Download Carrier 40CS024 Instruction manual
Transcript
40CG Indoor Unit/38CG Outdoor Unit 40CS Indoor Unit/38CS Outdoor Unit Console and Underceiling Duct Free Systems Visit www.carrier.com Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 INTRODUCTION ..........................................................................1 General ......................................................................................1 Electrical Requirements ............................................................1 Indoor and Outdoor Unit Location ..........................................1 Outdoor Unit .............................................................................4 Indoor Unit (General) ...............................................................4 INSTALLATION ...........................................................................4 Installing the Indoor Unit (Console) ........................................4 Refrigerant Line Routing ....................................................4 Installing the Mounting Bracket .........................................5 Drilling a Hole in the Wall for Drainage and Inter-Unit Connections..........................................................................5 Wiring the Indoor Unit........................................................5 Drainage...............................................................................5 Attaching the Remote Controller Rack ..............................5 Ceiling Installation ..............................................................5 Installing the Indoor Unit—Under Ceiling ..............................5 Mounting the Air Conditioner On the Bracket........................5 Continuing the Installation .......................................................7 Installing the Outdoor Unit ......................................................7 Wiring the Outdoor Unit.....................................................7 Connecting the Refrigerant Lines ............................................7 Flaring and Connecting .......................................................7 Air Vacuum and Refrigerant Charge .......................................7 Leak Test...................................................................................8 Electrical Data and Connections ..............................................8 Two-Way Air Conditioner (Optional Accessory) —Console Only ........................................................................8 Air Feedback System Installation (Optional) (Two-Way Air Conditioner)...................................................10 START-UP PROCEDURES........................................................10 Finishing the Job.....................................................................10 Indoor Unit ........................................................................11 Outdoor Unit......................................................................11 Explain the following items to the customer, with the aid of the User Manual: ...............................................................11 CARE AND MAINTENANCE...................................................12 Maintenance (Outdoor Unit) ..................................................12 Cleaning Coils ...................................................................12 Maintenance (Indoor Unit) .....................................................12 Lubrication.........................................................................12 To Remove And Clean Or Replace Air Filters................12 TROUBLESHOOTING ...............................................................17 SAFETY CONSIDERATIONS Installation and servicing of this air conditioning equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service air conditioning equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, on labels attached to or shipped with the unit and other safety precautions that may apply. Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls. Recognize safety information. This is the safety-alert symbol . When you see this symbol in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, or CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in personal injury or product or property damage. INTRODUCTION Step 1—General These instructions are intended as general guidelines. The air conditioner must be installed by trained and authorized personnel. Use the following size copper tubing for connecting the outdoor and indoor units: MODELS 38 & 40CG/CS-018 38 & 40CG/CS-024 38 & 40CG/CS-030 COPPER TUBING SIZE (IN.) 1/4 and 1/2 3/8 and 5/8 3/8 and 5/8 Installation must be performed in accordance with the manufacturer’s specifications, using only approved tubing, electrical cables and accessories. Step 2—Electrical Requirements The air conditioner must be directly connected to an appropriate power source. Use only Type “G” or “C” fuses, per Tables 4 and 5. Use a single-length power cable, without extensions. NOTE: All Wiring and power disconnects must meet local electrical codes. Control wires should be THHN 600v 18ga. Step 3—Indoor and Outdoor Unit Location The indoor and outdoor units should be installed as close to each other as possible. Do not exceed the tubing lengths and height differences which appear in Table 3. