Download Raypak MVB TYPE B 504-2004 Operating instructions
Transcript
system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, at maximum speed. Do not operate summer exhaust fan. Close fireplace dampers. 4. Place in operation the appliances being inspected. Follow the manufacturer’s instructions for lighting each appliance. Adjust thermostat so appliance will operate continuously. 5. Check the pressure at a pressure tap located 12 in. above the bottom joint of the first vertical vent pipe. Pressure should be anywhere between -0.01 and -0.08 in. WC. 6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and other gas burning appliances to their previous conditions of use. Model No. Vent Size (in.) Volume of Flue Products (CFM) 504 8 170 754 10 260 1104 10 380 1504 12 510 2004 14 680 NOTE: Data for 100% firing rate. Table M: Volume of Flue Products Data Horizontal Through-the-Wall Direct Venting (Category III) 7. Any improper operation of the common venting system should be corrected so that the installation conforms with the NFGC (U.S.) or B149 (Canada). When re-sizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the NFGC (U.S.) or B149 (Canada). Engineered Vent Systems Table M provides boiler discharge vent volumes of flue products at full fire for the calculation of appropriate vent sizing for common venting. Fig. 22: Horizontal Through-the-Wall Venting WARNING: Vent connectors serving any other appliances shall not be connected into any portion of mechanical draft systems operating under a positive pressure. If an MVB heater is installed to replace an existing heater, the vent system MUST be verified to be of the correct size and Category. If it is NOT, it MUST be replaced. NOTE: For extractor sizing, typical CO2 levels are 8.5% for natural gas and 9.5% for LP gas and flue temperature of 350° F. Fig. 23: Alt. Horizontal Through-the-Wall Venting California Hot Water Supply, Inc. (800) 249-7244 27