start
menu
Increase
CTC
EcoZenith
Decrease
General Information
emperature settings
Increase
NR
22:00
14:00
00:00
00:00
Monday 09:35
oom temp.
1
2
circuit 1
Room temp.
8.3.4 Holiday
circuit 2
DHW
Holiday
(50)
1
2
1
2
You use this option to set the number of days for which
you want the set
night reduction temperature to be
Night reduction
Holiday
1
constantly reduced. For example, if you want to go on
holiday.
g DHW comfort
HW
!
ature
al
58 ºC
-5 ºC
3 days
2
Room temperature settings
Room temp.
Heating circuit 1
Weekly program DHW
Start
menu
Heating circuit 2 (50)
CTC
EcoZenith
Weekly
program
Day by day
DHW Monday 09:35
2 - 09
Monday 1
06
18
- 21 red., is
The value by which the temperature is reduced,
-Room temp./Prim.
flow
Tuesday
07 - 09
-- - -set under Installer/Settings/Radiator system/
Wednesday Night reduction
08 - 09
-- - -Holiday
Thursday
08 - --- - 21
Factory setting: -2/-3 °C.
Friday
08 - --- - 21
Saturday
10 - 12
20 - 23
Room temp.
DHW
Installer
Sunday
10 - 12 Operation
20 - 23
0.0 hours
er
21,2 ºC
Holiday period
You can apply this setting for up to 300 days.
The period starts from the time you set this parameter
for.
Installer
2
22,2 ºC
1
Operation
8.4 DHW
Selecting DHW comfort
Weekly schedule
1
2
DHW
1
2
22,2 ºC
21,2 ºC
58 ºC
-5 ºC
Operation data EcoZenith
system data
You use this to set the DHW comfort level you want and
1
extra DHW.
peration data system
Temperature
You set the values for this option which apply to the
CTC EcoZenith i250’s normal operation. There are three
modes:
Economic – Small hot water requirement.
Extra
Hot water
0.0 hours
Status
HP upper tank
On
Tank upper °C
49 (58)
Temperature
Room
settings
Tank temperature
lower °C
42 (45)
Normal
Electric power kW
0.0+2.5 Stored oper data
Room
temp.
Current
L1/L2/L3
0.0 0.0 0.0
2
Diff func. Pump / ºC
Pool ºC
Heating circuit 1
!
Heating circuit 2
On 32
Off 22(20)
Weekly
Weeklyschedule
program
Heating circuit
(50)
Start
by setting to Economic
HeatingTip:
system
data
(Temperature Tank lower ≥ 35 °C )
Normal – Normal DHW requirement.
T ºC
60
1
2 that you are not
and
if you find
Operation
data system
heating
Operation
data
getting enough
hot water, increase
Night reduction
it to Normal, and so on.
Holiday
40
settings menu
(Temperature Tank lower ≥ 40 °C )
staller
Comfort – Large DHW requirement.
(Temperature Tank lower ≥ 45 °C )
Extra hot water
this system
option if you
want to activate the Extra DHW
anguage
Settings Select
Define
Service
function. When the function is activated (by setting the
number of hours) the heat pump immediately starts
to produce extra DHW. You also have the option to
ware display PCB: schedule
20120205
hot water production for certain times using
ware HP PCB:
01234
the Weekly program function (recommended).
Setpoint Upper tank 60ºC (Electric boiler extra DHW º)
Setpoint Lower tank = 58ºC
20
Selecting
DHW comfort
0
DHW
-20
Extra 16
Hot waterOut
20
0
Room1
Prim1
On
CTC EcoZenith i250
Return
8
Room2
12
Prim2
Temperature
Normalsettings menu
Installer
Installer
Weekly schedule
The example above shows that Temporary extra DHW is
activated (On) for 3.5 hours.
Time/Language
Settings
Heating
system data
Define system
Operation data system
Software display PCB:
Software HP PCB:
26
4
3.5hours
hours
0.0
20120205
01234
Service
1
2
3 days
Holiday period
Night reduction
General Information
Holiday
g DHW comfort
HW
8.4.1 Weekly program DHW
0.0 hours
er
You can use this menu to schedule periods during
weekdays when you want extra hot water. This
schedule is repeated every week.
ature
al
Options for the weekly program are Off or Day by day.
Weekly program
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Day by day
06 - 09
07 - 09
08 - 09
08 - -08 - -10 - 12
10 - 12
18
----20
20
DHW
- 21
- -- -- 21
- 21
- 23
- 23
Offschedule
Weekly
No scheduled hot water production.
Day by day
A weekly schedule which you program yourself. This
system data
is used if you always know when you repeatedly need
peration data system
extra hot water, for instance in the morning and evening.
Example 1:
Monday 06-0918-21
On Monday the timer comes on from 06–09 and 18–21;
normal operation applies apart from these times.
On Monday morning at 6 am the system starts producing more
hot water
until 9 amdata
whenEcoZenith
the temperature returns to normal
Operation
again. There is a further increase between 6 pm and 9 pm.
When
the clock is within theHP
range,
e.g.
on a Monday at 03:00,
Status
upper
tank
“DHW”
is displayed
Tank upper °C
49 (58)
Tank lower °C
42 (45)
Electric power kW
0.0+2.5 Stored oper data
Current L1/L2/L3
0.0 0.0 0.0
Diff func. Pump / ºC
On 32
Tip: Set the time approx.
Pool ºC
Off 22(20) 1 hour
!
Example 2:
Thursday
06 - --
-- - 21
The timer comes on from 06–21 on Thursdays.
earlier than you need the hot water
Heating
as it take some time to heat
upcircuit
the
water.
Operation data heating
T ºC
60
40
settings menu
20
staller
anguage
Weekly program DHW
0
-20
16
Out
Settings
Define system
ware display PCB:
ware HP PCB:
20
Room1
0
Prim1
4
Return
8
Room2
12
Prim2
Service
20120205
01234
CTC EcoZenith i250
27
General Information
Cooling
Temperature
Common heating/cooling
Normal
Condense pipe secured
Room temp. cooling
No
No
No
25.0
Weekly schedule
8.5 Operation data system
1
Heating system data
Operation data system
Room
Def CTC SMS
This menu displays current temperatures and the
operational data for your heating system.
Primary flow radiators
The temperature of the primary flow to the house’s
radiators is shown above the CTC EcoZenith i250
(42°C). This value will vary during the year according
to the parameters set and the current outdoor
temperature.
Return radiators
The return temperature of the radiator water returning to
EcoZenith is also shown above the CTC EcoZenith i250
(34°C). This value will vary during operation according to
the parameters set, the radiator system’s capacity and
the current outdoor temperature.
The screens also show the incoming and
outgoing temperatures from the heat
pump installed.
Activate
Level of signal
Phone Number 1
Phone Number 2
Hardware Version
Software Version
+46712345678
----------------1
1
1
9
Cooling
Operation data system
Installer
Time/Language
Settings
Software display PCB:
Software HP PCB:
Define system
Service
20120205
01234
The screen shows operating information with the CTC EcoPart
connected. When the pumps are in operation, the pump icons
also rotate on screen.
Information
Press the information button to display
the operational data for the relevant
item.
Current outdoor temperature
Shows the current outdoor
temperature.
The product uses this value to
calculate the various operational
parameters.
Brine in (CTC EcoPart only)
At the top left of the EcoPart (2°C) the brine’s current
temperature from the collector to CTC EcoPart is
shown.
CTC EcoZenith i250
Heating cir
The screen shows operational data with the CTC EcoAir
connected. When the pumps are in operation, the pump icons
also rotate
on screen.
Installer
settings
menu
HP in
At the right of the heat pump (34°C) the heat pump’s
return temperature is shown.
28
Yes
Nigh
HP out
At the right of the heat pump (42°C) the heat pump’s
outgoing temperature is shown.
Brine return (CTC EcoPart only)
The bottom left value (-1 °C) is the return temperature of
the brine going back into the collector hose. The values
vary during the year according to the heat source’s
capacity and the energy drawn out.
2
1
Current indoor temperature
2 the current room temperature
Shows
(if a room sensor is selected during
operation). If two radiator systems
are installed, the values for both are
displayed.
0.0 hours
er
Weekly program
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
ature
al
Day by day
DHW
06 - 09
18 - 21
07 - 09
-- - -08 - 09
-- - -General
Information
08 - --- - 21
08 - --- - 21
10 - 12
20 - 23
10 - 12
20 - 23
Weekly schedule
8.5.1 Operation data EcoZenith
system data
peration data system
This menu displays current temperatures and the
operational data for your EcoZenith i250. The first figure
is the actual operational value, with the value in brackets
being the setpoint which EcoZenith is trying to achieve.
Status
Tank upper °C
Tank lower °C
Electric power kW
Current L1/L2/L3
Diff func. Pump / ºC
Pool ºC
HP upper tank
49 (58)
42 (45)
0.0+2.5 Stored oper data
0.0 0.0 0.0
On 32
Off 22(20)
Heating circuit
Status
Shows EcoZenith i250’s operational status.
The various operational status options are:
•
settings menu
•
staller
anguage
Operation data EcoZenith
•
Settings•
ware display PCB:
ware HP PCB:
HP upper tank
The heat pump heats up the upper part of the tank
(DHW production).
HP lower tank
The heat pump heats up the lower part of the tank.
(Heat production).
HP + Add
Both the immersion heater and heat pump are
operating to heat up the tank.
Define
Add system
Service
Only the immersion heater is heating the tank.
Three Current values are displayed when the current
transformers (CTs) are connected and identified. If only one
Operation data heating
figure is displayed:
T ºC
60
- connect all three current transformers (CTs).
40
- then select the option Installer/Service/Control current
20
sensors.
0
-20
!
16
20
0
4
8
12
Out first
Room1
Prim1is the
Return
Room2
Prim2
The
figure
current
operating value. The value in
brackets is the setpoint that the CTC
EcoZenith is trying to achieve.
Tank upper °C
49 (60)
Shows
the
temperature
and
reference
value
in
the
upper
20120205
part 01234
of the tank.
Tank lower °C
42 (50)
Shows the temperature and reference value in the lower
part of the tank.
Electric power kW
Shows the electric boiler's additional power. Lower
and upper electric heaters. Example of 0.0 kW in lower
electric heater and 2.5 kW in upper electric heater.
Current L1/L2/L3
Shows the system’s total current consumption at the
various phases L1/L2/L3, provided that three current
sensors have been fitted to the unit’s incoming cables. If
the current sensors mounting devices are not identified,
only the phase with the highest load is displayed.
If the current exceeds the main fuse size, the boiler
automatically switches down a power step to protect
the fuses, for example, when several high-consumption
appliances are being used in the house.
CTC EcoZenith i250
29
General Information
Diff func.Pump/Temp. ºC
Differential thermostat function
Shows whether charge pump (G46) is switched on (ON,
OFF). Displays temperature of external tank. ºC (B46)
!
Pool ºC
Off 23 (22)
Pool function
Shows whether pumps (G50,G51) are switched on (ON,
OFF). Displays pool temperature and (setpoint)
If the expansion card has not been
installed and Pool has been defined,
the product will emit an alarm:
Comm. fault expansion card.
8.5.2 Operation Heating circuit
Op. Heating Circuit
Def heating circuit 1
Primary flow 1 °C
Primary flow1 ºC
Return flow ºC
Radiator pump
Mixing valve
Delay mixing valve
Primary flow 2ºC
Radiator pump 2
Mixing valve 2
Heating circuit 1
Yes
Shows the temperature supplied
to the system’s
Room sensor 1
Yes
Type
Wire
radiators, along with the temperature
which the system
is trying to achieve. This value will vary during the
year according to the parameters set and the current
outdoor temperature.
33(34)
31
Till
Open
180
33(34)
Från
Return flow °C
Shows the temperature of the water returning from the
radiator system to the CTC EcoZenith i250.
Radiator pump
Def heating
circuit 1pump’s operational status.
Shows
the radiator
Sett. Diff termostat function
Charge start diff temp ºC
Charge stop diff temp ºC
Charge temperature °C
Mixing
valve
Heating
circuit
1
Yes
Room sensor 1
Shows whether the mixing valveYes
increases (opens) or
Type
Wireless
Action
reduces (closes) the heat supplied to the radiators.
Disconnect
When the correct temperature has been achieved
Status
Associated
with the mixing valve, the valve’s motor then remains
Level of signal
stationary.
Battery
85%
Version
x0102
Delay mixing valve
A microswitch in the mixing valve’s motor ensures that
auxiliary heating is not used unnecessarily, for example,
when ventilating a room or if the temperature (outdoors)
occasionally drops during the night. The mixing valve
is delayed for the time period selected before auxiliary
heating is used. The screen shows the countdown of
the delay in minutes. If “Blocked” is shown, never open
the mixing valve to the immersion heaters of the upper
Define Cooling
tank.
Cooling
No
Common
heating/cooling
Primary
flow 2 ºC etc... No
Condense pipe secured
No
Displayed
if radiator system25.0
2 or
Room
temp. cooling
7
3
60
Test Diff thermostat function
Pump H-tank (G46)
Temperatures
H-tank (B6) ºC
Off
32
Cooling has been
defined
1
Room temp.
Def CTC SMS
30
Activate
Level of signal
Phone Number 1
Phone Number 2
CTC EcoZenith
Hardware Version
Software Version
2
Yes
i250
+46712345678
----------------1
1
1
9
Heating circuit 1
20.2 (20.0)
Cooling
20.2 (20.0)
General Information
8.5.3 Stored operation data
Stored oper data
t reduction heat circ. 1
ogram
y
Day by day
NR
00 - 06
22 - 24
This
menu shows the operating values for the
00 - 06
22 - 24
00 - 06 EcoZenith
22 - 24 i250 over a long period.
00 - 06
22 - 24
00 - 06 Total
23 -Operating
24
Time h
00 - 08
23 - 24
Shows
the
total
time
during which the product has
00 - 08
22 - 24
Maximum Primary Flow °C
--------
00:00
Electricity consumption kWh
Shows how much electrical energy that the product has
used with immersion heater operation (accumulated
total value).
day
riod
1540
Heat pump
Compressor
Charge pump
Brine pump
HP in/out °C
On
On 47%
On
35.5 / 42.3
Current L1
4.0
Installer
Time
21:34
3 days
Date
2012-02-05
Installer
Settings language
Day by day
06 - 09
07 - 09
08 - 09
08 - -08 - -10 - 12
10 - 12
DHW
18 - 21
-- - --- - --- - 21
-- - 21
20 - 23
20 - 23
Svenska
Nederlands
English
Deutsch
Suomi
Française
Dansk
Norsk
Settings
ation data EcoZenith
r °C
r °C
wer kW
/L2/L3
Pump / ºC
Total Operation time
Total operation time
Displays the total operating time of the compressor. (h)
kly program DHW
y
14196
51
20
been on.
Shows the highest temperature supplied to the
t reduction heat circ.
radiators. The value may indicate the radiator system’s/
ogram
Block
NR
house’s temperature requirements. The lower the value
Sunday 22:00
during
Friday
14:00 the winter period, the more suitable it is for heat
-------- pump
00:00 operation.
ogram
Total operation time h:
Max primary flow °C:
Consumtion kWh
Compressor:
HP upper tank
49 (58)
42 (45)
0.0+2.5 Stored oper data
0.0 0.0 0.0
On 32
Off 22(20)
Heating circuit
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
Upper tank
Remote control
None
Communication
Solar panels
Diff thermostat function
Pool
Save settings
Load settings
Load factory settings
Define system
ation data heating
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
CTC EcoZenith i250
31
oom
ogramtemp.
Day by day
00 00 00 00 00 00 (50)
00 -
ycircuit 1
circuit 2
06
06
06
06
06
08
08
1
2
NR
22 - 24
General
22 - 24
22 - 24
22 - 24
23 - 24
23 - 24
22 - 24
Night reduction
g DHW
HW
1
EcoAir
Compressor
On (On/Off)
Shows whether the compressor is operating or not.
