Download Emerson Liebert XDR Specifications
Transcript
Designing a Liebert XD Solution Table 20 Worksheet to calculate refrigerant charge Components Number of Units or Piping Length Pounds Per Component Total Total Verify that the refrigerant volume of the Liebert XD system with the longest piping length is within the allowable limit. If the allowable limit is exceeded, the Liebert XDP/Liebert XDC should be moved closer to the cooling modules (refer to 3.22 - Liebert XD Refrigerant for limits and related details). Another way to shorten the total pipe length is to reroute the pipe runs. 3.24 Chilled Water Piping The Liebert XDP is offered only with a two-way chilled water control valve. Some applications may require the use of a pressure activated bypass valve to prevent dead-heading of the chilled water pump. This bypass valve must be specified by the engineer responsible for design of the chilled water field piping system. NOTICE Risk of particles in chilled water. Can cause equipment damage and reduced cooling. Failure to install a strainer in the supply line to the Liebert XDP can result in damage to the unit’s heat exchanger. Install a 20-40 mesh strainer on the chilled water supply to the Liebert XDP. The strainer is required to prevent particles in the chilled water from entering the heat exchanger of the Liebert XDP. The maximum distance of the strainer from the Liebert XDP is 10 feet (3m). 42