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 533-80013 Printed in U.S.A. Form 38C/40C-1SI Pg 1 8-01 Replaces: New Tab misc. misc A01084 Fig. 1—Ceiling Installation A01212 Fig. 2—Console Installation 2 Table 1—Standard Parts (Console) PART NAME QTY Mounting Bracket(s) 1 Long Screws 9 Nut 2 Outdoor Sensor Connecting Cable 1 Absorption Cushions 4 Electric Terminals 16 Remote Controller Rack 1 DIAGRAM WIRELESS REMOTE CONTROLLER S TA R T S TO P 1 2 3 SLEEP D A I LY MODE FAN I I I II I II I II I II II I I Remote Controller and Batteries 1 A Insulation for Fittings Drain Hose Adapter 1 User Manual 1 3 A SWEEP Table 2—Standard Parts (Under Ceiling) PART NAME QUANTITY Upper and Lower Mounting Strips 2 Right and Left Mounting Strips 2 Left Side Strip 1 Right Side Strip 1 Anchor Screw (3/8-in. X 2-in.) 6 Screw (UNC 10 X 2-in.) 8 Nut (UNC 10) 8 Metal Screw (#10–1/2-in.) 2 DIAGRAM IIIIIIIII III III IIIIII Table 3—Maximum Tubing Lengths and Heights INDOOR UNIT OUTDOOR UNIT 40CG/CS-018 40CG/CS-024 40CG/CS-030 38CG/CS-018 38CG/CS-024 38CG/CS-030 LENGTH Mtr 30 40 30 HEIGHT Ft 98 131 98 Mtr 15 20 10 Ft 49 66 33 INSTALLATION Step 4—Outdoor Unit 1. Make sure to leave sufficient space around the unit. See Fig. 3 for minimum required distances between the unit and nearby walls. DO NOT BOX IN UNIT. Step 1—Installing the Indoor Unit (Console) REFRIGERANT LINE ROUTING The refrigerant lines may be routed in either of the two directions shown in Fig. 7. 2. Install the unit in a location with convenient access for service and maintenance purposes. INSTALLING THE MOUNTING BRACKET 3. Position the unit to minimize motor noise which reaches the customer and neighbors. 1. Carefully remove the air intake grille; remove the two screws at its sides and pull the grille out with its center retaining spring, as shown in Fig. 5. 4. In heating mode, water can form in the condenser. A drainage hose may be attached to the unit. Use an adapter as shown in Fig. 4. Step 5—Indoor Unit (General) 2. Remove the seven screws which appear in Fig. 5 and remove the front panel. NOTE: Make sure that the stepper motor and display cables are disconnected from the electronic control. (See Fig. 13.) 1. Make sure to leave sufficient space around the unit. See Fig. 6 and Fig. 16 for minimum required distances between the unit and the ceiling, floor and surrounding walls. 3. Position the mounting bracket on the wall and level. 4. Mark seven (minimum) drilling holes on the wall, as they appear in Fig. 8. 2. Locate the unit to ensure free air flow around it. 3. For greater convenience, place the power disconnect near the unit on the right side. 5. Drill the holes, insert the wall plugs and use the long screws to attach the mounting bracket to the wall. 4. Avoid installing the unit near a source of heat, such as direct sunlight, steam or a flame. 6. Check that the bracket is level and securely fastened to the wall. 5. Install the unit in a location with convenient access to refrigerant line connections for service and maintenance purposes. 7. Hang unit on mounting bracket and mark (2) holes from the bottom of the unit for the hold down screws. 4 4. Fill the remaining wall hole gap with an appropriate sealant material. a WIRING THE INDOOR UNIT 1. Route the inter-unit electric cable and the outdoor sensor cable towards the lower right corner of the indoor unit. 0.15m(6”) min. 2. Use a screw driver to insert the stripped wire ends into the terminal block, as shown in Fig. 13. 3. Make sure that the wires are connected in accordance with the wiring diagram on the drain pan. 0.15m(6”) min. 0.6m(2’) min. c 4. Attach the inter-unit electric cable with the cable clamp located on the unit. 5. Connect the Outdoor Sensor TH3 connector to its mating connector. (See Fig. 13.) 0.6m(2’) min. DRAINAGE 1. Connect the unattached end of the drainage tube to the drainage hose outlet. b 2. Seal the drainage connection to prevent leakage. 3. Make sure there are no kinks, “U” bends or flattened sections in the tube. 4. Check that the drainage functions properly. Fill the pan below the unit’s coil with water and observe that it drains out freely. A01146 UNIT 38CG/CS-018/024 38CG/CS-018/030 A 9.8-in. (320mm) 12.6-in. (320mm) B 25.2-in. (641mm) 25.2-in. (641mm) C 35.4-in. (900mm) 43.3-in. (1,100mm) 5. Connect the ends of the refrigerant lines to their appropriate fittings, following the guidelines in the “Connecting the Refrigerant Lines” section. 