Download Siemens MICROMASTER Operating instructions
Transcript
MM420 Parameter List P1233 04/02 Duration of DC braking CStat: CUT P-Group: FUNC Datatype: U16 Active: Immediately Unit: s QuickComm. No Min: Def: Max: 0 0 250 Level: 2 Defines duration for which DC injection braking is to be active following an OFF1 or OFF3, command. Setting this parameter between 1 and 250 sets the time duration (in seconds) of the DC injection starting with the OFF1 or OFF3 command. 1 ON OFF1/OFF3 t P0347 OFF2 t f OFF2 DC braking t DC braking ON OFF 2 t P1233 ON t OFF1/OFF3 P0347 OFF2 t f OFF2 DC braking OFF2 t DC braking ON OFF t P1233 Parameter P1232 still controls the level of DC injection. Value: P1233 = 0 : Not active following OFF1 / OFF3. P1233 = 1 - 250 : Active for the specified duration. Caution: Frequent use of long periods of DC braking can cause the motor to overheat. Notice: The DC braking function causes the motor to stop rapidly by applying a DC braking current (the current applied also holds the shaft stationary). When the DC braking signal is applied, the inverter output pulses are blocked and the DC current not applied until the motor has been sufficiently demagnetized (demagnetization time is calculated automatically from motor data). The inverter will not restart if an ON-command is given during this period. DC braking is not possible when using a synchronous motor (i.e. P0300 = 2). 70 MICROMASTER 420 Parameter List 6SE6400-5BA00-0BP0