0.0 hours
Charge pump
On 47%
Shows the charge pump's operational status and flow
as a percentage. (The example shows that the charge
pump is currently operating at 47% speed.)
ature
day
al
3 days
riod
Total Operation time
1540
3 days
Holiday period
Heat pump
Holiday
Block
NR
Sunday 22:00
Friday
14:00
comfort
-------- EcoPart
00:00
-------00:00
er
14196
51
20
Holiday
8.5.5 Heat pump
t reduction heat circ.
ogram
Information
Total operation time h:
Max primary flow °C:
Consumtion kWh
2Compressor:
Compressor
Charge pump
Brine pump
HP in/out °C
On
On 47%
On
35.5 / 42.3
Current L1
4.0
Weekly program DHW
Weekly program
Monday
Tuesday
Installer
Wednesday
Thursday
Friday
Time
Saturday
Sunday
Date
Day by day
DHW
06 - 09
18 - 21
07 - 09
-- - -08 - 09
-- - -08 - --- - 21
08 -21:34
--- - 21
10 - 12
20 - 23
10 -2012-02-05
12
20 - 23
Brine pump/Fan
On (On/Off)
Shows whether the brine pump/fan is operating or not.
Weekly schedule
HP in/out °C
35.5/42.3
Shows
the
heat
pump’s
return
and
primary
flow
system data
temperatures.
peration data system
(The example shows a return temperature of 35.5ºC and
a primary flow temperature of 42.3ºC.)
kly program DHW
Current
L1
Day by day
DHW
06 - 09 Shows
18 - the
21 current across the compressor (phase L1).
07 - 09
-- - -08 - 09
-- - -08 - --- - 21
08 - --- - 21
10 - 12
20 - 23
10 - 12 8.5.4
20 - 23Operation data heating
ogram
y
Operation data EcoZenith
Status
Tank upper °C
Installer
Tank
lower °C
Electric power kW
Current L1/L2/L3
Settings
Diff func.language
Pump / ºC
Pool ºC
Svenska
Pump / ºC
anguage
On 32
The22(20)
blue curve is the current outdoor temperature.
Off
SettingsThe green
Define and
system
Service
pink curves
are room temperatures 1
Heating circuit
and 2, respectively.
The red and grey curves are primary flow temperatures
2, respectively.
ware display PCB: 1 and
20120205
ware
HPdata
PCB:heating
01234
ation
The yellow curve is the CTC EcoZenith i250 return
temperature.
20
Room1
0
Prim1
32
4
Return
8
Room2
Nederlands
Française
Dansk
Operation
data heating
heating
Operation
data
CTC EcoZenith i250
Heating circuit
Deutsch
Norsk
Settings
Heating
circuit 1
40
Heating circuit 2
20 pump
Heat
Electric heater
0
Upper
tank
Remote control
None
-20
Communication
16
20
0
Solar panels
Out
Room1
Diff thermostat
functionPrim1
Pool
Save settings
Load settings
Load factory settings
4
Return
Define system
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
Diff thermostat function
Pool (G50, G51, B50)
12
Prim2
English
Suomi
T ºC
60
ation
data
EcoZenith
settings
menu
This displays the heating system’s operation data for the
HP upper tank
staller
last
r °C
4924
(58)hours. The furthest point to the right is the
r °C
42 (45) while the data for the last 24 hours is displayed
present,
wer kW
0.0+2.5 Stored oper data
to 0.0
the0.0
left. The time “rolls” forward.
/L2/L3
0.0
HP upper tank
49 (58)
42 (45)
0.0+2.5 Stored oper data
0.0 0.0 0.0
On 32
Off 22(20)
Service
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
No
No
8
Room2
12
Prim2
General Information
8.6 Installer
Installer settings menu
Installer
Stored oper data
t reduction heat circ. 1
ogram
y
Day by day
This menu NR
contains four sub-menus. Time/Language,
00 - 06
22 - 24
Settings,
Define
system and Service.
00 - 06
22 - 24
00 - 06
22 - 24
includes time and language settings for
00 - 06 Time/Language
22 - 24
00 - 06 your
23CTC
- 24 EcoZenith i250.
00 - 08
23 - 24
00 - 08 Settings
22 - 24
are used both by the installer and users for
14196
Define system
51
Service
20
Total Operation time
1540
Software display PCB:
Software HP PCB:
20120205
01234
installing the system.
Define system is used by the installer to define the
contents of your heating system.
t reduction heat circ.
ogram
Total operation time h:
Time/Language
Settings
Max
primary flow °C:
Consumtion kWh
Compressor:
Block
Sunday
Friday
---------------
Service
is used for troubleshooting and diagnosis. You
NR
22:00
will
find here the options Function test, Alarm history,
14:00 settings code, Quick start compressor and
Factory
00:00
Software
update.
00:00
Heat pump
Compressor
Charge pump
Brine pump
HP in/out °C
On
On 47%
On
35.5 / 42.3
Current L1
4.0
8.6.1 Time/Language
Installer
day
You
use this to set the date and time. The clock has
3
days
riod
y
21:34
Date
2012-02-05
a power backup and continues to run in the event
of a power cut. Summer/winter time is changed
automatically.
kly program DHW
ogram
Time
Time settings
When a green box appears around the time, press OK
and the first value is selected. Use the arrows to set the
correct value.
Op. Heating
Circuit
When you
press OK, the next value is highlighted.
Day by day
DHW
06 - 09flow1 18
Primary
ºC - 21 33(34)
07 - 09flow ºC-- - -- 31
Return
08 - 09 pump-- - -- Till
Radiator
08 - --valve -- - 21 Open
Mixing
Delay
valve
08 - mixing
--- - 21 180
Setting
the33(34)
language
Primary
2ºC
10 - 12flow
20 - 23
Radiator
2 - 23 Från
10 - 12 pump
The20
current
language has a green circle around it.
Mixing valve 2
Installer
Settings language
Settings language
Svenska
Nederlands
Svenska
Suomi
Norsk
Française
Deutsch
Settings
ation data EcoZenith
HP upper tank
r °C
49 (58)
r °C
(45)
Sett. Diff42
termostat
function
wer kW
0.0+2.5 Stored oper data
Charge start
7
/L2/L3
0.0diff
0.0temp
0.0 ºC
3
Pump / ºC Charge stop diff
Ontemp
32 ºC
Charge temperature
60
Off 22(20)°C
Heating circuit
English
Suomi
Heating circuit 1
Heating circuit 2
Heat pump
Electric
Settings heater
language
Upper tank
Remote control
None
Communication
Solar
panels
Dansk
Nederlands
Diff thermostat function
Pool
Save settings
Load settings
Eesti
Load
factory settingsPolski
Deutsch
English
Dansk
Norsk
Française
Čeština
Slovenščina
Define system
ation data heating
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
CTC EcoZenith i250
33
klyInstaller
program DHW
ogram
me
ay
ate
Settings language
Day by day
DHW
06 - 09 General
18
- 21
21:34
Information
07 - 09
-- - -08 - 09
-- - -2012-02-05
08 - --- - 21
08 - --- - 21
10 - 12
20 - 23
10 - 12
20 - 23
Svenska
Nederlands
English
Deutsch
Suomi
Française
Dansk
Norsk
8.7 Settings
ration
data EcoZenith
Installer
HP upper tank
ettings language
er °C
49 (58)
This
used to set the parameters for operating
r °C
42 is
(45)
ower kW
Stored
data that this default setting
the0.0+2.5
system.
It is oper
important
/L2/L3
0.0 0.0 0.0
venska
Nederlands
English
Deutsch
is
adjusted
for
your
property.
Values which are set
Pump / ºC
On 32
Off
22(20)
incorrectly may mean that your property is not warm
Suomi
enough orHeating
that ancircuit
unnecessarily large amount of energy
Française
Dansk
Norsk
is being
used to heat
your property.
Settings
8.7.1 Heating circuit 1 or 2
ration
data heating
eating circuit
1
eating circuit 2
Max. primary flow
55(30...80)
eat pump
The
maximum
permitted
temperature
supplied
to the
ectric heater
pper tank
radiators. This functions as an electronic limiter to
emote control
None
protect the floor coils in underfloor heating systems.
ommunication
olar panels
Radiator system 2 can only reach the same temperature
ff thermostat function
ool
as radiator system 1 or a lower temperature.
ave settings
20
0
4
8
12
oad settings
Min.
primary
flow
Off (Off, 15...65)
Room1 settings
Prim1
Return
Room2
Prim2
oad factory
You can use this option to set the minimum permitted
temperature if you want a specific level of background
Define system
heating during the summer in the basement or
underfloor heating coils, e.g. in the bathroom. The
eating circuit 1
eating circuit 2
heating in other parts of your property should then be
eat pump
switched off using thermostatic radiator valves or shutTC SMS
ooling
off valves. Note that the radiator pump will then operate
olar panels
for the whole
ff thermostat function
No summer. This means that the temperature
ool (G50, G51, B50) out to theNo
radiators does not fall below a selected
temperature, for example +27°C.
“Off” means that the function is turned off.
Service
Heating off, outside
18(10...30)
Outdoor temperature limit at which the house no
unction test
longer requires heating. The radiator pump stops and
arm log
actory settings codedthe mixing valve is kept closed. The radiator pump
uick start compressor.
is activated daily for a short period to reduce the risk
oftware update, USB
of jamming. The system restarts automatically when
rite log to USB
heating is required.
ontrol current sensors
e-installation
34
Heating off, minutes
120(30...240)
The delay period before the radiator pump stops as
described above.
CTC EcoZenith i250
Settings
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
Upper tank
Remote control
None
Communication
Solar panels
Diff thermostat function
Pool
Save settings
Load settings
Load factory settings
Define system
Heating circuit 1
Heating circuit 1
Heating
circuit
2
Max primary
flow °C
Heat
pump flow °C
Min primary
CTC
SMS
Heating
off, out °C
Cooling
Heating off
Solar
panels
Inclination °C
Diff
thermostat function
Adjustment °C
Pool
B50)
Room(G50,
tempG51,
reduced °C
or
Primary flow reduced °C
>>
55
Off
18
120
50
No
0
No
-2
-3
Service
Def heating circuit 1
Function test
Alarm log
Heating settings
circuit 1 coded
Factory
Room sensor 1
Quick start compressor.
Type
Software update, USB
Write log to USB
Control
current
sensors
Tip:
Read
more
Re-installation
!
Yes
Yes
Wire
about these settings
in the chapter on Your property’s
heating installation.
Function test
Heating circuit
Heat pump
Valves
Electric heater
Solar
Diff thermostat function
Pool
For example:
“Inclination 50” means that the temperature of the water
supplied to the radiators will be 50°C when the outdoor
temperature is -15°C, if the adjustment is set to 0. If the
adjustment is set to +5, the temperature will be 55°C
instead. The curve is increased by 5°C at all outdoor
temperatures, i.e. the curve is parallel offset by 5°C.
t pump
t
es
.heater
General Information
Inclination (default setting)
50(25...85)
Inclination means the temperature your property needs
at different outdoor temperatures. See more detailed
information about this in the chapter on Your property’s
heating installation. The value set corresponds to
the temperature of the radiators when the outdoor
temperature is -15ºC. After this default setting, fine
adjustment takes place in the “Room temperature”
menu.
Adjustment
0 (-20...20)
The curve adjustment means that the temperature
level can generally be raised or lowered at all outdoor
temperatures. After this default setting, fine adjustment
takes place in the “Room temperature” menu.
Room temp. reduced
-2 (0...-40)
“Room temp. reduced” is displayed if a room sensor is
installed.
You define here how many degrees the room
temperature will be reduced by during the various
scheduled reduction periods, e.g. Night reduction,
Holiday, etc.
Example:
Room temp red -2 means that the room temperature is
reduced by 2 °C from its normal temperature.
Example:
As a general rule, a Prim reduced value of 3-4 °C is
equivalent to a 1 °C reduction in room temperature in a
normal system.
Prim reduced
-3 (0...-40)
If there is no room sensor installed, “Prim reduced” is
displayed instead.
Radiatorsystem forts
Exact primary flow
No (No/Yes)
Exact primary flow means that the heat pump never
switches over and heats the upper tank (hot water
Off charging). This is provided solely by the electric heater.
Off
0
Off In summer mode however, i.e. if the outdoor
Off
Off temperature is above the limit (Heating off, outside), the
Off heat pump will be allowed to send water to the upper
Off
Inst. Radiatorsystem1
<<
Anti Water Hammer
HP max DHW
Drying period mode
Drying period temp ºC
No
Yes
Off
25
tank.
DHW increase
Yes (Yes/No)
When exact primary flow has been selected the “DHW
increase” function opens.
Yes means that the heat pump will follow the
temperature of the radiators for three start-ups. When
the heat pump performs start-up no. 4 the heat
Down
pump works until it achieves “maximum heat pump
temperature”. This is also termed “full condensation”.
No means that the heat pump will always follow the
temperature of the radiators.
Operation data heating 2
T ºC
60
40
20
0
-20
16
Out
20
Room1
0
4
8
Prim1
Return
Room2
Info golvtorkning estricht
12
Prim2
CTC EcoZenith i250
35
General Information
Drying period mode
Off (Off/1/2/3)
Floor drying function for newly-built properties.
The function limits the calculation of primary flow
temperature (setpoint) for “Your home’s heating
installation” to the schedule below.
Mode 1
Floor drying function for 8 days.
1. The (setpoint) of the radiator system is set to 25ºC for
4 days.
e
sh
’
me
o
r h on”
i
ou
“Y tallat
s
n
i
2.
1.
Radiatorsystem forts
12 345678 9etc...
2. On Days 5–8, the value set in “Floor function temp.
Test Heat pump ºC” is used.
Day
Inst. Radiatorsystem1
Example for Mode 1 with “Floor function temp. 38ºC”.
<<
Anti Water Hammer
HP max DHW
Drying period mode
Drying period temp ºC
(FromOffDay 9 onwards the value is calculated
Off
automatically
according to “Your home’s heating
0
Off
installation”)
Compr.
Brine p/Fan
Charge p
ost Manually
pressor heat
tray heater
ing Cable
y valve(Y11)
ng
ati
ºC
65
60
55
50
45
40
35
30
25
20
No
Yes
Off
25
Off
Off
FloorOff
drying function for 10 days + stepped increase
and decrease.
ºC
65
60
55
50
45
40
The final
35
Downstep may be less than 5ºC.
30
3. Stepped decrease: After the stepped increase 25
and 10 days at an even temperature, the
20
1. Stepped increase start: The (setpoint) of the
radiator system is set to 25ºC. The (setpoint) is
then raised by 5ºC each day until its (setpoint) is
equal to the “Floor function temp. ºC”.
Test valves
y valve
temperature (setpoint) is reduced to 25ºC in daily
5ºC stages.
The final step may be less than 5ºC.
(Following the stepped decrease and one
day at the (setpoint) of 25ºC the value is calculated
automatically according to “Your home’s heating
Test Elec.heater
installation”.)
ric heater L1A
ric heater L1B
ric heater L2A
ric heater L2B
ric heater L3A
ric heater L3B
ric heater A13
Off3
Mode
1.
Operation data heating 2
2. 10 days
T ºC
60
3.
40
20
0
1 2
-20
3
416 5
6
20
7
8 9 410
0
118 12 12
13 etc...
Room1
Prim1
Room2
Prim2
Example forOutMode
2 with
“FloorReturn
function
temp.
37ºC”.
Info golvtorkning estricht
CTC EcoZenith
Monday 09:35
Off
Off
In this
mode, the function starts in Mode 1 and this is
Off
then Off
followed by Mode 2 and finally by “Your home’s
Off
heating
Off installation”.
Floor function temp. ºC
25 (25...55)
Here you set the temperature for Mode 1/2/3 as shown
above.
Room temp.
Drying period activ
58 ºC
DHW
1
Operation
/
12
Installer
(25)
-5 ºC
Example for operation data Mode 2, Day 1 of 12 with
current (setpoint) 25ºC.
