Transcript
Symptom #2 Machine is running and the display indicates “HPC Fault” and an alert triangle 1. Navigate to the event log on the Service menu. Scroll down to HPC Fault #5. Open the event and view when and how often HPCO Fault has occurred. 2. If this is a one time event it may be intermittent and caused by conditions around the unit changing. For example: High ambient temperature, water turned off to condenser (water cooled unit) etc. 3. Run the system to see if the control trips at the rated pressure. If HPCO opens at a pressure significantly lower than the control setting of 440 psig replace the HPCO. 4. If the control opens at the correct pressure (+-10 lbs) find the root cause - Fan motor, dirty condenser, refrigeration system issue, etc. 184 Part Number STH025 02/12