Download Schneider Electric Advantys STB Specifications
Transcript
Analog Input Modules STB ACI 1230 Physical Description Physical Characteristics The STB ACI 1230 is a standard Advantys STB analog current input module with two single-ended analog channels that read inputs from analog sensors operating in the range 0 to 20 mA. The analog portion of the module is isolated from the island’s sensor bus to improve performance. To take advantage of this internal isolation feature, the sensors must be powered from an external power supply. If isolation is not required, you can use the module to deliver field power to the sensors—24 VDC for sensor 1 from the top connector, and 24 VDC for sensor 2 from the bottom connector. The module mounts in a size 1 I/O base and uses two six-terminal field wiring connectors. Front Panel View 2 3 1 4 5 6 1 2 3 4 5 6 112 locations for the STB XMP 6700 user-customizable labels model name LED array light green identification stripe, indicating an analog input module sensor 1 connects to the top field wiring connector sensor 2 connects to the bottom field wiring connector 31007715 6/2008 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com