Alarm log
st alarm:
brine flow
ed alarms:
ng phase order
. err m. protect
Time
07:20 6/3
HP (b) LP (b)
8.8
3.3
SH (K) I(A)
15.9 3.9
10:30 1/3
09:01 1/3
27.9
27.9
-227
42.2
36
8.6
3.6
CTC EcoZenith i250
Factory settings coded
50.0
0.0
“Your home’s heating
installation”
Off2
Mode
Day
Heating circuit 1
(50)
Sav
Loa
General Information
Night reduction
8.7.2 Set. heat pump
Holiday
Set. heat pump
CompressorPermitted/Blocked
The product is supplied with a blocked compressor. When
the compressor is blocked, the product operates like an
electric boiler. All other functions are intact.
Compressor
1
Min outdoor temp °C
2
Brine pump on
Tariff HP
Minimum run time
Permitted
-15
Auto
Off
6
Hea
Flo
50
57
60
5.5
55
6.0
180
25
3x400 V
Off
Mix
Rad
Mix
Rad
LED
Permitted means that the compressor is allowed to
operate.
Min. outdoor temp. °C
(Applies to the CTC EcoAir only)
1
-15 (-22...0)
This menu relates to settings for the outdoor temperature
at which the compressor is no longer permitted to
operate. When the heat pump has stopped a start signal
will only be given if the outdoor temperature is at least
2 °C warmer than the set value. The lowest outdoor
temperature required for start is -18 °C.
Brine pump Auto/10d/On
(Applies to the CTC EcoPart only)
“10D”. After installation is complete, you can choose to
run the brine pump constantly for 10 days to remove air
from the system. The pump then returns to auto mode.
“On” means that the brine pump will operate continuously.
“Auto” means that the circulation pump will operate at the
same time as the compressor.
2
Tariff HP
Not applicable. Applies only to products marked “Tariff”. It
must be set to Off.
Applies to the CTC EcoAir
1
Applies to the CTC EcoPart
Electric heater
2
Boiler upper °C
Boiler upper add °C
Boiler upper extra DHW °C
Boiler upper max kW
Boiler lower °C
Boiler lower max kW
Delay mixing valve
Main fuse A
Input voltage
Tariff EL
Upper tank
Stop temp HP °C
Start/stop diff upper ºC
Max time upper tank
Max time lower tank
Max
7
20
40
Min oper. time
6 (0...20)
Minimum operating time in minutes that the compressor is
permitted to operate. Even if the tank’s stop temperature
has been achieved, the compressor continues to supply
energy during this period.
CTC EcoZenith i250
37
Min outdoor temp °C
Brine pump on
Tariff HP
Minimum run time
2
General Information
8.7.3 Electric heater
Upper boiler °C
50 (30...60)
Temperature when the immersion heater kicks in
and helps EcoZenith i250 to produce domestic hot
water when there is great demand. A low setting is
recommended.
The immersion heater is also responsible for providing
the house with additional heating. If the house requires
a higher temperature than that selected, the control
system compensates by automatically raising the
temperature of the immersion heaters.
This temperature also reflects the settings chosen under
DHW.
Upper boiler add heat °C
57 (30...70)
The temperature of the boiler when EcoZenith i250
calls for assistance to reach the high temperature; the
immersion heater then works up to this value after the
set time delay on the mixing valve.
Upper boiler extra DHW
60 (30...70)
This means the boiler is to provide extra DHW. This
setting determines whether the electric heater should
help to produce extra hot water. Set the temperature
of the electric unit to the desired value when the option
for extra hot water is activated under the DHW menu.
A lower value means that the heat pump produces the
majority of hot water, not the immersion heater.
Upper boiler max. kW
5.5 (0...9.0)
You set the max. permitted power for the immersion
heater here.
Setting for the maximum permitted power for the electric
unit. 0 to 9.0 kW in steps of 0.3 kW.
Lower boiler °C
55 (30...70)
Setting for the temperature of the lower immersion
heater.
Lower boiler kW
6 (0/6.0)
Setting for the power of the lower immersion heater, 0
and 6 kW respectively. An additional 3 kW is possible.
See the chapter: Switching to 18 kW electric heater
power.
38
CTC EcoZenith i250
-15
Auto
Off
6
F
50
57
60
5.5
55
6.0
180
25
3x400 V
Off
M
R
M
R
L
Electric heater
Boiler upper °C
Boiler upper add °C
Boiler upper extra DHW °C
Boiler upper max kW
Boiler lower °C
Boiler lower max kW
Delay mixing valve
Main fuse A
Input voltage
Tariff EL
Upper tank
Stop temp HP °C
Start/stop diff upper ºC
Max time upper tank
Max time lower tank
Max
7
20
40
1
2
Room temp.
Heating circuit 1
Delay mixing valve
180 (30...240, blocked)
The mixing valve delay, the period before it draws
energy from the immersion heater, is set here. It can
be set from 30 to 240 minutes. If the value is set to
”Blocked”, the mixing valve will never open to the boiler.
(Blocked)
Main fuse A
20 (10...35)
The property’s main fuse size is set here. This setting
and the fitted current sensors ensure the fuses are
protected when using appliances which generate
temporary power peaks, for example, cookers, ovens,
engine heaters, etc. The product temporarily reduces
power drawn where this type of equipment is being
used.
Input voltage
3x400 V
The value is set here to indicate whether the CTC
EcoZenith is connected at 3x400 V, 1x230 V or 3x230
V. 3x400 V and 1x230 V are valid for the UK.
Tariff, EL
Off
Not applicable. Applies only to products marked “Tariff”.
It must be set to Off.
8.7.4 Upper tank
(Applies only if a heat pump has been installed.)
Stop temp HP °C
Max. (40...58, Max.)
At this temperature, the heat pump stops charging the
upper tank.
General Information
Sav
Sav
Loa
(50)
Night reduction
Holiday
Set. heat pump
Compressor
1
Min outdoor temp °C
2
Brine pump on
Tariff HP
Minimum run time
Permitted
-15
Auto
Off
6
Hea
Flo
50
57
60
5.5
55
6.0
180
25
3x400 V
Off
Mix
Rad
Mix
Rad
LED
Electric heater
Boiler upper °C
Boiler upper add °C
Boiler upper extra DHW °C
Boiler upper max kW
Boiler lower °C
Boiler lower max kW
Delay mixing valve
Main fuse A
Input voltage
Tariff EL
Upper tank
Stop temp HP °C
Start/stop diff upper ºC
Max time upper tank
Max time lower tank
Max
7
20
40
Start/stop diff upper °C
7 (3...10)
Hysteresis before the heat pump starts or stops
charging the upper tank.
Max. time upper tank
20 (10...150)
This is the maximum time in minutes spent by the heat
pump charging the upper tank if required in the lower
tank.
Max. time lower tank
40 (10...120)
This is the maximum time in minutes spent by the heat
pump charging the lower tank if required in the upper
tank.
CTC EcoZenith i250
39
General Information
8.7.5 Remote control
Shows the type of remote control selected.
“NR” = Remote night reduction, e.g. via the minicall
system. SO = Ripple control. Disconnecting the
compressor and immersion heater during a certain
period which is defined by the electrical supplier (special
equipment).
DHW = Extra hot water, used along with the Extra DHW
button.
1
2
8.7.6 Communication
Room temp.
These settings are activated for the Superior systems
and are not used in normal operation. They are not
Heating circuit
1
described
in these instructions.
Night reduction
1
Communication
MB address
Baud rate
Parity
Stop bit
1
9600
even
1
HP
HP
HP
Def
Com
Drip
Hea
4-w
Holiday
2
Room
temp. Solar
8.7.7
panels (accessories)
These settings are intended for accessory solar panels.
Heating circuit
See 1the (50)
CTC Solar controls/Expansion card manual for
more information.
Installer
NB: If the expansion card has not
been installed and solar panels are
Save settings
defined, the product will emit an
Save settings
Load factory
settings
alarm:
!
3-w
Comm. fault expansion card.
Night reduction
Holiday
Set. heat pump
Compressor
1
Min outdoor temp °C
2
Brine pump on
Tariff HP
Minimum run time
Def Heat pump
Permitted
-15
Auto
Off
6
Electric heater
Boiler upper °C
Boiler upper add °C
Boiler upper extra DHW °C
Boiler upper max kW
40 lowerCTC
Boiler
°C EcoZenith
Boiler lower max kW
Delay mixing valve
Heat pump
Flow/level switch
Off
None
Ele
Ele
Ele
Ele
Ele
Ele
Ele
Open
On
Off
Off
On
Lat
Low
Sto
Wro
Com
Test Heating circuit
50
57
60
5.5
i250
55
6.0
180
Mixing valve1
Rad pump1
Mixing valve2
Rad pump2
LED room sensor
Mixing valve
Delay mixing valve
Primary flow 2ºC
Radiator pump 2
Mixing valve 2
Open
180
33(34)
Från
General Information
S
8.7.8 Sett. Diff termostat function
Def heating circuit 1
The function must be defined before the settings can
be entered.
function is used if
Heating
circuit 1The operating thermostat
Yes
Room
sensor
1
Yes
you want to charge your system tank (e.g. EZ 250) from
Type
Wireless
a water-jacketed stove, or another water source.
Action
Sett. Diff termostat function
Charge start diff temp ºC
Charge stop diff temp ºC
Charge temperature °C
7
3
60
Disconnect
Status
However, this function cannot be combined with the
Associated
same
function in a solar heating system (when e.g. an
Level
of signal
Battery
EcoTank is connected to an EZ 85%
250). This is because
Version
x0102
the same outlets and sensors are used for both
functions.
Information about the operating thermostat function will
be displayed under Operation data.
Charge start diff. temp., °C
7 (3...30)
Here you can set the temperature difference determining
when charging from the heat source is started. The heat
source must be this many degrees warmer than the
Cooling
tankDefine
temperature
for charging to start.
Test Diff thermostat function
Pump H-tank (G46)
Temperatures
H-tank (B6) ºC
Off
32
Cooling
No
Chargeheating/cooling
stop diff. temp., No
°C
Common
Condense
No
Here youpipe
cansecured
set the temperature
Room temp. cooling
25.0
3 (2...20)
difference determining
when charging from the heat source is stopped. When
the temperature difference between the product and the
tank falls below this set value, charging stops.
1
2
Charge temperature, °C 60 (10...80)
Here you can set EcoZenith/EcoHeat's maximum
permitted
Room
temp. temperature in the lower tank. The charging
stops if this temperature is exceeded.
1
Def CTC SMS
Heating circuit
1
8.7.9
Pool
Activate
Level
of signal
The
settings for Pool
Phone Number 1
expansion
Phone Number 2 card.
Hardware Version
Software Version
Yes
require the installation of an
+46712345678
----------------1
1
1
9
See the CTC Solar controls/Expansion card manual for
Night
reduction
Holiday
more
information.
1
2
Communication
NB: If the expansion card has not
Room temp.
!
been installed and
Pool has been
1
the product
9600 will emit an
MB address
defined,
Baud rate
Parity circuit 1
Heating
alarm:
Stop bit
CoolingComm.
HP
HP
HP
Def
Com
Drip
Hea
4-w
even(20.0)
20.2
1
fault expansion
card.
20.2 (20.0)
Holiday
Night reduction
2
8.7.10Saving and loading settings
Room temp.
The following settings can be saved and loaded.
Operation data system
Save settings
Heating circuit 1
(50)
Here your own settings can be stored; confirm with the
"OK" button.
Installer
3-w
Save settings
Save settings
Load factory settings
Load settings
The saved settings can be reloaded using this option.
Night reduction
Holiday
Load factory settings
The product is supplied with the factory values set. They
can be restored by activating this function. Press OK
confirm.
However, the product and product size are
Set.toheat
pump
retained.
Compressor
1
Min outdoor temp °C
2
Brine pump on
Tariff HP
Minimum run time
Permitted
-15
Auto
Off
6
Def Heat pump
Heat pump
Flow/level switch
Off
None
CTC EcoZenith i250
41
Ele
Ele
Ele
Ele
Ele
Ele
Ele
HP upper tank
49 (58)
General
Information
42 (45)
0.0+2.5 Stored oper data
0.0 0.0 0.0
On 32
Off 22(20)
er °C
r °C
ower kW
/L2/L3
Pump / ºC
Heating circuit
8.8 Define system
ration data heating
Here you can define the method of use of the product.
Define functions such as: heat pump, room sensor,
radiator system 2, solar heating, etc.
For more information, see the relevant function on the
following pages.
20
0
Room1
1
2
Prim1
4
Return
8
Room2
Define system
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
Diff thermostat function
Pool (G50, G51, B50)
No
No
12
Prim2
Service
8.8.1 Def heating circuit 1 or 2
Room temp.
Specify whether the room sensor should be connected
to the system. No/Yes
Heating circuit 1
Select whether the room sensor for the heating system
is permanently connected or wireless. Wired/Wireless
Night reduction
1
Heat pump
Electric heater
Upper tank
Remote control
None
Communication
Solar panels
Diff thermostat function
Pool
Save settings
Load settings
Load factory settings
Op.
Def test
heating circuit 1
Function
Communication
Alarm log
Heating settings
circuit 1 coded
Factory
Room
sensor
1
MB
address
Quick
start
compressor.
Type rate
Baud
Software
update, USB
Parity
Write
log to USB
Stop bit
Control current sensors
Re-installation
Primary f
Return flo
HP
Radiator
MixingHP
va
Delay HP
mix
Deff
Primary
Com
Radiator
MixingDrip
va
Hea
4-w
Yes
1Yes
Wire
9600
even
1
Holiday
2
If a wireless room sensor has been installed, scroll down
Room temp.
to “Room sensor: Connect” and press “OK”. The cursor
moves to the word “Connect”. Press “OK” again. The
Heating circuit
1 now
(50) waits for the room sensor to communicate
system
with the heat pump.
See the manual for the wireless room sensor for more
information.
Night reduction
Holiday
Def heating circuit 1
Sett.
Installer
Heating circuit 1
Save settings
Room sensor 1
Save settings
Type
Load factory settings
Action
Disconnect
Status
Associated
Level of signal
Battery
Version
Charge sta
Charge3-w
sto
Charge tem
Yes
Yes
Wireless
85%
x0102
8.8.2 Def Heat pump
Set. heat pump
Heat pump
On/Off
Specify
here
whether
the
heat
pump
is
installed.
Compressor
Permitted
Min outdoor temp °C
-15
2
Brine pump
on
Flow/level
switchAuto
Tariff HP
Off
(Applies
Minimum run
time to the EcoPart
6
1
None/NC/NO
only.) Specify whether or which
type of level switch is installed in the system (accessory).
Choose between:
• None
• NC (Normally Closed)
• NO
(Normally Open).
Electric
heater
Boiler upper °C
Boiler upper add °C
Boiler upper extra DHW °C
Boiler upper max kW
Boiler lower °C
Boiler lower max kW
Delay mixing valve
Main fuse A
Input voltage
Tariff EL
42
50
57
60
5.5
55
6.0
180
25
3x400 V
Off
CTC EcoZenith i250
Def Heat pump
Heat pump
Flow/level switch
Test
Ele
Off
None
Ele
Pump H-ta
Ele
Temperatu
Ele
H-tank Ele
(B6
Ele
Ele
Define Cooling
Cooling
Common heating/cooling
Condense pipe secured
Room temp. cooling
No
No
No
25.0
Test Heating circuit
Mixing valve1
Rad pump1
Mixing valve2
Rad pump2
LED room sensor
Open
On
Off
Off
On
Def CTC SMS
Activate
Level of signal
Phone Number 1
Phone Number 2
Hardware Version
Software Version
Yes
+46712345678
----------------1
1
1
9
1
2
Lat
Low
Sto
Wro
Com
Roo
Heating c
Cooling
General Information
Op.
Def heating circuit 1
Heating circuit 1
Room sensor 1
Type
8.8.3 Define CTC SMS (accessory)
This is for defining whether SMS control is installed
(accessory).
Activate
Yes (Yes/No)
If “Yes”, the menus below will be displayed.
Level of signal
The level of signal of the reception is shown here.