6. Make sure the drainage hose is at the bottom side of the wall hole. (See Fig. 9.) Fig. 3—Dimensional Drawing (Outdoor Unit) 7. Connect the display panel connector to the display panel printed circuit board. (See Fig. 13.) 8. Reassemble the front panel, using the seven screws which appear in Fig. 5. ATTACHING THE REMOTE CONTROLLER RACK Use the two screws supplied to attach the remote controller rack to the wall in the location selected by the customer. (See Fig. 12.) CEILING INSTALLATION IMPORTANT: When performing a ceiling installation, make sure that Switch 1 on the Display Board is set to the ON position. (See Fig. 11.) The remaining switches are factory set and should not be changed. Step 2—Installing the Indoor Unit—Under Ceiling 1. The tubing connecting the indoor and outdoor units can be routed in one of two directions, as shown in Fig. 16. A01147 Fig. 4—Drainage Adapter Connection 2. If the tubing is routed horizontally (direction no. 1), the pipe cover at the bottom of the air conditioner must be removed. (See Fig. 19.) 8. Remove unit from bracket and install wall plugs. After attaching tubing and control/power wires. Remember to install (2) hold down screws at bottom of unit. 3. If the tubing is routed vertically (direction no. 2), a condensate pump must be installed for drainage. 4. To assemble the ceiling bracket, use the 4 mounting strips and the 8 UNC–10 screws and nuts, as shown in Fig. 17. DRILLING A HOLE IN THE WALL FOR DRAINAGE AND INTER-UNIT CONNECTIONS 5. Fasten the ceiling bracket to the ceiling using the 6 anchor screws, as shown in Fig. 18. 1. To make the connections between the indoor and outdoor units, a 3-in. hole should be drilled for the refrigerant lines, drainage hose and electric cables as shown in Fig. 9. 6. The location of the ceiling bracket should allow a minimum gap between the indoor unit and nearby walls, as shown in Fig. 16. 2. Make sure to drill outwards and downwards, so that the opening in the outside wall is at least 1/2-in. lower than the opening on the inside. NOTE: The anchor screws provided are intended for use with concrete ceilings. 3. Make sure the drainage hose is at the bottom side of the hole. (See Fig. 9.) NOTE: Use fasteners which are appropriate for the type of ceiling present at the installation site. 5 A01096 Fig. 5—Removing Air Intake Grille and Front Panel c a 0.2m 0.2m (8”)min. b 10mm(0.5”) min. (8”)min. 0.1m (4”)min. REFRIGERANT LINES OUTDOOR SENSOR CABLE ø70mm(3”) INDOOR LLATION OR INSTA OUTDOOR DRAINAGE TUBE ELECTRICAL CABLE A01151 FLO Fig. 9—Suggested Tubing Diameter and Contents A01202 40CG/CS-018 40CG/CS-024/030 A 8.74-in. (225mm) 8.74-in. (225mm) B 24-in. (610mm) 24-in. (610mm) C 39.4-in. (1000mm) 42.24-in. (1200mm) Indoor Power Outdoor Control Fan Fig. 6—Dimensional Drawing (Indoor Unit) Step Motor 1 3 2 8 TH3 TH2 TH1 Heat UNIT 8 Display 7 5 4 10 9 A01207 Fig. 10—Mounting Indoor Unit on Mounting Bracket A01203 Fig. 7—Refrigerant Line Routing Options A01206 A01100 Fig. 8—Inserting Drilling Holes on Wall Fig. 11—Switch 1 Factory Default ON Position 6 5. Connect the outdoor sensor cable, making sure the connector is properly inserted. 11:45 S TA R T STOP 1 2 3 D A I LY MODE SLEEP 72 FAN 6. Secure the inter-unit electric and sensor cable to the outdoor unit with the clamp shown in Fig. 14. SWEEP I I I II II I I I I II I II I I A A 7. Reassemble the plastic side cover. NOTE: A drainage tube can be connected to the outdoor unit to remove condensation formed during heating mode operation. Make sure that all screws and wires are properly fastened. Loose wires or connections can cause damage and present a fire hazard. Step 6—Connecting the Refrigerant Lines WIRELESS REMOTE CONTROLLER A01157 1. To connect the refrigerant lines, use only “L” type sealed, dehydrated copper refrigerant tubing. No other type of tubing may be used. Use of other types of tubing will void the manufacturer’s warranty. Fig. 12—Remoter Controller and Rack Step 3—Mounting the Air Conditioner On the Bracket 1. Remove the air conditioner front panel and air intake grille, as shown in Fig. 5. 2. Do not open service valves or remove protective caps from tubing ends until all the connections are made. 2. Fasten the left and right side strips to the air conditioner using 6 sheet metal screws, as shown in Fig. 19. Ensure that: 3. Take care to avoid kinks or flattening of the tubing. 4. Bend tubing with special bending tools to avoid the formation of sharp bends. a. The wide side of the strip is located at the bottom of the air conditioner. 5. Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system. b. The strip angle faces inward. 