Temperature/Resistance/Voltage
Description
The GL-235 is a differential temperature control for solar heating of pools, spas, and hot tubs. It
provides differential temperature control with an adjustable, calibrated water temperature high limit.
Automatic nocturnal cooling (for pools that overheat in hot climates) and recirculate freeze
protection functions can be enabled/disabled via internal jumpers.
All Goldline controls use 10K thermistor sensors. When disconnected from the control the sensor
will read 10K ohms at 25ºC/77ºF. Refer to the chart below for the resistance at other temperatures.
For a given temperature, the resistance reading should be accurate to ±1%. For a given resistance
reading, the temperature reading should be accurate to ±0.5ºF. Voltage measurements should be
accurate to ± 2%.
Ohm measurements made with sensor disconnected from unit. Voltage
measurements made with sensor connected to unit and power applied. Sensor voltages are DC volts.
Input power can be either 115 or 240 VAC. The output controls a 24VAC automatic valve actuator.
For older systems with 12VAC valves, an internal jumper can be moved to select 12VAC output
operation. The GL-235 also has a high voltage output for controlling a filter pump or booster pump.
Specifications
Power:
Output:
105-130VAC, .5A 50/60Hz.
or
195-250VAC, .3A 50/60Hz
Selectable low voltage 24VAC,
20VA, .85A or 12VAC, 20VA,
1.7A
Desired
Pool
Temp.:
Recirculate
freeze:
SPST-NO isolated contact
115VAC 1HP
240VAC 2HP
Nocturnal
cooling:
Sensors:
2 required (thermistor,
10Kohm @ 25C/77ºF).
Differential:
on at 4ºF, off at 1.5ºF
70-104ºF calibrated scale or Solar Off, 75 (24ºC) -104ºF (40ºC)
on some models
On at <40ºF (4.5ºC), off at >
42ºF (5.5ºC), Enabled via
jumper
On when collector 8ºF less than
pool and pool hotter than limit,
off when collector 3ºF less than
pool or pool cooler than high
limit. Enabled via jumper
Installation
Mounting
The GL-235 is designed for outdoor use. Mount the box vertically with the knockouts facing
downward. For safety, the GL-235 must be a minimum of 5 feet (horizontally) from the pool or
spa.
Power input
Turn off power at circuit breaker before wiring. Remove the internal panel to expose the wiring
connections. Either 115VAC or 240VAC can be used. Refer to the input wiring diagram (Figure 1)
on next page. WARNING: Applying 240VAC to the 120VAC input terminals will cause
permanent damage to the control.
°F
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Ohms
82,719
80,142
77,656
75,255
72,937
70,698
68,535
66,447
64,428
62,479
60,595
58,774
57,014
55,313
53,669
52,078
50,541
49,054
47,616
46,225
44,879
43,577
42,318
41,099
39,919
38,777
37,671
36,601
35,565
34,561
33,590
32,648
31,737
30,853
29,998
29,169
28,365
27,587
26,832
26,100
Volts
4.46
4.45
4.43
4.41
4.40
4.38
4.36
4.35
4.33
4.31
4.29
4.27
4.25
4.23
4.21
4.19
4.17
4.15
4.13
4.11
4.09
4.07
4.04
4.02
4.00
3.97
3.95
3.93
3.90
3.88
3.85
3.83
3.80
3.78
3.75
3.72
3.70
3.67
3.64
3.61
°F
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
Ohms
25,391
24,704
24,037
23,391
22,764
22,156
21,566
20,993
20,438
19,900
19,377
18,870
18,377
17,899
17,435
16,985
16,548
16,123
15,711
15,310
14,921
14,543
14,176
13,820
13,473
13,136
12,809
12,491
12,182
11,882
11,589
11,305
11,029
10,761
10,500
10,246
9,999
9,758
9,525
9,297
Volts
3.59
3.56
3.53
3.50
3.47
3.45
3.42
3.39
3.36
3.33
3.30
3.27
3.24
3.21
3.18
3.15
3.12
3.09
3.06
3.02
2.99
2.96
2.93
2.90
2.87
2.84
2.81
2.78
2.75
2.72
2.68
2.65
2.62
2.59
2.56
2.53
2.50
2.47
2.44
2.41
°F
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
Grounding
Refer to NEC and local codes for specific grounding requirements. In general, a separate ground
conductor must be run to the ground terminal on the pool service panel.
Low Voltage (LV) output: Solar Valve
The GL-235 controls a single valve. In most applications this is the solar valve, which diverts water
through the collector panels or through the normal pool loop depending on conditions.
2
11
Ohms
9,076
8,861
8,651
8,447
8,249
8,056
7,867
7,684
7,506
7,333
7,164
6,999
6,839
6,683
6,530
6,382
6,238
6,097
5,960
5,827
5,697
5,570
5,446
5,326
5,208
5,094
4,982
4,873
4,767
4,664
4,563
4,464
4,368
4,274
4,183
4,094
4,007
3,922
3,839
3,758
Volts
2.38
2.35
2.32
2.29
2.26
2.23
2.20
2.17
2.14
2.12
2.09
2.06
2.03
2.00
1.98
1.95
1.92
1.89
1.87
1.84
1.81
1.79
1.76
1.74
1.71
1.69
1.66
1.64
1.61
1.59
1.57
1.54
1.52
1.50
1.47
1.45
1.43
1.41
1.39
1.37
°F
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
Ohms
3,679
3,602
3,527
3,454
3,382
3,312
3,244
3,177
3,112
3,049
2,987
2,926
2,867
2,809
2,752
2,697
2,643
2,591
2,539
2,489
2,440
2,392
2,345
2,299
2,254
2,210
2,167
2,125
2,084
2,044
2,005
1,966
1,929
1,892
1,856
1,821
1,787
1,753
1,720
1,688
Volts
1.34
1.32
1.30
1.28
1.26
1.24
1.22
1.21
1.19
1.17
1.15
1.13
1.11
1.10
1.08
1.06
1.05
1.03
1.01
1.00
0.98
0.97
0.95
0.93
0.92
0.90
0.89
0.88
0.86
0.85
0.84
0.82
0.81
0.80
0.78
0.77
0.76
0.75
0.73
0.72