Primary f
Return flo
Radiator
Mixing va
Delay mix
Primary f
Radiator
Mixing va
Yes
Yes
Wire
Def CTC SMS
Activate
Level of signal
Phone Number 1
Phone Number 2
Hardware Version
Software Version
Yes
+46712345678
----------------1
1
1
9
Def heating circuit 1
Phone Number 1
The first activated phone number is shown here.
Phone Number 2
The second activated phone number is shown here.
Hardware Version
The hardware version of the SMS accessory is shown
here.
Sett.
Heating circuit 1
Room sensor 1
Type
Action
Disconnect
Status
Associated
Level of signal
Battery
Version
Charge sta
Charge sto
Charge tem
Yes
Yes
Wireless
85%
x0102
Software version
The software version of the SMS accessory is shown
here.
NB: For more information on the SMS function, see the
“CTC SMS” manual.
Test
Pump H-ta
Temperatu
H-tank (B6
8.8.4 Define cooling (accessory)
Define Cooling
(Only applies to EcoPart.)
Cooling is adjusted using primary flow sensor 2 (B2),
which means that radiator system 2 and cooling cannot
be used simultaneously.
Common heating/cooling
Cooling
Common heating/cooling
Condense pipe secured
Room temp. cooling
No
No
No
25.0
No
Cooling
No (No/Yes)
This is for selecting whether cooling is installed.
Condense pipe secured
No (No/Yes)
If a condense pipe for the system has been secured,
significantly lower temperatures are permitted at
various points in the system. WARNING Build-up of
condensation in the house structure can lead to damp
and damage from mildew.
1
2
Roo
Def CTC SMS
Activate
Yes
Heating c
Level of signal
See
the CTC EcoComfort manual for more
Phone Number 1
+46712345678
information.
Phone Number 2
----------------Hardware Version
Software Version
1
1
Cooling
1
9
(No) means a setting range for room temperature of
18–30ºC and (Yes) means a setting range of 10–30ºC
Nig
In the event of doubt, contact an expert surveyor for an
assessment.
Room temperature cooling
25 (10 or 18...30)
This is used to set the desired room temperature for
cooling.
Operation data system
CTC EcoZenith i250
43
r °C
°C
wer kW
/L2/L3
ump / ºC
HP upper tank
49 (58)
42 (45)
General
0.0+2.5 StoredInformation
oper data
0.0 0.0 0.0
On 32
Off 22(20)
Heating circuit
Electric heater
Upper tank
Remote control
None
Communication
Solar panels
Diff thermostat function
Pool
Save settings
Load settings
Load factory settings
8.8.5 Def Solar panels
Solar panels No/Yes
ation data heating
Specify here whether solar panels are used. This
function will only work if an expansion card is connected
to the product.
See the CTC Solar controls/Expansion card manual for
more information.
20
Room1
0
Prim1
4
Return
8
Room2
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
Diff thermostat function
Pool (G50, G51, B50)
No
No
12
Prim2
8.8.6 Define Differential thermostat
function
Differential thermostat function No/Yes
Specify here whether operating thermostat function is
used. The differential thermostat function is used if you
want to charge your EcoZenith from a water-jacketed
stove, or another heating source.
However, this function cannot be combined with the
same function in a solar heating system (when e.g. an
EcoTank is connected to an EZ 250). This is because
the same outlets and sensors are used for both
functions.
Information about the Differential thermostat function will
be displayed under Operation data.
8.8.7 Def. Pool
Specify here whether pools are used. This function
will only work if an expansion card is connected to the
product.
See the CTC Solar controls/Expansion card manual for
more information.
44
Define system
CTC EcoZenith i250
Service
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
!
NB: If the expansion card has not
been installed and solar or Pool has
been defined, the product will emit
an alarm:
Comm. fault expansion card.
Settings
ation
1 data
2 heating
eating circuit 1
eating circuit 2
eat pump
Room temp.
lectric heater
pper tank
emote control
None
ommunication
Heating circuit 1
olar panels
iff thermostat function
ool
ave settings
20
0
4
8
oad settings
Room1
Prim1
Return
Room2
oad factory settings
Heating
1
Heating
circuit circuit
1
Heating circuit 2
Max pump
primary flow °C
55
Heat
General
Communication
Min SMS
primary
flow °C
Off
CTC
Heating off, out °C
18
Cooling
Heating
off
120
Solar
panels
MB address
1 50
Inclination °C
Diff
thermostat
function
No
Baud rate
9600
Adjustment °C
0
Pool
(G50, G51, B50)
No
Parity
even
Room
temp
reduced °C
Stop bit
1 -2
or
Primary flow reduced °C
-3
>>
12
8.9 Service
Prim2
Night reduction
Define system
1
!
HP
HP
HP
De
Co
Dri
He
4-w
Service
Holiday
2
eating circuit 1
eating circuit 2
eat pump
NB: This menu
Room temp.
TC SMS
installer only.
ooling
olar panels
Heating
circuit 1
(50)
iff thermostat
function
No
ool (G50, G51, B50)
No
Information
is intended for the
Def test
heating circuit 1
Function
Alarm log
Factory
Heatingsettings
circuit 1coded
Quick
compressor.
Roomstart
sensor
1
Type
Software
update, USB
WriteInstaller
log to USB
Control current sensors
Re-installation
Save settings
Yes
Yes
Wire
3-w
Save settings
Load factory settings
8.10 Function test
Service
This menu is intended to test the function of the
Night reduction
Holiday
various components in the product. When the menu
unction test
is activated, all the product’s functions stop. Each
larm log
actory settings coded
component can then be tested separately or together.
uick start compressor.
All control functions are shut off. The only protection
Set.
oftware update, USB heat pump
against incorrect operation are pressure sensors and
Write log to USB
Compressor
Permitted
ontrol current
sensors
the immersion heater’s
superheat protection. When you
1
Min outdoor temp °C
-15
e-installation
2
exitonthe menu, EcoZenith
Brine pump
Auto returns to normal operation.
Tariff HP
Off
If
no
button
is
pressed
for 10 minutes, the product
Minimum run time
6
automatically returns to normal operation.
8.10.7.1 Test heating circuit
Electric heater
If two radiator systems are installed, the values for both
are displayed here. 50
Boiler upper °C
Boiler upper add °C
57
Mixing
valve
Boiler upper
extra DHW °C
60
Boiler upper max kW
5.5
Opens
and closes the
Boiler lower
°C
55 mixing valve. (Open/Close)
Boiler lower max kW
6.0
Delay mixing
valve
180
Rad
pump
Main fuse A
25
Input voltage
3x400
V
Starts and stops the
radiator
pump. (On/Off)
Tariff EL
Off
Function test
Heating circuit
Heat pump
Valves
Electric heater
Solar
Diff thermostat function
Def Heat pump
Pool
Heat pump
Flow/level switch
!
Ele
Ele
Ele
Ele
Ele
Ele
Ele
Off
None
When you exit the menu, CTC
EcoZenith returns to the start menu.
Test Heating circuit
Mixing valve1
Rad pump1
Mixing valve2
Rad pump2
LED room sensor
Open
On
Off
Off
On
Lat
Low
Sto
Wr
Co
LED room sensor
The room sensor alarm function can be controlled
from here. When activated, the room sensor’s red LED
Upper tank
comes on steady.
Stop temp
HP °C
Max
Communication
Start/stop8.10.7.2
diff upper ºC Test Heat
7
pump
Max time upper tank
20
MB time
address
1
Max
lower
tank
40
Function test carried out on the heat
Baud rate
9600
Parity
even
HP
Compr.
Stop bit
1
pump.
(On/Off)
(On/Off) This is where the function test is carried out
on the compressor. The fan or brine pump and charge
pump are also operating so that the compressor is not
going to trigger its pressure switches.
Installer
Save settings
Save settings
Load factory settings
Co
Up
Low
Co
Exp
Log
Co
Test Heat pump
HP Compr.
HP Brine p/Fan
HP Charge p
Defrost Manually
Compressor heat
Drip tray heater
Heating Cable
4-way valve(Y11)
Off
Off
0
Off
Off
Off
Off
Off
Test valves
3-way valve
Down
CTC EcoZenith i250
45
General Information
Communication
Test Heat pump
Communication
MB address
1
Baud rateHP Brine pump/Fan
9600
Parity
Communication
MB address
1 the fan or brine
(On/Off) Activation of1even
Stop
Baudbit
rate
9600
Parity
even
MB address
1
Stop
bit HP Charge pump 1
Baud rate
9600
(On/Off)
Function
test
0–100%.
Parity
even
Stop bit
1
Test Heat pump
(On/Off)
pump.
(On/Off)
Manual defrosting (Applies to the CTC EcoAir only)
Manual defrosting function test (On/Off)
Def heating circuit 1
Compressor heater(Applies to the CTC EcoAir only)
Heating
circuit 1 heater function
Yes test (On/Off).
Compressor
Room sensor 1
Yes
Type
Wire
Installer
Heater condensation tray(Applies
to the CTC EcoAir
only)
Installer
Save settings
Heater condensation tray function test (On/Off).
Save settings
Installer
Load
factory settings
Save settings
Heating cable(Applies to the CTC EcoAir only)
Save settings
Load factory
settings
Heating
cable function test. (Accessory) (On/Off)
Save settings
HP Compr.
HP Brine p/Fan
HP Charge
Test pHeat pump
Compr.
Defrost
HP BrineManually
p/Fan
Compressor
HP Charge p heat
HP
Compr.
Drip
tray
heater
Defrost Manually
HP
BrineCable
p/Fan
Heating
Compressor
heat
HP
p
4-way
valve(Y11)
DripCharge
tray
heater
Defrost
Manually
Heating Cable
Compressor
heat
4-way valve(Y11)
Drip tray heater
Op.
Heating
Circuit
Heating Cable
4-way valve(Y11)
Primary flow1 ºC
33(34)
Return flow ºC
31
Radiator
Till
Testpump
valves
Mixing valve
Open
Delay mixing valve
180
Test
valves
Primary
flow 2ºC
33(34)
3-way
valve
Radiator pump 2
Från
Mixing
valve
2
Test
valves
3-way
valve
Off
Off
0
Off
Off
Off
0
Off
Off
Off
0
Off
Off
Off
Off
Off
Off
Off
Off
3-way valve
Down
S
Down
Down
Save settings
4-way
valve
Load factory
settings
(Applies to the CTC EcoAir only)
4-way valve function test (On/Off).
S
8.10.7.3 Test Valves
Def heating circuit 1
Sett. Diff termostat function
Function test carried out on the flow conditioner. Flow
test (Up/Down)
(upper and lowerYes
parts of the tank
Heating
circuit 1
Def
Heat
pump
Room
sensor
1
Yes
respectively).
Type
Wireless
Def
Heat pump
Action
Heat pump
Off
8.10.7.4
Test Elec.heater
Disconnect
Flow/level
switch
None
Status
Def
Heat
pump
Heat pump
Offto test the immersion
You use this function
Associated
Flow/level
switch
None
Level of signal
phases: L1, L2 and L3.
Battery
85%
Heat pump
Off
Version
x0102
Flow/level
switch
None
Charge start diff temp ºC
Charge
stopElec.heater
diff temp ºC
Test
Charge temperature °C
Test Elec.heater
Electric heater L1A
Electric heater L1B
Electric
heater
L2A
Test
Elec.heater
L1A
Electric heater L2B
L1B
Electric heater L3A
L2A
L1A
Electric heater L3B
L2B
L1B
Electric heater A13
L3A
Electric
heater
Electric heater L2A
L3B
Electric
heater
Electric heater L2B
A13
Electric heater L3A
Electric heater L3B
Electric heater A13
heater’s
The modes available are On/Off.
8.10.7.5 Test Solar
This function will only work if an expansion card is
connected to the product.
the CTC
Solar controls/Expansion card manual for
TestSee
Heating
circuit
more
information.
Test Heating circuit
Mixing valve1
Open
Rad pump1
On
8.10.7.6
Test
differential
MixingTest
valve2
valve1
Open
Heating circuit Off
Rad pump2
Off
function
pump1 Define Cooling
On
LED
room
sensor
On
Mixing
valve2
Off
Mixing
valve1
Open
Rad
pump2
Off
Cooling
No
Pump transfer (G46)
Rad pump1
On
LED
room
sensor heating/coolingOn
Common
No
Mixing valve2
Off test.
Charge
pump
function
Condense pipe secured
No
Rad pump2
Off
Room temp. cooling
25.0
LED room sensor
On
Pump H-tank (G46)
Alarm log
Temperatures
Latest alarm:
H-tank
(B6)flow
ºC
Low brine
Stored
alarms:
log
LatestAlarm
alarm:
Wrong
phase
Low brine
floworder
Com.
m. protect
Storederr
alarms:
Latest
Wrong alarm:
phase order
Low
flow
Com.brine
err m.
protect
Stored alarms:
Wrong phase order
Com. err m. protect
(On/Off)
8.10.7.7 Test Pool
Def CTC SMS
Activate
Level of signal
Phone Number 1
Phone Number 2
Hardware Version
Software Version
Yes
+46712345678
----------------1
1
1
9
1
2
CTC EcoZenith i250
Off
Time
07:20 6/3
Time
10:30
07:20 1/3
6/3
09:01 1/3
Time
10:30 1/3
07:20
09:01 6/3
1/3
HP (b) LP (b)
32
8.8
3.3
HP (b) LP (b)
27.9
8.6
8.8
3.3
27.9 3.6
HP
(b)
LP
27.9 8.6 (b)
8.8
27.9 3.3
3.6
SH (K)
15.9
SH (K)
-227
15.9
42.2
SH
-227(K)
15.9
42.2
I(A)
3.9
I(A)
50.0
3.9
0.0
I(A)
50.0
3.9
0.0
10:30 1/3
09:01 1/3
27.9
27.9
-227
42.2
50.0
0.0
8.6
3.6
Factory settings coded
Factory settings coded
Code
Upper tank
Lower
tank temp.
Factory
settings
CodeRoom
Compressor
Upper tank operation
Expansion
Lower tankvalve
Code
Log
compressor
Compressor
operation
Heating
circuit
1 stop
Upper
tankvalve
Cooling
Expansion
Lower
tank
Log compressor
stop
Compressor
operation
Cooling
Cooling
Expansion valve
Log compressor stop
Cooling
Night reduction
46
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Test
Difflog
thermostat function
Alarm
thermostat
This function will only work if an expansion card is
connected to the product.
See the CTC Solar controls/Expansion card manual for
more information.
7
3
60
0000
coded
0000
0000
20.2 (20.0)
20.2 (20.0)
Holiday
Flow/level switch
None
8.11 Alarm log
Heat pump
Test Heating circuit Off
Flow/levelYou
switch
can use this to None
read
information about the latest
Mixing valve1
Open is displayed at the top and the
alarms. The latest alarm
Rad pump1
On
four latest alarms are
Mixing valve2
Off shown under Stored alarms.
Off
which reoccurs
within an hour is ignored so
On
as not to fill up the log. If all the alarms are the same,
this can indicate that there is an intermittent fault, e.g. a
loose contact.
!
Information
Electric
heaterlog
L1A
Alarm
Electric heater L1B
Electric heater L2A
Latest
Electricalarm:
heater L2B
Low
brine
flow L3A
Electric
heater
Stored
Electricalarms:
heater L3B
Wrong
Electricphase
heaterorder
A13
Com. err m. protect
Time
07:20 6/3
10:30 1/3
09:01 1/3
Off
Off
Off
HP
Off (b)
8.8
Off
Off
27.9
Off
27.9
LP (b)
3.3
SH (K) I(A)
15.9 3.9
8.6
3.6
-227
42.2
50.0
0.0
Alarm log
Test Heating circuit
Mixing valve1
Rad pump1
Mixing valve2
Rad pump2
LED room sensor
Off
Off
Off
Off
General
Off
Off
Test Elec.heater
Def Heat pump
Rad pump2
alarm
LED room An
sensor
Electric heater L1B
Electric heater L2A
Electric heater L2B
Electric heater L3A
Electric heater L3B
Electric heater A13
Factory
Latest
alarm: settings
Time coded
HP (b) LP (b) SH (K) I(A)
Low brine flow
07:20 6/3 8.8
3.3
15.9 3.9
Stored alarms:
Code
0
0
0
0
Wrong phase order 10:30 1/3 27.9 8.6
-227 50.0
Upper
tank
Com. err
m. protect 09:01 1/3 27.9 3.6
42.2 0.0
Lower tank to log in to the Factory settings
NB: Only an authorised service engineer is allowed
Compressor operation
coded option. Severe operational problemsExpansion
and faults
may occur affecting the
valve
Log compressorNote
stop that in such cases the
product if values are amended without authorisation.