3. Mount the indoor unit on the bracket. Slide the protruding parts of the side strips onto the ceiling bracket so that the 4 safety screw holes on the left and right strips align with those on the ceiling bracket. 6. Avoid sags in the suction line to prevent the formation of oil traps. 7. Insulate the tubing with 3/8-in. walled thermal pipe insulation. Inserting the tubing into the insulation before making the connections will save time and improve installation. The suction and liquid lines should never come in direct contact. 4. Make sure that the air conditioner is tilted slightly toward the drainage outlet on the right side. Use water to test for proper drainage. Fix the tilt by adjusting the height of the right strip relative to the left one. FLARING AND CONNECTING 1. Remove the protective cap from the flare fitting. 5. Fasten the air conditioner to the ceiling bracket using the 4 side screws. (See Fig. 20.) 2. Remove the protective cap from the tubing and cut to the required length. Make sure that the cut is perpendicular and clean, without burrs. Step 4—Continuing the Installation After attaching the air conditioner to the ceiling bracket, continue the installation procedure in the previous section, titled “Drainage.” 3. Slip the flare nut on the tubing and flare the tube end, using standard flaring tools. 4. Tighten the nut until resistance is met. Mark the nut and the fitting. Using a suitable wrench tighten an additional 1/4 turn. Use the following specified torque, according to connection size: NOTE: If the drainage is routed in direction no. 1, as shown in Fig. 16, cut out the oval opening in the air intake opening for the drainage tube and route the tube through the air intake grille. (See Fig. 21.) Liquid line: 1/4-in. - (12.3 ft/lb) 3/8-in. - (29 ft/lb) Suction line: 1/2-in. - (36 ft/lb) 5/8-in. - (47 ft/lb) 3/4-in. - (72 ft/lb) 5. The valves on the outdoor unit must remain closed until all four connections have been made. NOTE: Set DIP switch no. 1 to the “ON” position. (See Fig. 11.) The other factory switches are set at the factory and should not be changed. Step 5—Installing the Outdoor Unit 1. The outdoor unit must be installed on a solid surface. 2. Make sure that the unit is level. 3. Fasten the outdoor unit legs to the base, as shown in Fig. 14. Place the rubber absorption cushions (supplied with the outdoor unit) under the unit’s legs to prevent vibrations. Step 7—Air Vacuum and Refrigerant Charge When all the fittings are connected, air must be expelled, as follows: WIRING THE OUTDOOR UNIT 1. Remove the outdoor unit plastic side cover. 2. Loosen the screws on the terminal block. 1. Open the service port cap on the suction line valve (large valve). 3. Attach the electrical terminals supplied to the inter-unit control and power cable wires. 2. Connect the vacuum pump to the service port via the pressure gauge and operate the pump for 15 minutes. 4. Connect the wires to the terminal block, in accordance with the coding which appears in Fig. 15. 3. Make sure that full vacuum is present and disconnect the vacuum pump. 7 POWER INDOOR OUTDOOR FAN CONTROL TH3 TH2 TH1 Heat Control 3 2 8 5 4 8 Display 7 10 9 STEP MOTOR 1 TH3 TH2 TH1 HEAT Fan Power Outdoor Indoor Step Motor 1 3 4 5 7 HEAT TH3 TH2 TH1 STEP MOTOR DISPLAY 10 DISPLAY 2 6 8 9 A01210 Fig. 13—Connecting Wire Ends to Terminal Block 1 23 456 7 1 23 456 7 PLUG TO CONNECT WITH OUTDOOR SENSOR CABLE (TH3) INTER-UNIT ELECTRIC CABLE CLAMP ABSORPTION CUSHION X4 A01158 Fig. 14—Outdoor Unit Installation Guideline INDOOR UNIT HIGH SPEED HEAT PUMP MEDIUM SPEED LOW SPEED COMPRESSOR *HEATER HDE PHASE NEUTRAL 1 3 4 5 7 10 2 6 8 9 OUTDOOR UNIT BLACK ~ BROWN YELLOW GRAY/ORANGE RED ~ BLUE WHITE 1 2 3 4 5 6 7 8 9 10 8. Make sure that the valves are properly opened. Be careful not to open them more than required as this may damage the thread. DISCONNECT SWITCHES (NOT SUPPLIED) OUTDOOR INDOOR 2 POWER BROWN 6 POWER BLUE GROUND GR/YEL GREEN/YELLOW 9. Replace the stem cap. Oil the cap beam and hand tighten the cap, until resistance is met. Use a suitable wrench to tighten the cap by an additional 1/2 turn. Step 8—Leak Test Leak test all fittings with appropriate test equipment. OUTDOOR SENSOR CABLE (TH3) Step 9—Electrical Data and Connections Refer to Table 4 or 5 for unit electrical information. * FOR H/P MODELS A01159 Step 10—Two-Way Air Conditioner (Optional Accessory) —Console Only Fig. 15—Wiring Diagram Schematic 4. Open the liquid line valve (small valve) with an Allen wrench. 5. Open the suction line valve (large valve) with an Allen wrench. 6. The outdoor unit is supplied with sufficient refrigerant for 26 ft of tubing. Add 0.9 oz of refrigerant and 0.35 oz of oil for each additional foot of tubing used. If the tubing is shorter than 26 ft, remove gas from the system through the service valve into a recycling device. 