Boiler Piping SECTION IV - Boiler Piping General Piping Requirements - - - - - All plumbing must meet or exceed all local, state and national plumbing codes. Support all piping using hangers. DO NOT support piping by the appliance or its components. - Use isolation valves to isolate system components. - Install unions for easy removal of the CHALLENGER from the system piping. WARNING Should not contain any shut-off valves or obstructions. No shut-off valve should be piped between the appliance and relief valve. Low Water Cut Off / CH Pressure Sensor NOTICE 1. The CHALLENGER has a ASME Maximum Allowable Working Pressure of 43.5 PSI [3 bar]. The appliance is supplied with a 30 psi [2 bar] pressure relief valve and must be piped using the PRV connection as shown in Fig. 3 page 15. - - 2. To avoid potential water damage to the surrounding area or potential scalding hazard due to the operation of the relief valve, the discharge piping: - Should not be subject to conditions where freezing could occur. Failure to comply with the guidelines on installing the pressure relief valve and discharge piping can result in personal injury, death or substantial property damage. Pressure Relief Valve (PRV) - Should terminate with a plain end, not with a threaded end. The material of the piping should have a serviceable temperature rating of 250ºF [121ºC] or greater. WARNING Use a two wrench method when tightening piping onto the appliance connections. Use one wrench to prevent the appliance piping from turning / twisting. Failure to support the appliance piping and connections in this manner could cause damage to the appliance and its components. - above any drain connection to allow clear visibility of the discharge. - Must be connected to the discharge outlet of the relief valve and directed to a safe place of disposal. Length should be as short and direct as possible. The size of the discharge line should not be reduced, maintain the same size as the outlet of the relief valve. - Should be directed downward towards the floor at all times. The piping should terminate at least 6 inches [153 mm] 14 The Low Water Cut Off (LWCO) only applies for space heating. Operation of the LWCO does not prevent a domestic hot water call for heat. The CHALLENGER is equipped with a factory installed pressure sensor type LWCO. The minimum operating Central Heating (CH) system pressure is 7 psig [0.5 bar]. If CH System pressure is below 7 psig [0.5 bar] the main display will flash a soft lockout of “LOP” followed by the pressure reading. Once CH system pressure is increased above 7 psi [0.5 bar] normal boiler operation will be restored. If the appliance is installed as domestic hot water heater only, set parameter 1 (installation type) to 2 (domestic only) to eliminate the “LOP” error in the main display, see page 52 for setting parameters. Check local codes if a LWCO is required. If so, determine if this device meets their requirements.