Download Danfoss DHP-AX Specifications
Transcript
15.2 Measurement points Conversion table for sensors DD When reading the resistance of the sensors, the sensor leads must first be disconnected from the control equipment. Outdoor sensor 15.3 Other sensors °C Ohm, Ù °C Kiloohm, kÙ -30 1884 0 66,3 -25 1443 5 52,4 -20 1115 10 41,8 -15 868 15 33,5 -10 681 20 27,1 -5 538 25 22,0 0 428 30 18,0 5 343 35 14,8 10 276 40 12,2 15 224 45 10,1 20 183 50 8,5 25 150 55 7,1 30 124 60 6,0 35 103 65 5,0 40 86 70 4,2 75 3,7 80 3,1 85 2,7 90 2,3 95 2,0 1. 2. 3. Disconnect the sensor cable at the I/O card. First measure the sensor including the cable. Then measure the sensor only. Check points Temperatures Name Values Condensing temperature 0.5 – 1.5 °C above supply line temperature Evaporation temperature 7 - 8 °C lower than incoming brine Overheating 4 - 8 K temperature difference Radiator circuit 5 - 10 K temperature difference Overheating R407C 4K ±1 K VMBMH302 Service – 45