7. Close the service port caps on the suction line and the liquid valves. Allows simultaneous air conditioning of adjacent rooms when installed as a console 1. Prepare a wooden frame with the proper dimensions. (See Fig. 22.) 2. Locate the indoor unit and install its mounting bracket. 3. Before mounting the indoor unit on the wall, open a hole in the wall to install the wooden frame using the unit as a guide 4. Insert the frame in the wall and fill in any gaps between the frame and the wall hole with an appropriate material. 8 2 1 OUTDOOR SENSOR CABLE REFRIGERANT LINES ELECTRICAL CABLE DRAINAGE TUBE 10 cm MINIMUM A01093 Fig. 16—Tubing Routing Options 2 1 2 2 1 2 1 2 2 2 1 1 BRACKET SCREWS 2 ANCHOR SCREWS 2 A01094 Fig. 17—Assembling the Ceiling Bracket A01095 Fig. 18—Mounting Ceiling Bracket to Ceiling 9 PIPE COVER WIDE SIDE A01097 Fig. 19—Fastening Left and Right Sides to Air Conditioner PROTRUSION 3 FASTEN THE 4 SAFETY SCREWS ON THE SIDES OF THE AIR-CONDITIONER 2 MAKE SURE THAT THE PROTRUDING PARTS OF THE SIDE STRIPS FIT INTO THE RUNNERS ON THE MOUNTING BRACKETS 1 SLIDE THE AIR CONDITIONER INTO THE MOUNTING STRIPS A01098 Fig. 20—Mounting Indoor Unit onto Ceiling Bracket A01099 Fig. 21—Drainage Tube Routing Option 5. Cut the required openings in the insulation material on the back of the unit. The air feedback grille is installed when air from the adjacent room is to be sampled by the thermostat when installed as a console. 1. Affix a gasket around the air feedback opening at the rear of the air conditioner (approximately 12-in. from the opening). 2. Drill a hole in the shared wall to insert the return air tube. 3. Mount the indoor unit on its mounting bracket. 4. Insert the tube into the hole until it reaches the opening at the rear of the unit. 5. Insert the grille on the end of the tube. 6. Complete the installation by attaching the plastic frame to the wall using screws. 6. Mount the indoor unit on its mounting bracket, as previously described. 7. Seal any gaps between the back of the unit and the wall using a sealing material. 8. Install the grille into the wooden frame and attach it to the frame using two wood screws. 9. Finish the installation by performing all the necessary steps located throughout this instruction. Step 11—Air Feedback System Installation (Optional) (Two-Way Air Conditioner) See Fig. 23. 10 Table 4—Electrical Data - Indoor Unit MODEL MCA MOCP Power Supply Full Load Amps Fan Motor Amps Electric Heater (watts) Electric Heater (amps) 40CG-018 0.8 15 40CG-024 0.8 15 0.6 0.6 n/a n/a 0.6 0.6 n/a n/a 40CG-030 40CS-018 0.8 11.5 15 20 208/230V, 60 Hz, 1 Ph 0.6 8.9 0.6 0.6 n/a 2000 n/a 8.3 40CS-024 17.0 30 40CS-030 17.0 30 13.1 0.6 3000 12.5 13.1 0.6 3000 12.5 40CS-024 30.4 35 40CS-030 36.1 40 1.5 9.6 61.0 1.5 14.2 94.0 Specifications and performance data are subject to change without notice. MCA–Minumum Circuit Amps MOCP–Maximum Over Current Protection Table 5—Electrical Data - Outdoor Unit MODEL MCA MOCP Power Supply Fan Motor Amps Full Load Amps Locked Rotor Amps 40CG-018 11.4 15 40CG-024 14.1 20 1.5 7.4 48.0 1.5 9.6 61.0 40CG-030 40CS-018 19.8 22.1 30 25 208/230V, 60 Hz, 1 Ph 1.5 1.5 14.2 7.4 94.0 48.0 Specifications and performance data are subject to change without notice. MCA–Minumum Circuit Amps MOCP–Maximum Over Current Protection WALL THICKNESS REAR AIR OUTLET REAR OUTLET GRILL 112(4.4”) 173(6.8”) A 12(0.5 WALL EVAPORATOR ”) min 45 (1 .8” ) B WOODEN FRAME A01101 BACK OPENINGS OPEN SIZE A B (in.) 2 3 4 5 6 7 9.1 13.4 17.7 22.1 26.4 30.7 (mm) 230 340 450 560 670 780 (in.) 11.2 15.5 19.85 24.2 28.5 32.8 (mm) 284 394 504 514 724 834 AIR FEEDBACK GRILLE Fig. 22—Dimensional Drawing PVC TUBE AIR SPONGY FEEDBACK GASKET OPENING A01102 START-UP PROCEDURES Fig. 23—Two Way Air Conditioner Step 1—Finishing the Job OUTDOOR UNIT 1. Hide the tubing where possible. 1. Are there unusual noises or vibrations during operation? 2. Make sure that the drainage tube slopes downwards along its entire length. 2. Is noise, drain water or air flow from the unit likely to disturb the neighbors? 3. Insulate tubing and connections. 3. Are there any gas leaks? 4. Fasten tubes to the outside wall. EXPLAIN THE FOLLOWING ITEMS TO THE CUSTOMER, WITH THE AID OF THE USER MANUAL: 5. Seal the hole through which the cables and tubing pass. 6. Connect the air conditioner to the power source and turn it on. 1. How to turn the air conditioner on and off; selecting cooling, heating and other operating modes; setting a desired temperature; setting the timer to automatically start and stop air conditioner operation; and the other features of the remote controller and display panel. 7. Check all air conditioner operating modes. Consult the User Manual. INDOOR UNIT 1. Do all the remote controller buttons function properly? 2. How to remove and clean the air filter. 