Cooling
Open
On
Off
Off
On
warranty terms do not apply.
Factory settings coded
This menu is intended to set the manufacturer's
operational and alarm limits. A 4-digit code must be
specified to be able to amend these limits. However,
you can also take a look without any code to see what
options feature in the menu.
Factory settings coded
Code
Upper tank
Lower tank
Compressor operation
Expansion valve
Log compressor stop
Cooling
0000
CTC EcoZenith i250
47
ation data heating
General Information
20
Room1
0
Prim1
4
8
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
Diff thermostat function
Pool (G50, G51, B50)
No
No
12
Quick
start compressor
Return
Room2
Prim2
(Applies only if heat pump is installed.)
When starting up the product, the compressor’s start
is delayed by 10 minutes. This function speeds up this
process.
Software update, USB
This is only for service engineers. This option can be
used to update the software in the display via USB. The
software update process is complete when the start
menu appears.
Write log to USB
This is only for service engineers. This function can be
used to save logged values to a USB memory stick.
Service
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
!
NB: The power to the product
must not be interrupted, under any
circumstances, during the update
process.
Control current sensors
This is for identifying which current sensor is connected
to the relevant phase.
All three currents (L1, L2 and L3) will appear in the
current operational data when EcoZenith i250 has
identified the current transformers’ relevant phases.
When activating the function “Control current
sensors” it is important that you have switched off
any major consumers of electricity in the house.
Also make sure that the backup thermostat in CTC
EcoZenith i250 is turned off.
Re-installation
This command re-launches the installation sequence.
See the chapter on First start.
48
CTC EcoZenith i250
!
NB: Turn off the power and always
restart the product after the
program update! Several minutes
may pass before the display
communicates clearly after restart.
General Information
9. Operation and
Maintenance
When the installer has installed your new system, you should check along
with the installer that it is in perfect operating condition. Let the installer show
you where the switches, controls and fuses are so that you know how the
system works and how it should be maintained. Bleed the radiators after
around three days of operation and top up with water if required.
increase
decrease
Boiler and radiator system safety valve
Check around four times a year that the valve is working by manually turning
the control. Check that water is coming out of the safety valve discharge.
Mixing Valve
The mixing valve is operated automatically from the control system, ensuring
that the radiators reach the correct temperature, no matter what season it
is. However, where a fault occurs, you can operate the valve by pulling out
the knob on the motor and turning it clockwise to reduce the temperature or
anticlockwise to increase it.
Draining the tank
The CTC EcoZenith should be disconnected from the power source when
it is being drained. The drain valve is positioned at the bottom left of the
unit when viewed from the front, behind the front of EcoZenith. When
draining the whole system, the mixing valve should be fully open, i.e. turned
anticlockwise as far as it will go. Air must be supplied to the closed system.
!
Do not forget to reset the mixing valve
to the automatic
position by pushing
in the knob again.
Operation stop
The CTC EcoZenith i250 is shut down using the operating switch. If there
is a risk of the water freezing, all the water should be drained from the heat
pump and the radiator system (see drainage above).
The DHW circuit, which contains around five litres, must also be emptied.
Disconnect the cold water connection to CTC EcoZenith i250. Feed a hose
into the cold water connection to CTC EcoZenith i250. The hose must go
down to the bottom of the coil for all the water to be drained. Draining is
carried out by siphoning out the water.
CTC EcoZenith i250
49
General Information
10. Troubleshooting/appropriate measures
The CTC EcoZenith i250 is designed to provide reliable operation and high
levels of comfort, and to have a long service life. Various tips are given
below which may be helpful and guide you in the event of an operational
malfunction.
If a fault occurs, you should always contact the installer who installed your
unit. If the installer believes the malfunction is due to a materials or design
fault, then they will contact Enertech AB to check and rectify the issue.
Always provide the product’s serial number.
DHW
Many people want to gain maximum benefit from the CTC EcoZenith i250’s
low operating costs.
!
The control system is equipped with three comfort levels for hot water. We
recommend starting at the lowest level and if there is not enough hot water,
increase it to the next level. We also recommend that you operate a regular
hot water pattern.
Check that the hot water temperature is not being affected by a poor mixing
valve, whether in the CTC EcoZenith i250 or possibly the shower mixer.
The Heating System
A room sensor, which should be fitted when possible, ensures that the
temperature in the room is always suitable and stable. For optimal running,
radiator thermostats should always be fully open in the area where the room
sensor is located.
!
Avoid running hot
water at the highest
flow capacity. If you
run a bath at a rather
slower rate instead,
you will get a higher
temperature.
Avoid placing the
room sensor close
to the stairway due
to the uneven air
circulation.
A correctly operating heating circuit is of significant importance to the heat
pump’s operation and affects energy savings.
When adjusting the system, always do so with all radiator thermostats fully
open. The thermostats can be individually adjusted after a few days in rooms
where lower temperatures are desired.
50
CTC EcoZenith i250
!
If you do not have
radiator thermostats
on the upper floor,
you may need to
install them.
General Information
If you do not achieve the set room temperature, check:
• that the radiator system is correctly adjusted and is functioning
normally. that radiator thermostats are open and the radiators are
equally warm all over. Touch the entire radiator surface. Bleed the
radiators. The CTC EcoZenith i250's economical operation demands a
radiator system that functions effectively.
• that EcoZenith is operating and no error messages are displayed.
• that there is sufficient electrical power available. Increase if necessary.
Also check that the electric power output is not limited due to
excessively high electricity loads in the property (load monitor).
• that the product is not set to the “Max. allowed primary flow
temperature” mode with a too low set value.
• that “Primary flow temperature at –15°C outdoor temperature” is set
sufficiently high. Increase if necessary. More can be read about this in
the chapter on The house heating curve. However, always check the
other points first.
• that the temperature reduction is set correctly. See Settings/Radiator
system.
• that the mixing valve is not in the manual position.
If the heat is not even, check:
• that the placement of the room sensors is appropriate for the house.
• that the radiator thermostats don’t interfere with the room sensor.
• that no other heat sources/cold sources interfere with the room sensor.
• that the mixing valve is not in the manual position.
CTC EcoZenith i250
51
General Information
Current Monitor
The CTC EcoZenith i250 has an integrated current monitor. If the system
is fitted with a current sensor, the property’s main fuses are continuously
monitored to ensure they are not overloaded. If this should happen, electric
stages are disconnected from the CTC EcoZenith.
The electrical power of the CTC EcoZenith i250 may be restricted where high
heating requirement levels are combined with, for example, single-phase
motor heaters, cookers, washing machines or tumble dryers. This may result
in inadequate heating or hot water temperatures. If the CTC EcoZenith is
restricted, “High current, elpower redu (X A)” appears in text form in the
display. Consult an electrician to determine whether the fuse size is correct
or the three phases in the house are evenly loaded.
Vent valve
Air problems
If you hear a rasping sound from the tank, check that it has been properly
bled. Turn the boiler vent valve so that any air can be evacuated. Top up with
water where required, so that the correct pressure is achieved. If this noise
recurs, call a technician to check the cause.
Unusual noise when shutting off DHW
In some cases, unusual noises may be produced by the house's pipe
system and the CTC EcoZenith i250 due to the jolts which occur when the
flow is quickly interrupted. There is no fault with the product, but the noise
may occur when older model outlets are used. More recent outlets are
often fitted with a soft-closing mechanism. If an unusual sound comes from
hard-closing dishwasher and washing machines, this can be remedied using
a shock arrestor. A shock arrestor can also be an alternative to soft-closing
water taps.
Motor protection (when heat pump is connected)
The CTC EcoZenith i250 constantly monitors the compressor’s operating
current and an alarm is triggered if the compressor is using an unusually high
current. When a fault occurs the message "Motor protect high current" is
displayed.
The cause of the fault may be as follows:
• Phase failure or mains interruption. Check the fuses, which are the
most common cause.
• Compressor overload. Call out a service engineer.
• Faulty compressor. Call out a service engineer.
• Inadequate circulation between the heat pump and boiler. Check the
heat medium pump (left pump, viewed from front). Call out a service
engineer.
• Abnormally high temperature in the brine circuit. Call out a service
engineer.
52
CTC EcoZenith i250
!
Don’t forget that the
radiators may also
need bleeding.
General Information
10.1 Information messages
Information messages are displayed when appropriate and are intended to
inform users about various operational situations.
Start delay
Start delay
The compressor is not allowed to start too quickly when it has stopped. The
delay is usually approx. 10 minutes.
Heating off, radiator sys
Shows that the product is operating in summer-time mode when only hot
water is required, not heating.
Ripple control
Shows that ripple control is active. Ripple control is a device which an
electricity provider can fit with the aim of disconnecting high current draw
equipment requiring power for a short period of time. Not currently in use
in the UK. The compressor and electrical power are blocked when ripple
control is active.
High current
The property’s main fuses are overloaded due to the fact, for instance, that
several appliances requiring power are being used simultaneously. The
product reduces the electrical power over time.
Tariff, HP off.
Not used.
Tariff, EL, off.
Not used.
Compressor blocked
The compressor is set to be shut down, e.g. before drilling or digging
has been carried out for the collector loops. The product comes with the
compressor shut off. This option is selected under the Installer/Settings/Heat
pump menu.
CTC EcoZenith i250
53
General Information
10.2 Alarm texts
Alarm: Wrong phase order
compressor
Reset alarm
If a fault occurs with a sensor, for instance, an alarm is triggered. A message
appears on the display with information about the fault.
You reset the alarm by pressing the Reset alarm button on the display.
If several alarms are triggered, they are displayed one after the other. An
outstanding fault cannot be reset without being rectified first. Some alarms
are reset automatically if the fault disappears.
The description below also includes an alarm for connected heat pump.
Alarm text
Description
Wrong phase order
compressor
The product’s compressor motor must rotate in the right direction. The
product checks that the phases are connected correctly; otherwise, an
alarm is triggered. In this case, two of the phases to the product need to be
changed. The power supply to the system must be shut off when rectifying
this fault. This fault generally only occurs during installation.
Alarm sensor
An alarm is displayed if a fault occurs with a sensor that is not connected or
has short-circuited and if the value is outside the sensor's range. If this sensor
is important to the system’s operation, the compressor stops. In this case,
the alarm is reset manually after the fault has been rectified. For the following
sensors the alarm is reset automatically after correction:
Sensor upper tank (B5), Sensor lower tank (B6), Sensor prim flow 1 (B1),
Sensor prim flow 2 (B2), Sensor out (B15), Room sensor 1 (B11), Room
sensor 2 (B12), Sensor brine out, Sensor brine in, Sensor HPin, Sensor HPout,
Sensor discharge, Sensor suction gas, Sensor high pressure, Sensor low
pressure.
54
Motor protect compressor
High/low current has been detected to the compressor. Press reset and
check whether the alarm recurs. If the fault recurs, contact your installer.
High pressure switch
The refrigerant’s high pressure switch has been triggered. Press reset and
check whether the alarm recurs. If the fault recurs, contact your installer.
Low brine temp
Incoming brine temperatures from borehole/ground loop are too low. Press
reset and check whether the alarm recurs. If the fault recurs, contact your
installer to check the dimensions of the cold side.
CTC EcoZenith i250
General Information
Alarm text
Description
High brine temp
Incoming brine temperatures from borehole/ground circuits are too high. Press
reset and check whether the alarm recurs. If the fault recurs, contact your
installer to check the heat source.
Excessively high brine circuit temperatures over a long period can
damage the compressor.
Low brine flow
Low brine flow is very often due to air in the collector system, particularly
just after installation. Collectors which are too long can also be a cause. Also
check that the brine pump is set to the fastest speed. Press reset and check
whether the alarm recurs. Also check the brine filter that has been installed.
If the fault recurs, contact your installer.
4-way valve alarm
This alarm is displayed if a fault occurs with EcoAir's 4-way valve or if the
connection pipes to the EcoAir are incorrectly connected. Press reset and
check whether the alarm recurs. If the alarm recurs, check that the charge
pump is pumping water to the heat pump's lower connection. If the fault
recurs, contact your installer.
Max. thermostat
If the heat pump has been stored in an extremely cold place, the max.
thermostat may have been triggered. You reset it by pressing in the button on
the electrical switchboard behind the front panel.
Always check on installation that the max. thermostat has not tripped.
Communication error PCB,
Communication error HP,
This message is displayed when the display card cannot communicate with
the relay card.
Communication error motor
protection
Communication error expansion
This message is displayed when the display card cannot communicate with
the HP control card.
card
This message is displayed when the HP control card cannot communicate
with the motor protection.
This message is displayed when the display card cannot communicate with
CTC Solar controls/Expansion card.
Fuses
This message appears when fuse F1 has been triggered.
High compr. temp
This message appears when the compressor temperature is high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
Low evaporation
This message appears when the evaporation temperature is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
CTC EcoZenith i250
55
General Information
Alarm text
Description
High evaporation
This message appears when the evaporation temperature is high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
Low suct gas exp. valve
This message appears when the suction gas temperature is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
Low evapor exp. valve
This message appears when the expansion valve’s evaporation temperature is
low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
High evapor exp. valve
This message appears when the expansion valve’s evaporation temperature is
high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
Low superheat exp. valve
This message appears when the expansion valve’s superheat temperature is
low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
EVO off
This message appears when there is a fault with the expansion valve control.
Contact your installer.
Phase missing
This message appears in the event of a phase failure. Call in a specialist to
check the cause.
Compressor type?
This message appears if there is no information about the compressor type.
Heat pump alarm
This message appears if the heat pump is in alarm mode.
Driver
Driver fault.
Press reset and check whether the alarm recurs.
If the fault recurs, contact your installer and tell them the error code number
where applicable.
Driver: Offline
56
CTC EcoZenith i250
Communication error. The electrical connection box and driver of the heat
pump are not communicating.
Installation
Installation
11.
Installation
This chapter is aimed at anyone responsible for one or more of the
installations required to ensure that the product works the way the property
owner wants.
Take your time going through functions and settings with the property owner
and answer any questions. Both you and the CTC EcoZenith i250 benefit
from a user who has completely understood how the system operates and
should be maintained.
!
The product must
be transported and
stored in an upright
position.
11.1 Transportation
Transport the unit to the installation site before removing the packaging.
Handle the product in the following manner:
• Forklift
• Lifting eye that has been fitted to the lifting sleeve on top of the
EcoZenith i250. An extra sleeve can be found in the middle, under the
insulation.
• Lifting band around the pallet. NB: Can only be used with the
packaging on.
Remember that the CTC EcoZenith i250 has a high centre of gravity and
should be handled with caution.
11.2 Unpacking
Unpack the CTC EcoZenith i250 when it is placed next to its installation
site. Check that the product has not been damaged in transit. Report any
transport damage to the carrier. Also check that the delivery is complete
according to the list below.
11.3 Standard delivery
• CTC EcoZenith i250 system tank with factory-installed charge pump for
connection of heat pump.
• Kit bag containing:
––Installation and Maintenance Manual
––Outdoor sensor
––Room sensor
––Safety valve 9 bar (clean water)
––Sensor, 2 off (to and from pipes)
––Current sensor, 3 off
––2 x cable ties
––Insulation EPP centre 41 mm.
––Support sleeve 22x1 cu
CTC EcoZenith i250
57
Installation
12. Pipe installation
The installation must be carried out in accordance with current standards
and regulations. Refer to the Warm and Hot Water Installation Instructions
1993. The product must be connected to an expansion vessel in an open or
closed system.
Do not forget to flush the radiator system clean before connection.
Apply all the installation settings based on the description in the chapter
“First start”.
