Download Raypak Temp-Tracker Operating instructions
Transcript
ADJUST MENU MODE 5 (Page 3 of 3) Item Field (With Default Settings Shown) Range 0:10 to 5:00 min Description MINIMUM ON TIME Select the minimum amount of time that the stage contact must remain on before it is allowed to turn off. Note: This setting is only available when STAGE MODE is set to P. 0:10 to 5:00 min MINIMUM OFF TIME Select the minimum amount of time that the stage contact must remain off before it is allowed to turn back on. Note: This setting is only available when STAGE MODE is set to P. OFF, 0:20 to 9:55 min, On PUMP DELAY Select the system pump purge time after shutting off the burner. 35 to 100°F (2 to 38°C), OFF WARM WEATHER SHUT DOWN Select the heating system warm weather shut down for outdoor reset operation. Heat demands are ignored once the outdoor air temperature exceeds this setting. °F or °C TEMPERATURE UNITS Select to display temperature in degrees Fahrenheit or in degrees Celsius. Table O: Adjust Menu, Mode 5 (page 3 of 3) 29 Setting