2. Do the display panel lights work properly? 3. How to set the air deflection louver. 3. Does the air deflection louver function properly? 4. Present the User Manual and this installation sheet to the customer. 4. Does the drainage work? 11 CARE AND MAINTENANCE Step 1—Maintenance (Outdoor Unit) TO REMOVE AND CLEAN OR REPLACE AIR FILTERS Operating your system with dirty air filters may damage the indoor unit and, in addition, can cause reduced performance, intermittent system operation, frost build up on the indoor coil, and blown fuses. Inspect and clean or replace the air filters monthly. Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in electric shock or injury from rotating fan blade. CLEANING COILS Coil should be washed out with water or blown out with compressed air. Clean coil annually or as required by location and outdoor air conditions. Inspect coil monthly and clean as required. Fins are not continuous through coil sections. Dirt and debris may pass through first section, become trapped between the row of fins and restrict outdoor unit airflow. Use a flashlight to determine if dirt or debris has collected between coil sections. To Remove Air Filters Remove filters by pulling them straight out. To Clean Or Replace Filters Filters can be vacuumed or washed in warm water. Shake filter to remove any excess water, and replace by sliding filter behind grille until filter snaps in place. If the filter has begun to break down or is torn, replace it. Replacement filters are available through your Carrier distributor. Clean coil as follows: 1. Turn off unit power To Clean Indoor Unit Bottom/Front Panel 2. Using a garden hose or other suitable equipment, flush coil from the outside to remove dirt. Be sure to flush all dirt and debris from drain holes in base of unit. Fan motors are waterproof. If the bottom/front panel of the unit becomes dirty or smudged, wipe the outside of the panel with a soft dry cloth. Use a mild liquid detergent and wipe off carefully with a dry cloth. Step 2—Maintenance (Indoor Unit) To Clean Indoor Coil To clean the coil, remove indoor unit bottom/front panel and vacuum the coil fins, using care not to bend or damage fins. To avoid the possibility of electric shock, before performing any cleaning and maintenance operations, always turn off power to the system by pressing the mode button on the remote control until the display shows ’’OFF,’’ and turn off the separate disconnect switch located near the unit. If the indoor unit is on a separate switch, be sure to turn this disconnect off as well. To Clean Condensate Drains Clean all drains and drain pans at the start of each cooling season. Check the flow by pouring water into the drain. To Clean Or Replace Drain Pan 1. Place a plastic sheet on the floor to catch any water that may spill from drain pan. 2. Remove the intake grille and distribution assembly. 3. Remove the condensate water in the drain pan by letting water drain into a 3-gallon bucket. Do not wash filter in water over 120°F (to avoid shrinkage). Do not expose filter to fire (to avoid fire damage). Do not expose filter to direct sunlight. Clean filter more frequently when air is extremely dirty. Do not attempt to clean or service components in control box. LUBRICATION The indoor-fan, automatic air sweep, and the outdoor-fan motors are factory lubricated and require no oiling. 12 INDOOR UNIT WIRING DIAGRAM TH2 TH1 OUTDOOR UNIT RVS MAIN DISPLAY TAC - 460 TH3 BK TH3 5A CON5-4 CON7 OR N BR ¥¥BR 2 GR/YEL CONTACTOR IH RL6 ¥12VDC CON9 5A CON6-3 ¥ BLUE FC BR BLUE FAN MOTOR BLUE 5A RED CON6-1 BLK BLK IL 5 1 2 1 ¥ RED ¥ RED CON6-9 HEATER(OPT) HEATER TC ST 1 1 23 456 POWER SUPPLY 2 CON4 13 BLUE BR GR/YEL MODELS (Indoor) 40CS-018-301 40CS-024-301 40CS-030-301 FC A2 2 ¥BR HEATERÕS THERMOSTAT ¥ BR CON8 4 6 3 4 ¥ RED ¥ 6 ¥GR/YEL 5 ¥¥ GR/YEL OR RL ¥ BLUE WH BLK 5A CON6-5 ¥ GR/YEL 5 CON5-7 IT WHT ¥¥BLUE 6 BK 12 CON6 J3 ¥¥YEL 4 A1 CONTACTOR J5 PS OVERLOAD ONLY ON ROTARY COMP 1 23 456 BK BLUE P3 RED 16 ¥ BLUE 9 WH 3 BR 13 RL3 RL BLUE GRAY/OR 5A CON5-5 OH 3 6 TB WH 2 WH OL RL ¥¥ WH ¥¥ OR ¥YEL ¥ OR 7 10 BR RED YEL/GR CON1 WH ¥¥ RED ¥ BLUE CONTR ¥¥YEL YEL WH 2 3 4 5 1 2 3 4 5 6 7 10 BLUE 10 YEL RED 5A CON5-6 1 2 3 4 5 6 7 10 ¥¥ BR 15 RVS OH 1 BK 12 ¥BR 15 BK (YEL) ¥ BR 14 RL1 RL 1A CON5-1 1A CON5-3 ¥ BR COMP ¥¥ BK ¥ GR/YEL RL2 BK ¥ BK CON5 ¥ BLUE CON3 ¥OR ¥YEL CON2 SWEEP MOTOR TH3 R C S FUSE 6A ST ¥ SAFETYTHERMOSTAT TC ¥ THERMAL CUTOFF FC ¥ FAN CAPACITOR ¥ REVERSING VALVE RVS SOLENOID ¥ 12 AWG WIRE ¥¥ 14AWG WIRE Fig. 24—Wiring Diagram COMPR. FAN MOTOR MODELS: (Outdoor) 38CS-018-301 38CS-024-301 38CS-030-301 A01196 I N D O O R U N I T E L E C T R I C A L D I A G R A M O U T D O O R U N I T CONTRACTOR TH2 TH1 2 2 7 COMP. MAIN DISPLAY TAC-460 5 CON2 CON3 7 COMPRESSOR OL 5 5 CON5 COMP. RL1 RVS OH 1A