12.1 Filling
Filling valve (no. 90, see schematic diagram on next page) is connected
to the radiator return pipe. Alternatively, the valve can be installed in the
direction of the expansion pipe. When the boiler and system are being filled
with water, the mixing valve (Y1) must be fully open. Pull out the knob on the
valve and turn it anticlockwise as far as you can. Do not forget to push and
set the knob on the valve to automatic mode after filling.
If the heat pump is not connected, connections 1 and 2 must be capped
when filling with water. (See figure)
12.1.1 Pressure drop in mixing valve
The diagram below shows a drop in pressure in the mixing valve.
Start with the heat requirement in kW (e.g. 15 kW), then move vertically
to the selected ∆t (e.g. 10 °C). Then move horizontally to the line for the
EcoZenith i250 mixing valve = line 6.3 DN20. The reading for the pressure
drop is taken from the scale directly below (4 kPa).For EcoZenith i250, see
valve DN20.
58
CTC EcoZenith i250


Installation
6
UPM2, UPM GEO and UPM2K
12.1.2 Pump curve charge pump
Performance curves and technical data
The diagram below shows the pump curve for the factory-installed charge
pump for a Grundfos UPM2 15-60 130 heat pump.
UPM2 15-60 130, 1 x 230 V, 50/60 Hz
p
[kPa]
60
H
[m]
6
5
40
4
30
3
20
2
10
1
0
0
0.0
6
P1
[W]
0.2
0.0
0.4
0.6
0.1
0.8
1.0
0.2
1.2
1.4
0.3
1.6
1.8
0.4
2.0
0.5
2.2
2.4
0.6
2.6
0.7
Q [m³/h]
2.8
0.8
Q [l/s]
UPM2, UPM GEO, UPM2K
50
40
EEI ≤ 0.23
30
10
The diagram
below shows the pump curve for CTC accessory item no. 586988301
Grundfos
0UPMS 15–75 130
UPM2
15-75
130, 1 xpump.
230 V, 50/60 Hz
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
p data,
H 1 x 230 V, 50 Hz
Electrical
[kPa] [m]
1.6
Speed
70
Min.
8
P1 [W]
7
3.8
0.04
Max.
60
6
48
0.36
1.8
2.0
2.2
2.4
2.6
Q [m³/h]
2.8
I1/1 [A]
50
Dimensional
sketches
and control box positions
5
40
4
30
3
20
2
10
1
0
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4
P1
[W]
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Q [m³/h]
1.0
Q [l/s]
70
60
50
EEI ื 0,23
40
30
Pump type
UPM2 15-60
Dimensions [mm]
20
10
0
L1
L2
L3
B3
B4
B5
H1
H2
130
22
131
85
48
54
25.5
108
Connection
Net weight
[kg]
Quantity per
pallet
G1
2.25
160
Technical data 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 Q [m³/h]
System pressure:
1.0 MPa (10 bar)
Elektrische Daten - 1 x 230Max.
V, 50
Hz
Minimum inlet pressure:
Drehzahl
Liquid temperature:
MIN
Motor protection:
MAX
0.05 MPa (0.5 bar) at 95 °C liquid
temperature
P1 [W]
I1/1 [A]
+2 °C to +95 °C (TF 95)
3,8Overload protection 0,04
70
0,52
Revision date: 1 november 2011
Maßskizzen und Klemmenkastenstellungen
TM05 1400 2711 - TTM04 9482 4310
TM04 9518 3710 - TM04 9200 3710
Kennlinien und technische Daten
Pump 20
curve charge pump 15–75, 130 (Accessories)
TM04 9516 3710 - TM04 9200 3710
50
Enclosure class:
IP44
Insulation class:
H
Equipment class:
I
Approval and marking:
VDE, CE
CTC EcoZenith i250
59
Installation
12.2 Schematic diagram
This shows the main connection between the CTC EcoZenith i250 and the property’s radiator and hot water system.
Different installations and systems may look different, such as a one- or two-pipe system, which means that the
finished installation may be different.
47
Exp
B1
B11
B15
11
G1
B12
Y2
G2
B2
Cold water inlet
12
91
91
90
48
93
65
94
92
B7
P
94
95
Y1
!
B5
cTc
B6
60
01
Radiator system 2
can only give the
same temperature as
radiator system 1 or a
lower temperature.
01 CTC EcoZenith i250
Y2 Mixing valve, radiator system 2
B1 Primary flow sensor for radiator system 1
11 Radiator system 1
B2 Primary flow sensor for radiator system 2
12 Radiator system 2
B5 Sensor upper tank
47 Electric shut-off valve for radiator system
B6 Sensor lower tank
48 Non-return valve for incoming cold water
B7 Sensor, radiator return
65 Mixing valve for DHW
B11 Room sensor 1
90 Filling valve, radiator system
B12 Room sensor 2
91 Adjustment valves for radiator coils
B15 Outdoor sensor
92 Boiler safety valve (factory-installed), 2.5 bar
G1 Circulation pump, radiator system 1
93 Safety valve for DHW
G2 Circulation pump, radiator system 2
94 Shut-off valve
Y1 Mixing valve, bivalent radiator system
95 System/boiler pressure installed on return pipe
CTC EcoZenith i250
Installation
Circulation pump, radiator system (G1) (G2)
The circulation pump is fitted on the boiler’s primary flow and must be
connected electrically from the boiler; see chapter on Electrical installation.
!
Mixing valve DHW (65)
NB: It is important to
fit a shut-off valve (94)
to both the primary
and return flows.
Install a mixing valve for the hot tap water in order to avoid the risk of
scalding.
Safety valve DHW (93)
Fit the enclosed valve to the incoming cold water connection. Connect the
waste pipe to the waste system directly to the floor gully or, if the distance is
more than two metres, to a funnel. The waste pipe must slope towards the
waste system, be installed frost-free and left open to the atmosphere/without
pressure.
Non-return valve (48)
Fit the non-return valve to the incoming cold water connection.
Shut-off valve (94)
It is important to fit a shut-off valve (94) to both the primary and return flows.
Boiler safety valve (92)
The boiler’s safety valve (2.5 bar) is fitted in the factory on the left side of the
top. Connect the waste pipe to the waste system directly to the floor gully
or, if the distance is more than two metres, to a funnel. The waste pipe must
slope towards the waste system, be installed frost-free and left open to the
atmosphere/without pressure.
!
NB: The waste pipe
must be fitted to the
waste system.
Filling valve for radiator system (90)
Fit a filling valve between the cold water connection and the radiator return
pipe, or between the cold water pipe and the expansion pipe. Observe the
building regulations of the Swedish National Board of Housing, Building and
Planning (Boverket) and the standard SS-EN 1717.
Manometer system pressure (95)
Fit the manometer on the expansion pipe or radiator return pipe.
Electric shut-off valve (47)
If the sub-mixing valve (radiator system 2) is to operate in the summertime
while radiator system 1 is switched off, the system can be supplemented
by an electric shut-off valve that closes the flow through the switching off of
radiator pump (G1).
CTC EcoZenith i250
61
Installation
Expansion vessel connection
The CTC EcoZenith i250 is best connected to a closed expansion vessel.
The CTC EcoZenith i250 is designed to be fitted to an 18 l closed expansion
vessel. The expansion vessel is either fitted in the area under the tank or on
top of the product (see pictures). The expansion vessel with installation kit is
available as an accessory.
Expansion vessel
for installation
above the tank.
!
Expansion vessel
for installation
under the tank.
NB: If the heat pump is not connected, the
connections not being used must be capped off!
If you connect the product to an open system, the distance between the
expansion vessel and the highest placed radiator must not be less than 2.5
metres in order to avoid introducing oxygen into the system.
Note that no hot water circulation may be connected as it affects the
function of the EcoZenith and the system. If the EcoZenith i250 is connected
to another heat source, e.g. an existing boiler, the installations must have
separate expansion vessels.
Water taps
In some cases, unusual noises may be produced by the house’s pipe
system and the EcoZenith i250 due to the jolts which occur when the flow
is quickly interrupted. There is no fault with the product, but the noise may
occur when older model outlets are used. More recent outlets are often fitted
with a soft-closing mechanism. Alternatively, a shock arrestor can be fitted.
Keeping the jolting to a minimum also helps avoid unnecessary wear and
tear affecting the DHW system.
62
CTC EcoZenith i250
Installation
12.3 Connection to heat pump
The heat pump is connected to the top (CTC EcoZenith i250L, see figure
below) or bottom (CTC EcoZenith i250H).
The charge pump for the heat pumps is factory-installed in the
CTC EcoZenith i250L.
The CTC EcoZenith i250 L has pipes at the rear right edge for connection of
the heat pump.
The CTC Eco Air’s lower connection (5) is connected to the right connection
(2) when viewed from the front, so that water is pumped out to the heat
pump. The CTC EcoAir's upper connection (4) is thus connected to the left
connection (1).
The CTC EcoZenith i250 H heat pump is connected directly to the supplied
charge pump (3) located under the tank. The heat pump’s lower connection
(5) must be connected to the charge pump (3) so that water is pumped out
to the heat pump. The heat pump’s upper connection is connected to the
right diverting valve (viewed from the front).
Draining: A drain valve must be fitted to the EcoZenith’s left connection
(where the charge pump is mounted). It functions as drainage for both the
boiler and the radiator system.
Pipe connection for CTC EcoZenith i250 L


1. Incoming (heated water) from heat pump
2. Outgoing (cold water) to heat pump
CTC EcoZenith i250
63
Installation
Pipe connection for CTC EcoZenith i250H
(The picture shows the back of the product)



Pipe connection for CTC EcoAir 400


64
Outgoing (heated) water to boiler.
5.
Incoming (cold) water from boiler.
CTC EcoZenith i250
Incoming (heated
water) from heat
pump Ø22
2.
Outgoing (cold water)
to heat pump,union
3/4
3.
Preassembled
charge pump on
CTC EcoZenith i250L
installed on 250H
(behind the diverting
valves). The pump
pumps water to the
connected heat pump.
Pipe connection for CTC EcoPart 400

4.
1.

Installation
12.4 DHW system
You can connect a DHW circulation system. You can see this kind of
connection in the figure below.
CW
DHW pump (43) BV
BLV
VVB
BLV
CW
DHW
cTc
CTC EcoZenith i250
65
Installation
13. Energyflex
Energyflex is a collective term that describes CTC's unique opportunity for
maximum flexibility and combining difference heat sources in a simple way.
The most common combination is a heat pump and electric boiler.
It is worth noting here that when installed the CTC EcoZenith i250 can serve
as an electric boiler alone, but it can subsequently be augmented with:
CTC EcoPart Heat Pump (ground source))
CTC EcoAir Heat Pump (air to water)
Solar Energy
The CTC EcoHeat/EcoZenith now has integrated functionality for simple
augmentation with
Solar Energy
Pool
Wood-Fired Heating
Regarding wood-fired heating:
The integrated "Differential thermostat function" control initiates the charge
from, e.g., the existing wood-fired system or fireplace when the temperature
is higher than it is in the CTC EcoHeat/EcoZenith i250
Bear in mind that it can also be a good idea to install an automatic charger
that can protect the wood-fired system from condensation, etc
If the wood-fired system needs more water than the 223 l contained in the
product, the system needs to be supplemented with an accumulator tank.
Example of wood-fired system with group
of chargers
!
Energyflex can also be used to draw energy, e.g. to heat
a swimming pool
Connecting external systems can seriously affect the EcoZenith’s operation and
performance and can therefore produce undesirable effects if the system is not
installed correctly.
If you are unsure how to make the connection, contact CTC for suggestions on
how to install the system.
Schematic diagram only The installer adds expansion vessels, safety valves, etc., and sizes the system.
66
CTC EcoZenith i250
Installation
Introduction Energyflex - EcoSol
The CTC EcoHeat and CTC EcoZenith i250 H/L have a water volume of 223 l with layered disc and solar output.
Solar output (3/4) is a part of Energyflex.
223L
223L
Solar output
(3/4)
CTC Ecoheat 400
(223L with solar output and layered disc).
223L
CTC EcoZenith i250 H/L
(223L with solar output and layered disc).
H
Solar output (3/4)
H. Symbol of tank volume in CTC EcoHeat 400 and
CTC EcoZenith i250.
The tank in the CTC EcoHeat 400 and CTC EcoZenith i250 will be called the
H-tank (main tank).
Energy can be collected through the solar outputs (solar panels, wood-fired
boiler) or generated (swimming pool).
Available as accessories are pre-bent pipes with couplings and insulation to
facilitate installation.
Also available as accessories are CTC Solar Control/Expansion Card
Accessory pipe kit Energyflex kit 400
fitted to H-tank
CTC EcoZenith i250
67
Installation
System options, Energyflex
The flexibility in the CTC EcoHeat and CTC EcoZenith i250 is optimised
because the products contain functionality for five basic systems. These are:
Solar "system 1"
Solar "system 2"
Solar "system 3"
Diff thermostat function
Pool
Solar also offers the facility to recharge the drill hole or collect energy for an
extra tank, with or without a solar coil.
*The differential thermostat function can be connected to an existing PCB in
the CTC EcoHeat 400/CTC EcoZenith i250, while Solar systems 1, 2, 3 and
Pool require the product to be supplemented with the CTC Solar Control/
Expansion Card accessory.
Explanations of system options
Solar system 1
Charge from solar panels only to the H-tank (H) in the CTC EcoHeat 400 or
CTC EcoZenith i250
Solar system 2
Charge from solar panels only to the EcoTank buffer tank +
CTC EcoHeat 400/CTC EcoZenith i250.
Solar system 3
Charge from solar panels either to X-Volume or CTC EcoHeat 400/
EcoZenith i250.
Using a diverting valve, the charge is prioritised
either to the H-tank in the EcoHeat/EcoZenith i250
or to the external X-volume
G99
G98
B5
Diff thermostat function
The differential thermostat function is used if you
want to charge your EcoHeat/EcoZenith from an
existing wood-fired boiler, a water-jacketed stove or
another cheap heat source.
The function compares the temperature in the
EcoHeat/EcoZenith and the external heat source.
Charging starts when it is warmer in the external
heat source.
NB: For certain heat sources, e.g. solid fuel boilers,
automatic chargers are recommended, among other
things to counteract condensation in the fire box.
B46
H-tank
05
B6
G46
Y11
Schematic diagram for differential thermostat function
Schematic diagram only The installer adds expansion vessels, safety valves, etc., and sizes the system.
68
CTC EcoZenith i250
Installation
14. Electrical installation
Installation and connection in the CTC EcoZenith i250 must be undertaken
by an authorised electrician. All wiring must be installed according to
applicable regulations. The boiler is internally connected by the factory and
set for a 5.5 + 6.0 kW power output. Depending on the country in which
CTC EcoZenith i250 is to be installed, it is available with a 400 V or 230 V
electrical connection.
Electrical connections are made behind the product's front panel. Undo
the screws on the top (2 screws), bend out and put the front to one side
(disconnect any network cables on the front printed circuit card for easier
access). The terminal blocks are located behind the electrical
connection box cover. Connection cables are inserted in the cable ducts
on the unit’s top cover, which exit at the same height as the bottom of the
electrical connections box. Sensor cables are inserted separately as far as
possible through the cable ducts to the right of the product’s top cover.
Safety switch
The installation should be preceded by an omnipolar safety switch according
to overvoltage category III, which ensures disconnection from all electric
power sources.
Circulation pump connection for radiator system
The radiator pump is connected electrically to the terminal board. Electrical
data: 230V 1N~. Internal fuse 10 A.
Symbol for max.
thermostat:
Max. thermostat
If the heat pump has been stored in an extremely cold place, the max.
thermostat may have been triggered. You reset it by pressing in the button
on the electrical switchboard behind the front panel.
Always check on installation that the max. thermostat has not tripped.
14.1 Electrical installation 400 V 3N~
The CTC EcoZenith i250 must be connected to 400 V 3N~ 50 Hz and
protective earth.
Terminal block no.: L1, L2, L3, N, PE.
The minimum group fuse size is specified in “Technical data”.
