1.4 Energy Saving
The inverter system’s capacity modulation range is from 30% to 100%, while MDS system’s capacity
modulation range is from 10% to 100%.
Quick response to the capacity modulation.
Min. power consumption is only 10% of the full load power consumption.
Compared to the inverter system, there is no power consumption of transducer.
Compared to the nominal capacity scroll system, it can save 20% energy consumption.
10HP system
EER
100%
Digital
compressor
operating
Fixed
compressor
100% operating
10%
Traditional air
Traditional inverter
conditioning system
system
MDS system
Heavy loading
Load
Light loading
1.5 Flexible Combination of Indoor Units
The max. capacity of the indoor units is as 130% as the outdoor units capacity.
The outdoor units can connect different numbers of indoor units according to the outdoor units capacity.
One outdoor unit can be connected up to 48 indoor units.
Various types of indoor units are available.
There are various indoor units for option: concealed exposed, ceiling concealed, high static pressure fan coil
and ceiling exposed/floor standing.
1.6 Long Accessory Pipe Connection Design
Max. accessory pipe length is 15m (12HP-30HP), max. height is 50m (8HP—30HP).
Height
Max. accessory pipe total
length (m)
Max. accessory pipe
length (m)
OT
IT
12-30HP
350
150
50
40
10HP
250
125
50
40
8HP
250
125
50
40
6HP
150
70
30
30
5HP
150
70
30
30
4HP
150
70
20
20
3HP
100
50
20
20
Note:
OT means the outdoor unit is above the indoor unit,
IT means the outdoor unit is below the indoor unit.
page 3