CON5-1 1A CON-5 1 OH 1 2 5A CON5-8 3 HEAT OL 5A CON5-4 OM 5A CON5-5 RL3 CON6 CON7 RL5 LT RL7 IL IH RL5 14 12VOC CON9 5 4 2 5 1 C FC 3 OVERLOAD ONLY ON ROTATY COMP. POWER SUPPLY 3 4 10 1 10 2 3 5A CON6-5 5A CON6-1 FC ST HEATERÕS THERMOSTAT TC FAN MOTOR 6 0 6 CON6-9 HEATER (OPT) TH3 0 CON4 CON8 S 6 2 CON6-7 5A CON6-3 1 RVS HEATER RL4 R 8 CON1 SWEEP MOTOR 4 8 FAN MOTOR RL2 RL3 CONTR 1 5 TH3 TH3 FUSE BA MODELS (Outdoor): 38CS-018-301 38CS-024-301 38CS-030-301 MODELS (Indoor): 40CS-018-301 40CS-024-301 40CS-030-301 Fig. 25—Wiring Diagram A01197 I N D O O R U N I T W I R I N G TH1 D I A G R A M T H2 O U T D O O R M AIN D ISPL AY TAC - 4 6 0 U N I T RVS TH 3 TH3 BK TH3 CON2 CON5 CON3 RL2 COMP. RL1 RVS BK 1A BK 1 2 ¥ ¥ BK 1 CON5-1 1A YEL G R AY /D R CON5-3 RL8 CONTR 4 RED 5 WH 7 5A OM CON5-6 ¥ ¥Y E L 3 ¥ ¥ RED ¥ ¥WH CON1 1 2 2 3 3 4 4 5 5 6 6 7 7 ¥ BR 1 5 BK( YEL ) R ED 1 6 ¥ BL U E 9 WH 2 P3 J 3 5A OL RL4 1 CON5-4 RED 16 ¥ G R /Y E L ¥ G R / YEL 5 BLUE FC ¥ FAN CAPACITOR FUSE BA RVS ¥ REVERSINGVALVE SOLENOID ¥ 12 AWG WIRE ¥ ¥ 14 AWG WIRE 1P H - S 2675706- A CONTRACTOR R 1 2 3 4 5 6 OVERLOAD ONLY ON ROTARY COMP BK P5 ¥BK ) J5 FAN MOTOR S C BR G R /Y E L CH ¥ CRANKCASE HEATER (OPTION). A1 1 2 3 4 5 8 C O N4 ALL HIDDEN LINES ( ON H MODELS. 4 FC WH BR RED Y E L /G R 0 A2 L P OWE R S UP P LY HEATER( O PT) 1 BK ¥ BR 15 ¥ BR N 0 ¥BR CON8 2 FA N MOTO R CON6-9 CON9 4 BLUE ¥ BR 14 - 1 2 VD C B 5A CON6-3 ¥ GR/YEL FC BR BK IM RL6 ¥ BLUE RED CON6-1 BLK BLK 15 OR 5A IL RL7 WH 3 BR 13 BLK CON6-5 BLUE 10 IT G R /Y E L WH 2 RL5 CON7 2 WH CON5-7 5A WH T ¥¥ BR ¥ BLUE CON6 SWEEP M OTO R 6 BR CON5-5 ¥¥ BLUE BK 12 5A OM RL3 0 ¥ G R /Y E L 5 BLUE MODELS (Indoor) 40CG-018-301 40CG-024-301 40CG-030-301 CH BK COMPR. MODELS (Outdoor) 38CG-018-301 38CG-024-301 38CG-030-301 Fig. 26—Wiring Diagram A01198 INDOOR UNIT ELECTRICAL DIAGRAM OUTDOOR UNIT CONTACTOR TH2 TH1 2 MAIN DISPLAY TAC - 460 CON2 CONTR CON3 2 7 COMP 7 5 OL 1 4 5 6 COMPRESSOR 5 5 FAN MOTOR CON5 R RL2 COMP RL1 RVS RL8 OH 1A CON5-1 1A CON5-3 1 OH 1 2 5A CON5-6 3 HEAT 1 DL 5A CON5-4 OH 5A CON5-5 RL3 C CH FC 3 OVERLOAD ONLY ON ROTARTY COMP CON1 RL4 POWER SUPPLY S 6 RVS CON6 CON5-7 16 SWEEP MOTOR RL5 CON7 IT RL7 RL6 ¥12VDC CON9 5A CON6-5 IL 5A CON6-1 IH 5A CON6-3 FC FAN MOTOR 6 HEATER(OPT) ¥ 6 4 MODELS (Indoor) 40CG-018-301 40CG-024-301 40CG-030-301 TH3 2 CON8 6 CON6-9 CON4 TH3 TH3 MODELS (Outdoor) 38CG-018-301 38CG-024-301 38CG-030-301 FUSE 6A Fig. 27—Wiring Diagram A01199 TROUBLESHOOTING Table 6—Indicator Lamps Troubleshooting LAMPS STATUS INDICATION CORRECTIVE ACTION POWER flashes 10 seconds after A/C start-up (with or without other signal lamps) Communication problem. • Check connection between indoor (TAC-440) and outdoor (TAC-420) units (for TAC-400, ANC). • Check connection between TAC-444 and TAC-460 (for TAC-404). POWER, COMPRES. and PRESSURE lamps flash. Thermistor failure. • Check TH-1 for correct resistance. • Check for proper connection between TH-1 and TAC-444. • Replace TH-1 if necessary. POWER, COMPRES. and IMPEDANCE lamps flash. Thermistor failure. • Check TH-2 for correct resistance. • Check for proper connection between TH-2 and TAC-444. • Replace TH-2 if necessary. POWER lamp flashes and PRESSURE is lit, AIR CON is Off. Low Pressure • Check if the filters are clean. • Check TH-1 and TH-2 for correct resistance. • Check cooling system for normal operation. POWER and PRESSURE lamps flash, AIR CON is Off. High Pressure. • In Heat mode: Check if the evaporator is blocked. (Check if filters are clean.) • Check TH-2 (in Heating mode) or TH-3 (in Cool mode) for correct resistance. • Check cooling system for normal operation. FILTER is lit. Filter cleaning. • Clean all filters. POWER, IMPEDANCE lamps flash, COMPRES. is lit. Low voltage. • Check power supply voltage. • Check electrical connections. • Replace TAC-444. POWER lamp flashes, IMPEDANCE and COMPRES. lamps lit. AIR CON lamp flashes after A/C start-up. Voltage failure at start-up. • Check power supply voltage. • Check electrical connections. • Replace TAC-444. POWER lamp flashes, IMPEDANCE and COMPRES. are lit before A/C startup. High Voltage. • Check power supply voltage. • Check electrical connections. • Replace TAC-444. POWER lamp flashes, IMPEDANCE and COMPRES. are lit. AIR CON is lit after A/C startup. High voltage during compressor operation. • Check power supply voltage. • Check electrical connections. • Replace TAC-444. 