14.2 Electrical installation 230V 1N~
The CTC EcoZenith i250 must be connected to 230V 1N~ 50 Hz and
protective earth. Terminal block no.: L1, N, PE
The minimum group fuse size is specified in “Technical data”.
CTC EcoZenith i250
69
Installation
14.3 Positioning of electrical components
Automatic circuit breakers.
Backup heating thermostat.
Max. thermostat.
Upper immersion heater.
Connection to display.
Terminal block: G41-G48.
Charge pump PWM:
G45-G46
Terminal block: G31-G40.
Return sensor: G31-G32
Extra VV/Night reduction: G33-G34
Current sensor: G37-G40
Communication HP.
Terminal block: G51-G53
Brown cable: G51
White cable: G52
Green cable: G53
Terminal block: G11-G22.
Outdoor sensor: G11-G12
Primary flow sensor 1: G13-G14
Primary flow sensor 2: G15-G16
Room sensor 1: G17-G19
Room sensor 2: G20-G22
Terminal block: A11-A20.
Charge pump 1: A12
Mixing valve 2: A15-A17
Diverting valves VV: A18-A20
Terminal block: A21-A30.
Mixing valve 1: A27-A29
Terminal block: G61–G76.
Contactors.
Electrical installation
CTC EcoZenith i250
L1 - 3x400 V/(1x230 V)
L2 - 3x400 V
L3 - 3x400 V
N
PE
Lower immersion heater.
Strain reliever.
Heat pump power supply.
The black connector
that only supplies any
connected heat pumps with
power is connected here.
70
CTC EcoZenith i250
Installation
14.4 Electrical connection to heat pump
General
The CTC EcoAir 406-410 or CTC EcoPart 406-412 heat pumps receive their
power supply from the EcoZenith i250 via a separate connector.
Charge pump
The factory-installed charge pump for heat pumps is connected internally in the
CTC EcoZenith i250 L.
The charge pump is connected to CTC EcoZenith i250 H in the preassembled connector (Molex and PWM) located under the electrical cabinet.
Charge pump Molex switch
When working on the heat pump
Before starting any work on the heat pump the safety switch installed in front of
the CTC EcoZenith i250 should be activated.
Charge pump PWM switch
14.4.1 Communication
The CTC EcoAir 406-410, 520M or CTC EcoPart 406-412 heat pumps are
controlled from the EcoZenith i250. Other makes of heat pump cannot be
controlled from the EcoZenith. Communication between the products takes
place via an LiYCY (TP) communication cable, which is a 4-conductor shielded
cable, where the communication-bearing conductors are of twisted pair type.
The connection is made in the communication port on the PCB and in the heat
pump in accordance with its instruction manual.
G51 = Brown cable, G52 = white cable, G53 = green cable.
The detailed illustration from
the wiring diagram shows the
communication connection.
CTC EcoAir
Grey communication connector.
CTC EcoPart
Communication terminal
block.
Connection
communication.
G51, G52, G53
EcoZenith connection box
CTC EcoZenith i250
71
Installation
14.4.2Heat pump power supply 400 V 3N~
The heat pump must be supplied with power from CTC EcoZenith i250 using
the provided black connector located in the bottom of the electrical cabinet.
(NB: no supply to CTC EcoZenith i250)
The minimum group fuse size is specified in “Technical data”.
Recommended cable 400 V 3N~ Ölflex 110 5G 2.5 black.
The cable is connected between the products in accordance with the heat
pump’s instruction manual.
14.4.3Heat pump power supply 230V 1N~
The heat pump must be supplied with power from CTC EcoZenith i250 using
the provided black connector located in the bottom of the electrical cabinet.
Black connector
(NB: no supply to CTC EcoZenith i250)
The minimum group fuse size is specified in “Technical data”.
Recommended cable 230 V 1N~ Ölflex 110 3G 4 black.
The cable is connected between the products in accordance with the heat
pump’s instruction manual.
14.4.4Connecting the heat pump connector
• We recommend pulling the cable through the cable clip before you connect
the wires. The cable clip can also be fitted afterwards.
(See figure 1)
a. Outer sleeve scaled to 55 mm
b. Wires scaled to 9 mm
c. Advanced protective earth wires scaled to 7 mm
EcoZenith connection box
• Open the terminal block by pushing a screwdriver (blade width 2.5mm) into
the block. Connect the stripped wires in the specified positions. Check that
only the stripped parts are clamped to the terminals, NO INSULATION!
(see figures 2 and 3)
• Fix the cable clip to the connector. The word TOP should be visible on the
terminal and the cable clip
(see figure 4)
Push the cable clip onto the connector. Then tighten the screw to obtain the
desired tension.
see figure 5)
Connector for supplying power to heat pumps!
Figure 1
72
CTC EcoZenith i250
Figure 2
Figure 3
Figure 4
Figure 5
Installation
14.5 Extra low voltage protection
The following outputs and inputs have extra low voltage protection: current
sensor, outdoor sensor, room sensor, primary flow sensor, return sensor,
NR/SO, temperature sensor, level switch and PWM signals.
Connection of outdoor sensor (B15)
The sensor should be set up on the house’s northwest or north side, so that
it is not exposed to morning and evening sun. If there is a risk of the sensor
being affected by the sun’s rays, it must be protected by a screen.
Place the sensor at around 2/3 of the height of the facade near a corner, but
not under a roof projection or other form of wind protection. Do not place it
either above ventilation ducts, doors or windows where the sensor may be
affected by factors other than the actual outdoor temperature.
Connection of room sensor (B11) (B12)
The room sensor is fitted at a central point in the house, in the most open
position possible, ideally in a hall between several rooms. This is the best
position for the sensor to record an average temperature for the house.
Feed a three-conductor cable (minimum 0.5 mm2) between the heat pump
and room sensor. Then attach the room sensor securely in a position at
roughly two thirds of the way up the wall. Connect the cable to the room
sensor and EcoZenith.
!
Do not attach the
sensor cable permanently until you have
tested where the
best location is.
Connection of primary flow sensor (B1, B2) /return sensor
(B7)
Fit the primary flow sensor to the primary flow pipe, ideally after the
circulation pump. Fit the return sensor to the return pipe.
The sensing part is towards the end of the sensor (see sketch).
Contact paste
Sensory element
Primary flow pipe
Tie strap
Sensors
Sensor cable
Insulation
• Attach the sensor using the tie strap provided.
• Ensure that the sensor makes good contact with the pipe.
Apply contact paste to the front part of the sensor between the sensor
and the pipe if good contact is otherwise difficult to obtain.
• Important! Insulate the sensor using pipe insulation.
• Connect the cables to the EcoZenith’s terminal board.
CTC EcoZenith i250
73
Installation
14.5.1 Remote-controlled temperature reduction
The night temperature reduction function can be activated via a closed
function on the electricity remote control input, pins G33 and G34 on the
terminal board. The function can be controlled remotely using “Minicall”, for
instance.
While the input is short circuited, the temperature reduction is activated,
regardless of other settings. When the short circuit ceases, the product
returns to ordinary settings.
The size of the reduction is set in the menu: Installer/Settings/Radiator
system/Prim reduced.
NOTE: the input function can be selected according to the following:
• NR = Night reduction of temperature (time-controlled lowering of
temperature)
• SO = Shut off (compressor and power output blocked by the electricity
supplier)
• DHW = Extra hot water button (accessory)
14.5.2Current sensor connection
The three current sensors, one for each phase, are fitted on the fuse panel in
the following manner.
Each phase from the electricity distribution board supplying the EcoHeat
is channelled through a current sensor before termination at the relevant
terminal. This allows the phase current to be sensed all the time and
compared with the value set for the heat pump's load switch. If the current
is higher, the control unit drops to a lower heat output on the immersion
heater. If this is insufficient, the heat pump is also limited. When the power
drops back to the set value, the heat pump and immersion heater are
reconnected.
This means that the current sensors, along with the electronics, prevent
more power being supplied than the main fuses can tolerate.
The current sensors’ holes for cables are 11 mm in diameter.
Use at least 0.5 mm2 cable.
L1
From electricity meter
1
2
3
4
L2
L3
Current sensor
74
CTC EcoZenith i250
Fuse panel
Connection block
1
2
3
4
To boiler
Low current
1
2
3
4
1
2
3
4
Installation
14.5.3Terminal boards
There are terminal boards for sensors, radiator pumps,
etc. behind the panel.
L1
L2
L3
N
PE
Utegivare / Outdoor sensor
Framledningsgivare 2 / Primary flow sensor 2
RG-1
RG-2
RG-4
RG-1
RG-2
RG-4
Rumsgivare 1 / Indoor sensor 1
Rumsgivare 2 / Indoor sensor 2
Returgivare / Return flow sensor
Fjärr- / Rundstyrning
Night temp / Ext control
Gemensam/Common
L1
L2
L3
Svart öppna / Black open
Brun stäng / Brown close
Blå / Blue
L1
N
PE
L1
N
PE
Klenspänning / Low voltage
Framledningsgivare 1 / Primary flow sensor 1
Strömkännare / Current sensor
Shunt 2 / Mixing Valve 2
Radiator pump 1
230V 1N~
G 11
G 12
G 13
G 14
G 15
G 16
G 17
G 18
G 19
G 20
G 21
G 22
G 31
G 32
G 33
G 34
G 37
G 38
G 39
G 40
A 15
A 16
A 17
A 31
A 33
PE
A 36
A 34
PE
Radiator pump 2
Matning / Power supply
Dataskyltens mått (BxH): 146x168mm
Material: Självhäftande vinyl eller motsv.
Tryck: Svart tryck på vit botten
585248401 Skylt inkoppling EH 3.1
400V 3N~
!
Open the spring block first using
a screwdriver before the cable is
inserted. Otherwise, there is a risk of
poor contact. Also make sure that
the conductor is sufficiently stripped.
CTC EcoZenith i250
75
Installation
14.6 Settings made by the installation electrician.
The following settings shall be made by the installation electrician after
installation:
• Select main fuse size
• Select the power limitation for the immersion heater.
• Check room sensor connection
• Check that the sensors connected indicate reasonable values.
Carry out the following checks:
Main fuse and effect limitation settings
See the chapter on First start.
Check room sensor connection
• Go to the menu: Installer/Service/Function test/Radiator system.
• Go down and select the option LED room sensor and press OK.
• Select On using the + button and press OK.
Check that the room sensor LED lights up. If not, check the cables and
connection.
• Select Off using the - button and press OK. If the OK LED goes off, the
check is complete.
• Return to start menu by pressing the Home button.
Check connected sensors
If any sensor is incorrectly connected, a message will appear on the display,
e.g. “Alarm sensor out”. If several sensors are incorrectly connected, the
different alarms are displayed on different rows.
If no alarm is displayed, the sensors are connected correctly.
The current sensor connection has no alarm, but the current value can be
read in the Operation data menu. Note that the tolerance/accuracy is very
low with small current values.
14.7 Installing a backup power supply
The DIP switch on the PCB is used to set the backup power supply. The DIP
switch is marked "RESERV" (BACKUP).
When the switch is set to ON, the step is actively operating in backup
heating mode.
3x400 V
Switch
5
4
3
2
1
Phase
L3
L2
L2
L1
L1
Current
10 A
10 A
2.6 A
10 A
1.3 A
Power
1.2 kW
2.3 kW
0.6 kW
2.3 kW
0.3 kW
1x230 V
76
Switch
-
4
3
2
1
Phase
-
L2
L2
L1
L1
Current
-
8.7 A
8.7 A
8.7 A
13 A
Power
-
2.0 kW
2.0 kW
2.0 kW
3.0 kW
CTC EcoZenith i250
Installation
14.8 Switching to 18 kW electric heater
power.
CTC EcoZenith i250 3x400 V can be reconnected to a 18 kW immersion
heater.
NB: Installation must be carried out by a qualified electrician.
Connecting
!
Warning Begin
by disconnecting
the power to the
product. Installation
must be carried
out by a qualified
electrician.
1. Begin by disconnecting the power to the product.
2. Free the three black wires with insulation sleeves from the cabling.
3. Undo the smallest switch (K2 on the electrical diagram) by pulling the yellow fastening backwards.
CTC EcoZenith i250
77
Installation
4. The black wires should have a designation stating the cable number and
connection position. For example, 46 K2:1, where the 1 stands for screw
joint position 1.
Begin by loosening the screw joint at position 1 and freeing the brown
wire. Mount the brown and respective black wires in the same screw
joint.
Repeat for screw joints on positions 3 and 5.
Tighten screw joints 1 to 5, inclusive.
Remount the switch on the DIN rail and lock using the yellow catch.
Then check that the switch is firmly in position on the DIN rail.
5. Mount the black wires in the free spaces on the electric heater.
NB: Only for angled flat pins with black end cable sleeves.
78
CTC EcoZenith i250
Installation
14.9 Connection of pump (G46) to
Diff. therm. func.
230 V 1N~
The Circulation pump (G46) is connected at the following terminal blocks:
Relay card in the EcoZenith i250 (see wiring diagram).
Note the cable colours!
Phase:
brown
Zero:
blue
Earth:
yellow/green
Terminal block
A:11(EcoZenith i250)
Check the function by test running the pump in menu “Installer/Service/
Function test” in the control system.
14.10Connection of sensor (B46) to
Diff. therm. func.
Ntc22k
Sensor B46 is connected to terminal block G65,G66
CTC EcoZenith i250
79
Installation
14.11Wiring diagram 3x400 V
80
CTC EcoZenith i250
Installation
CTC EcoZenith i250
81
Installation
14.12Wiring diagram 1x230 V
82
CTC EcoZenith i250
Installation
CTC EcoZenith i250
83
Installation
14.13Component list, wiring diagram
No.
Component.
A1
Display
A2
Relay/main card
B1
Primary flow sensor 1
B2
Primary flow sensor 2
B5
Upper tank sensor
B6
Lower tank sensor
B7
Return sensor
B11
Room sensor 1
B12
Room sensor 2
B15
Outdoor sensor NTC 150
B 46
Sensor external tank – Differential thermostat function.
COM HP Communication heat pump
84
G51 = Brown cable, G52 = white cable, G53 = green cable.
E13
Backup heating thermostat E13
F1
Automatic circuit breaker 10 A
F2
Automatic circuit breaker HP 10 A
F10
Max. thermostat
G1
Radiator pump 1
G2
Radiator pump 2
G11
Charge pump 1
G46
Charge pump external tank – Differential thermostat function
H
H-tank
K1
Contactor 1
K2
Contactor 2
K19
Pressure/level switch
K20
Night red/circulation/extra DHW
X1
Terminal block, incoming supply
X10
Terminal block, HP supply
Y1
Mixing valve 1
Y2
Mixing valve 2
Y11
Non return valve
Y21
Diverting valve DHW
Y22
Diverting valve DHW
Y98
Expansion tank
Y99
Expansion tank
CTC EcoZenith i250
Main tank (EcoHeat/EcoZenith i250)
Black connector
ning av
Installation
Givare 22kΩ, framledning/ retur 2,5m
CTC EcoAir 105-125, EcoEl, Excellent II
CTC EcoHeat, EcoLogic, EcoZenith
CTC EcoFlex, EasyFlex, V40 Lambda
14.14
Resistances
583742308
6210120 394:- for sensors
OBS! EcoAir har utegivare NTC
22k!