17 Table 7—General Troubleshooting Chart SYMPTOM PROBABLE CAUSE a. Power supply to unit not connected (POWER LED Off). CORRECTIVE ACTION Check for proper connection of power at disconnect Reset automatic circuit breaker or b. Fuse Blown (POWER LED Off). replace line fuse. Press ON/SEND button on Remote Control, or use the AUTO 3-position slide switch for A/C fails to start. c. ON/SEND has not been pressed. automatic constant 22°C Set Point (when Remote Control is not available). d. Indoor unit does not receive transmitted Make sure that nothing is blocking the Remote Control commands. transmission to the A/C display. Slide the 3-position switch on the Display e. AUTO-OFF-REMOTE switch is set to Off. to REMOTE (RMOT) position. Check if the Remote Control is on the desired mode. If not, select the correct mode (refer a. The selected mode is on Fan Only, to your User manual). Also note that or on Cool when heating is desired. each 15 minutes (max), the compressor Only indoor fan ventilator works, will be switched on for 3 minutes (at least). although cooling or heating is desired. Observe the temperature setting on the Remote Control. b. Temperature is set to a value which Also note that each 15 minutes (max), is too high (in Cool mode.) the compressor will be switched on for 3 minutes (at least). a. In Heat Mode: Indoor fan motor blocked. Remove obstruction. Only indoor fan motor and compressor b. In Cool mode: System runs while Wait up to 90 seconds until Anti-Ice routine working. Outdoor fan motor stopped. evaporator Anti-ice routine take place. is completed. a. Run capacitor of outdoor fan Replace outdoor fan motor run capacitor. In Cool mode: High pressure, or; motor is burnt. in Heat mode: Outdoor coil freeze b. Winding of outdoor fan motor is shorted. Replace outdoor fan motor. a. Overload safety device on compressor Switch Off power and try again after one hour. Only indoor fan motor and outdoor fan is cut out due to high temperature. motor are working. No cooling and/or b. Compressor run capacitor is burnt. Replace compressor run capacitor. heating take place. c. Compressor winding shorted. Replace compressor. 1. Check voltage. Repair wiring if necessary. a. Indoor fan motor is blocked 2. Check indoor fan wheel if tight on or turns slowly. motor shaft. Tighten if necessary. b. Indoor fan motor capacitor is burnt. Replace indoor fan motor capacitor. No air supply at indoor unit (compressor operates). c. Indoor fan motor winding is burnt. Replace indoor fan motor. d. In Heat mode: Delayed start for Normal software delay (max. 20 sec) indoor fan motor. e. Clogged air filters. Clean filters. a. Lack of refrigerant (will be accompanied Unit must be charged (according to by whistling noise): Causes ice formation the nameplate) after localizing the Low Capacity. on the evaporator coil (in Cool mode). gas leak. b. Clogged air filters. Clean filters. In Heat mode: only compressor runs, Wait (max.) 10 minutes until the A/C outdoor and indoor fan motors are A/C operates in De-Icing cycle. resumes normal operation. stopped. AIR CON indicator flashes. Note: Check for broken wires and loose cable lugs first! Warning : Always unplug the A/C before performing cleaning or maintenance activities. 18 Table 7—General Troubleshooting Chart (Continued) SYMPTOM PROBABLE CAUSE Water accumulates and overflows from evaporator drain pan. Drain pan pipe or hose is clogged or the spout of drain pan is clogged. Water dripping from the condenser base (in Heat mode). Water drain outlet or the spout is clogged. a. The 3-position slide switch on the A/C display is in AUTO or OFF position. b. Faulty Remote Control settings. Unit does not operate in desired mode. c. Remote Control low battery. d. IR detector. The A/C is interfered by other Remote Control or our Remote Control interfering other instruments. Common IR Code. In Cool mode: the unit (compressor) do not start. a. Faulty TH-3 (outdoor) sensor. b. Faulty TH-3 Extension Cable (between indoor and outdoor). Note: Check for broken wires and loose cable lugs first! Warning : Always unplug the A/C before performing cleaning or maintenance activities. 19 CORRECTIVE ACTION Disassemble plastic drain-pipe from spout of evaporator drain pan. Flush with clean water. Open condenser cover, clean out water outlet, clean the base inside thoroughly. Change the slider position to REMOTE (RMOT). 1. If Remote Control symbols respond to the commands correctly, check the A/C ID Code (Standard or Alternative). Refer to “Changing A/C ID Code” and to Remote Control DIP switch 3 setting. 2. If Cool commands are OK, but Heat symbol is skipped on LCD, refer to Remote Control DIP switch 7 setting. 3. Replace Remote Control. Replace Remote Control batteries. Try shorter distance between Remote Control and A/C.If no response, replace IR detector. Modify the Remote Control IR transmission code. Refer to “Changing A/C ID Code” and to Remote Control DIP switch 3 setting. Replace the TH-3 sensor. Replace TH-3 Extension Cable. Copyright 2001 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 38c40c1si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 533-80013 Printed in U.S.A. Form 38C/40C-1SI Pg 20 8-01 Replaces: New Tab misc. misc