NTC 22 kΩ
Hot gassensor
sensorNTC 150
Outdoor
sensor
nce Ω
Temperature °C
NTC 22 kΩ
Resistance Ω
4
130
800
4
125
906
5
120
1027
8
115
1167
3
110
1330
2
105
1522
8
100
1746
3
95
2010
7
90
2320
9
85
2690
2
80
3130
9
75
3650
3
70
4280
1
65
5045
0
60
5960
2
55
7080
32
50
8450
52
45
10130
85
40
12200
77
35
14770
00
30
18000
59
25
22000
19
20
27100
41
15
40
Givare, ret
(Kollektorg
Temperature°C
°C
Temperature
Hot gassensor
sensor
Outdoor
ResistanceΩΩ
Resistance
130
70
125
65
1449
32
1650
37
120
60
115
55
1882
43
2156
51
110
50
105
45
2477
60
2849
72
100
40
3595
3297
85
3831
102
2080
1575
6115
182
7212
224
3090
2585
Temp
Tempe
-
4465
123
5209
150
33540
70
10
65
5
60
0
55
-5
50
-10
45
-15
40
-20
35
-25
30
-30
25
-35
20
-40
15
8560
276
10142
342
12125
428
14564
538
17585
681
21338
868
25986
1115
32079
1443
39611
1883
48527
2478
60852
3289
76496
10
41800
10
98322
98
5
52400
5
125779
64
0
66200
17
-5
84750
65
-10
108000
-15
139000
-20
181000
-25
238000
Suctio
PT1000
CTC EcoZenith i250
1
1
1
85
Installation CTC EcoAir 520M
15. Connection of CTC EcoAir 520M
heat pump
The CTC EcoAir 520M is a modulating heat pump that is fully designed to
work with the CTC EcoZenith i250L.
The following applies when installing the CTC EcoAir 520M with the
CTC EcoZenith i250 H/L:
• Powered separately. The products are switched on separately. Control
cabling only between the products.
• CTC circulation pump item no. 586988301 (7.5m HP) can be added to
handle flow requirements with normal installation.
• The heat pump strives to deliver the correct temperature to the
primary flow water. The setpoint for the upper tank or lower tank. If
there is insufficient power the compressor speed increases. When the
temperature approaches the setpoint the compressor speed reduces.
The CTC EcoAir 520M is set at the factory to automatically
vary (modulate) the compressor speed between 20 and 90
rps in cold weather and to vary it between 20 and 50 rps in
warm weather as shown in the adjoining diagram.
s
rp
100
90
80
70
60
50
40
30
20
10
0
-25-20-15-10 -5 0 5 10 15 20 25 30 Outdoor ºC
The CTC EcoZenith i250 is supplied with suitable factory settings for the CTC EcoAir 520M.
Enertech AB recommend these for optimal operating economy.
86
CTC EcoZenith i250
Installation CTC EcoAir 520M
Inverter_Inverter_In
15.1 Menu functions unique to the CTC EcoAir 520M
The following menu functions are unique to heat pumps
that use inverter technology. (CTC EcoAir 520M)
15.1.1 Operation data heat pump
Compressor
On/Off/65 rps
This shows whether or not the heat pump is operating
as well as showing the compressor speed (rps).
Heat pump
Compressor
Charge pump
Fan
HP in/out °C
On 65 rps
On 47%
On
35.5 / 42.3
Current L1
4.0
The compressor speed is automatically tailored to the
energy requirement, up to the maximum permitted
speed as determined by the outdoor temperature.
Charge pump
On/Off/47%
Settings Heat pump
Display of the charge pump's operational status and
Compressor:
Permitted
speed as a percentage.
Fan (On....Off)
Shows whether the fan is operating or not.
HP in/out °C
Shows the heat pump’s return and primary flow
temperatures.
Min outtemp °C
Tariff VP
Cold temp limit
Max RPS
Warm temp limit
Max RPS warm temp
>>
Förs
-15
Off
0
90
20
50
Current L1
Shows the current across the compressor (phase L1).
Förs
Settings Heat pump
<<
Max RPS silent mode
Silent mode
HS<>DHW time (sek)
Charge pump
Auto adj. charge pump
50
120
50
Förs
Set. Silent mode
Silent mode
Off
Monday
00-06
22-24
Tuesday
00-06
22-24
Wednesday
00-06
22-24
Thursday
00-06
22-24
Friday
00-06
23-24
Saturday
00-08
23-24
Sunday
00-08
The CTC EcoZenith i250 is supplied with suitable factory settings for the CTC22-24
EcoAir 520M.
Enertech AB recommend these for optimal operating economy.
Inst. Ljudreducering
Silent mode
Monday
On
00-06
Active
22-24
CTC EcoZenith i250
87
Installation CTC EcoAir 520M
15.1.2 Heat pump Settings
CompressorPermitted/Blocked
The product is supplied with a blocked compressor.
When the compressor is blocked, the product operates
like an electric boiler. All other functions are intact.
Compressor
Charge pump
Fan
HP in/out °C
On 65 rps
On 47%
On
35.5 / 42.3
Current L1
4.0
Settings Heat pump
Compressor:
Min outtemp °C
Tariff VP
Cold temp limit
Max RPS
Warm temp limit
Max RPS warm temp
>>
Försla
Permitted
-15
Off
0
90
20
50
Permitted means that the compressor is allowed to
operate.
Min. outdoor temp. °C
-15 (-22...0)
This menu relates to settings for the outdoor temperature
at which the compressor is no longer permitted to
operate. When the heat pump has stopped a start signal
will only be given if the outdoor temperature is at least
2 °C warmer than the set value. The lowest outdoor
temperature required for start is -18 °C.
Försla
Settings Heat pump
<<
Max RPS silent mode
Silent mode
HS<>DHW time (sek)
Charge pump
Auto adj. charge pump
50
120
50
Tariff HP
Must be set to “Off”.
Compressor speed
Limit cold temp. (T2ºC)
0
Temperature limit for winter power. When the outdoor
temperature is this or lower, the compressor speed is
adjusted up to speed R2.
Limit warm temp. (T1ºC)
20
Temperature limit for summer power. When the outdoor
temperature is this or higher, the compressor speed is
adjusted up to speed R1. The heat pump starts and
stops at the actual value and setpoint value.
Max. rps warm temp. (R1 rps)
50
Maximum compressor power in warm weather. Sets
the maximum speed of the compressor at outdoor
temperature T1
Max. rps (R2 rps)
90
Compressor power in cold weather. Sets the maximum
speed of the compressor at outdoor temperature T2
s
Rp
Set. Silent mode
100Silent mode
Off
90 Monday
00-06
22-24
R2
80 Tuesday
00-06
22-24
70 Wednesday
00-06
22-24
60 Thursday
00-06
22-24
50 Friday
00-06
23-24
R1
40 Saturday
00-08
23-24
00-08
22-24
30 Sunday
20
10
T2
T1
0
-25-20-15-10 -5 0 5 10 15 20 25 30
Inst. Ljudreducering
Silent mode
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
On
00-06
00-06
00-06
00-06
00-06
00-08
00-08
Active
22-24
22-24
22-24
22-24
23-24
23-24
22-24
The CTC EcoZenith i250 is supplied with suitable factory settings for the CTC EcoAir 520M.
Enertech AB recommend these for optimal operating economy.
88
CTC EcoZenith i250
Försla
Outdoor ºC
Cold temp limit
Max RPS
Warm temp limit
Max RPS warm temp
Installation
>>
15.1.3 Heat pump Settings continued
Max. rps on noise reduction
50
Max. rps on noise limitation. The compressor’s
maximum speed when noise limitation is active.
NB: You should note that the maximum output of
the heat pump will fall and the need to add heat may
increase.
Noise reduction 0
90
20
50
CTC EcoAir 520M
Försla
Settings Heat pump
<<
Max RPS silent mode
Silent mode
HS<>DHW time (sek)
Charge pump
Auto adj. charge pump
50
120
50
Yes/No
It is possible to start a schedule with limited compressor
speed to reduce the sound image.
Heating<>DHW Switching time (sec.)
120
Time in seconds during which the compressor maintains
a constant speed while switching from the upper to the
lower tank (or from the lower to the upper tank)
Charge pump
50 (In progress, 25,100)
Charge pump speed in %. Automatic mode strives for
∆t 7ºC. If a value of 100 is reached and displayed in red
there is insufficient flow in the heat pump.
If a value of 25 is reached and displayed in red then ∆t
<7ºC.
The speed is set using “Auto setting charge pump”.
When the test is running, “In Progress” is displayed.
If a value is selected it becomes a fixed value and is
displayed in red.
The value is also displayed in red on installation as “Auto
setting charge pump” has not been run.
Försla
Set. Silent mode
Silent mode
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Off
00-06
00-06
00-06
00-06
00-06
00-08
00-08
22-24
22-24
22-24
22-24
23-24
23-24
22-24
Inst. Ljudreducering
Silent mode
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
On
00-06
00-06
00-06
00-06
00-06
00-08
00-08
Active
22-24
22-24
22-24
22-24
23-24
23-24
22-24
Auto setting charge pump
This function starts the calculation of the optimal charge
pump speed. The function is activated by marking
the “Auto setting charge pump” line and pressing
“OK”. While calculation is in progress, “In progress”
is displayed below the “Charge pump” line. Once
calculation is compete the new value is placed in the
“Charge pump” line, e.g. 72%
The calculation takes approx. 5 minutes. Do not touch
the screen while “In progress” is displayed.
Different operating modes and seasons may produce
differing results. Any calculation should therefore be
repeated after 4 weeks.
The CTC EcoZenith i250 is supplied with suitable factory settings for the CTC EcoAir 520M.
Enertech AB recommend these for optimal operating economy.
CTC EcoZenith i250
89
Installation CTC EcoAir 520M
15.1.4 Set Schedule Noise reduction
Noise reduction
On/Off
Shows whether noise reduction is active (ON) or not (OFF)
Max RPS silent mode
Silent mode
<<
HS<>DHW time (sek)
Max
RPS
silent mode
Charge
pump
Silent
mode
Auto adj.
charge pump
HS<>DHW time (sek)
Charge pump
Auto adj. charge pump
50
120
50
120
50
Försla
Set. Silent mode
Silent mode
Off
Monday
00-06
Set. Silent mode
Tuesday
00-06
Silent mode
Off
Wednesday
00-06
Monday
00-06
Thursday
00-06
Tuesday
00-06
Friday
00-06
Wednesday
00-06
Saturday
00-08
Thursday
00-06
Sunday
00-08
Friday
00-06
Saturday
00-08
Sunday
00-08
22-24
22-24
22-24
22-24
22-24
22-24
23-24
22-24
23-24
22-24
22-24
23-24
23-24
22-24
Factory setting for noise reduction.
Noise reduction has NOT been activated (OFF)
Inst. Ljudreducering
The example shows that noise reduction is on:
From Monday 22:00 until Tuesday 06:00
“Active” means that the noise is currently being
limited; if factory settings are used this means that the
compressor speed may not exceed 50 rps.
Silent mode
On
Inst. Ljudreducering
Monday
00-06
Tuesday
00-06
Silent mode
On
Wednesday
00-06
Monday
00-06
Thursday
00-06
Tuesday
00-06
Friday
00-06
Wednesday
00-06
Saturday
00-08
Thursday
00-06
Sunday
00-08
Friday
00-06
Saturday
00-08
Sunday
00-08
Active
22-24
22-24
Active
22-24
22-24
22-24
22-24
23-24
22-24
23-24
22-24
22-24
23-24
23-24
22-24
e.g. where Noise reduction has been activated
(On) and noise reduction is currently in
progress (On – Active)
The CTC EcoZenith i250 is supplied with suitable factory settings for the CTC EcoAir 520M.
Enertech AB recommend these for optimal operating economy.
90
CTC EcoZenith i250
Försla
Installation
16. First start
When the CTC EcoZenith i250 is delivered, the heat pump is blocked to avoid it
being started unintentionally. EcoZenith I250 can be installed and started before
the bedrock/ground source or air/water heat pump is put into operation.
The EcoZenith i250 can also be started without a room sensor being fitted as
the curve which has been set then regulates the heating. Deselect the room
sensor in the Settings menu. The sensor can however always be fitted for the
alarm LED function.
Before first start
1. Check that the EcoZenith I250 and system are full of water and have been
bled.
(The EcoZenith i250 is bled through the safety valve on the top cover Före
of the
första start
1.
product.)
2.
3.
2. Ensure that, where applicable, the brine system is filled with water and anti4.
5.
6. Kontrollera att reservvärmetermostaten är i frostskyddsläge. Reservvärmetermostaten
freeze and that it is bled, or ensure that the compressor is blocked.
återfinns i kablagets nedre del, bakom fronten. För att ställa reservvärmestermostaten i
frostskyddsläge vrid moturs så långt det går så att mejselspåret står vertikalt (off-läge), vrid
(This applies when docking with the CTC EcoPart 400.)
sedan tillbaka medurs tills mejselspåret står i linje med figuren för frostskydd (ca 1/8 varv).
Frostskyddsinställning, ca + 7 °C.
3. Check that all connections are tight.
4. Check that sensors and the radiator pump are connected to the power
screwdriver slot
source.
5. The backup heating thermostat has OFF as its factory setting. The recommended position is
= Antifreeze setting, around +7°C. The backup heating thermostat is reset on the electrical switchboard behind the front panel.
It is in the OFF position when it is turned anticlockwise as far as it will go (the
screwdriver slot should be vertical).
Symbol for backup heating
NB: At the end of the installation, check the current transformers’
thermostat:
connection. In this situation it is important that you have switched off
any major consumers of electricity in the house. Also make sure that the
backup thermostat is turned off.
CTC EcoZenith i250
91
Installation
First start
Switch on the power using the safety switch. The display comes on.
CTC EcoZenith i250 now asks the following:
1. Select language and press OK
2. Confirm that the system is filled with water and press OK. Press next.
3. Size of main fuse Choose between 10 and 35 A.
4. Enter the supply voltage 3x400 (1x230/3x230 apply only to export
variants)
5. Specify the maximum electric heater power. Choose between 0.0 and
9.0 kW in different steps.
This applies to electric heaters in the upper tank.
6. Select the option permitting the compressor (if the collector system is
ready or the air/water pump is already installed). When the compressor
is started for the first time, it is automatically checked that it is running in
the correct direction. An error message is displayed in the panel display
if it is rotating in the wrong direction. Switch any two phases to change
the direction of rotation.
7. Brine pump On, Auto (Auto/10d/On) (For CTC EcoHeat/EcoPart only)
Auto means that the brine pump is automatically operating at the same
time as the heat pump (factory setting).
10d means that the brine pump is running continuously during the first
10 days in order to assist with bleeding.
“On” means that the brine pump is running constantly.
8. Specify max. primary flow 1 °C for radiator system 1.
9. Specify inclination 1 for radiator system 1.
10. Specify the adjustment for radiator system 2.
11. Current sensors identified. The CTC EcoZenith i250 then starts and the
start menu appears.
12. Enter the set values in the parameter list so that the customer knows
what has been set in addition to factory settings during installation.
92
CTC EcoZenith i250
!
Save these
settings under:
Installer/Settings/
Save settings
Försäkran om överensstämmelse
Déclaration de conformité
Declaration of conformity
Declaration of
Conformity
Konformitätserklärung
Enertech AB
Box 313
S-341 26 LJUNGBY
försäkrar under eget ansvar att produkten
confirme sous sa responsabilité exclusive que le produit,
declare under our sole responsibility that the product,
erklären in alleiniger Verantwortung, dass das Produkt,
EZ250 C1 3x400V E18/
EZ250 C1 1x230V E12/ EZ250 C1 3x230V E14
som omfattas av denna försäkran är i överensstämmelse med följande direktiv,
auquel cette déclaration se rapporte est en conformité avec les exigences des normes suivantes,
to which this declaration relates is in conformity with requirements of the following directive,
auf das sich diese Erklärung bezieht, konform ist mit den Anforderungen der Richtlinie,
EC directive on:
Pressure Equipment Directive 97/23/EC, § 3.3
(AFS 1999:4, § 8)
Electromagnetic Compatibility (EMC) EN 2004/108/EC
Low Voltage Directive (LVD) EN 2006/95/EC
Överensstämmelsen är kontrollerad i enlighet med följande EN-standarder,
La conformité a été contrôlée conformément aux normes EN,
The conformity was checked in accordance with the following EN-standards,
Die Konformität wurde überprüft nach den EN-normen,
EN 55014-1 /-2
EN 61 000-3-2/3-3/4-2,-3,-4,-5,-6,-11
EN 60335-1, 2-21
EN 62233
Ljungby 2013-06-26
Marcus Miller
Technical Manager
161 421 50 10-01
Enertech AB. P.O Box 309 SE-341 26 Ljungby Sweden.
www.ctc.se, www.ctc-heating.com